TABLE OF CONTENTS
LIEBERT DS MODEL NUMBER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
1.0
LIEBERT DS CONFIGURATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
1.1
Cooling Configurations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.2
Blower Configurations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.3
2.0
3.0
4.0
5.0
6.0
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
6.1
6.2
7.0
7.1
7.2
7.3
7.4
7.5
7.6
7.7
7.8
8.0
8.1
8.2
9.0
ANCILLARY ITEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9.1
Floor Stands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
9.2
Plenums . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
9.3
10.0
PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107
10.1
11.0
11.1
11.2
11.3
12.0
12.1
12.2
12.3
12.4
12.5
12.6
12.7
13.0
13.1
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
13.2
13.3
14.0
14.1
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
14.2
14.3
15.0
15.1
15.2
15.3
15.4
15.5
16.0
16.1
16.2
16.3
16.4
Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159
17.0
ii
10
11
12
13
14
15
Air Distribution
DS = Downflow Standard
VS = Upflow Standard
Factory
Configuration
Number
Nominal kW
028, 035, 042, 053, 070, 077, 105
(8, 10, 12, 15, 20, 22, 30 tons)
Humidification
0 - None
I - Infrared
S - Steam Generating
Canister
Cooling Type
A = Air-Cooled
D = Dual-Cool, Air-Cooled
H = Dual-Cool, Water-Cooled
K = GLYCOOL (Liebert Economizer Coil)
W = Water/Glycol
Compressor
D - Digital Scroll, R-407C
S - Scroll, R-407C
U - Semi-Hermetic with Four-Step, R-407C
V- Semi-Hermetic with Four-Step, R407C
(DS105 water/glycol/GLYCOOL only)
Reheat Type
0 - None
E - 3-Stage Electric
S - SCR
Voltage
A - 460/3/60
B - 575/3/60
C - 208/3/60
D - 230/3/60
2 - 380/3/60
Fan Type
0 = Forward-Curved
Blowers
1 = Electronically
Commutated (EC)
Fans
Liebert DS
Liebert DS Configurations
1.0
LIEBERT DS CONFIGURATIONS
1.1
Cooling Configurations
NOTE
All field-installed piping must comply with applicable local, state and federal codes.
AIR-COOLED
Air-cooled unit piping is spun closed from the
actory and contains a nitrogen holding charge.
ach installation requires field-supplied
efrigerant and piping to a condenser.
GLYCOL-COOLED
Glycol-cooled units are factory-charged and
tested. Field-supplied and field-installed piping is
required from the unit to the drycooler and pump
package.
WATER-COOLED
Water-cooled units are factory-charged and
tested. Field-supplied and field-installed
water piping is required from the unit to the
cooling tower.
DUAL-COOL
This system has all of the features of a compressorized
system, but adds a second cooling coil that is connected
to a source of chilled water. Cooling is provided by
circulating chilled water, when available, through this
second coil and reducing compressor operation.
Liebert DS
Liebert DS Configurations
1.2
Blower Configurations
Figure 1
Return Air
Filter
Filter
Front
Front
Coil
Coil
Supply
Air
Blower
Blower
Raised
Floor
Raised
Floor
Figure 2
Supply
Air
Return Air
Filter
Filter
Front
Front
Coil
Coil
Blower
Blower
Raised
Floor
Raised
Floor
Supply Air
Floor
Stand
(optional)
Supply
Air
Floor Stand
(optional )
Supply
Air
Liebert DS
Liebert DS Configurations
Figure 3
Supply
Air
Supply
Air
Supply
Air
Supply
Air
EC Fan
Front
Coil
EC Fan
Front
Coil
Filter
Filter
Return Air
Return
Air
Ductwork
Figure 4
Supply Air
Front
Blower
Front
Coil
Coil
Filter
Filter
Return
Air
Return
Air
Liebert DS
Blower
Liebert DS Configurations
Figure 5
Front
Supply Air
Blower
Front
Coil
Blower
Coil
Filter
Filter
Return
Air
Return
Air
Ductwork
Ductwork
Liebert DS
Liebert DS Configurations
1.3
Figure 6
1
2
17
16
15
3
14
4
13
5
12
11
10
8
7
6
Liebert DS
18
18
DPN000958
Rev. 4
Liebert DS Configurations
Figure 7
18
1
2
17
4
5
16
6
15
7
14
13
9
12
10
11
DPN001222
Rev. 2
Liebert DS
2.0
Table 1
028
035
042
053
070
077
105
116.4
(34.1)
143.6
(42.1)
163.6
(47.9)
210.6
(61.7)
247.1
(72.4)
270.3
(79.2)
352.5
(103.3)
116
(34)
141.2
(41.4)
160.9
(47.9)
210.2
(61.6)
245.9
(72)
269.2
(78.9)
337.5
(98.9)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
110.5
(32.4)
136.8
(40.1)
156.1
(45.7)
198.9
(58.3)
234.8
(68.8)
257.1
(75.3)
338.2
(99.1)
105.9
(31)
128.1
(37.5)
146.2
(45.7)
193.9
(56.8)
226.6
(66.4)
248.8
(72.9)
307.2
(90)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
105.3
(30.9)
130.8
(38.3)
149.5
(43.8)
189
(55.4)
223.9
(65.6)
245.8
(72)
325
(95.2)
93.9
(27.5)
113.8
(33.3)
129.9
(43.8)
173.3
(50.8)
201.3
(59)
221.5
(64.9)
80
(273.1)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
120.8
(35.4)
137.1
(40.2)
155.3
(45.5)
216.8
(63.5)
258.6
(75.8)
277.6 (81.3)
353.7 (103.6)
120
(35.2)
136.4
(40)
154.7
(45.3)
215.7
(63.2)
255.6
(74.9)
275.1 (80.6)
338.3 (99.1)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
113.9
(33.4)
130.4
(38.2)
148.1
(43.4)
206.5
(60.5)
248
(72.7)
265.8 (77.9)
340.2 (99.7)
108.7
(31.8)
124.6
(36.5)
141.9
(41.6)
199.1
(58.3)
235
(68.9)
253 (74.1)
308.2 (90.3)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
107.8
(31.6)
124.7
(36.5)
141.9
(41.6)
197.4
(57.8)
69.9
(238.4)
255.5 (74.9)
327.8 (96)
96.1
(28.2)
110.8
(32.5)
126.3
(37)
177.6
(52)
209.4
(61.4)
224.9 (65.9)
274.3 (80.4)
6200
8,000
9,600
(10533.9) (13,592) (16,310)
11,000
(18,689)
13,700
(23,276)
7.9 (5.9)
10.5 (7.8)
4,400
(7,476)
3.75 (2.8)
1
5,200
(8,835)
1
Liebert DS
Table 2
028
Model Size
035
042
053
070
077
105
137.6
(40.3)
140.0
(41.0)
157.6
(46.2)
205.3
(60.2)
240.6
(70.5)
262.6
(76.9)
345.6
(101.3)
129.6
(38.0)
137.6
(40.3)
155.3
(45.5)
203.8
(59.7)
237.9
(69.7)
259.9
(76.2)
329.6
(96.6)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
131.8
(38.6)
133.3
(39.1)
150
(43.9)
195.1
(57.2)
229.3
(67.2)
250.6
(73.4)
331.5
(97.1)
117.2
(34.3)
124.6
(36.5)
140.5
(41.2)
187.1
(54.8)
217.7
(63.8)
238.2
(69.8)
299.4
(87.7)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
126.5
(37.1)
127.2
(37.3)
143.3
(42)
185.6
(54.4)
218.9
(64.1)
239.7
(70.2)
318.4
(93.3)
104.2
(30.5)
110.3
(32.3)
124.2
(36.4)
166.2
(48.7)
192.9
(56.5)
210.9
(61.8)
265.4
(77.8)
Net APPLICATION DATA BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
116.4
(34.1)
135.5
(39.7)
149.2
(43.7)
212.1
(62.1)
252.6
(74.0)
270.1 (79.1)
346.9 (101.6)
136.9
(40.1)
116.0
(34.0)
148.9
(43.6)
209.3
(61.3)
246.6
(72.3)
265.6 (77.8)
330.4 (96.8)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
110.5
(32.4)
130.8
(38.3)
141.9
(41.6)
202.5
(59.3)
243
(71.2)
259 (75.9)
333.5 (97.7)
105.9
(31.0)
123.2
(36.1)
136.1
(39.9)
191.6
(56.1)
225
(65.9)
242.6 (71.1)
300.4 (88.0)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
105.3
(30.9)
125.4
(36.7)
135.7
(39.8)
194.2
(56.9)
233.9
(68.5)
249.3 (73)
321.1 (94.1)
93.9
(27.5)
109.4
(32.1)
120.6
(35.3)
170.4
(49.9)
200.1
(58.6)
215.2 (63.1)
266.6 (78.1)
4,400
(7,476)
5,200
(8,835)
6,300
(10,704)
7,500
(12,743)
9,000
(15,291)
10,400
(17,670)
13,700
(23,276)
2 (1.5)
3 (2.2)
5 (3.7)
3 (2.2)
5 (3.7)
7.5 (5.6)
10 (7.5)
3 (2.2)
5 (3.7)
7.5 (5.6)
5 (3.7)
7.5 (5.6)
10 (7.5)
15 (11.2)
Number of Fans
1.
