LP-GAS SERVICEMANS
HANDBOOK
LP-GAS SERVICEMANS
HANDBOOK
The Fisher Controls LP-Gas Servicemans Handbook
serves as a general reference of information on LP-Gas
and for the installation, operation and maintenance of
LP-Gas equipment. It provides key data and answers
important questions that are relevant to management
and field servicemen in the LP-Gas industry.
Users of this handbook should consult applicable
federal, state and local laws as well as pertinent
industry regulations, including National Fire Protection
Association (NFPA) Pamphlets No. 54 and 58.
Fisher Controls shall have no responsibility for any
misinterpretation of the information contained in this
handbook or any improper installation or repair work or
other deviation from the procedures recommended in
this handbook.
For additional copies of this handbook please contact
your local Fisher Distributor, or call 1-800-558-5853, or
1-319-378-8673.
50
Table of Contents
PROPERTIES OF LP-GASES ..................................... 2
VAPOR PRESSURE OF LP-GASES ........................... 4
DETERMINING TOTAL LOAD ..................................... 5
VAPORIZATION RATE ................................................. 6
CYLINDER AND TANK MANIFOLDING ....................... 9
CONTAINER LOCATION AND INSTALLATION ......... 11
Container Preparation .................................................... 15
PROPANE
BUTANE
Formula
C3H8
C4H10
-44
31
0.504
0.582
4.20
4.81
0.630
0.549
36.38
31.26
8.66
6.51
1.50
2.01
3,595
3,615
23.86
31.02
2.15
9.60
1.55
8.60
184
773
167
808
2,488
21,548
91,502
3,280
21,221
102,032
PROPANE
BUTANE
C3H8
C4H10
-42
-1
0.504
0.582
504
582
1.464
1.276
0.271
0.235
0.539
0.410
Formula
Initial Boiling Point, C
Specific Gravity of Liquid
(Water = 1.0) at 15.56C
Weight per Cubic Meter of
Liquid at 15.56C, kg
1.50
2.01
493-604
482-538
1,980
1,991
23.86
31.02
2.15
9.60
1.55
8.60
428
216
388
226
92,430
49,920
25,140
121,280
49,140
28,100
TEMPERATURE
-40
-40
-30 -34.4
3.6
4.5
9.2
4.9
1.9
20
16
3.5
-17.8
28
22
15
11
7.3
10 -12.2
37
29
20
17
13
3.4
20
-6.7
47
36
28
23
18
7.4
30
-1.1
58
45
35
29
24
13
40
4.4
72
58
44
37
32
18
50
10
86
69
53
46
40
24
6.9
60
15.6
102
80
65
56
49
30
12
70
21.1 127
95
78
68
59
38
17
80
26.7
140
125
90
80
70
46
23
90
32.2
165
140
112
95
82
56
29
100 37.8
196
168
137
123
100
69
36
110 43.3
220
185
165
148
130
80
45
VAPORIZATION RATE
The rate of vaporization of a container is dependent upon
the temperature of the liquid and the amount of wetted
surface area of the container.
The temperature of the liquid is proportional to the outside
air temperature and the wetted surface area is the tank
surface area in contact with the liquid. Therefore, when
the outside air temperature is lower or the container has
less liquid in it, the vaporization rate of the container is a
lower value.
To determine the proper size of ASME storage tanks or the
proper number of DOT cylinders for various loads, it is important to consider the lowest winter temperature at the
location.
Multiple cylinders or tanks may be manifolded to give the
required vaporization capacity. Withdrawal of gas from one
or two containers can lower the container pressure substantially due to the refrigeration of the vaporization gas.
Regulator capacity is then reduced because of the lower
inlet pressure. Where any reasonably heavy gas load is
expected, put sufficient cylinders on each side of an automatic changeover system.
See pages 7 and 8 for more information.
250
500
1,000
40F
214,900
288,100
478,800
852,800
30F
187,900
251,800
418,600
745,600
20F
161,800
216,800
360,400
641,900
10F
148,000
198,400
329,700
587,200
0F
134,700
180,600
300,100
534,500
-10F
132,400
177,400
294,800
525,400
-20F
108,800
145,800
242,300
431,600
-30F
107,100
143,500
238,600
425,000
LBS. OF
PROPANE
IN CYL.
-20F
0F
20F
100
65,000
71,000
79,000
94,000
90
60,000
65,000
72,000
85,000
80
54,000
59,000
66,000
77,000
70
48,000
52,000
59,000
69,000
60
43,000
46,000
52,000
61,000
50
37,000
40,000
45,000
53,000
45,000
40F
40
31,000
34,000
38,000
30
26,000
28,000
31,000
37,000
20
20,000
22,000
25,000
29,000
10
15,000
16,000
18,000
21,000
COPPER PIGTAIL
SCH 80 1/2-IN PIPE MANIFOLD
AUTOMATIC CHANGEOVER
REGULATOR
1st STAGE
REGULATOR
Schematic of a
tank manifold
installation
2nd STAGE
REGULATOR
10
11
12
Crawl space opening,
windows, or exhaust fan
3-ft
Min.
3-ft
Min.
10-ft Min.
