Beruflich Dokumente
Kultur Dokumente
Render System
2
3
4
5
System Build up
Physical Properties
Key Considerations - Designers
Key Considerations - Installers
Installation Procedures
Detail Solutions
Components & Accessories
Detail Drawings NBT DIFFUTHERM
NBT Product Overview: Insulation
6
7
8
9
10
13
14
18
23
Content
NB
Performance Guide
at
TN
u r al I n
s u la ti o n P r o d
u cts
for
Airtightness
Principle
A
building are
envelope
be airtight
when all ventilaopenings
closed.should
The design
requirement
for air
tion
openings
are
closed.
The
design
requirement
for
changes has to be provided by opening the windows
air
changesother
has tocontrollable
be provided ventilation
by opening openings
the windows
manually,
or
manually,
other controllable
ventilation
suitable mechanical
ventilation
systems. openings or suitable mechanical ventilation systems.
When assessing the air permeability of the building
When
assessing
the air permeability
of the
enenvelope,
the following
aspects must
be building
considered
velope,
the following aspects must be considered sepaseparately:
rately:
Individual building components must exhibit the
necessary
Individual airtightness
building components
mustwith
exhibit
the
in accordance
building
necessary standards
airtightness in accordance with building
component
component
standards
The
overall air
permeability of the building envelope
must
The overall
air
permeability
of the building
meet the limiting
and target
values ofenvelope
building
must meet the limiting and target values of building
regulations
regulations
Local
air permeability (leaks, primarily on the inside)
can
Local
(leaks,because
primarily
onallow
the inside)
leadairtopermeability
moisture damage
they
moist
can
lead
to
moisture
damage
because
they
allow
interior air to infiltrate the construction
moistair
interior
air to infiltrate
the construction
Local
permeability
and associated
draughts can
have
Locala air
permeability
andonassociated
draughts
detrimental
effect
the thermal
comfortcan
of
have
a detrimental
effect
theto
thermal
comfort
of
the
occupants
and can
alsoonlead
increased
energy
the
occupants
and
can
also
lead
to
increased
enconsumption
ergy consumption
Air permeability
Air permeability
The air
permeability of the
the building
building envelope
envelope isis specified
specified
The
air permeability
of surface
surface area
by the ratio of
area of
of the
the building
building to the hourly
PaPa
pressure
difference.
In Part
air exchange
exchangerate
ratefor
fora a5050
pressure
difference.
In
L Building
Regulations
an airanpermeability
of 10.0
m3 /
Part
L Building
Regulations
air permeability
of 10.0
/h 2is/hallowed,
for 0.6
ESTAir
best
practice for CSH
3 an
m23/m
is allowed.
changes/hour
at 50level
Pa presair permeability
of 3.0
sure
for Passivhaus
. m3/m2/h, for higher CSH levels
an air permeability of 1.0 m3/m2/h and for PASSIVHAUS
an
air permeability
of 0.6 m3/m2/h are accepted as the
Design
and construction
maximum.
To ensure that the building envelope has the necessary
degree of airtightness, an airtightness layer is required
Design
and
construction
over all parts
of the
construction on the warm side of
the thermal insulation. Generally, the vapour control
To ensure
that the
building
envelope
has the necessary
layer
and airtight
layer
functions
are combined
and prodegreee
airtightness
layer type
is required
vided
by of
oneairtightness,
membrane,an
sheeting
or a board
mateover(OSB,
all parts
of the board,
construction
on the
warm fibreboard,
side of the
rial
multi-ply
plywood,
gypsum
thermal
insulation.