2.
3.
4.
Liebert DS
Table 3
028
035
042
053
070
077
105
17.1 (1.6)
17.1 (1.6)
24.7 (2.3)
24.7 (2.3)
24.7 (2.3)
32.3 (3.0)
85.3 (25.0)
102.4
(30.0)
REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular; capacity does not include fan motor heat
51.2
(15.0)
51.2
(15.0)
51.2
(15.0)
85.3
(25.0)
85.3
(25.0)
102.4
(30.0)
HUMIDIFIER SECTION
Infrared Humidifier (Steam canister humidifiers available on downflow models)
11.0 (5.0)
11.0 (5.0)
FILTER SECTION
Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (Filter types cannot be mixed, must
be all MERV 8 or all MERV 11.)
Downflow Models
Quantity
4 @ 25x20 4 @ 25x20
Upflow Models
(Front and Rear return) Filters located in separate filter box on rear return; located on lower unit panel on front return
Quantity
8
25x20
1/2
1/2
1/2
5/8
5/8
5/8
5/8
5/8
5/8
5/8
7/8
7/8
7/8
1-1/8
1/4
1/4
1/4
1/4
1/4
1/4
1/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
1/2
Model (R-407C refrigerant) MCM056_8 MCM056_8 MCM056_8 MCM056_8 MCM080_8 MCM080_8 MCL110_8
Number of Fans
DUAL-COOL UNITS DATA, Water (0% Glycol), Net Application Data kBTUH (kW)
CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower.
75F DB, 61.1 WB (23.9C DB, 16.2C WB) 45% RH, 45F EWT, 55F LWT Based on Forward-Curved Blowers
89.2
(26.2)
101.6
(29.8)
109.8
(32.2)
170.4
(49.9)
188.8
(55.3)
196.8
(57.7)
258.8
(75.8)
85 (24.9)
98.2 (28.8) 107.8 (31.6) 157.1 (46) 176.4 (51.7) 185.4 (54.3) 249.1 (73)
19 (71.9)
Pressure Drop, ft. (kPa), valve, coil 6.1 (18.23) 8.3 (24.81)
36.4 (138)
41.7 (158)
10.50
(31.39)
10.40
(31.09)
13.3 (39.8)
46 (174)
59.4 (225)
4400
(7475)
5500
6600
(9344)
(11213)
Fluid Volumes
8000
(13592)
9600
(16310)
11000
(18689)
13,700
(23,256)
5 (19.0)
5 (19.0)
8 (30.4)
8 (30.4)
8 (30.4)
10 (38.0)
5 (19.0)
Liebert DS
10
3.0
Table 4
28
35
42
053
070
077
105U
105V
143.8
(42.1)
132
(38.7)
171
50.1)
220
(65.1)
268.3
(78.6)
297.1
(87.1)
382.3
(112.1)
356.1
(104.3)
135
(39.6)
108.2
(31.7)
166.9
(48.9)
212.9
(63.4)
258.2
(75.7)
285.4
(83.6)
354.6
(103.9)
345.8
(101.3)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
138.1
(40.5)
135.4
(39.7)
163.4
(47.9)
212.1
(62.2)
256.9
(75.3)
284.7
(83.4)
367.7
(107.8)
339.7
(99.5)
122.4
(35.9)
117.3
(34.4)
151.4
(44.4)
197.7
(58)
68.9
(235)
76
(259.5)
94.3
(321.9)
93.2
(318.2)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
Sensible kBTUH (kW)
38.9
(132.7)
41.4
(141.4)
45.9
(156.7)
59.4
(202.6)
245.8
(72)
273
(80)
352.9
(103.4)
327.8
(96.0)
109.3
(32)
131.9
(38.7)
134.7
(39.5)
176.4
(51.7)
209
(61.2)
230.8
(67.6)
285.7
(83.7)
283.7
(83.1)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
(not available after 12/31/15)
120
(35.2)
143.3
(42)
162.1
(47.5)
224.1
(66.3)
275.6
(80.8)
301.9
(88.5)
379.9
(111.3)
119.9
(35.1)
142.1
(41.6)
161
(47.2)
215.6
(64.3)
262.6
(77)
288.3
(84.5)
353.4
(103.6)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
116.1
(34)
136.7
(40.1)
154.8
(45.4)
216.1
(63.3)
264.6
(77.5)
290.2
(85)
365.9
(107.2)
111
(32.5)
129.4
(37.9)
147
(43.1)
200.1
(58.6)
238.9
(70)
262.3
(76.9)
321.1
(94.1)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
111.8
(32.8)
131
(38.4)
148.4
(43.5)
206.5
(60.5)
253.5
(74.3)
279.1
(81.8)
352.2
(103.2)
99.2
(29.1)
115.2
(33.8)
130.9
(38.4)
178.3
(52.2)
212.7
(62.3)
233.6
(68.5)
285.9
(83.8)
5,200
(8,835)
6200
(10534)
8,000
(13,592)
9,600
(16,310)
11,000
(18,689)
13700
(23276)
13700
(23276)
3.75
(2.8)
3.75
(2.8)
3.75
(2.8)
3.4
(2.5)
5.4
(4.0)
7.9
(5.9)
10.5
(7.8)
10.5
(7.8)
11
Liebert DS
Table 5
28
35
42
053
070
077
105U
105V
141.6
(41.5)
144.7
(42.4)
165.2
(48.4)
211.9
(62.1)
262.5
(76.9)
289.9
(85.0)
376.4
(110.3)
348.9
(102.2)
132.8
(38.9)
141.9
(41.6)
161.7
(47.4)
194.6
(57)
248.4
(72.8)
274.4
(80.4)
348.7
(102.2)
