CHEVRON PACIFIC INDONESIA


PG&T DEPARTMENT INFRARED SOUTH
THERMOGRAPHIC INSPECTION REPORT

Identification Details

Status

<Fault>

<Location>

Minas

<Substation>

5B

<Equipment_No>

Feeder 02

<Tag_No>

5D-30 (Well 5D-93 &


5D-83)

<Equipment_Type>

FCO

<Equipment_Part>

Fuse & Connection

Area 1, 2, 4, 6

<Longitude> E

<Latitude> N

10125.004'

0047.003'

Celsius
90,00 50,08

<Level_Severity>
<Load_Phase> A

Medium
<Object_Distance> m
7
Area

Temp

38,7C

45,00

50,1C

40,00

34,5C

35,00

40,3C

30,00

34,6C

44,6C

4
Max.
40,28

3
Max.
34,51

25,00
20,00

1
Max.
38,75

15,00

5
Max.
34,57

2
Max.
50,08

6
Max.
44,59

-20,00 13,74

Thermoteknix Miricle 17:09:40 14/07/2014 e : 0,83 Bg : 27,00C

Analysis
1. The bottom side of Fuse Cut Out shown in Area 2 was 50.1C (15.6C hotter than
reference Area 3 (34.5C), while Area 2 was 38.7C (4.2C hotter than reference Area 3
(34.5C), but did not exceed above 75C for temperature limit baseline refer to Table
1(b): Reference Conditional Explanation of Symmetrical Load Electrical (Bare
Overhead Conductors)).
2. The top side of Fuse Cut Out shown in Area 6 was 44.6C (10.0C hotter than reference
Area 5 (34.6C), while Area 4 was 40.3C (5.7C hotter than reference Area 5 (34.6C),
but did not exceed above 75C for temperature limit.
3. Possible causes of local temperature increase are one or combination of these; oxides,
dirty materials, improper contact, physically defect or internal problems.
Note: Dismantle, clean up and check all suspected
fuses, fingers & their terminations. Repair/replace if
necessary. Retighten/re-torque/re-align all connections
when reinstalling.

Recommended Action:
Requires attention

Thermographer/ Analyst

Project Manager

Contractor
Riky Ramadhan

DIMENSI BARUMAS PERDANA

Sugiharno S.

Agustinus Wahyu Sarjono