(Note 2)
Figure 3 Cylinders
(1 ft = 0.3048 m)
Cylinders not
filled on site
Central A/C
compressor (source of
ignition)
5-ft
Min. (Note
1)
25-ft
Min. (Note
2)
25-ft
Min. (Note
2)
10-ft
Min.
5-ft
Min.
10-ft
Min.
exhaust fan
5-ft
Min.
Nearest line of adjoining
property that may be built
Crawl space
upon
opening, windows, or
w.c.
Gal.
r 125
Unde
10-ft Min.
(Note 1)
(1 ft = 0.3048 m)
10-ft Min.
1
(Note 1) 25-50
0G
al. w
.c.
501
-20
00
Ga
l. w
.c.
Central A/C
compressor
(source of
ignition)
10-ft
Min. (Note
1)
Und
Gal. er 125
w.c.
Note 1: Regardless of its size, any ASME tank filled on site must be located so that the
filling connection and fixed liquid level gauge are at least 10 ft. away from any external
source of ignition (i.e., open flame, window A/C, compressor, etc.), intake to direct vented
gas appliance or intake to a mechanical ventilation system.
13
14
10-ft Min.
(Note 1)
less
10-ft
Min. (Note
2)
10-ft
Min. (Note
2)
10-ft
Min. (Note 1)
200
0G
al. w
.c. o
r
10-ft
Min. (Note
1)
(1 ft = =0.3048 m)
Central A/C
compressor (source of
ignition)
MINIMUM AMOUNT OF
METHANOL REQUIRED
15
16
SHUTOFF VALVE
MULTI-PURPOSE
VALVE
PRESSURE GAUGE
SERVICE VALVE
OUTLET
SHUTOFF
VALVE
VAPOR
EQUALIZING
VALVE
PIPE
COUPLING
SERVICE VALVE
PRESSURE
GAUGE
17
18
19
Example:
A private home is to be supplied with a LP-Gas system serving a
central furnace, range and water heater. The gas demand and
piping lengths are shown on the sketch below.
Figure 7
Fisher 1st
Stage Regulator
25
A
WATER
HEATER
40,000
BTU/HR
15
12
B
RANGE
75,000 BTU/HR
30
Section 2
10
C
FURNACE
120,000 BTU/HR
For First-Stage:
1) Length of first-stage piping = 25 feet (round up to 30 ft. for use
in Table 7a, b, c.).
2) Total gas demand = 40,000 + 75,000 + 120,000 = 235,000
BTU/HR.
3) From Tables 7a, b, and c, use 1/2 iron pipe; or 1/4 Type L or
3/8 ACR copper tubing or 1/2 plastic tubing. (Assume a 10
psig first-stage regulator setting and a 1 psig pressure drop.)
For Second-Stage:
1) Total second-stage piping length = 30 + 10 + 15 = 55 feet
(round up to 60 ft. for use in Table 8a and 8b).
2) Gas demand requirements and pipe selection from Table 8a
and 8b (Assume a 11 w.c. setting and 1/2 w.c. pressure drop):
For Outlet A, demand = 40,000 BUT/HR, use 1/2 iron pipe or 3/8
Type L or 5/8" ACR copper tubing.
For Outlet B, demand = 75,000 BUT/HR, use 1/2 iron pipe or 1/2
Type L or 5/8 ACR copper tubing.
For Outlet C, demand = 120,000 BUT/HR, use 3/4 iron pipe or
5/8 Type L or 3/4 ACR copper tubing.
For Section 1, demand = 40,000 + 75,000 = 115,000 BTU/HR, use
3/4 iron pipe or 5/8 Type L or 3/4 ACR copper tubing.
For Section 2, demand = 40,000 + 75,000 + 120,000 = 235,000
BTU/HR, use 1 iron pipe.
20
21
E = 35ft
MANIFOLD
xxx
REGULATOR
D = 30ft
A = 20ft
R
xxxxx
xxx
C = 10ft
B = 10ft
WATER HEATER
36,000 BTU/HR
FURNACE
80,000 BTU/
HR
DRYER
28,000 BTU/HR
LENGTH FT
LOAD 1000
BTU/HR
S E LE C T
CSST SIZE
B
C
D
E
10
10
30
35*
80
36
28
52
129
50
28
64
1/2
3/8
3/8
1/2
22
1,834
1,570
1,391
1,261
1,160
1,079
1,012
956
768
657
582
528
486
452
424
400
363
334
310
291
275
221
189
30
40
50
60
70
80
90
100
150
200
250
300
350
400
450
500
600
700
800
900
1000
1500
2000
3,835
3,283
2,909
2,636
2,425
2,256
2,117
2,000
1,606
1,374
1,218
1,104
1,015
945
886
837
759
698
649
609
575
462
395
3/4 NPT
(0.824")
7,225
6,184
5,480
4,966
4,568
4,250
3,988
3,767
3,025
2,589
2,294
2,079
1,913
1,779
1,669
1,577
1,429
1,314
1,223
1,147
1,084
870
745
1 NPT
(1.049")
14,834
12,696
11,252
10,195
9,379
8,726
8,187
7,733
6,210
5,315
4,711
4,268
3,927
3,653
3,428
3,238
2,934
2,699
2,511
2,356
2,225
1,787
1,529
1 1/4 NPT
(1.38")
22,225
19,022
16,859
15,275
14,053
13,074
12,267
11,587
9,305
7,964
7,058
6,395
5,883
5,473
5,135
4,851
4,395
4,044
3,762
3,530
3,334
2,677
2,291
1 1/2 NPT
(1.61")
42,804
36,634
32,468
29,419
27,065
25,179
23,624
22,315
17,920
15,337
13,593
12,316
11,331
10,541
9,890
9,342
8,465
7,788
7,245
6,798
6,421
5,156
4,413
2 NPT
(2.067")
Data taken and reprinted from Table 12.22 in NFPA 54, 2002 ed.