338.8
(99.3)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
135.9
(39.8)
137.9
(40.4)
157.4
(46.1)
205.2
(59.7)
251.6
(73.7)
278.1
(81.5)
361.8
(106)
332.8
(97.5)
120.2
(35.2)
128.3
(37.6)
146.1
(42.8)
180.6
(51.9)
225.5
(66.1)
248.8
(72.9)
315.9
(92.6)
311.7
(91.3)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
130.5
(38.3)
131.9
(38.6)
150.7
(44.2)
196.9
(57.2)
240.8
(70.6)
266.7
(78.2)
346.9
(101.7)
321.1
(94.1)
107.1
(31.4)
113.8
(33.3)
129.3
(37.9)
162.1
(46.4)
200.3
(58.7)
220.8
(64.7)
279.8
(82)
277.9
(81.4)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
(not available after 12/31/15)
117.8
(34.5)
139.7
(40.9)
156.3
(45.8)
219.6
(64.9)
269.6
(79.0)
295.1
(86.5)
374
(109.6)
117.7
(34.5)
138.5
(40.6)
155.5
(45.6)
207.9
(62.0)
252.5
(74.0)
277.3
(81.3)
347.5
(101.8)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
113.9
(33.4)
133.2
(39.0)
148.8
(43.6)
212.1
(62.2)
259.1
(75.9)
283.6
(83.1)
360
(105.5)
108.8
(31.9)
125.8
(36.9)
141.6
(41.5)
192.6
(56.4)
229.3
(67.2)
251.5
(73.7)
315.2
(92.4)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)
109.6
(32.1)
127.5
(37.4)
142.3
(41.7)
202.9
(59.5)
248.5
(72.8)
272.9
(80)
346.3
(101.5)
97
(28.4)
111.7
(32.7)
125.5
(36.8)
171.5
(50.3)
203.9
(59.8)
223.7
(65.5)
280
(82.1)
6200
(10534)
7,500
(12,743)
9,000
(15,291)
10,400
(17,670)
13,700
(23,276)
13,700
(23,276)
2 (1.5)
3 (2.2)
5 (3.7)
3 (2.2)
5 (3.7)
7.5 (5.6)
10 (7.5)
10 (7.5)
3 (2.2)
5 (3.7)
7.5 (5.6)
5 (3.7)
7.5 (5.6)
10 (7.5)
15 (11.2)
15 (11.2)
Number of Fans
1.
2.
3.
4.
5,200
(8,835)
Liebert DS
12
Table 6
028
035
042
053
070
077
105U
105V
17.1 (1.6)
17.1 (1.6)
24.7 (2.3)
24.7 (2.3)
24.7 (2.3)
32.3 (3.0)
32.3 (3.0)
Rows of Coil
85.3
(25.0)
102.4
(30.0)
102.4
(30.0)
20.0 (68.3)
20.0 (68.3)
102.4
(30.0)
102.4
(30.0)
22.0 (10.0)
22.0 (10.0)
REHEAT SECTION
Electric Reheat - Three-stage, Stainless Steel Fin Tubular, capacity does not include fan motor heat
Capacity, kBTUH (kW), Standard Selection
51.2
(15.0)
51.2
(15.0)
51.2
(15.0)
Capacity, kBTUH (kW), Optional Selection 34.1 (10.0) 34.1 (10.0) 34.1 (10.0)
85.3
(25.0)
85.3
(25.0)
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (optional selection)
Capacity, kBTUH (kW)
51.2
(15.0)
51.2
(15.0)
51.2
(15.0)
85.3
(25.0)
85.3
(25.0)
85.3
(25.0)
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb./hr. (kg/h) 11.0 (5.0)
11.0 (5.0)
11.0 (5.0)
FILTER SECTION
Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11 (Filter types cannot be mixed, must be all MERV 8 or all
MERV 11.)
Downflow Models
Quantity
25x20
25x20
25x20
25x20
4 @ 25x20
4 @ 25x20
25x20
25x20
25x20
Upflow Models (Front and Rear Return)Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity
172.3
(50.5)
204.3
(59.9)
255
(74.7)
316.5
(92.7)
360.4
(105.6)
475.5
(139.3)
475.5
(139.3)
28
(105.90)
29 (109.7)
34 (128.7)
43 (162.7)
53 (200.6)
60 (227.1)
79 (299.0)
79 (299.0)
Pressure Drop, ft. of water (kPa), with valve 8.9 (26.70) 9.5 (28.4)
12.8 (38.3)
31.3 (93.6)
31.3 (93.6)
WATER COOLED SYSTEM - Digital Scroll Compressors, based on 75F/45% room conditions
Condenser Flow Requirements - Maximum design water pressure 150psi (1034kPa), 350psi (2413kPa) available as option; with EC Fans
THR, kBTUH (kW)
141.8
(41.6)
169.8
(49.8)
194.5
(57)
258.5
(75.8)
325.3
(95.3)
365.6
(107.2)
459.6
(134.7)
55.5
(210.1)
236.6
(62.5)
295.3
(78)
91.4 (30.6)
28.5
(107.9)
32.5 (123)
44 (166)
27.5 (9.2)
35.3 (11.8)
35 (11.7)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
1-5/8
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
DUAL-COOL UNITS APPLICATION DATA, Water (0% Glycol), Net Application Data kBTUH (kW)
CAUTION: CuNi coil option must be specified when Econ-O-Coil is applied to open water tower.
