Beruflich Dokumente
Kultur Dokumente
Level
Subject
Session
2008/2009 Semester 1
Date
10 December 2008
Time
6:30 pm - 9:00 pm
Time Allowed :
2.5 hours
Psychrometric charts
Graph paper
Question 1
A restaurant is air-conditioned with the following systems, cooling loads and design
parameters:
Interior Zone
VAV
System
Indoor temperature:
Cooling
Heating
Maximum cooling load: Sensible
Latent
Minimum load:
Sensible
Latent
Design supply air state:
Primary air flow rate:
Min. turn down ratio
a)
12 kW
3 kW
4.5 kW
1.5 kW
24oC
21oC
Perimeter Zone
Fan-coil
14oC, 90% RH
10 kW
2.5 kW
- 4 kW
1kW
0.15m3/s
0.1m3/s
(90% RH, same moisture content as room air)
0.4
N/A
the design supply air flow rate of the VAV system to maintain the indoor
temperature;
(3 marks)
(ii) the space relative humidity at the maximum load conditions;
(3 marks)
(iii) the air volume flow rate and indoor temperature at the minimum load
conditions; and
(3 marks)
(iv) the design cooling coils load.
(3 marks)
b) Determine for the perimeter zone:
(i)
the design supply air flow rate of the fan-coil system to maintain the
indoor temperature;
(3 marks)
(ii) the adjusted sensible and latent load on the fan-coil unit at maximum load
condition, assuming that the Sensible Heat Ratio (SHR) of the fan-coil unit
follows the maximum load conditions;
(3 marks)
(iii) the resulting indoor moisture content and relative humidity at the
maximum load conditions; and
(3 marks)
(iv) the heating load at the minimum load conditions if electric duct heater is
provided.
(4 marks)
Question 2
A primary-secondary pumping system with four identical chillers is shown in Figure
Q2(a). The design chilled water flow rate for each primary pump is 20 L/s, and the
supply and return temperatures are 7oC and 12oC respectively. A decoupler by-pass
pressure control is installed for sequencing control of chillers. Figure Q2(b) shows the
relation between the cooling output of a typical cooling coil and the chilled water flow
rate through the coil. Tables Q2(a) provides the system pressure drop characteristics
and Table Q2(b) summarises the performance of each secondary pump.
a)
b)
c)
d)
e)
f)
Determine the settings of chilled water flow rate and the corresponding flow rate
in the by-pass line for switching ON or OFF of each chiller as the load changes.
You may adopt a safety factor of 15% for OFF schedule of chiller to avoid
system hunting.
(4 marks)
Conduct proper calculations to determine the return chilled water temperatures,
both TR and Tr as shown in Figure Q2(a).
(5 marks)
Construct the pump characteristics curve and system characteristics curve on the
graph paper provided.
(4 marks)
Determine the ON-setting flow rate for each secondary pump.
(4 marks)
At each flow setting determined in (a), determine the number of operating
secondary loop pump.
(4 marks)
<Answers for (a) through (c) and (f) should be entered in Table Q2 (c), and to be
submitted together with the answer book. A spare copy is attached at the end of
this question paper.>
Figure Q2(a)
Qp
QS
Qb
Decoupler
by-pass pipe
Chillers &
primary-loop pumps
TR
Tr
Figure Q2(b) Relation between the cooling output of a typical cooling coil and the
chilled water flow rate through the coil
fraction of designed
cooling output
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0
0
20
25
40
100
60
225
80
400
100
625
120
900
10
15
20
25
30
35
40
450
450
450
430
400
360
300
230
146
Increasing Load
ON/OFF action
Flow in
primary
main
(L/s)
Qp
Flow in
secondary
main
(L/s)
Qs
Flow in
by-pass
line
(L/s)
Qb
Starting 1st
chiller and
primary pump
20
< 20
Starting 2nd
chiller and
primary pump
40
20 + #
20
Return chilled
water
temperature
(oC)
Tr
TR
-
No. of
operating
secondary
pump
1
Starting 3rd
chiller and
primary pump
Starting 4th
chiller and
primary pump
Decreasing Load
Switching off
4th chiller and
primary pump
80
Switching off
3rd chiller and
primary pump
Switching off
2nd chiller and
primary pump
Remarks: # You may ignore in the calculation of return chilled water temperatures.
Question 3
A two-loop chilled water pumping system with a cooling capacity of 1500 tons is shown in
Figure Q3(a). Three identical constant speed secondary-loop pumps are used to deliver
chilled water under the design-load condition. The pressure/flow rate characteristics of each
secondary pump are as shown in Figure Q3(b). The control valve is an equal percentage valve
with inherent characteristics as shown in Figure Q3(c). The cooling coil output-flow
characteristics is as shown in Figure Q3(d). The design valve authority is 0.3.
a)
Under the design-load condition, the control valve at the furthest branch will allow the
design flow rate of the branch, which is 40m/h, to pass through it when it is fully open.
Determine:
(i)
the KV and the corresponding pressure drop across the control valve at the furthest
branch;
(4 marks)
(ii) the Kv of the control valve at the second furthest branch if the design flow rate is
30 m3/h; and
(4 marks)
(iii) the pressure drop through all elements in the furthest branch, excluding the control
valve.
(4 marks)
b)
Under a part-load condition where the total cooling load required by all the branches is
reduced to 66% of the design cooling load, all the secondary pumps are still in
operation, and the cooling load requirement of the furthest branch is reduced to 50%.