1/2 NPT
(0.622")
Piping Length,
Feet
120,604
103,222
91,484
82,891
76,258
70,944
66,564
62,876
50,492
43,214
38,300
34,703
31,926
29,701
27,867
26,323
23,851
21,943
20,413
19,153
18,092
14,528
12,435
3 NPT
(3.068")
176,583
151,132
133,946
121,364
111,654
103,872
97,460
92,060
73,927
63,272
56,077
50,810
46,744
43,487
40,802
38,541
34,921
32,127
29,888
28,043
26,489
21,272
18,206
3 1/2 NPT
(3.548")
245,995
210,539
186,597
169,071
155,543
144,703
135,770
128,247
102,987
88,144
78,120
70,782
65,119
60,581
56,841
53,691
48,648
44,756
41,637
39,066
36,902
29,633
25,362
4 NPT
(4.026")
Maximum Undiluted Propane Capacities based on 10 psig first stage setting and 1 psig pressure drop. Capacities in 1000 BTU per hour
TABLE 7A PIPE SIZING BETWEEN FIRST-STAGE (HIGH PRESSURE REGULATOR) AND SECOND-STAGE (LOW PRESSURE REGULATOR)
23
Type
Nominal 3/8"
1/2"
5/8"
3/4"
Type L Tubing
7/8"
1/4"
3/8"
1/2"
5/8"
3/4"
Outside (0.375) (0.500) (0.625) (0.750) (0.875) (0.375) (0.500) (0.625) (0.750) (0.875)
Inside 0.311
0.436
0.555
0.68
0.785
0.315
0.430
0.545
0.666 0.785
Length
(Ft.)
30
299
726
1367
2329
3394
309
700
1303
2205
40
256
621
1170
1993
2904
265
599
1115
1887
2904
50
227
551
1037
1766
2574
235
531
988
1672
2574
60
206
499
939
1600
2332
213
481
896
1515
2332
70
189
459
864
1472
2146
196
443
824
1394
2146
80
176
427
804
1370
1996
182
412
767
1297
1996
90
165
401
754
1285
1873
171
386
719
1217
1873
100
156
378
713
1214
1769
161
365
679
1149
1769
150
125
304
572
975
1421
130
293
546
923
1421
200
107
260
490
834
1216
111
251
467
790
1216
250
95
230
434
739
1078
90
222
414
700
1078
300
86
209
393
670
976
89
201
375
634
976
350
79
192
362
616
898
82
185
345
584
898
400
74
179
337
573
836
76
172
321
543
836
450
69
168
316
538
784
71
162
301
509
784
500
65
158
298
508
741
68
153
284
481
741
600
59
144
270
460
671
61
138
258
436
671
700
54
132
249
424
617
56
127
237
401
617
800
51
123
231
394
574
52
118
221
373
574
900
48
115
217
370
539
49
111
207
350
539
1000
45
109
205
349
509
46
105
195
331
509
1500
36
87
165
281
409
37
84
157
266
409
2000
31
75
141
240
350
32
72
134
227
350
24
3394
Plastic Tubing Size (CTS) and Pipe Size (IPS) (Dimensions in Parenthesis are Inside Diameter)
1/2 in. CTS SDR 1 in. CTS SDR 1/2 in. IPS SDR
7.00 (0.445)
11.00 (0.927)
9.33 (0.660)
30
762
5225
2143
40
653
4472
1835
50
578
3964
1626
60
524
3591
1473
70
482
3304
1355
80
448
3074
1261
90
421
2884
1183
100
397
2724
1117
125
352
2414
990
150
319
2188
897
175
294
2013
826
200
273
1872
778
225
256
1757
721
250
242
1659
681
275
230
1576
646
300
219
1503
617
350
202
1383
567
400
188
1287
528
450
176
1207
495
500
166
1140
468
600
151
1033
424
700
139
951
390
800
129
884
363
900
121
830
340
1000
114
784
322
1500
92
629
258
2000
79
539
221
Table Reprinted from Table 12.15 and 12.16 from NFPA 58, 2001 edition.