75F DB, 62.57 WB (23.9C DB, 16.9C WB) 45% RH, 45F EWT, 55F LWT; with EC Fans
Total Capacity, kBTUH (kW)
89.2
(26.2)
101.6
(29.8)
109.8
(32.2)
170.4
(49.9)
198.1
(58)
196.8
(57.7)
280.1
(82.1)
280.1
(82.1)
85
(24.9)
98.2
(28.8)
107.8
(31.6)
157.1
(46)
181.4
(53.2)
185.4
(54.3)
63.7
(4)
63.7
(4)
19
(1.2)
22.4
(1.4)
25.5
(1.6)
36.4
(2.3)
47.2
(3.0)
46.1
(2.9)
54.9
(3.5)
54.9
(3.5)
10.50
(31.39)
10.40
(31.09)
17.2
(51.41)
15.9 (47.6)
18 (53.80)
18 (53.80)
Pressure Drop, ft. (kPa), valve, coil 6.1 (18.23) 8.3 (24.81)
FLUID VOLUMES
Econ-O-Coil Fluid Volume, gal (l)
5 (19.0)
5 (19.0)
5 (19.0)
8 (30.4)
8 (30.4)
8 (30.4)
10 (38.0)
10 (38.0)
4 (15.2)
4 (15.2)
4 (15.2)
7 (26.6)
7 (26.6)
7 (26.6)
8 (30.4)
8 (30.4)
13
Liebert DS
4.0
Table 7
028
035
042
053
070
077
105U
105V
125.3
(36.7)
130.4
(38.2)
149.9
(43.9)
194.8
(57.1)
238.9
(70)
265.7
(77.9)
346.3
(101.5)
330.9
(97.0)
124.4
(36.4)
130.4
(38.2)
149.9
(43.9)
193.5
(56.7)
237.7
(69.7)
263.8
(77.3)
333.4
(97.7)
329.8
(96.6)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
119.1
(34.9)
122.3
(35.8)
141
(41.3)
185.1
(54.2)
226.8
(66.5)
252.9
(74.1)
331.4
(97.1)
306.1
(89.7)
112.9
(33.1)
120.9
(35.4)
138.8
(40.7)
177.6
(52.1)
218.1
(63.9)
242.2
(71.0)
304
(89.1)
301.4
(88.3)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
113.6
(33.3)
115.8
(33.9)
133.8
(39.2)
176
(51.6)
215.9
(63.3)
241.5
(70.8)
317.1
(92.9)
288.5
(84.5)
100.3
(29.4)
107.6
(31.5)
123.6
(36.2)
158.4
(46.4)
194.5
(57.0)
215.7
(63.2)
269.6
(79.0)
267.4
(78.4)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)
108.7
(31.9)
128
(37.5)
145.2
(42.5)
203.6
(59.7)
244.5
(71.6)
272.6
(79.9)
344.6
(101.0)
108.7
(31.9)
128
(37.5)
145.2
(42.5)
203
(59.5)
242.2
(71.0)
269.2
(78.9)
332.3
(97.4)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
103
(30.2)
120.6
(35.3)
136.8
(40.1)
193.4
(56.7)
233.1
(68.3)
260.5
(76.3)
330.7
(96.9)
102.6
(30.1)
119.6
(35.1)
135.9
(39.8)
187
(54.8)
221.1
(65.1)
246.6
(72.3)
303.6
(89.0)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)
97.6
(28.6)
114.7
(33.6)
130.2
(38.2)
184.1
(54.0)
223.2
(65.4)
249.8
(73.2)
317.6
(93.1)
92
(27.0)
107.1
(31.4)
121.8
(35.7)
167.2
(49.0)
198.4
(58.1)
219.7
(64.4)
270
(79.1)
11,000
(18,689)
13.700
(23,276)
13.700
(23,276)
3.75
(2.8)
3.75
(2.8)
3.75
(2.8)
3.4
(2.5)
5.4
(4.0)
7.9
(5.9)
10.5
(7.8)
10.5
(7.8)
Liebert DS
14
Table 8
028
035
042
053
070
077
105U
105V
123.1
(36.1)
126.8
(37.2)
144.4
(42.3)
194.8
(57.1)
233.2
(68.3)
258.8
(75.9)
340.4
(99.8)
324.4
(95.1)
122.2
(35.8)
126.8
(37.2)
144.4
(42.3)
193.5
(56.7)
229.9
(67.4)
254.9
(74.7)
327.4
(96.0)
323.1
(94.7)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
116.9
(34.2)
118.8
(34.8)
135.3
(39.6)
185.1
(54.2)
221.8
(65)
246.6
(72.3)
325.5
(95.4)
300.0
(87.9)
110.7
(32.4)
117.3
(34.4)
133.4
(39.1)
177.6
(52.1)
209.7
(61.5)
232.5
(68.1)
298
(87.3)
295.3
(86.5)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
111.4
(32.7)
112.3
(32.9)
128
(37.5)
176
(51.6)
211.5
(62)
235.6
(69.1)
311.2)
(91.2
282.6
(82.8)
98.1)
(28.7)
104.1
(30.5)
118.3
(34.7)
158.4
(46.4)
186.4
(54.6)
206.2
(60.4)
263.7
(77.3)
262.2
(76.8)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
(not available after 12/31/15)
106.5
(31.2)
124.5
(36.5)
139.4
(40.8)
199.3
(58.4)
239
(70.1)
265.7
(77.9)
338.7
(99.3)
106.5
(31.2)
124.5
(36.5)
139.4
(40.8)
197.1
(57.8)
234.3
(68.7)
259.8
(76.1)
326.3
(95.6)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
100.8
(29.6)
117
(34.3)
130.8
(38.3)
189.8
(55.6)
228.3
(66.9)
254.3
(74.5)
324.8
(95.2)
100.4
(29.4)
116.1
(34)
130.2
(38.1)
180.5
(52.9)
213.5
(62.6)
236.7
(69.4)
297.7
(87.2)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)
Sensible kBTUH (kW)
95.4
(28)
111.2
(32.6)
124
(36.4)
181.1
(53.1)
218.8
(64.1)
244
(71.5)
311.6
(91.3)
89.8
(26.3)
103.5
(30.3)
116.3
(34.1)
161
(47.2)
190.1
(55.7)
210.1
(61.6)
264
(77.4)
6,300
(10,704)
7,500
(12,743)
9,000
(15,291)
10,400
(17,670)
13,700
(23,276)
13,700
(23,276)
2 (1.5)
3 (2.2)
5 (3.7)
3 (2.2)
5 (3.7)
7.5 (5.6)
10 (7.5)
10 (7.5)
3 (2.2)
5 (3.7)
7.5 (5.6)
5 (3.7)
7.5 (5.6)
10 (7.5)
15 (11.2)
15 (11.2)
Number of Fans
1.
2.
3.
4.
5.
