Scientific Background
Dipl.-Ing. (FH) Electrical Engineering
Professional Background
10 years at Maschinenfabrik Reinhausen GmbH
Technical Service / Troubleshooting
07.06.2013
Page 2
Agenda
6.
7.
8.
9.
Diagnostics
07.06.2013
Page 3
U1
Mwg = Main winding
Cwg = Coarse winding
Rwg = Regulating winding
LU = Diverter switch insert
Mwg
555 wdgs
Cwg
120 wdgs
Transformer:
OLTC:
Step voltage:
%
40 MVA, 110 kV 16
/ 21 kV
17.6 kV
M III 350 Y 123/C 10 19 1G
17.6 kV : 9 steps 1.955 kV/step 1.78 %
U2
21 kV
129 wdgs
Rwg
108 wdgs
12 wdgs/step
Nominal:
Example 1:
Example 2:
LU
2
1
U1 = N1
U2 N2
U2 = 21 kV = constant
U1 = 110 kV
N1 = 110 kV 129 wdgs / 21 kV = 675 wdgs
U2 = 110 kV 129 wdgs / 675 wdgs = 21.02 kV
U1 = 116 kV
N1 = 116 kV 129 wdgs / 21 kV = 711 wdgs
U2 = 116 kV 129 wdgs / 711 wdgs = 21.05 kV
07.06.2013
Page 4
Vectorial diagram
Contact movement
A,B
Main contacts
(only for V III 350 Y/,
V III 500 Y / ,
V I 350, V I 700)
OILTAP
Type M since 1972
a,b
Main switching
contacts
a1, b1
Transition contacts
Ra, Rb
Transition resistors
Ua, Ub
Voltages of tappings
Ust
Step voltage
U, I
Voltage, current of tapchanger terminals
07.06.2013
Page 5
Vectorial diagram
Contact movement
A,B
Main contacts
(only V III 350 Y/,
V III 500 Y/ ,
V I 350, V I 700)
OILTAP
Type V since 1979
a,b
Main switching
conttacts
a1, b1
Transition contacts
R
Transition resistor
Ua, Ub
Voltages of tappings
Ust
Step voltage
U, I
Voltage, current of
tap-changer terminals
07.06.2013
Page 6
VACUTAP
Type VR since 2004
e. g. VRF III 1300 10 steps
3-pole
Star connection
Insulation to ground
Um = 76 kV
Switching sequence
Transition resistor
07.06.2013
Page 7
VACUTAP
Type VV since 2000
e. g. VV III 400
10 steps
MTS
MSV
TTS
TTV
STC
R
IC
Uwe Seltsam, Maschinenfabrik Reinhausen GmbH
07.06.2013
Page 8
IB
IB = Operating through-current
IK = Circulating current
R = Transition resistor
07.06.2013
Page 9
or
no. of operations
Neutral-point application
after every 5 7 years
after every 50,000 150,000 operations
Delta application
after every 2 4 years
after every 20,000 100,000 operations
07.06.2013
Page 10
07.06.2013
Page 11
Calculation
No. of ops. specification for parts change
Calculation algorithm for oil carbonization
Calculation algorithm for single and difference wear
Maintenance time
Visual presentation
Present condition 0 ... 100 %
Prediction for 100 % moment
Semaphore function green/yellow/red
Red signal prevents additional operations
by the motor-drive unit, but it is not
integrated into the tripping circuit for the
circuit breaker.
Front panel Tapguard 260
Uwe Seltsam, Maschinenfabrik Reinhausen GmbH
07.06.2013
Page 12
TCB
TCA
MCA
MCA
MCB
MSCA
MSCB
TCA
TCB
variable value
Contact system of diverter switch type M
variable value
approx. 6 ms
25 30 V
Step voltage
Ust
Cu or CuW sintered material
SG
MCA
MSCA
TCA
TCB
SCB
MCB
MC = Main contact
MSC = Main switching contact
TC = Transition contact
R
= Transition resistor
SG = Spark gap
Max. permissible single wear = 4 mm
Max. permissible difference in wear = 2.5 mm
07.06.2013
Page 13
Depending on wear
Arc contacts, etc.
Preventively
Cover gasket, etc.
Up-dating
Tap selector:
Maintenance after every 1.0 to 1.2 million operations,
depending on OLTC type
07.06.2013
Page 14
Criterion:
Heat removal from the transition resistors must
not be restricted by oil carbonization.
07.06.2013
Page 15
1)
2)
3)
4)
07.06.2013
Page 16
Motor-drive unit
Visual check
Heater in operation
Door closed
Protective relay
Functional check
together with transformer
protection test
Reliability (effectiveness)
Oil monitoring
Disconnected
transformer
07.06.2013
Page 17
Dielectric strength*
Water content
Neutral-point application
Minimum 30 kV / 2.5 mm
Maximum 40 ppm
Use in auto-transformer or
regulation in delta winding
Minimum 40 kV / 2.5 mm
Maximum 30 ppm
Minimum 30 kV / 2.5 mm
Maximum 30 ppm
The temperature of the oil sample must be measured at the time when the oil was taken.
The values specified for dielectric strength apply to oil temperatures of 20 5 C at the time of
evaluating the oil sample.
Recommendation:
Dielectric strength of > 50 kV / 2.5 mm for new insulating oil that must be filled in after maintenance.
07.06.2013
Page 18
Ask the OLTC manufacturer if other insulating liquids (ester liquids, etc.) are used.
07.06.2013
Page 19
Facts:
Diverter switch oil of OILTAP is a mixture of oil,
carbon deposits and humidity
Water absorption of carbon deposits is several times
as high as water absorption of oil
Carbonized oil with inadmissibly high water content puts
insulation distances at risk which are exposed to voltage
stress
Effects:
Electrical-field distortion with local discharges
Thermal decomposition of surface of insulating material
Creepage paths
Breakdown of insulating distance with flashover
Switching shaft
Example of creepage paths
07.06.2013
Page 20
Vacuum interrupter
07.06.2013
Page 21
RS2001
Burst membrane
MPreC
Uwe Seltsam, Maschinenfabrik Reinhausen GmbH
07.06.2013
Page 22
9. Diagnostics
07.06.2013
Page 23
9. Diagnostics
No. of ops.
Oil
temp.
[C]
H2
CH4
C2H6
C2H4
C2H2
CO
CO2
16
127
31
70
359
10
344
17500 39400
29000
50
17796 12205
3642
36170 102172
330
3032
10800 48100
50000
22
13553 13000
4200
50000 103000
317
7733
4900
O2
N2
25300
07.06.2013
Page 24
9. Diagnostics
Torque measurement:
Integral part of monitoring TM100 and
TG260, including assessment (semaphore
function). Online procedure.
Torque measurement directly on OLTC head
with mobile measuring device.
Example of torque progress
07.06.2013
Page 25
Summary
Maintenance
maintenance intervals of the respective on-load tap-changer shall be observed at any time to
ensure trouble-free operation of the transformer. Original spare parts and trained service staff
have also be seen as mandatory.