Beruflich Dokumente
Kultur Dokumente
A CPR-Fed System
Ok lets start at the evaporative condenser at its outlet the high
pressure liquid drain line, identified in Figure 1 as warm liquid (165 psig).
This pressure is equivalent to 90 F condensing[1] at 78 F ewbt. The
system shown is single stage compression. Liquid flows by gravity from the
condenser outlet into a small pilot receiver. Liquid level in this pilot is
maintained by a high-side float. If the liquid level rises above the float, the
downstream expansion valve modulates open. If the liquid level falls below
the float level, the expansion valve modulates towards the closed position.
Upon passing through the expansion valve, the exiting refrigerant is now
under a pressure of 65 psig. During this throttling process, a portion of the
upstream high pressure liquid flashes to vapor. It is this rate of change in
refrigerant volume that provides the force required to move liquid through
the liquid piping distribution system. Considering both upstream and
downstream pressures (180 psia and 80 psia), the mass ratio of refrigerant
liquid given up to flash vapor during adiabatic irreversible throttle at these
conditions may be found from:
(1)
where:
Eq (1) solves to 10% flash at the conditions stated. However, the volume of
the refrigerant changes vastly more than a measly 10%. From 180 psia to
80 psia, the volume increases by roughly 130 times. Since this expansion
process occurs inside of a system having a fixed volume, the resulting force
generated from the expansion process becomes available to lift liquid uphill
against gravity while overcoming friction losses in piping and valves.
Actually, the foregoing explanation becomes a really nasty calculus problem
probably best described with a third-order differential equation, so well let
Eq (1) do for now. Upon exiting the expansion valve, the liquid and vapor
enter a controlled pressure receiver, CPR in Figure 1. Upon entering, liquid
separates from vapor by gravity. Liquid then becomes available for
circulation to the various evaporators located throughout the facility.
The flash vapor formed across the expansion valve exits the CPR through a
back pressure regulator and then enters the piping conveying liquid and
vapor returning from the evaporators, upstream of the accumulator. This
pressure regulator is the governor of vapor pressure within the CPR. Cold
liquid leaves the CPR at 65 psig (45 F at saturation but subcooled slightly to
~ 40 F more on this liquid subcooling later) and journeys out to the
various evaporators through a network of piping.
CPR-Fed Evaporators
Whenever an evaporator manufacturer selects a particular evaporator having
x many rows of tubing (assuming an air-cooling evaporator) with y many fins
per inch, it is commonplace for that manufacturer to assume that when liquid
arrives in their evaporator, that it will boil immediately no having to wait
around for it to warm up to its saturation (boiling) temperature. This
assumption marks a critical decision because it is the strong force in overall
evaporator effectiveness the operating h[2] for the evaporator. If liquid
Gravity flooded (regulator in dry suction line from surge drum), and
forces (versus the drag force from upward moving vapor). Vapor exits the
top of the accumulator and returns to the compressor(s) for processing.
Liquid falls by gravity out of the accumulator into a small vessel known as a
pumper drum or liquid transfer. As liquid enters this vessel, it displaces
an equal volume of vapor back through a three-way valve (de-energized
position, common port to low pressure port) and into the accumulator. When
liquid reaches the upper site glass, a float switch (not shown in Figure 1)
repositions the ports within the three-way valve, closng the LP port and
opening the HP port to common. Hot gas, regulated to the setpoint of the
outlet pressure regulator, flows into the top of the pumper drum. This action
instantly subcools all liquid contained within this vessel as the gas pressure
in the vapor head space increases. This pressure change also causes the
upstream check valve to close while simultaneously opening the downstream
check valve. Now liquid begins to flow out of the pumper drum, through a
liquid transfer line and into the CPR. Whenever ammonia liquid becomes
pressurized (by using high pressure vapor), its temperature changes but
slowly. This now colder 17 F liquid pressurized to 65 psig mixes with the
saturated liquid inside the CPR which subcools the whole mass. This
subcooling becomes available to overcome liquid static lift + friction pressure
losses within the liquid supply piping network without forming vapor bubbles.
From the accumulator, dry suction vapor at 30 psig flows back into the
compressor where its pressure is raised to 165 psig, becoming very hot in
the process (~245 F reciprocating compressors; 130 F liquid-injected
screws; 185 F thermosiphon oil cooled screws). This vapor then travels into
the condenser for desuperheating and reliquification.
Alternate Control of CPR Vapor Head Space Pressure
In most CPR systems, it is common to see the hot gas piping shown in Figure
1 with a red dashed line along with its pressure regulator. The purpose of
this line and regulator is to maintain some preset minimum pressure within
the CPR. But one will notice that in essence, we now have dual regulators
installed in separate lines controlling the same receiver pressure. Can these
fight each other? If not properly set up, you bet your bippy! In each and
every case, this extra line and regulator has proven unnecessary, provided
the system designer initially realized that a CPR-fed system has a limitation
that limitation being its overfeed rate (or recirculation rate[4] if you will).