the vapour
control layer
etc.). Such
materialsGenerally,
require fixings
and permanent
air
and airtight
funtions
are combined
and of
provided
by
tight
seals atlayer
joints
and junctions
in the form
adhesive
one membrane,
sheeting
or a board
material
tape,
glue, mechanical
fasteners
etc.,type
or may
need (OSB,
to be
multi-ply
board,
plywood,
held
in place
with
battens.gypsum fibreboard, etc.). Such
materials
require
fi
xings and permanent
air tight
seals at
Rock wool and glass-fibre
boards, wood
fibreboards,
joints andpanelling,
junctions planking,
in the form
of adhesive
tape,
glue,
wooden
acoustic
linings,
building
mechanical
fasteners
may need
to bethe
held
in place
papers,
plaster
boardetc.,
etc.orcannot
achieve
degree
of
with battens.required for modern buildings.
airtightness
Principle
A building envelope should be airtight when all ventilation
adjoining
Testing
elements such as
In
order doors
to
windows,
achieve
an
airand foundations. The installation of several layers each of
tight building
measures
checks
during
which
are only envelope,
partially airtight
will notand
result
in a building
construction
and
after
completion
of
the
building
are
with an adequate degree of sealing.
necessary. If the airtightness layer has been properly
designed
Testingand planned, expensive blower door measurements, leak detection by means of smoke tests or IR
thermography,
andan
unnecessary
costs
of repairs
can be
In order to achieve
airtight building
envelope,
measures
saved.
and checks during construction and after completion of
the building are necessary. If the airtightness layer has
A
properly
designed
building
will
been
properly
designedand
and constructed
planned, expensive
blower
fulfil
airtightness
requirements
without
the
need
for
door measurements, leak detection by means of smoke
further
special
work.
NBT
systems
provide
proper
tests or IR thermography, and unnecessary costs of repairs
design
and site support to ensure that the correct
can be saved.
levels of airtightness are achieved.
A properly designed and constructed building will
fulfil airtightness requirements without the need
for further special work. NBT systems provide proper
design and site support to ensure that the correct
levels of airtightness are achieved.
Summer Overheating
40
External amplitude
Temperature C
45
35
30
25
Internal amplitude
20
15
Temperature on the inside surface
10
6h
Day 1
9h
12h
15h
18h
21h
24h
3h
6h
Day 2
hours after
the- external
solar radiation peak this
combination of low6-D 12
(k-value)
(0.038
0.047 W/mK),
means (2100J/kgK)
that the decrement
delay of a wall or roof conspecific heat
and for insulation
As part of a buildings design it ishigh
important
to capacity
struction
should
be
between
6 - 12farhours.
boards a high
density (140 - 240 kg/m). These values
consider the effects of summer overheating
control, particularly when there are rooms
in roofs
or
exceed
any conventional
insulation material. This means
In
terms
of achieving
theseasatisfactory
values, an insuwhere the construction system is lightweight
such
that with NBT PAVATEX woodfi
bre insulation
roof or
lation material that has a high thermal mass is needed
as steel or timber frame.
lightweight structure such as lightweight frame building
to produce better values. A combination of density, thercan perform as though it was a much more massive
mal conductivity and specific heat capacity is required.
Summer overheating is caused by any orstructure.
a combination
of three reasons:
NBT PAVATEX woodfibre boards have an excellent
high internal gains from appliances, people, maThe consequence is the
reduction ofofinternal
temperatures
combination
low (k-value)
(0.038 - 0.047 W/mK),
chines etc.
by 4 C or more in high
summer
compared
to a room(2100J/kgK)
which
specific
heat
capacity
and for insu high solar gain through windows due to poor summay
have
the
same
U-value
but
conventional
insulation.
lation
boards
a
high
density
(140
240
kg/m).
These
mer shading
values far exceed any conventional insulation mate heat passing directly through the walls
rial. This means that with NBT PAVATEX woodfibre
insulation a roof or lightweight structure such as
The solution to the first is to reduce the gains or ventilightweight frame building can perform as though it
late, the second requires better shading, and the third
was a much more massive structure.
is solved by reducing peak heat gain to the room by
changing the decrement delay and factor.