Length of
Pipe or
Tubing, Feet
TABLE 7C POLYETHYLENE PLASTIC TUBE AND PIPE SIZING BETWEEN FIRST-STAGE AND SECOND-STAGE REGULATORS
Maximum undiluted propane capacities listed are based on 10 psig first stage setting and 1 psi pressure drop. Capacities in 1000 BTU/HR
25
26
67
58
150
200
608
83
89
97
107
120
140
155
175
197
231
255
287
336
418
156
167
182
201
227
265
292
330
372
434
480
541
632
787
1,450
1 NPT
(1.049")
320
344
373
412
465
543
600
677
763
892
984
1,111
1,298
1,616
2,352
1 1/4 NPT
(1.38")
479
515
560
618
697
814
899
1,014
1,144
1,337
1,475
1,664
1,945
2,422
3,523
1 1/2 NPT
(1.61")
922
991
1,078
1,189
1,342
1,568
1,730
1,952
2,203
2,574
2,841
3,205
3,745
4,664
6,786
2 NPT
(2.067")
Data taken and reprinted from Table 12.24 in NFPA 54, 2002 ed.
40
74
125
400
84
100
42
94
80
350
110
60
51
122
50
46
137
40
300
160
30
250
291
200
10
20
1/2 NPT
(0.622")
Piping Length,
Feet
2,599
2,793
3,036
3,351
3,781
4,418
4,876
5,501
6,207
7,253
8,004
9,031
10,552
13,141
19,119
3 NPT
(3.068")
3,805
4,090
4,446
4,906
5,536
6,468
7,139
8,055
9,088
10,619
11,720
13,223
15,450
19,240
27,993
3 1/2 NPT
(3.548")
Maximum Undiluted Propane Capacities based on 11 inch w.c. setting and 0.5 inch w.c. pressure drop.
Capacities in 1000 BTU per hour
TABLE 8A PIPE SIZING BETWEEN SECOND-STAGE (LOW PRESSURE REGULATOR) AND APPLIANCE
5,301
5,698
6,193
6,835
7,712
9,011
9,945
11,221
12,661
14,793
16,326
18,421
21,523
26,802
38,997
4 NPT
(4.026")
27
115
79
63
54
48
43
37
33
29
26
23
20
18
17
16
216
148
119
102
90
82
70
62
55
50
43
38
34
32
29
0.555
10
20
30
40
50
60
80
100
125
150
200
250
300
350
400
47
32
26
22
20
18
15
14
12
11
9
8
7
7
6
0.436
0.311
Length,
F eet
Inside
0.500
0.375
Outside
3/4
367
253
203
174
154
139
119
106
94
85
73
64
58
54
50
0.68
0.750
5/8
0.625
ACR (Refrigeration)
1/2
3/8
Type
Nomimal
535
368
296
253
224
203
174
154
137
124
106
94
85
78
73
0.785
0.875
7/8
49
34
27
23
20
19
16
14
12
11
10
9
8
7
7
0.315
0.375
1/4
110
76
61
52
46
42
36
32
28
26
22
19
18
16
15
0.430
0.500
3/8
206
141
113
97
86
78
67
59
52
48
41
36
33
30
28
0.545
0.625
1/2
Type L Tubing
348
239
192
164
146
132
113
100
89
80
69
61
55
51
47
0.666
0.750
5/8
535
368
296
253
224
203
174
154
137
124
106
94
85
78
73
0.785
0.875
3/4
Maximum undiluted propane capacites are based on 11 inch w ater column setting and 0.5 inch w ater column pressure drop.
Capacities are in 1000 BTU per Hour.
28
13
15
18
19
23
25
30
31
37
46
62
3/8 Inch
--1/2 Inch
--3/4 Inch
----1Inch
1 1/4 Inch
1 1/2 Inch
2 Inch
10
426
558
927
1,106
1,735
2,168
4,097
4,720
7,128
15,174
34,203
25
262
347
591
701
1,120
1,384
2,560
2,954
4,564
9,549
21,680
30
238
316
540
640
1,027
1,266
2,331
2,692
4,176
8,708
19,801
40
203
271
469
554
896
1,100
2,012
2,323
3,631
7,529
17,159
50
181
243
420
496
806
986
1,794
2,072
3,258
6,726
15,357
75
147
196
344
406
663
809
1,457
1,685
2,675
5,480
12,551
80
140
189
333
393
643
768
1,410
1,629
2,591
5,303
12,154
124
169
298
350
578
703
1,256
1,454
2,325
4,738
10,877
100
101
137
245
287
477
575
1,021
1,182
1,908
3,860
8,890
150
250
300
400
86
77
69
60
118 105
96
82
213
191 173 151
248 222 203 175
415 373 343 298
501 448 411 355
880 785 716 616
1,019 910 829 716
1,658 1,487 1,363 1,163
3,337 2,981 2,719 2,351
7,705 6,895 6,296 5,457
200
53
72
135
158
268
319
550
638
1,027
2,101
4,883
500
Data taken and reprinted from Table 12.29 in NFPA 54, 2002 ed.
Table does not include effect of pressure drop across the line regulator. Where regulator loss exceeds 1/2 psi (based on 13 inch w.c. outlet pressure), do not use this table.
Consult with regulator manufacturer for pressure drops and capacity factors. Pressure drops across a regulator may vary with flow rate. CAUTION: Capacities shown in
table may exceed maximum capacity for a selected regulator. Consult with regulator or tubing manufacturer for quidance.* Table includes losses for four 90-degree bends
and two end fittings. Tubing runs with larger numbers of bend and/or fittings shall be increased by an equivalent length of tubing to the followin equation: L = 1.3n where
L is the additional length (ft) of tubing and N is the number of additional fittings an/or bends.