5,200
(8,835)
15
Liebert DS
Table 9
Model Size
028
035
042
053
070
077
105U
105V
17.1 (1.6)
17.1 (1.6)
17.1 (1.6)
24.7 (2.3)
24.7 (2.3)
24.7 (2.3)
32.3 (3.0)
32.3 (3.0)
REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat
Capacity, kBTUH (kW),
Standard Selection 51.2 (15.0)
51.2 (15.0)
51.2 (15.0)
85.3 (25.0)
85.3 (25.0)
85.3 (25.0)
102.4 (30.0)
102.4) (30.0
34.1 (10.0)
34.1 (10.0)
51.2 (15.0)
51.2 (15.0)
51.2 (15.0)
20.0 (68.3)
20.0 (68.3)
85.3 (25.0)
85.3 (25.0)
30.0 (102.4)
30.0 (102.4)
22.0 (10.0)
22.0 (10.0)
22.0 (10.0)
22.0 (10.0)
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection)
Capacity, kBTUH (kW) 51.2 (15.0)
51.2 (15.0)
51.2 (15.0)
85.3 (25.0)
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb/hr (kg/h)
11.0 (5.0)
11.0 (5.0)
11.0 (5.0)
22.0 (10.0)
FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11
(Filter types cannot be mixed, must be all MERV 8 or all MERV 11)
Downflow Models
Quantity
2 @ 25x20
1 @ 25x16
2 @ 25x20
1 @ 25x16
4 @ 25x20
4 @ 25x20
4 @ 25x20
4 @ 25x20
4 @ 25x20
25x20
25x20
25x20
25x20
25x20
25x20
25x20
25x20
OUTDOOR DRYCOOLERS - STANDARD 95F AMBIENT SELECTION; SEE Table 49 FOR OTHER SELECTIONS
Model Number
Number of Fans
D-174
D-174
D-225
D-260
D-310
D-350
D-466
D-466
189 (55.4)
238.3 (69.8) 297.7 (87.2) 341.8 (100.2) 456.9 (133.9) 456.9 (133.9)
32
(121.1)
33.5
(135)
39
(148)
49
(185)
62
(234.7)
70
(265)
96
(363)
96
(363)
12.9
(38.5)
14
(41.9)
18.6
(55.7)
16
(47.7)
25
(74.7)
31.3
(93.6)
50.6
(151.3)
50.6
(151.3)
28 (106)
248 (72.7)
33.5 (127)
39 (148)
52 (163.5)
64 (242)
73.5 (278)
91.5 (264.9)
14.0 (41.9)
18.6 (55.6)
17.9 (53.5)
26.6 (79.5)
34.4 (102.8)
46.2 (138.1)
1-5/8" (41)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
1-5/8" (41)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
Liebert DS
16
5.0
LIEBERT DS GLYCOOL
Table 10
SYSTEM DATA
028
035
042
053
070
077
105U
105V
124.6
(36.5)
129.3
(37.9)
148.4
(43.5)
197.9
(58.0)
236.3
(69.3)
263.7
(77.3)
342.6
(100.4)
327.4
(95.9)
123.7
(36.3)
129.3
(37.9)
148.4
(43.5)
197.8
(58.0)
235.1
(68.9)
259.7
(76.1)
328.7
(96.3)
325.1
(95.2)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
118.4
(34.7)
121.2
(35.5)
139.5
(40.9)
187.4
(54.9)
224.2
(65.7)
251.5
(73.7)
327.8
(96.1)
302.7
(88.7)
112.3
(32.9)
119.8
(35.1)
137.2
(40.2)
182.3
(53.4)
215.5
(63.2)
237.2
(69.5)
299.1
(87.7)
296.8
(87)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45.1% RH
Total kBTUH (kW)
112.9
(33.1)
114.7
(33.6)
132.3
(38.8)
177.7
(52.1)
213.3
(62.5)
240.5
(70.5)
313.7
(91.9)
285.3
(83.6)
99.6
(29.2)
106.6
(31.2)
122
(35.8)
163
(47.8)
192
(56.3)
210.9
(61.8)
265.1
(77.7)
263.5
(77.2)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
Total kBTUH (kW)
108
(31.7)
127.1
(37.2)
143.5
(42.1)
201.6
(59.1)
241.9
(70.9)
263.7
(77.3)
340.9
(99.9)
108
(31.7)
127.1
(37.2)
143.5
(42.1)
201.1
(58.9)
239.6
(70.2)
257.9
(75.6)
327.6
(96.0)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
102.4
(30)
119.6
(35.1)
135.1
(39.6)
191.4
(56.1)
230.6
(67.6)
252.3
(73.9)
327.1
(95.9)
102
(29.9)
118.6
(34.8)
134.1
(39.3)
185.1
(54.2)
219.5
(64.3)
234.8
(68.8)
298.8
(91.2)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)
96.9
(28.4)
113.7
(33.3)
128.5
(37.6)
182.3
(53.4)
220.7
(64.7)
242
(70.9)
314.1
(92.0)
91.4
(26.8)
106.1
(31.1)
120.1
(35.2)
165.5
(48.5)
195.8
(57.4)
208.3
(61.0)
265.4
(77.8)
5,200
(8,835)
6200
(10,534)
8,000
(13,592)
9,600
(16,310)
10,400 13,500
(17670) (22937)
13,500
(22937)
3.75
(2.8)
3.75
(2.8)
3.75
(2.8)
3.4
(2.5)
5.4
(4.0)
7.9
(5.9)
10.5
(7.8)
10.5
(7.8)
17
Liebert DS
Table 11
028
035
042
053
070
077
105U
105V
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor, Semi-Hermetic Compressors
Semi-Hermetic Compressors (Four-Step Cooling) with Forward-Curved Blowers
85F DB, 64.5F WB, 52.3F DP (29.4C DB, 18.1C WB) 32.4% RH
122.4
(35.9)
125.7
(36.8)
142.8
(41.9)
193.2
(56.6)
230.8
(67.6)
255.7
(74.9)
336.5
(98.6)
319.1
(93.5)
121.5
(35.6)
125.7
(36.8)
142.8
(41.9)
191.9
(56.2)
227.5
(66.7)
251.7
(73.8)
322.6
(94.6)
316.8
(92.8)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
116.2
(34.1)
117.7
(34.5)
133.7
(39.2)
183.4
(53.8)
219.4
(64.3)
243.5
(71.4)
321.7
(94.3)
295.2
(86.5)
110
(32.3)
116.3
(34.1)
131.9
(38.6)
176
(51.6)
207.3
(60.8)
229.2
(67.2)
293
(89.5)
289.5
(84.8)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
110.7
(32.5)
111.1
(32.6)
126.5
(37.1)
174.4
(51.1)
209
(61.3)
232.4
(68.1)
307.6
(90.1)
278.2
(81.5)
97.4
(28.5)
103
(30.2)
116.7
(34.2)
156.8
(45.9)
184
(53.9)
202.8
(59.4)
258.9
(75.9)
256.9
(75.3)
Net Application Data BTUH (kW), Standard Air Volume and Evaporator Fan Motor
Scroll Compressors Only
(not available after 12/31/15)
105.8
(31)
123.5
(36.2)
137.8
(40.4)
197.4
(57.9)
236.6
(69.3)
262
(76.8)
334.8
(98.1)
105.8
(31)
123.5
(36.2)
137.8
(40.4)
195.3
(57.2)
231.8
(67.9)
256.2
(75.1)
321.5
(94.2)
80F DB, 62.9F WB, 52.3F DP (26.7C DB, 17.1C WB) 38.2% RH
Total kBTUH (kW)
100.2
(29.4)
116.1
(34)
129.3
(37.9)
187.9
(55.1)
225.9
(66.2)
250.6
(73.4)
321
(94.1)
99.8
(29.2)
115.1
(33.7)
128.6
(37.7)
178.8
(52.4)
211.1
(61.9)
233.1
(68.3)
292.7
(89.4)
75F DB, 61.1F WB, 52.3F DP (23.9C DB, 16.2C WB) 45% RH
Total kBTUH (kW)
94.7
(27.8)
110.2
(32.3)
122.5
(35.9)
179.1
(52.5)
216.4
(63.4)
240.3
(70.4)
307.9
(90.3)
89.1
(26.1)
102.5
(30)
114.7
(33.6)
159.2
(46.7)
187.6
(55)
206.6
(60.5)
259.3
(76)
13,700
(23,276)
13,700
(23,276)
6,300
(10,704)
7,500
(12,743)
9,000
(15,291)
10,400
(17,670)
2 (1.5)
3 (2.2)
5 (3.7)
3 (2.2)
5 (3.7)
7.5 (5.6)
10 (7.5)
10 (7.5)
3 (2.2)
5 (3.7)
7.5 (5.6)
5 (3.7)
7.5 (5.6)
10 (7.5)
15 (11.2)
15 (11.2)
Number of Fans
1.
2.
3.
4.
5.