The consequence is the reduction of internal temperatures by 4 C or more in summer compared to a room
which may have the same U-value but conventional insulation.
Leveling render
(if required)
HERM
DIFFUT
HERM
Masonry substrate
DIFFUT
HERM
DIFFUT
NBT DIFFUTHERM
1.
2.
3.
3.
4.
1. 2. 3.
4.
5.
NBT DIFFUTHERM
100 mm
120 mm
140 mm
160 mm
180 mm
200 mm
U-Value [W/mK]
Admittance [W/mK]
Sound insulation ca. [dB]
Decrement delay [h]
0.35
1.48
52
15.25
0.25
1.52
53
17.53
0.22
1.52
54
18.86
0.20
1.52
54
20.15
0.18
1.
55
21.43
NBT DIFFUTHERM
100 mm
120 mm
140 mm
160 mm
180 mm
200 mm
0.33
1.48
52
21.60
0.24
1.52
53
23.92
0.21
1.52
54
>24
0.19
1.52
54
>24
0.17
1.51
55
>24
0.28
1.51
53
16.31
0.28
1.48
53
21.60
System Guarantee:
Airtightness:
Building Height:
Fire Resistance:
Render:
DPC-Level:
Movement Joints:
Weather Tightness:
Rain Penetration:
Colours:
Please be aware, when choosing colours for the top
coat, that it must be taken into account that the LIGHTBRIGHT RELATION VALUE is not less than 20.0. This
is due to the fact that dark colours can be directly linked
to elevated thermal stress, which leads to an increased
risk for cracks.
Please check page 29 and 30 of the BAUMIT Product
Brochure Render, Plasters, Mortars for further
information and a wide range of different colours.
Grain size:
Coarse-grained finishes (2 - 5 mm grain sizes) are
preferred for long-term durability and appearance.
Apply equalisation paint to the finish render coat to avoid
discolouration from uneven drying.
To select paints for applying to the finished surface
without significant reduction of the vapour permeability of
the RENDER system, refer to NBT.
Boards:
Renders:
1
2
3
4
5
6
7
8
9
General:
Fixings:
Access:
Adverse Weather/Storage:
Cutting:
The boards are easily cut with any of the following tools:
NBT PAVATEX jigsaw blades (bayonet fitting to suit
most makes of jigsaws)
Standard wave edge insulation knife
Circular saw, hand-held or bench mounted with a
fine, cross-cut, tungsten tipped blade
Safety goggles and dust mask must be worn during
cutting to protect the user from the small, nonhazardous,
dust particles.
10
50
NBT recommends fixings - Ejot NTU (min. embededment 35mm) for solid substrate
- Ejot STR-U (min embedment 35mm) for soft substrate.
Remove pin for hammer in NTU fixings and insert plug into well
cleaned drill hole (depth guage recommended to achieve embedment
+ 10mm) until washer meets surface of diffutherm, hammer in so that
washer plate rests just below surrounding surface of diffutherm
Fitting:
Above plinth area: Fix the base rail and corner rail
above DPC to substrate, using 2 fixing per meter. Rail
connector clips may be fitted at all rail joints. Attach clipon drip profile to complete run of base and corner rail.
Additional Meshing:
Bed the mesh in NBT base coat mortar and then apply
the main meshed render layer.