**EDH - Equivalent hydraulic Diameter - A measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas
capacity of the tubing.
EHD** FLOW
DESIGNATION
CSST
TUBE
SIZE
2,676
1,839
1,477
1,264
1,120
1,015
934
869
815
770
682
618
569
529
10
20
30
40
50
60
70
80
90
100
125
150
175
200
1,106
1,189
1,293
1,427
1,610
1,704
1,816
1,952
2,122
2,342
2,643
3,088
3,845
5,595
2,084
2,240
2,435
2,688
3,033
3,210
3,422
3,678
3,998
4,412
4,978
5,817
7,243
10,539
1 NPT
(1.049")
6,892
6,411
4,279
7,491
8,268
9,329
9,876
10,526
11,314
12,298
13,573
15,314
17,893
22,282
32,420
1 1/2 NPT
(1.61")
4,600
5,000
5,518
6,226
6,591
7,025
7,551
8,208
9,059
10,221
11,942
14,872
21,638
1 1/4 NPT
(1.38")
12,348
13,273
14,427
15,923
17,966
19,020
20,271
21,790
23,685
26,140
29,494
34,461
42,913
62,438
2 NPT
(2.067")
19,681
21,155
22,995
25,378
28,635
30,314
32,309
34,729
37,750
41,663
47,009
54,925
68,397
99,516
2 1/2 NPT
(2.469")
Data taken and reprinted from Table 12.23 in NFPA 54, 2002 ed.
1/2 NPT
(0.622")
Piping
Length, Feet
34,792
37,398
40,651
44,865
50,621
53,590
57,116
61,395
66,735
73,653
83,103
97,098
120,914
175,927
3 NPT
(3.068")
Maximum Undiluted Propane Capacities based on 2 psi setting and 1 psi pressure drop.
Capacities in 1000 BTU per hour
70,964
76,280
82,914
91,510
103,251
109,307
116,499
125,227
136,118
150,229
169,504
198,049
246,625
358,835
4 NPT
(4.026")
29
30
Table 9B Tube Sizing Between Second Stage and Appliance
1053
723
581
497
441
399
342
303
268
243
208
184
167
154
143
10
20
30
40
50
60
80
100
125
150
200
250
300
350
400
434
298
239
205
182
165
141
125
111
100
86
76
69
63
59
0.436
0.311
Length, Feet
Inside
0.500
0.375
Outside
1982
1362
1094
936
830
752
644
570
506
458
392
347
315
290
269
0.555
3/4
3377
2321
1864
1595
1414
1281
1096
972
861
780
668
592
536
493
457
0.68
0.750
5/8
0.625
ACR (Refrigeration)
1/2
3/8
Type
Nomimal
4922
3383
2716
2325
2061
1867
1598
1416
1255
1137
973
863
782
719
669
0.785
0.875
7/8
449
308
248
212
188
170
146
129
114
104
89
79
71
66
61
0.315
0.375
1/4
1015
698
560
479
425
385
330
292
259
235
201
178
161
148
138
0.430
0.500
3/8
1890
1299
1043
893
791
717
614
544
482
437
374
331
300
276
257
0.545
0.625
1/2
Type L Tubing
3198
2198
1765
1511
1339
1213
1038
920
816
739
632
560
508
467
435
0.666
0.750
5/8
4922
3383
2716
2325
2061
1867
1598
1416
1255
1137
973
863
782
719
669
0.785
0.875
3/4
Maximum undiluted propane capacites are based on 2 psi setting and 1 psi pressure drop. Capacities are in 1000 BTU per Hour.
31
13
15
18
19
23
25
30
31
37
46
62
3/8 Inch
--1/2 Inch
--3/4 Inch
----1 Inch
1 1/4 Inch
1 1/2 Inch
2 Inch
72
99
181
211
355
426
744
863
1,415
2,830
6,547
5
50
69
129
150
254
303
521
605
971
1,993
4,638
10
39
55
104
121
208
248
422
490
775
1,623
3,791
15
34
49
91
106
183
216
365
425
661
1,404
3,285
20
30
40
20
30
58
66
118
137
227
265
397
884
2,082
50
19
26
53
60
107
126
207
241
359
805
1,902
60
17
25
49
57
99
117
191
222
330
745
1,761
70
80
15
23
45
52
94
109
178
208
307
656
1,554
25
15
22
44
50
90
102
169
197
286
656
1,554
90
14
20
41
47
85
98
159
186
270
621
1,475
100
200
11
9
15
14
31
28
36
33
66
60
75
69
123 112
143 129
217 183
506 438
1,205 1,045
150
8
12
25
30
53
61
99
117
163
390
934
8
11
23
26
50
57
90
107
147
357
854
250 300
In Thousands of BTU per Hour of Undiluted Propane at a pressure of 11 in. W.C. and a pressure drop
of 0.5-in. w.c. (Based on a 1.50 specific gravity gas.)
Data taken and reprinted from Table 12.28 in NFPA 54, 2002 ed.