5,200
(8,835)
Liebert DS
18
Table 12
028
035
042
053
070
077
105U
105V
17.1 (1.6)
17.1 (1.6)
17.1 (1.6)
24.7 (2.3)
24.7 (2.3)
24.7 (2.3)
32.3 (3.0)
32.3 (3.0)
REHEAT SECTION
Electric Reheat - Three-Stage, Stainless Steel Fin Tubular, Capacity Does Not Include Fan Motor Heat
Capacity, kBTUH (kW), Standard
51.2 (15.0)
Selection
51.2 (15.0)
51.2 (15.0)
85.3 (25.0)
85.3 (25.0)
85.3 (25.0)
102.4 (30.0)
102.4 (30.0)
34.1 (10.0)
34.1 (10.0)
51.2 (15.0)
51.2 (15.0)
51.2 (15.0)
68.3 (20.0)
68.3 (20.0)
85.3 (25.0)
85.3 (25.0)
102.4 (30.0)
102.4 (30.0)
22.0 (10.0)
22.0 (10.0)
22.0 (10.0)
22.0 (10.0)
Electric Reheat - SCR Control, Stainless Steel Fin Tubular (Optional Selection)
Capacity, kBTUH (kW) 51.2 (15.0)
51.2 (15.0)
51.2 (15.0)
85.3 (25.0)
HUMIDIFIER SECTION
Infrared Humidifier
Capacity, lb/hr (kg/h)
11.0 (5.0)
11.0 (5.0)
11.0 (5.0)
22.0 (10.0)
FILTER SECTION - Disposable Type - Nominal Sizes and Quantities, Standard MERV 8 or Optional MERV 11
(filter types cannot be mixed, must be all MERV 8 or all MERV 11)
Downflow Models
Quantity
2 @ 25x20
Nominal Size, inches 1 @ 25x16
2 @ 25x20
1 @ 25x16
2 @ 25x20
1 @ 25x16
4 @ 25x20
4 @ 25x20
4 @ 25x20
4 @ 25x20
4 @ 25x20
Upflow Models (Front & Rear Return) Filters located in separate filter box on rear return, located on lower unit panel on front return
Quantity
Nominal Size, inches
25x20
25x20
25x20
25x20
25x20
25x20
25x20
25x20
OUTDOOR DRYCOOLERS - Standard 95F Ambient Selection; See Table 49 for other selections
Model Number
Number of Fans
D-174
D-174
D-225
D-260
D-310
D-350
D-466
D-466
32 (121)
159 (46.6)
33 (125)
189.2 (55.5) 240.8 (70.6) 297.7 (87.2) 339.3 (99.4) 455.9 (133.6) 455.9 (133.6)
40 (151)
49 (185)
62 (235)
71 (269)
95 (360)
95 (360)
Pressure Drop, ft. of water (kPa), 12.9 (38.50) 13.6 (40.60) 19.6 (58.59) 16.0 (47.83) 25.0 (74.73) 32.2 (96.25) 49.6 (148.30) 49.6 (148.30)
GLYCOOL SYSTEM - Digital Scroll Compressors, Based on 75F/45% Room Conditions with EC
Fans
THR, kBTUH (kW) 134.5 (39.4) 162.4 (47.6) 186.8 (54.7)
104F (40C) EGT, GPM (l/m)
28 (98.4)
33.5 (127)
39 (148)
248 (72.7)
51 (193)
72 (273)
89 (337)
Pressure Drop, ft. of water (kPa) 10.0 (29.89) 14.0 (41.85) 18.6 (55.60) 17.2 (51.41) 26.6 (79.51) 33.1 (98.84) 43.8 (130.92)
1-5/8" (41)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
1-5/8" (41)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
2-1/8" (54)
1/4
1/4
1/4
1/4
1/4
1/4
1/4
1/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
3/4
1/2
1/2
1/2
1/2
1/2
1/2
1/2
1/2
5/8
5/8
5/8
5/8
5/8
5/8
5/8
5/8
ECON-O-COIL APPLICATION DATA (GLYCOOL Units), 40% Ethylene Glycol, Net Application Data, kBTUH (kW)
75F DB, 62.57FWB (23.9C, 16.9C) 45% RH, 45F EGT Room Conditions with EC Fans
Total capacity kBTUH (kW) 82.8 (24.3)
93.9 (27.5) 103.9 (30.4) 156.8 (45.9) 182.3 (53.4) 182.3 (57.2)
243.3 (71.3)
243.3 (71.3)
93.9 (27.5) 103.9 (30.4) 152.6 (44.7) 176.9 (51.8) 176.9 (55.3)
238.2 (69.8)
238.2 (69.8)
89 (337)
89 (337)
28 (106)
33.5 (127)
39 (148)
51 (193)
64 (242)
72 (273)
Pressure Drop, ft. of water (kPa) 18.4 (55.0) 25.7 (76.82) 33.8 (101.03) 38.9 (116.27) 59.1 (176.65) 73.5 (219.70) 75.2 (224.78) 75.2 (224.78)
FLUID VOLUMES
Unit Volume Without Econ-O-Coil,
gal (l)
4 (15.2)
4 (15.2)
4 (15.2)
7 (26.6)
7 (26.6)
7 (26.6)
8 (30.4)
8 (30.4)
9 (34.2)
9 (34.2)
9 (34.2)
14 (53.2)
14 (53.2)
14 (53.2)
17 (64.6)
17 (64.6)
19
Liebert DS
Electrical Data
6.0
ELECTRICAL DATA
6.1
Table 13
Reheat
Options
Electric
Standard, kW
None
Electric
Standard kW
None
Electric,
Downsized kW
Electric,
Downsized kW
Humidifier
Options
Infrared
Infrared
None
None
Humidifier
No Humidifier
Model
#
Volts 208
FLA
DS028 WSA
208
67.3
64.8 32.1 25
43
82
47.3
49.8
66.1
55
55
70
70
FLA
78.2
78.1
92.5
46
36
85.2
83
110
50
45
110
110
32 27.1 86.3
40
30
75.9 37.7 33
90
78.2
30
60
60
30
25
70
25
70
69
67
80
80
64.8
92.5
46
36
71.9
83
110
50
40
110
40
30
75.9 37.7 33
41.2 35.8
26.9 20.4
35
69
67
32.7 24.8
80
80
64.8
64.8
31.9 25.6
78.4
76.4
37.8 29.6
35
25
100
89.6
DS053 WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8
90.6
90.62 44.9 33.4 117.2 112.8 56.5 45 110.52 107.4 53.1 40.3
50
150
150
70
50
110
110
60
45
125
125
70
50
125
FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4
125
45
25
100
70
50
70
55.3
92.1
125
110
32.7 27.1
70
56.9
45
125
35
30
100
50
45
35
70
110
45
30
100
150
45
90
40
82.6
150
50
80
FLA 119.9 116 57.1 43.5 109.2 104.8 52.4 42 119.9 116 57.1 43.5
OPD
110
75.9 37.7 33
80
25.6 19.9
31.1 24.1
80
30
51.9
62.8
80
35
53.5
64.8
30
70
460 575
80
45
70
230
70.7
90
30
208
FLA
90
40
43
OPD
OPD
80
82
35
44.1 33.5
60
45
DS070 WSA 156.9 152 72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.15 119.02 56.6 43
OPD
175
175
80
60
175
175
80
60
80
60
150
50 134.9 131 61.4 47.5 112.6 112.6 49.4 38.4 139.2 134.8 61
175
175
80
60
150
150
70
50
175
175
50
112.6
150
70
50
DS077 WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.37 124.4 54.6 42.4 151 146.6 66.2 54 129.27 126.15 58.5 45.3
OPD
175
175
80
70
175
175
80
70
175
175
80
60
150
150
70
50
175
175
80
70
150
150
70
50
FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9
DS105 WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3
OPD
1.
2.
3.
4.
5.
6.