Reveals:
Fully paste the rear side of the reveal boards using NBT
base coat and trowel through using a tooth trowel. Apply
a ISO-BLOCO sealing tape along the edge of the board
and place the board tightly up against the window or
door frame. if required use reveal fixings (Ejot DDA)
Render System:
11
12
NBTDIFFUTHERM
MASONRY EWI
Render
NBT
Detail- Solutions
Detail Solutions
1
Edges:
1 Edges:
Key to Details
Weather tightness with use of ISO-BLOCO sealing
Weather tightness with use of ISO-BLOCO sealing
tape
tape
1 Edges:
Key to Details
2
Plinth:
Weather
tightness
with
use
of
ISO-BLOCO
sealing
2
Plinth:area 300 mm
Plinth
tape 300 mm
Plinth
Use
plintharea
& perimeter insulation board (XPS) in
1
Use
plinth & perimeter insulation board (XPS)
plinth
area
2 in plinth
Plinth:area
Use base rail at bottom of NBT DIFFUTHERM
Plinth
300 mm
Use base
rail area
at bottom
of NBT DIFFUTHERM
1
Use
plinth
&
perimeter
insulation board (XPS)
3
Window and door:
in
plinth
area
with use of ISO-BLOCO sealing
3 Weather
Windowtightness
and door:
Use
base
railwith
at bottom
NBT DIFFUTHERM
tape
and
APU-rails
(window
frame
sealing
bead)
Weather tightness
use
of of
ISO-BLOCO
sealing
Usetape
window
sills with up stands. For wind driven
and APU-rails
rain
exposer
zone
3&4
use
expansion resistance sill
Window
and
door:
3 Use
window
sills
with
upstands
ends. Contact
NBT tightness
for details.
Weather
use to
of window
ISO-BLOCO
NBT DIFFUTHERM board with
pattern
andsealing
NBT DIFFUTHERM
board
pattern
to
window
and
tape and
APU-rails
door opening
(see
below)
door opening
below)
Use(see
window
sills with upstands
NBT DIFFUTHERM board pattern to window and
door opening (see below)
3
3
3
3
Board Pattern:
Board Pattern:
NOTE:
PLEASE FIND DETAIL DRAWINGS AT THE END OF THIS MANUAL
NOTE:
Set outNOTE:
NBT
DIFFUTHERM
boards so that
board edges
DO NOTAT
coincide
with the
PLEASE
FIND STANDARD
DETAIL
DRAWINGS
THE END
OF
FIND
DETAIL DRAWINGS AT THE END OF THIS MANUAL
cornersPLEASE
of
wall
openings.
THIS MANUAL. Contact NBT for full detail manual or for specific
detail help.
out NBT
boards
that board
NOT
with the
AlwaysSet
ensure
that DIFFUTHERM
the vertical joints
areso
staggered
by edges
at leastDO
200
mmcoincide
between
corners
of
wall
openings.
courses and
is supported
on at so
least
twoboard
studs.edges DO NOT
Set that
out each
NBT board
DIFFUTHERM
boards
that
13
NBT
MASONRYEWI
- Render
NBT DIFFUTHERM
Components
& Accessories
Components & Accessories
BAUMIT MC 55 W
BAUMIT HM 50
BAUMIT SEP01
BYSEP02
BAUMIT SEP02
BYSEP03
BAUMIT SEP03
BYSFWHITE
Please check www.natural-building.co.uk or contact NBT for other top coat finishes
14
NTU
STR-U
DDA
15
NBTDIFFUTHERM
MASONRY EWI
- Render
NBT
Components
& Accessories
Components & Accessories
Render Stop
stop profi
le
System
Profile
Similar in appearance to the base rail the stop end profile
is used where the NBT DIFFUTHERM system finishes up
against another wall of a different type, e.g. against timber
or rainscreen cladding or a masonry wall. They are fixed
vertically against the other wall with ISO-BLOCO sealing
tape between the profile and wall to ensure the joint is
sealed against the weather. The lip on the edge of the
profile is used to provide a solid edge for the render to
finish up to. Length 2500 mm.
BYY9246
BYY9248
BYY9250
Movement beads
Applied where a movement joint occurs in the structure.
The boards must be spaced apart over the joints and the
bead set in NBT base coat mortar across the joint. Provides
a neat joint to take up movement of the render. Length
3000 mm.