Determine:
(i)
the corresponding pressure drop across the control valve at the furthest branch;
Secondary-loop
pumps
Decoupler Bypass Pipe
Flow meter
B
Primary-loop
pumps
Flow switch
Figure Q3(b) Pump characteristic curve for the each secondary pump model
500
450
Pumpr
Press.
(kPa)(kPa
Pumpr
Press.
400
350
300
250
200
150
100
50
0
0
50
100
150
200
250
300
350
Figure Q3(c) Inherent characteristic curve for the equal percentage control valve
100
90
80
70
% Flow
60
50
40
30
20
10
0
0
10 20 30 40 50 60 70 80 90 100
% Valve Lift
Figure Q3(d) Relation between the cooling output and the chilled water flow rate
fraction of designed
cooling output
0.9
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
Question 4
Four nos. of the chillers specified in Table Q4 are installed to meet with the design cooling
load in a building. Each of the four identical chillers is connected to one constant speed
chilled water pump with rated power input of 20kW.
The power input for a chiller is related to the part-load ratio (PLR) by the following equation:
where
Wi
= power input, kW
Wi,full = power input at full-load, kW
a, b, c = chiller specific part-load coefficients
Water-cooled centrifugal
600 kW
12oC / 7oC
Rated COP
Part-load coefficients: a, b, c
4oC
a)
Calculate the COP of the chiller running at full-load, 80% and 50% load.
(6 marks)
b)
Discuss, with the aid of a graph, how the chiller COPs will vary with part-load ratios
from full-load to 10% load.
(5 marks)
c)
Determine when the total cooling load decreases to 1620 kW, how many chillers should
be operated to give better efficiency based on the graph of part (b)? Calculate the
required total power input at this condition.
(6 marks)
d)
Determine the evaporating temperature and the chilled water return temperature based
on the part load condition as determined in part (c). You may assume the chilled water
supply temperature is controlled at a design constant.
(8 marks)
Question 5
a)
Figure Q5 shows two space air diffusion system designs being considered for an office
room. The total cooling load of the room is 2.5 kW, and the design supply air flow rate
is 0.2m/s. Determine which design is preferable based on the design conditions shown
in Table Q5 (a) and (b). The outdoor conditions are 33C DB and 80% RH.
(12 marks)
b)
c)
There is a potential problem in design A/B or both. What is/are the problem(s)? (Hints:
The problem is not related to thermal comfort)
(4 marks)
d)
Figure Q5
(6 marks)
(3 marks)
Layout and section for two space air diffusion designs (Not to scale)
2.5m
2m
2m
Sidewall
grille
Window
5m
Sidewall
grille
Window
Window
Sidewall
grille
Window
Sidewall
grille
4m
Section
Section
Design A
Design B
FCU
Table Q5
(a)
(b)
100
2.5
125
3
150
3.5
180
4.2
200
4.7
230
5.3
260
5.9
Air diffusion performance index (ADPI) selection guide for sidewall grille
Room Load
(W/m)
T0.25 / L
for Max. ADPI
Max.
ADPI (%)
250
190
125
65
1.1
1.1
1.0
0.9
68
82
83
85
10
For ADPI
Greater Than
(%)
80
80
80
Range of
T0.25 / L
0.6 1.3
0.8 1.4
0.7 1.1
310
6.4
Question 6
Figure Q6(a) shows the supply air system that serves an office premises in a building. The
supply flow rate for the room accounts for two-third of the total supply flow rate from the
fan. The supply air is discharged into the room through two ceiling-diffusers of dimensions
500mm 500mm. The floor area of the room is 5m 5m (Length Width) and the false
ceiling height is 3.5m above the floor level. The reverberation time of the room is 1 second.
a)
Calculate the sound pressure level in the room at the point (X) 2.5m above floor level at
the corner, which is due to noise transmission from the fan through the ducting system
into the room. State any assumption you have made.
(20 marks)
b)
Determine if any noise reduction measures will be required to meet NR40 in the room
and, if so, recommend the applicable measures. What precaution should also be taken?
(5 marks)
The noise data of the fan and the octave band SPL limits for meeting NR40 are given in
Table Q6. The required duct noise calculation data are given in Figures Q6(b) to (e).
Table Q6
Octave Band Frequency (Hz)
125
250
500
1000
2000
4000
75
76
75
74
71
66
56
49
44
40
37
35
11
To other rooms
3.5 m
Headroom
Ceiling diffuser
@0.5m3/s; 0.25m2
2.5 m
Ground Floor
1.5 m3/s
Elevation
400mm 350mm (2 m)
To other rooms
D2
4m
12
Plan View
Figure Q6(c)
13
Figure Q6(d) Corrections to sound power level at grille to give direct sound pressure level in
room
Figure Q6(e) Corrections to grille sound power level to give reverberant sound pressure
level
14
Table Q2(c)
Flow in
secondary
main
(L/s)
Qs
Flow in
by-pass
line
(L/s)
Qb
Starting 1st
chiller and
primary pump
20
< 20
Starting 2nd
chiller and
primary pump
40
20 + #
20
Increasing Load
ON/OFF action
Return chilled
water temperature
(oC)
Tr
TR
No. of
operating
secondary
pump
Starting 3rd
chiller and
primary pump
Starting 4th
chiller and
primary pump
Decreasing Load
Switching off
4th chiller and
primary pump
80
Switching off
3rd chiller and
primary pump
Switching off
2nd chiller and
primary pump
Remarks: # You may ignore in the calculation of return chilled water temperatures.
15