**EDH - Equivalent hydraulic Diameter - A measure of the relative hydraulic efficiency between different tubing sizes. The greater the value of EHD, the greater the gas capacity
of the tubing.
* Table includes losses for four 90-degree bends and two end fittings. Tubing runs with larger numbers of bend and/or fittings shall be increased by an equivalent length
of tubing to the followin equation: L = 1.3n where L is the additional length (ft) of tubing and N is the number of additional fittings an/or bends.
EHD** FLOW
DESIGNATION
CSST
TUBE
SIZE
32
10
11
12
13
CU FT/HR
BTU/HR
Figure 9
100
250,000
200
500,000
PROPANE FLOW RATE
300
750,000
400
1,000,000
500
1,250,000
10 PSIG
600
1,500,000
OUTLET PRESSURE
INCHES OF WATER COLUMN
33
REGULATOR SELECTION
TABLE 11
TYPE OF
REGULATOR OR
SERVICE
CAPACITY, BTU/HR
RECOMMENDED
FISHER
REGULATOR
First-Stage1
(Reduces
tank pressure to
10 psig or less)
1,100,000
2,400,000
R122H
R622H
Second-Stage2
(Reduces first stage
outlet pressure to
14" w.c. or less)
875,000 - 1,375,000
2,300,000 - 2,600,000
5,500,000
10,500,000 - 14,500,000
R622
HSRL
S302G
S202G
Integral Two-Stage1
(Combines a high
pressure and a 2nd
stage regulator)
350,000
750,000
R232
R632
High Pressure3
(Reduces tank
pressure to a lower
pressure in excess
of 1 psig)
750,000 -1,200,000
2,625,000 - 5,250,000
13,000,000 - 38,000,000
6,000,000 - 10,775,000
14,000,000
29,295,000 -36,225,000
67C
64 or 64SR
299H
627
630-104/78
99
2-PSI2 Service
(Reduces 1st stage
pressure to 2 psig)
1,400,000
1,500,000
R652E
R622E
34
TWO-STAGE REGULATION
Advantages of Two-Stage Regulation
Uniform Appliance Pressure - Two-staging lets the firststage regulator supply a nearly constant inlet pressure to
the second-stage regulator at the house. This means the
second-stage regulator has an easier time of maintaining
appliance pressure at 11 w.c., thus improving the system
efficiency.
Lower Installation Costs - Smaller pipe or tubing can be
used between the first and second-stage regulators due
to the higher pressure, thus reducing installation and
piping material costs.
Freezeups - Two-stage systems reduce problems due to
regulator freezeups caused by excessive water in gas.
Larger orifices make it more difficult for ice to form and
block the passage area. The expansion of gas at two
different orifices in a two-stage system greatly reduces
the refrigeration effect that causes freezeups. See Fisher
Bulletins LP-18 and LP-24 for more detailed information
on freezing regulators.
Flexibility of Installation - A high pressure regulator can
feed a number of low pressure regulators, thus enabling
the addition of appliances in the future to the same pressure line without affecting their individual performance.
Fewer Trouble Calls - With two-stage regulation, you can
expect fewer trouble calls due to pilot outage or burner
adjustment. This means higher appliance efficiency, lower
service costs and better customer relations.
35
REGULATOR INSTALLATION
Figure 10
FIRSTSTAGE REGULATOR
11 WC
SECONDSTAGE REGULATOR
USUALLY 10 PSIG
TWO-STAGE REGULATION
Two Regulators, one at tank and one at building,
reduce pressure down to burner pressure (11 w.c.)
A two-stage regulator system or an integral two-stage
regulator shall be required on all fixed piping systems
that serve appliance systems at 11 w.c. This includes
R.V., manufactured housing and food service installations.
(Exceptions: Small portable appliances and outdoor
cooking appliances with input ratings of 100,000 BTU/HR
or less, certain gas distribution systems utilizing multiple
second-stage regulators and systems that provide an
equivalent level of overpressure protection).
This standard along with changes in UL 144 requiring
increased regulator relief valve capacity or an overprotection shutoff device, results in the maximum pressure downstream of the second-stage regulator being limited to 2
psig even with a regulator seat failure.
See Fisher Bulletin LP-15 for more detailed information
on regulator operation, installation and maintenance.
36
REGULATOR INSTALLATION
Regulator Vents
Regulators should be installed in accordance with NFPA
58 and any other applicable regulations, as well as the
manufacturers instructions. The following guidelines
shall be followed:
Outdoor Installations - A regulator installed outdoors without a protective hood must have its vent pointed vertically
down, as shown in the drawing.
Figure 11
VENT POINTED
DOWN
37
REGULATOR INSTALLATION
Regulator Vents (cont.)
Indoor Installations - In a fixed pipe system, regulators installed indoors require a vent line to the outside air. A
screened vent assembly (Fisher Type Y602 series or equivalent) must be used at the end of the vent line. The vent
assembly position and location precautions are the same
as for regulator vents. The vent line must be the same size
as the regulator vent and adequately supported. See Figure below.