BYYWE79/79
BYYWE80/80
BYY2031
16
NBT
MASONRY EWI
- Render
NBT DIFFUTHERM
Components
& Accessories
Components & Accessories
Self-Adhesive
Self adhesive
Strip
Strip
Removable
Protection
Strip
3726
Self-Adhesive
Self
Bandadhesive
Band
APU Rail
Fixed to door or window frames tight against the edge of
the NBT DIFFUTHERM. The render is finished flush with the
outside of the APU rail and the sacrificial strip removed.
Provides a secondary waterproof seal with no additional
mastic required. Self-adhesive band can be removed to
enable a protective sheet to be applied to cover door and
windows - this is then discarded by breaking away the
removable protection strip. Length 2600 mm. Packed in
bundles of 50.
BYY3726
FXISO-600 6-15
Reinforcing mesh
Small, 300 mm x 300 mm patches are first applied diagonally
to the corners of windows and doors. When the specified
render thickness has been applied the reinforcing mesh
is applied into the surface of the wet render. The mesh
should overlap 100 mm where it meets. Prevents cracking
and increases flexibility. Roll: 50 m length, 1 m width
BYYR131
Glassfibre mesh
17
Re-EWI-R-WR-01
1.
2.
3.
4.
5.
6.
KEY TO COMPONENTS
For exposed soffit extend the Diffutherm board to the underside of flashing membrane butt to roof
insulation and render to finish.
Please refer NBT Retrofit Roof Detail Manual for roof specifications.
NOTES
Ensure the Diffutherm board top edge butt tight to the roof insulation (Isolair).
Ensure Diffutherm is rendered or sealed with appropriate stop-profile at all exposed junctions
Ensure all penetrations through Diffutherm/plinth board are sealed with iso-bloco expanding foam
tape (prior to application of base coat) and secondary mastic seal (following application of base coat
and prior to finish coat)
External wall insulation reduces air infiltration through walls, however, if possible
Ensure all penetrations through woodfibre/plinth board are sealed with Iso-Bloco expanding foam
tape
Ensure internal airtightness continuity between the wall and the floor.
Where exceptional airtightness levels are required, consider a continuous lime plaster parge coat with
additional taping of penetrations and openings, prior to application of EWI.
Eaves Detail
18
19
300
11
12
10
20
Re-EWI-R-WF-01
1.
2.
3.
4.
5.
6.
7.
8.
KEY TO COMPONENTS
Do not block existing airbricks to underfloor voids under suspended timber floors - add airbrick extensions
where required. Conversely, ensure airbricks to heated internal spaces are blocked (providing they
are not necessary for Building Regs. Requirements) and adopt appropriate internal ventilation strategy.
NOTES
I so-bloco expanding foam tape to be installed along topmost edge of plinth board (under base-rail) to
prevent tracking moisture. Ensure the base-rail drip is proud of plinth board by 20mm
Ensure Diffutherm is rendered or sealed with appropriate stop-profile at all exposed junctions
Ensure all penetrations through Diffutherm/plinth board are sealed with iso-bloco expanding foam
tape (prior to application of base coat) and secondary mastic seal (following application of base coat
and prior to finish coat)
Undertake drainage measure at wall base to ensure water falls away from wall (French drain with soak
away, ground surface inclined away from wall)
External wall insulation reduces air infiltration through walls, however, if possible
Ensure all penetrations through woodfibre/plinth board are sealed with iso-bloco expanding foam
tape
Ensure internal airtightness continuity between the wall and the floor.
Where exceptional airtightness levels are required, consider a continuous lime plaster parge coat with
additional taping of penetrations and openings, prior to application of EWI.
Extend plinth board well below interior floor level where possible to minimise thermal bridging through
foundations
Ensure insulation is well fixed to substrate
Ensure Diffutherm sits firmly in base-rail and plinth board butts closely to the underside, use PVC baserail to minimise thermal bridging
Plinth Detail 1
150
300
11
12
10
6
7
8
9
3
4
8
5
20
Re-EWI-R-WF-02
1.
2.
3.
