Identification Details
Status
<Fault>
<Location>
Minas
<Substation>
5B
<Equipment_No>
Feeder 02
<Tag_No>
<Equipment_Type>
FCO
<Equipment_Part>
Area 1, 2, 4, 6
<Longitude> E
<Latitude> N
10125.004'
0047.003'
Celsius
90,00 50,08
<Level_Severity>
<Load_Phase> A
Medium
<Object_Distance> m
7
Area
Temp
38,7C
45,00
50,1C
40,00
34,5C
35,00
40,3C
30,00
34,6C
44,6C
4
Max.
40,28
3
Max.
34,51
25,00
20,00
1
Max.
38,75
15,00
5
Max.
34,57
2
Max.
50,08
6
Max.
44,59
-20,00 13,74
Analysis
1. The bottom side of Fuse Cut Out shown in Area 2 was 50.1C (15.6C hotter than
reference Area 3 (34.5C), while Area 2 was 38.7C (4.2C hotter than reference Area 3
(34.5C), but did not exceed above 75C for temperature limit baseline refer to Table
1(b): Reference Conditional Explanation of Symmetrical Load Electrical (Bare
Overhead Conductors)).
2. The top side of Fuse Cut Out shown in Area 6 was 44.6C (10.0C hotter than reference
Area 5 (34.6C), while Area 4 was 40.3C (5.7C hotter than reference Area 5 (34.6C),
but did not exceed above 75C for temperature limit.
3. Possible causes of local temperature increase are one or combination of these; oxides,
dirty materials, improper contact, physically defect or internal problems.
Note: Dismantle, clean up and check all suspected
fuses, fingers & their terminations. Repair/replace if
necessary. Retighten/re-torque/re-align all connections
when reinstalling.
Recommended Action:
Requires attention
Thermographer/ Analyst
Project Manager
Contractor
Riky Ramadhan
Sugiharno S.
01 Fault at FCO 5D-30 (Well 5D-93 & 5D-83) - Substation 5B Feeder 02 Crew 01 - 14-07-2014