Single-Pole, Double-Throw
Switch
A pplication Overview
The F63 Float Switch should not be used with liquids
that are lighter than water (specific gravity less
than 1.0). Refer to Table 1 for product descriptions.
IMPORTANT:
CAUTION:
Equipment damage
hazard.
To avoid equipment damage, do
not use the F63 switches with
hazardous fluids or in hazardous
atmospheres.
F63AC
F63EC
F63BF
F63FF
Float
Copper Float
Polypropylene Float
Copper Float
Polypropylene Float
Enclosure
General Purpose
Enclosure
General Purpose
Enclosure
NEMA 3R Raintight
Enclosure
NEMA 3R Raintight
Enclosure
Application
Temperature at
Enclosure
O peration
I nstallation
IMPORTANT:
D imensions
2.94
75
1.50
Hex (Wrench flats to be used for tightening
38
switch to installation.)
1 in. 11-1/2 NPT
3.69
94
1.00
25
UP
1.13
29
1.00
Hex
25
5.09
131
2.78
71
12.70
322.5
1.39
35
1/2 -14 NPSM Thread
1.09
28
F63BF Models Only
1.59
40
4.44
113
13.03
331
2.66
67
1.17
30 Hex (Wrench flats to be used for tightening
switch to installation.)
1 in. 11-1/2 NPT
1.00
25
UP
4.00
102
4.78
121
1.39
35
1.39
35
12.42
315
1.09
28
0.875
Diameter Hole
22
0.50
for
Conduit with
13
1.09 Diameter Knockout Ring
28
12.75
324
W iring
WARNING: Shock hazard. To avoid
possible electric shock or
damage to the equipment,
disconnect the power supply
before making wiring
connections.
Make all wiring connections only with copper
conductors and in accordance with the National
Electric Code and local regulations.
The F63AC and F63EC models have color-coded
screw terminals. Remove the cover to make wiring
connections. Use the terminal screws furnished
(8-32 x 1/4 in. binder head). Substitution with other
screws will void the warranty and agency approvals.
Refer to Figures 6 and 7 for terminal identification.
A djustments
O rdering Information
Description
F63AC-1
F63BF-1
F63EC-1
F63FF-1
C heckout Procedure
Before applying power to the F63, make sure
installation and wiring connections are according to job
specifications.
After all necessary adjustments and electrical
connections have been made, put the system into
operation and observe at least three complete
operation cycles before leaving the installation site.
T roubleshooting
Table 2: F63 Float Switch Troubleshooting
Problem
Water (in the form of
condensation) is within
the enclosure.
Solution
If using F63AC or F63EC, use
vaportight enclosure instead.
If using F63BF or F63FF,
inspect grommet in conduit
conductor. Replace unit if
grommet is defective.
If the bellows are leaking,
replace unit.
Specifications
Product
Minimum Tank Diameter
Maximum Liquid Pressure
F63BF
F63FF
F63AC
F63EC
Minimum
-20F (-29C) or
Liquid Freezing Point
-20F (-29C) or
Liquid Freezing Point
32F (0C) or
Ambient Dew Point
32F (0C) or
Ambient Dew Point
Maximum
250F (121C)
175F (79C)
250F (121C)
175F (79C)
F63BF
F63FF
F63AC
F63EC
-20F (-29C)
-20F (-29C)
32F (0C)
32F (0C)
120 VAC
208 VAC
240 VAC
277 VAC
--
16.0
8.8
8.0
--
96.0
52.8
48.0
--
Non-inductive Amperes
16.0
16.0
16.0
16.0
Liquid Temperatures
Ambient Temperatures
Minimum
Electrical Ratings
Horsepower
Pilot Duty
F63BF and F63FF
Case
Cover
Wiring Connections
Enclosure
Switch
Pipe Connector
One 7/8 in. (22 mm) Hole for 1/2 in. Conduit
with 1-3/32 in. (28 mm) Knockout Ring for
3/4 in. Conduit
Conduit Connection
Finish
Agency Listings
CSA Certified:
Shipping Weight
F63BF
F63FF
F63AC
F63EC
Individual Pack
Overpack of 10
27 lb (12.2 kg)
31 lb (14.1 kg)
26 lb (11.8 kg)
26 lb (11.8 kg)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications,
consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.