4.
5.
6.
7.
8.
KEY TO COMPONENTS
Do not block existing airbricks to underfloor voids under suspended timber floors - add airbrick extensions
where required. Conversely, ensure airbricks to heated internal spaces are blocked (providing they
are not necessary for Building Regs. Requirements) and adopt appropriate internal ventilation strategy.
NOTES
I so-bloco expanding foam tape to be installed along topmost edge of plinth board (under base-rail) to
prevent tracking moisture. Ensure the base-rail drip is proud of plinth board by 20mm
Ensure Diffutherm is rendered or sealed with appropriate stop-profile at all exposed junctions
Ensure all penetrations through Diffutherm/plinth board are sealed with iso-bloco expanding foam
tape (prior to application of base coat) and secondary mastic seal (following application of base coat
and prior to finish coat)
Undertake drainage measure at wall base to ensure water falls away from wall (French drain with soak
away, ground surface inclined away from wall)
Protect the first 300mm above ground level of the build-up using NBT Plinth base coat.
External wall insulation reduces air infiltration through walls, however, if possible
Ensure all penetrations through woodfibre/plinth board are sealed with iso-bloco expanding foam
tape
Ensure internal airtightness continuity between the wall and the floor.
Where exceptional airtightness levels are required, consider a continuous lime plaster parge coat with
additional taping of penetrations and openings, prior to application of EWI.
Extend plinth board well below interior floor level where possible to minimise thermal bridging through
foundations
Ensure insulation is well fixed to substrate
Ensure Diffutherm sits firmly in base-rail and plinth board butts closely to the underside, use PVC baserail to minimise thermal bridging
Plinth Detail 2
20
>30mm
10
7
6
8
1.
2.
3.
4.
5.
6.
KEY TO COMPONENTS
Use Balcony Drip bead on the corner of sill head for exposed location
Use NBT Nanopore or Silicon render for exposed location
Aluminium extension sill with EPDM seals, vertical drip face of 40mm, thermal expansion compensation
side clips are recommended for exposed locations.
Minimise thermal bridge through sill by cutting back existing sill flush with masonry or rebating back of
diffutherm boards to enable front face of sill to be insulated. Where possible insulate the upper face of
the existing sill prior to installation of the extension sill.
NOTES
E
nsure internal airtightness continuity between the wall and the window frame. If fitting new windows,
seal/tape the frame to the window/door reveals.
Where exceptional airtightness levels are required, consider a continuous lime plaster parge coat with
additional taping of penetrations and openings, prior to application of EWI.
Re-EWI-R-WO-01
3
4
5
RETROFIT
EWI - NBT RENDER SYSTEM - Opening Detail
Standard Head & Sill
1
THERMAL PERFORMANCE OF JUNCTION
10
Ensure insulation is well fixed to the substrate
2
Ensure the continuity of the insulation throughout the junction
7
Ensure reveal is insulated with min. 20mm Diffutherm reveal board. Please contact NBT if 20mm reveal
insulation is not possible (exposed fixed frame width <30mm).
3
6
AIRTIGHTNESS LAYER CONTINUITY
8
4
External wall insulation reduces air infiltration through walls, however, if possible
Ensure all penetrations through woodfibre/plinth board are sealed with iso-bloco expanding foam
tape
5
21
>150
6
7
8
9
20
3
4
1
2
Re-EWI-R-WR-06
1.
2.
3.
4.
5.
6.
7.
8.
KEY TO COMPONENTS
NOTES
I so-bloco expanding foam tape to be installed along topmost edge of lead flashing (under base-rail) to
prevent tracking moisture. Ensure the base-rail drip is proud of plinth board by 20mm
Ensure Diffutherm is rendered or sealed with appropriate stop-profile at all exposed junctions
Ensure all penetrations through Diffutherm/plinth board are sealed with iso-bloco expanding foam
tape (prior to application of base coat) and secondary mastic seal (following application of base coat
and prior to finish coat)
External wall insulation reduces air infiltration through walls, however, if possible
Ensure all penetrations through woodfibre/plinth board are sealed with iso-bloco expanding foam
tape
Ensure internal airtightness continuity between the wall and the floor.