225
225
225
225 110 90
Liebert DS
20
200
200 110 80
225
225
110 100
200
200
110 80
Electrical Data
Table 14
Reheat Options
Electric, Std. kW
None
Electric, Std. kW
None
Humidifier Options
Infrared or Steam
Generating Canister
Infrared or Steam
Generating Canister
None
None
Model
028
028
035
035
042
042
Motor
hp Volts
2.0
3.0
3.0
5.0
5.0
7.5
208
230
460
208
230
460
070
5.0
5.0
230
460
575
208
230
460 575
66.4
63.2
52.5
63.2
81.1
77.3
56.8
77.3
45.7
23
18.2
OPD
80
80
60
30
25
40
30
70
70
35
30
80
80
40
30
60
FLA
69.5
66.0
55.3
66.0
WSA
84.2
80.1
40.3
33
62.8
59.6
80.1
OPD
90
80
40
30
80
70
FLA
72.9
69.4
62.1
69.4
WSA
88.5
84.4
67.3
84.4
OPD
90
90
FLA
79.0
75.0
67.7
75.0
WSA
94.6
90.0
72.9
90.0
OPD
100
100
FLA
86.5
82.7
WSA
104
99.3
OPD
110
110
FLA
94.0
89.5
45
45
50
35
35
50
90
90
125
110
40
90
35
90
80
90
40
45
35
70
70
35
25
89.8
89.5
41
101.4
96
50
40
41
74.8
WSA 137.5 131.6 66.2 50.8 109.4 104.0 53.3 42.5 137.5 131.6 66.2 50.3 82.8
70
110
100
125
125
89.3
100
30
45
150
50
45
40
25
50
80
30
110
80
60
82.5
110
35
60
45
30
82.7
50
35
90
100
110
45
30
100
110
60
35
80
OPD
053
208
FLA
575
WSA
OPD
053
575
50
125
60
50
125
110
60
125
60
50
150
125
70
50
110
110
50
50
45
40
FLA 118.2 112.8 56.7 43.2 107.5 101.6 52.0 41.7 118.2 112.8 56.7 43.2 80.9
WSA 143.6 137.2 69.0 53.5 115.5 109.6 56.1 44.7 143.6 137.2 69.0 52.5 88.9
OPD
110
110
60
45
FLA 127.5 122.1 59.5 46.1 126.1 120.2 57.6 46.1 127.5 122.1 59.5 45.4 99.5
98
46
34.5
150
150
70
50
125
125
70
50
150
150
70
50
WSA 155.2 148.8 72.5 55.2 136.5 130.6 62.4 49.7 155.2 148.8 72.5 55.2 109.9 108.4 50.8 38.1
OPD
175
150
80
60
175
150
80
60
175
150
80
60
150
125
70
50
FLA 135.0 128.9 62.9 49.0 133.6 127.0 61.0 49.0 135.0 128.9 62.9 48.3 107.0 104.8 49.4 37.4
070
077
7.5
7.5
WSA 162.7 155.6 75.9 58.1 144.0 137.4 65.8 52.6 162.7 155.6 75.9 58.1 117.4 115.2 54.2 41.0
OPD
175
FLA
145
175
80
60
175
175
80
60
175
175
80
60
150
150
70
50
138.4 64.4 52.6 145.0 138.4 64.0 52.6 140.7 134.6 64.4 50.1 118.4 116.2 52.4 41.0
WSA 169.8 162.8 77.8 60.4 156.8 150.2 69.2 56.6 169.8 162.8 77.8 60.4 130.2 128.0 57.6 45.0
OPD
200
175
90
70
200
175
80
70
175
175
90
70
175
175
70
60
FLA 151.6 144.4 67.4 54.6 151.6 144.4 67.0 54.6 147.3 140.6 67.4 52.1 125.0 122.2 55.4 43.0
077
10.0
WSA 176.4 168.8 80.8 62.4 163.4 156.2 72.2 58.6 176.4 168.8 80.8 62.4 136.8 134.0 60.6 47.0
OPD
200
200
90
70
200
200
90
70
200
175
90
70
175
FLA 177.4 170.2 88.4 72.6 177.4 170.2 88.4 72.6 169.9 166.6 84.5 66.1 150.8
105
10.0
175
148
80
60
76.8 61.0
WSA 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 165.8 163.0 84.7 67.3
OPD
250
225
125
100
250
225
125
100
225
225
110
90
225
200
110
90
FLA 192.3 184.2 95.4 78.6 192.3 184.2 95.4 78.6 185.3 180.6 91.5 72.1 166.2 162.0 83.8 67.0
105
15.0
WSA 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 181.2 177.0 91.7 73.3
OPD
1.
2.
3.
4.
5.
250
250
125
100
250
250
125
100
250
250
125
100
225
225
110
90
21
Liebert DS
Electrical Data
Table 14
Electric, Downsized kW
Humidifier Options
Model
Motor, hp
028
028
035
035
042
042
053
053
070
070
077
077
105
105
1.
2.
3.
4.
5.
2.0
3.0
3.0
5.0
5.0
7.5
3.0
5.0
5.0
7.5
7.5
10.0
10.0
15.0
230
460
575
208
230
460
575
FLA
55.4
52.5
26.6
23.9
52.6
50.3
25.3
19.6
WSA
63.9
61.2
30.8
25.6
63.9
61.2
30.8
23.8
OPD
70
70
35
30
70
70
35
25
FLA
58.5
55.3
28
25.1
55.7
53.1
26.7
20.8
WSA
67.0
64.0
32.2
26.8
67.0
64.0
32.2
25.0
OPD
80
70
35
30
70
70
35
25
FLA
65.3
62.1
30.6
26.1
59.1
56.5
28.0
21.3
WSA
71.2
68.2
33.8
28.0
71.2
68.2
33.8
25.7
OPD
90
80
40
35
80
80
40
30
FLA
71.4
67.7
33.4
28.3
65.2
62.1
30.8
23.5
WSA
77.3
73.8
36.6
30.2
77.3
73.8
36.6
27.9
OPD
90
90
45
35
90
80
40
30
FLA
86.4
82.7
41.6
36.1
73.1
71.6
35.8
28.7
WSA
93.5
89.8
45.1
38.9
86.7
83.2
41.7
32.7
OPD
110
110
50
50
100
100
50
40
FLA
93.9
89.5
45.0
39.0
80.6
78.4
39.2
31.6
WSA
101.0
96.6
48.5
41.8
94.2
90.0
45.1
35.6
OPD
125
110
60
50
110
110
50
45
FLA
101.4
96.0
49.2
39.5
84.3
80.8
40.9
31
WSA
109.4
104.0
53.3
42.5
102.7
98.6
49.9
37.8
OPD
125
125
60
50
110
110
60
45
FLA
107.5
101.6
52.0
41.7
90.4
86.4
43.7
33.2
WSA
115.5
109.6
56.1
44.7
108.8
104.2
52.7
40.0
OPD
125
125
70
50
125
125
60
45
FLA
126.1
120.2
57.6
46.1
99.7
98
46.5
35.4
WSA
136.5
130.6
62.4
49.7
120.5
115.8
56.2
42.7
OPD
175
150
80
60
150
125
70
50
FLA
133.6
127.0
61.0
49.0
107.2
104.8
49.9
38.3
WSA
