Sie sind auf Seite 1von 2

Formula

Horsepower DC: Volts x Amps x Efficiency)/746


Horsepower AC: (Volts x Amps x 1.732 x Eff x PF)/746
Watts DC: Volts x Amps
Watts AC: Volts x Amps x PF x 1.732
Kilowatts: (Volts x Amps x PF x 1.732)/1000
Amperes DC: Watts / Volts
Amperes AC: (746 x Horsepower)/(Volts x eff x PF x 1.732)
KVA: (Volts x Amps x 1.732)/1000
Fan Motor HP: (CFM x Pressure (lbs/sq ft))/(33000 x eff)
Pump Motor HP: (GPM x Head (ft) x Specific Gravity)/(3960 x eff of pump)

How to Calculate/Find the Rating of Transformer in kVA (Single Phase and Three
Phase)?

Rating of a Three phase transformer in kVA


kVA = (3. V x I) /1000

In simple words,
Transformer rating in kVA = 100 kVA

Primary Voltages = 11000 = 11kV


Primary Current = 5.25 A

Secondary Voltages = 415V


Secondary Current = 139.1 Amperes.

KVA = (3 x V x I)/1000

(Primary voltage & primary current)


KVA =(3 x 11000V x 5.25A)/1000 = (1.732 x 11000V x 5.25A)/1000 = 100,025
VA/1000 = 100kVA
Or
(Secondary voltages & Secondary Current)
KVA= (3 x 415V x 139.1A)/1000 =( 1.732 x 415V x 139.1A)/1000= 99,985 VA/1000 =
99.98kVA