TO
APPLIANCE
Figure 12
VENT ASSEMBLY
VENT
LINE
BASEMENT
DISCHARGE
OPENING MUST
BE AT LEAST 3
FT FROM ANY
OPENING
BELOW IT
FROM
FIRST-STAGE
REGULATOR
Underground Tanks - A vent tube is required on these installations to prevent water from entering the regulators
spring case. The vent tube connects to the regulator vent
and terminates above any possible water level, see Figure
below. Be sure that the ground slopes away from the tank
dome as illustrated. See Figure below.
Figure 13
Moderately crown surface
around dome. This prevents
water collecting and running
into dome or standing
around dome.
2 Minimum
Regulator
bonnet
closure cap
must be tight.
38
39
40
REGULATOR INSPECTION
The following items should be checked at each gas delivery and at regularly scheduled testing and maintenance
program intervals.
The customer should be instructed to turn off the tank service valve if gas can be smelled, pilot lights fail to stay on,
or any other abnormal situation takes place.
Improper Installation
The regulator vent
Figure 14
must be pointed
down or under a
protective cover.
Regulators without
drip lip vents must
be under a protective cover. Proper
Drip Lip
installation also
minimizes weather
related vent blockage and internal corrosion.
Vent Blockage
Make sure the regulator vent, vent assembly, or vent tube
is not blocked with mud, insect nests, ice, snow, paint, etc.
The screen should be clean and properly installed.
Internal & External Corrosion
Replace any regulator that has had water in the spring case
or shows evidence of external or internal corrosion. Regulators that have been flooded or that have been installed
horizontally which minimizes moisture drainage, or on underground tanks, or in coastal areas are more susceptible
to internal corrosion.
To inspect for internal corrosion:
1) Remove the regulators closing cap and look down into
the spring case (a flashlight may be needed).
2) On some regulators it may be necessary to shut down
the system and remove the adjusting screw and main
spring to adequately see any internal corrosion.
41
Regulator Age
Locate and replace old regulators. Replace regulators
that are over 15 years of age or that have experienced
conditions (corrosion, underground systems, flooding, etc.)
that would shorten their service life. Older regulators are
more likely to fail because of worn or corroded parts. Replace with a two-stage regulator system.
Abnormal Pressure
Regulator disc wear (especially on older regulators) or
foreign material (dirt, pipe scale, etc.) lodged between the
regulator disc and orifice can cause higher than normal
outlet pressure to the appliances at lock up or extremely
low flows. A pressure test of the system will be required to
verify the outlet pressure under these conditions. Replace
the regulator if pressure is high. Check the system for foreign material and clean out or replace pigtails as needed.
Always retest the system after replacing a regulator.
See Fisher Bulletin LP-32 and the instruction manual for
more detailed information on inspecting LP-Gas regulators.
42
TROUBLESHOOTING DOMESTIC
TANK FITTINGS
A periodic inspection and maintenance program is recommended for domestic tank fittings. The following briefly
discusses ways to avoid and correct potential safety problems with the most common domestic fittings.
A more complete examination of this subject can be found
in NPGA Safety Bulletin 306.
Filler Valves
Always use a filling hose adaptor on the end of the hose
end valve during the filling process. After filling the tank,
do not disconnect the Acme coupling from the filler valve
until the Fill valve is closed and all pressure between the
hose end valve and the Fill valve has been bled off. If
pressure discharge continues, the filler valve may have
malfunctioned. DO NOT REMOVE THE FILL HOSE AS
THE INTERNAL PARTS MAY BE BLOWN OUT. If light
tapping does not close the Fill valve, disconnect the Filling
Hose Adaptor from the Hose End Valve, leaving the Filling
Hose Adaptor on the Fill valve. The tank will probably
have to be emptied to replace the Fill valve.
Some Fill valve designs allow the seat disc to be replaced
while the tank is pressurized. On these designs, make
sure the lower back check is still functioning by forcing open
the upper back check with an adaptor. Take care to dislodge only the upper back check and not both back checks.
If there is little leakage with the upper back check open,
then the lower back check is in place and the disc can be
replaced by following the manufacturers instructions.
Relief Valves
DO NOT STAND OVER A RELIEF VALVE WHEN TANK
PRESSURE IS HIGH. A relief valves purpose is to relieve
excessive tank pressure which can be caused by overfilling, improper purging of air from the container, overheating of the tank, improper paint color, or high vapor pressure, to list just a few reasons. Check the tank pressure
gauge if the relief valve is leaking. On a 250 psi design
43
TROUBLESHOOTING DOMESTIC
TANK FITTINGS (cont.)
Relief Valves (cont.)
pressure tank for example, if the relief valve is discharging
between the 240 to 260 psig range, the relief valve is working properly as long as it reseats.
A relief valve that discharges substantially below 240 psig
or that does not reseat when the tank pressure is lowered,
will have to be replaced. Do not attempt to force the valve
closed. Lower the tank pressure by withdrawing gas or
cooling the outside of the tank.
Always keep a rain cap on the relief valve to help keep out
dirt, debris and moisture.
Relief valves, like other pieces of equipment, will not last
forever. Fisher recommends that a relief valve not be used
for over 15 years. Earlier replacement may be required
because of severe service conditions or applicable federal,
state, or local codes.