Where exceptional airtightness levels are required, consider a continuous lime plaster parge coat with
additional taping of penetrations and openings, prior to application of EWI.
Porch/Canopy Detail
770 x 2500 mm
750 x 2480 mm
22*, 35 & 60 mm
0.044 W/(mK)
200 kg/m3
250 kPa (at 10 % compr-
ession)
Size:
Cover area:
Thicknesses:
k-value / lD:
Density:
Compr. strenght:
Size:
600 x 1020 mm
Cover area:
590 x 1010 mm
Thicknesses:
40, 60, 80 & 100 mm
k-value / lD:
0.043 W/(mK)
Density:
175 kg/m3
Compr. strenght: 70 kPa (at 10 % compr
ession
800 x 1600 mm
780 x 1580 mm
60, 80, 100 mm
0.043 W/(mK)
180 kg/m3
100 kPa (at 10 % compr-
ession)
Sizes/Cover:
Thicknesses:
k-value / lD:
Density:
Compr. strenght:
Size:
600 x 1020 mm
Cover area:
590 x 1010 mm
Thicknesses:
52, 72 & 92 mm
(Pavadentro/Hardboard) k-value / lD:0.043 / 0.14 W/
(mK)
(Pavadentro/Hardboard) Density:175/740 kg/m3
(Pavadentro) Compr. strenght: 70 kPa (at 10 %
compression)
600 x 1020 mm
20 -140 mm
0.038 W/(mK)
110 kg/m3
50 kPa (at 10 % compr-
ession)
NBT PAVATHERM-FORTE
Wood fibre board for insulating floors or internal walls with plaster
Size:
Cover:
Thicknesses:
k-value / lD:
Density:
Compr. strenght:
Size/Cover:
Thicknesses:
k-value / lD:
Density:
Compr. strenght:
600 x 1020 cm
590 x 1010 mm
40 & 60 mm
0.043 W/(mK)
175 kg/m3
70 kPa (at 10 % comprression)
NBT Pavaflex
600 x 1020 mm
80, 100, 120, 140 mm
0.043 W/(mK)
175 kg/m3
70 kPa (at 10 % compression)
Size I:
Size II:
Thicknesses:
k-value / lD:
Density:
Compr. strenght:
Size/Cover:
600 x 1020 mm
Thicknesses:
40 & 60 mm
k-value / lD:
0.046 W/(mK)
Density:
220 kg/m3
Compr. strenght: 150 kPa (at 10 % compr
ession)
375 x 1350 mm
575 x 1350 mm
50, 80, 100 & 140* mm
0.038 W/(mK)
55 kg/m3
-
Bags of 8 kg (compressed)
e.g. 1 m2 at 228 mm
0.035 W/(mK)
35 kg/m3
23
Natural
BuildingMaterials
Materials
Systems
Natural Building
andand
Systems
high performance systems NBT PAVATEX woodfibre systems
provide exceptional thermal & acoustic insulation, summer overheating protection and moisture
control for the whole building in wall roof and floor
as non-polluting and the NBT systems lead to breathable constructions; NBT PAVATEX insulation
is specified exclusively by the Sentinal Haus Institute for healthy housing
wiedely used across Europe in all climates and conditions; pysical values are 3rd party tested and
guarenteed and production is according to BS EN
local service & support Pavatexs partner in the UK is Natural Building Technologies (NBT) who are a Technical Sales Company with nationwide coverage based in
Oakley, Bucks. NBT lead the UK sustainable materials & systems for high performance building
shells
developed in Switzerland for more than 70 years by the worlds most inovative woodfibre insulation
manufacturer
24