When a CPR-fed system has been properly set up and adjusted, this second
hot gas regulator and piping is not needed. If the hot gas line and outlet
regulator is installed, be absolutely sure that this optional regulator (Phot) is
set for a lower pressure than the back pressure regulator (Pcold) in the cold
vapor line. A minimum of 5 8 psi difference is recommended. If these
settings are reversed (Phot > Pcold), your electric bill will go through the
roof. Why? The regulator with the highest pressure setting (Phot in this
case) overrides the lower pressure regulator, forcing it wide open. The
quantity of gas that will pass through these two regulators (now in flow
series) becomes a function of the regulator port diameters and their
respective pressure setpoints. A few years ago, a class attendee mentioned
that he had encountered this phenomenon at his plant. After reversing the
setpoints of the two regulators (Phot and Pcold), they shut down a formerly
loaded 300 hp screw.
Pumper Drum Liquid Return to CPR Top or Bottom?
What makes the system in Figure 1 atypical are two features: the absence of
a hot gas connection to the top of the CPR (just discussed) and the point of
connection for the returning cold liquid from the pumper drum. In the
system shown, it connects to the top of the CPR (a horizontal vessel in this
case). However it is far more common to see this connection made to the
bottom of the CPR, well below the vessel liquid freeboard[5].
Some years ago, I visited the refrigeration system shown in the next figure
a packaged ice plant in the Deep South. Note where the liquid return from
the pumper drum is made to the CPR in Figure 2.
Figure 2 Pumper Drum Connected to Bottom of CPR
The vessel on the left in this photo is the accumulator; the little middle
puppy is the pumper drum. The vessel on the right is a CPR. The float
switch shown to the right of the pumper drum initiates a liquid transfer. In
the system shown (and that in Figure 1), cessation of transfer (de-energizing
the three-way valve) is accomplished with a time-delay relay. What
distinguishes these two systems is the elevation of the liquid return into the
CPR above or below the CPR freeboard.
There is some disagreement regarding the placement of the liquid return
connection to the CPR should it be above or below its liquid freeboard?
Below is far more common. This location has the advantage of maintaining
more of the liquid subcooling effect of returning liquid from the pumper
drum. However it is my opinion that this connection should be made above
the CPR liquid freeboard for technical reasons I wont go into here. True,
some subcooling is given up as returning cold liquid falls through a warmer
vapor head space. However it is my opinion that the advantages outweigh
the disadvantages and Ill let it go at that.
Setting the Transfer Time Delay Relay
Nearly all CPR systems in the U.S. use a time-delay relay as the means of
ceasing a liquid transfer from the pumper drum to the CPR as discussed. A
few (but only a few) systems use alternate means of ceasing transfer, those
employing a second lower float switch (usually insufficient clearance available
for this) or a float column with a resistance probe connected to a control
panel. However as far as shear numbers of them, the time delay relay wins
out. To set this relay, one must be in clear view of the site glasses on the
pumper drum. When liquid reaches the upper site glass, transfer
automatically begins. When liquid reaches the lower site glass, transfer
should cease. Dont attempt to force all liquid out of a pumper drum stay
within the two site glasses. Thats what theyre there for in the first place.
When insulating the pumper drum, remember to include an extended length
frost shield for the lower site glass, otherwise you wont be able to see
anything because that lower glass will completely frost over.
If youre considering a CPR-fed system, my recommendation is to return
liquid to the top of the CPR as shown in Figure 1, or to employ the optional
arrangement shown in the next figure.
Hartford Return Loop
Up until the late 1890s, the Hartford Steam Boiler Insurance Company (now
Hartford Insurance Company) was the major policy issuer for insuring
residential steam boilers. Hartford was also paying out considerable bucks to
replace boilers and rebuild houses because their insured boilers were blowing
up left and right. Then one day, an ingenious engineer with Hartfords Boiler
Division came up with the piping arrangement shown in Figure 3. Up until
then, boiler return connections were made below the boiler freeboard. This
method of connection commonly forced all the water out of the boiler when
the steam pressure rose. Raising the connection elevation solved the
problem and the name stuck Hartford Return Loop. These are still used
today. If you wish to return liquid ammonia below the liquid freeboard, then
my recommendation is to use this method. Yes, youll pay for another vessel
opening, an angle valve plus a tee, but this is only a one-time payment and
one very well worth its initial investment.
Figure 3
Disadvantages:
(one per side port required) are fed into side ports of each screw. This issue
quickly becomes hugely complex; difficult to size port diameters of each
regulator; side port gas/motor amperage overload is common when products
of defrost are returned to the CPR.
Higher energy consumption than mechanically-pumped liquid overfeed
systems when high pressure hot gas is used for pressurizing both the CPR
and the dump trap for liquid transfer to the CPR. An option to substantially
reduce compressor energy involves installation of a transfer pump; CPR
vapor is then used instead of higher pressure hot gas as the means of
pressurizing the dump trap (seldom done but a heck of a good idea; lower
risk than using high pressure gas for transfer).
[1]
[2]
[3]
[4]
Freeboard, as the term is used in this paper, denotes the relative elevation of the
liquid level. The term originates from the boiler industry and is equal to the square feet
of steam disengaging area. Because a rapid decrease in vapor head space pressure will
result in flash gas, and this flash gas must escape from the liquid surface without
carrying liquid with it, the term freeboard also becomes applicable to vessels
containing saturated liquid ammonia.
[5]