Liquid Withdrawal Valves
A damaged seat or missing internal parts may allow an
excessive amount of liquid discharge when the closing cap
is loosened. These valves have a bleed hole in the closing
cap to vent liquid before the cap is completely unscrewed.
If a significant amount of the liquid continues to vent from
beneath the cap after 30 seconds, do not remove the cap.
Should only vapor be leaking from under the cap, the connection to the withdrawal valve can usually be made.
There is the possibility of liquid spray while opening the
withdrawal valve with an angle valve-special adaptor. For
this reason, protective clothing should be worn and extreme
care taken throughout the entire process.
Service Valves
Show the customer this valve and tell him to shut it off if
gas is escaping into the house or any other abnormal situation takes place. Check the stem seal and shut off seats
periodically for leakage and replace them if necessary
(empty the tank first).
44
PROPANE
BUTANE
ORIFICE OR
DRILL SIZE
PROPANE
BUTANE
0.008
519
589
51
36,531
41,414
0.009
656
744
50
39,842
45,168
0.01
812
921
49
43,361
49,157
0.011
981
1,112
48
46,983
53,263
0.012
1,169
1,326
47
50,088
56,783
80
1,480
1,678
46
53,296
60,420
79
1,708
1,936
45
54,641
61,944
78
2,080
2,358
44
60,229
68,280
77
2,629
2,980
43
64,369
72,973
76
3,249
3,684
42
71,095
80,599
75
3,581
4,059
41
74,924
84,940
74
4,119
4,669
40
78,029
88,459
73
4,678
5,303
39
80,513
91,215
72
5,081
5,760
38
83,721
94,912
71
5,495
6,230
37
87,860
99,605
70
6,375
7,227
36
92,207
104,532
69
6,934
7,860
35
98,312
111,454
113,566
68
7,813
8,858
34
100,175
67
8,320
9,433
33
103,797
117,672
66
8,848
10,031
32
109,385
124,007
65
9,955
11,286
31
117,043
132,689
64
10,535
11,943
30
134,119
152,046
170,466
63
11,125
12,612
29
150,366
62
11,735
13,304
28
160,301
181,728
61
12,367
14,020
27
168,580
191,114
60
13,008
14,747
26
175,617
199,092
59
13,660
15,846
25
181,619
205,896
58
14,333
16,249
24
187,828
212,935
57
15,026
17,035
23
192,796
218,567
56
17,572
19,921
22
200,350
227,131
55
21,939
24,872
21
205,525
232,997
54
24,630
27,922
20
210,699
238,863
53
28,769
32,615
19
223,945
253,880
52
32,805
37,190
18
233,466
264,673
Propane2,516
Propane1.52
Propane11
Propane0.9
Butane3,280
Butane2.01
Butane11
Butane0.9
45
46
CONVERSION FACTORS
Multiply
By
To Obtain
0.0394
3.2808
0.155
10.764
Inches
Feet
Sq. Inches
Sq. Feet
35.315
0.0353
0.1337
0.061
2.114
0.2642
2.2046
1.1024
Cubic Feet
Cubic Feet
Cubic Feet
Cubic Inches
Pints (US)
Gallons (US)
Pounds
Tons (US)
0.4018
1.733
0.0361
14.50
0.1450
14.222
0.068
0.0353
4.403
Inches w.c.
Inches w.c.
Pounds/sq. in.
Pounds/sq. in.
Pounds/sq. in.
Pounds/sq. in.
Atmospheres
Cubic Feet/hr.
Gallons/min.
0.9478
3.968
3.414
0.00001
0.00948
BTU
BTU
BTU/HR
Therms
Therms
MISCELLANEOUS
Kilojoules
Calories, kg
Watts
BTU
Megajoules
47
CONVERSION FACTORS
Multiply
By
To Obtain
25.4
0.3048
6.4516
0.0929
Millimeters
Meters
Sq. Centimeters
Sq. Meters
0.0283
28.316
7.481
16.387
0.473
3.785
0.4535
0.9071
Cubic Meters
Liters
Gallons
Cubic cm.
Liters
Liters
Kilograms
Tonnes
2.488
0.577
27.71
0.0689
6.895
0.0703
14.696
28.316
0.2271
Millibars
Ounces/sq. in.
Inches w.c.
Bars
Kilopascals
Kilograms/sq. cm.
Pounds/sq. in.
Liters/hr.
Cubic Meters/hr.
1.055
0.252
0.293
100,000
105.5
Kilojoules
Calories, kg
Watts
BTU
Megajoules
MISCELLANEOUS
BTU
BTU
BTU/HR
Therms
Therms
48
Propane:
Butane:
Air:
0.63
0.55
0.77
Propane:
Natural Gas:
Air:
1.15
1.83
1.42
Propane:
Butane:
Natural Gas:
0.81
0.71
1.29
Butane:
Natural Gas:
Air:
0.87
1.59
1.23
-40
-40
30
-1.1
90
32.2
-30
-34.4
32
100
37.8
-20
-28.9
40
4.4
110
43.3
-10
-23.3
50
10.0
120
48.9
-17.8
60
15.6
130
54.4
10
-12.2
70
21.1
140
60.0
20
-6.7
80
26.7
150
65.6
49
Handbook
D450116T012
05/05
LP-10