Sie sind auf Seite 1von 4

TYPE

MODEL

Air-to-air total heat exchange (sensible heat + latent heat)


Partition . Spacing plate-special treated paper
Galvanized steel sheet
No coating
Self-extinguishing heat insulation
Totally enclosed capasitor permanent split-phase induction motor, 4 poles, 2 units
244mm dia. centrifugal fan
Non-woven fabrics filter
-5C to +40C, RH 90% or less
Lossnay ventilation/Bypass ventilation
High (Extra High) -Low switching
80kg
Single phase 220V 50Hz
Lossnay ventilation
Bypass ventilation
Extra High
High
Low
Extra High
High
3.3
3.0
2.6
3.6
3.1
720
650
550
770
670
1000
1000
800
1000
1000
277
277
222
277
277
1365
1130
960
1365
1130
1350
1170
1000
1300
1050
100
0
0
100
0
71
71
73
-

Heat exchange system


Heat exchanger material
Material
Cladding
Paint specifications
Heat insulating material
Motor
Blower
Filter material
Operation environment
Functions
Weight
Power source
Ventilation mode
Notch
Current
[A]
Power consumption
[W]
[m3/h]
Air volume
[L/s]
SA
Fan speed [min-1]
RA
External static pressure
[Pa]
Temperature exchange efficiency [%]
Enthalpy exchange efficiency for coolig [%]
(OA 34.5CDB 75.1%RH RA 26.5CDB 64.6%RH)
Noise [dB]

VOLUME
SIGN

CEILING CONCEALED LOSSNAY


LGH-100RBD-HK-2

(Measured at 1.5m under the center of


Lossnay)

Low
2.6
550
800
222
960
880
0
-

60

60

62

40

39

37

41

40

38

Under 9.0A
10M1 or more (DC500V megger)
AC 1500V 1 minute
Non-woven fabrics filter Efficiency: ASHRAE colorimetric method 65%

Starting current
Insulation resistance
Dielectric strength
HE filter (Option)

Characteristic curve

500

External static pressure


(Pa)

400

Extra High

*Attention

300

1. The current, input and efficiency are


based on the above air volume.
2. Notch can be switched between High
and Low.
The main unit switch must be used to
select the Extra High notch.

High
Low

200

100

200

400

600

800

1000

1200

(m3/h)
0

50

100

150
200
Air volume (L/s)

250

300

350

* Specifications subject to change without notice.

SPECIFICATIONS

DATE
15-May-05

TYPE
MODEL
NUMBER

P. 11/19

CEILING CONCEALED LOSSNAY


LGH-100RBD-HK-2
No. ND104A48

1/4

Drawings and Dimensions


RA intake

EA outlet

OA intake

250

250

Duct attachment

250

250

150

155

RA
(return air)

Damper plate

Ceiling suspension fixture

50

Air exhaust fan

660

25

Air supply fan

Heat exchanger
(Lossnay core)

HE FILTER
(Option)

1480

Cable
SA
(supply air)

638

250

445

256

SA outret

Air filters

30

155

Control box

RA duct cover
Cable
Maintenance panel

610

95

137 161

30
OA
(outside air)

800

EA
(exhaust air)

*Attention

UNIT

SCALE

mm

N.T.S

1. If condensation is expected to dorm, the insulated ducts should be used dor OA/EA pipes.
2. Effective area od SA opening : 990cm2
3. Effective area od RA opening : 595cm2

* Specifications subject to change without notice.

DRAWINGS AND DIMENSIONS

DATE
15-May-05

TYPE
MODEL
NUMBER

P. 12/19

CEILING CONCEALED LOSSNAY


LGH-100RBD-HK-2
No. ND104A48

2/4

Schematic

*Connect thick line and dashed line


Lossnay unit
PE

Power source
-50Hz 220V

TM1
L

CN8-2

RED

CN8-1
BROWN
BLACK
GREY
YELLOW

CN10
N

BLACK

Breaker
TR

High

SW4

RED
(Supply fan)
ORANGE
BLUE
M2
WHITE

E. High
WHITE
WHITE

CN1

High

SW3

YELLOW

RED
(Exhaust fan)
ORANGE
BLUE
M1
WHITE

E. High

CN7
RED

GM

RED
ORANGE
BLUE
WHITE

CN9

C
BROWN

LS
CN2

BROWN

SW2

SW1
TM3
10
X7

TH1
(OA)
TH2
(RA)

BLACK

CN5
GREY

BLACK

GREY

BLACK

BLUE

BLACK

BLUE
ORANGE
ORANGE

Control box

8
X8
7
CN6
TM2

Transmission
line

12V, 24VDC
Mr.SLIM
(non-polar)
1

Malfunction monitor output


Max AC100V 1A Min AC100V 100mA
AC200V 100mA
AC200V 1A
DC 5V 100mA
DC 24V 1A

Transmission line
(non-polar)

External
control input
1

Operation monitor output


Max AC100V 2A Min AC100V 100mA
AC200V 100mA
AC200V 2A
DC 5V 100mA
DC 24V 2A

Tr

an

sm

iss

ion

lin

Timer control
(a-contact)

*Attention

Main unit
(second)
Remote control switch

TM1 to TM3 connects in the place on install.


(optional parts)
PZ-41SLB-E
TM1 to TM3 are screw terminal connection.
*External control input can not connect with the "Sub" set Lossnay unit.
*Output from Terminal No.3 on TM2 is DC12V, 10-15mA use a-contact that is available to use in that voltege.

Mark explanation
MARK
M1
M2
C
GM
LS
TH1
TH2
SW1
SW2
SW3
SW4

NAME

MARK
NAME
TM1
Terminal block (power source single phase 220V)
TM2
Terminal block (Transmission line and external
control input of the Lossnay)
TM3
Terminal block (Monitor output)
TR
Control circuit transformer
X7
Relay contact (For operation monitor output)
X8
Relay contact (For malfunction monitor output)

Exhaust fan
Supply fan
Capacitor
Motor for Bypass movement
Microswitch
Thermistor for outside air
Thermistor for return air
Switch (main/sub change)
Switch (test-movement)
E. High-High select switch (exhaust fan)
E. High-High select switch (supply fan)

* Specifications subject to change without notice.

SCHEMATIC

DATE
15-May-05

TYPE
MODEL
NUMBER

P. 13/19

CEILING CONCEALED LOSSNAY


LGH-100RBD-HK-2
No. ND104A48

3/4

NC Curves
50Hz
Background noise : 25dB or less (A range)
Measurement site : Anechoic chamber
Operation conditions : Lossnay ventilation

1.5m

Measurement
point

90
Extra-high
High
Low

Octave band sound pressure level (dB)

80
70

NC-70

60

NC-60

50

NC-50

40

NC-40

30

NC-30

20
10

NC-20
NC-10
63

125

250

500

1k

2k

4k

8k

Octave band centre frequency (Hz)

* Specifications subject to change without notice.

NC CURVES

DATE
15-May-05

TYPE
MODEL
NUMBER

P. 14/19

CEILING CONCEALED LOSSNAY


LGH-100RBD-HK-2
No. ND104A48

4/4