144.0
137.4
65.8
52.6
128.0
122.6
59.6
45.6
OPD
175
175
80
60
150
150
70
50
FLA
145
138.4
64.0
52.6
118.4
116.2
52.4
41.0
WSA
156.8
150.2
69.2
56.6
135.1
129.8
61.5
47.9
OPD
200
175
80
70
175
175
70
60
FLA
151.6
144.4
67.0
54.6
125.0
122.2
55.4
43.0
WSA
163.4
156.2
72.2
58.6
141.7
135.8
64.5
49.9
OPD
200
200
90
70
175
175
80
60
FLA
177.4
170.2
88.4
72.6
150.8
148
76.8
61.0
WSA
192.4
185.2
96.3
78.9
175.2
168.6
86.0
67.4
OPD
250
225
125
100
225
200
110
90
FLA
192.8
184.2
95.4
78.6
166.2
162.0
83.8
67.0
WSA
207.8
199.2
103.3
84.9
190.6
182.6
93.0
73.4
OPD
250
250
125
100
225
225
110
90
Liebert DS
None
Volts
22
Electrical Data
6.2
Table 15
Reheat
Options
Humidifier
Options
Model# Volts 208
FLA
028
82
OPD
80
Infrared
Infrared
230
None
230
40
30
70
70
35
30
82
80
None
Humidifier
None
60
55
55
OPD
40
70
70
90
45
30
80
80
33
46
36
85.2
83
OPD
50
45
110
110
110
110
30
90
90
30
25
70
70
35
30
45
45
30
26.2 19.7
35
25
69
67
80
80
32.7 27.1
40
30
78.2 75.7 37.5 29.4 64.8 64.8 31.9 25.6 78.1 75.9 37.7 33
110
460 575
60
90
230
30
43
Electric,
Downsized kW
40
43
Electric,
Downsized kW
78.9 39.2 30.5 47.3 47.3 23.3 18.5 64.8 62.8 31.1 25.9 64.8
80
25
None
70
70.7 68.2 33.4 25.5 63.1 60.9 29.5 25.2 70.7 68.2 33.4 25.5 49.8 49.8 23.7 17.8 63.1 60.9 29.5 25.2 56.9
Electric
Standard kW
FLA
042
None
67.3 64.8 32.1 25.5 56.3 54.1 26.9 24.2 67.3 64.8 32.1
WSA
FLA
035
Electric
Standard, kW
110
46
36
83
50
40
100
110
100
45
70
35
25
69
67
80
80
32.7 24.8
35
25
64.8
45
100
100
92.1
35
110
50
45
35
WSA 145.3 140.4 69.4 53.9 117.2 112.8 56.5 45 145.3 140.4 69.4 52.8 90.6 90.62 44.9 33.4 117.2 112.8 56.5 45 110.5 107.4 53.1 40.3
OPD
150
150
70
50
125
125
70
50
150
150
70
50
110
110
60
45
125
125
70
50
125
125
60
45
FLA 129.2 125.3 59.9 46.4 127.8 123.4 58 46.4 129.2 125.3 59.9 45.7 101.2 101.2 46.4 34.8 127.8 123.4 58 46.4 101.4 101.2 46.9 35.7
070
175
175
72.9 55.5 138.2 133.8 62.8 50 156.9 152.0 72.9 55.5 111.6 111.6 51.2 38.4 138.2 133.8 62.8 50 122.2 119.02 56.6 43
80
60
175
175
80
50 139.2 134.8 61
60
175
175
50 134.9 131
80
60
150
150
70
50
175
175
80
60
150
150
70
50
WSA 164 159.2 74.8 57.8 151. 146.6 66.2 54 164.0 159.2 74.8 57.8 124.4 124.4 54.6 42.4 151 146.6 66.2 54 129.3 126.15 58.5 45.3
OPD
175
175
80
70
175
175
80
70
175
175
80
60
150
1*0
70
50
175
175
80
70
150
150
70
50
FLA 171.5 167.1 83.7 69.1 171.5 167.1 83.7 69.1 164 163.5 79.8 62.6 144.9 144.9 72.1 57.5 171.5 167.1 83.7 69.1 144.9 144.9 72.1 57.5
105U
105V
1.
2.
3.
4.
5.
6.
WSA 198.8 198.2 97.4 76.4 186.5 182.1 91.6 75.4 198.8 198.2 97.4 76.4 159.9 159.9 80 63.8 186.5 182.1 91.6 75.4 169.3 165.5 81.3 63.9
OPD
225
FLA
164 163.5 82.5 64.7 158.6 154.2 75.7 62.2 164 163.5 82.5 64.7 132
225
225
110
90
200
200 110 80
WSA 198.8 198.2 100.1 78.5 173.6 169.2 83.6 68.5 198.8 198.2 100.1 78.5 147
147
OPD
200 100 80
225
225
110
90
225
225 110 90
225
225
110
90
200
225
200
110 80
132 64.1 50.6 158.6 154.2 75.7 62.2 140.4 137.4 69.6 54.7
72 56.9 173.6 169.2 84 68.5 169.3 165.5
225
225 110 90
200
200
84
66
100 80
23
Liebert DS
Electrical Data
Table 16
Reheat Options
Electric, Std. kW
None
Humidifier
Options
Infrared or Steam
Generating Canister
Infrared or Steam
Generating Canister
028
035
035
042
042
2.0
3.0
3.0
5.0
5.0
7.5
575
208
230
460
575
208
230
460
575
208
230
460
FLA
66.4
63.2
31.8
25.2
55.4
52.5
26.6
23.9
66.4
63.2
31.8
24.7
42.1
41.4
20.8 16.5
WSA
81.1
77.3
38.9
31.5
59.7
56.8
28.8
25.6
81.1
77.3
38.9
30.2
46.4
45.7
23
18.2
OPD
80
80
40
30
70
70
35
30
80
80
40
30
60
60
30
25
FLA
69.5
66.0
33.2
26.4
58.5
55.3
28.0
25.1
69.5
66.0
33.2
25.9
45.2
44.2
22.2 17.7
WSA
84.2
80.1
40.3
33
62.8
59.6
30.2
26.8
84.2
80.1
40.3
31.4
49.5
48.5
24.4 19.4
OPD
90
80
40
30
80
70
35
30
90
80
40
30
60
60
FLA
72.9
69.4
34.5
26.4
65.3
62.1
30.6
26.1
72.9
69.4
34.5
26.4
52.0
51.0
24.8 18.7
WSA
88.5
84.4
41.9
33.0
70.5
67.3
33.1
28.0
88.5
84.4
41.9
32.0
57.2
56.2
27.3 20.6
OPD
90
90
45
35
90
80
40
35
90
90
45
35
70
70
FLA
79.0
75.0
37.3
28.6
71.4
67.7
33.4
28.3
79.0
75.0
37.3
28.6
58.1
56.6
27.6 20.9
WSA
94.6
90.0
44.7
35.8
76.6
72.9
35.9
30.2
94.6
90.0
44.7
34.2
63.3
61.8
30.1 22.8
OPD
100
100
45
35
90
90
45
35
100
100
45
35
80
80
FLA
86.5
82.7
41.6
36.1
86.4
82.7
41.6
36.1
86.5
82.5
41.4
32.5
73.1
71.6
35.8 28.7
WSA
104
99.3
49.9
39.1
93.5
89.8
45.1
38.9 104.0
99.3
49.9
39.1
80.2
78.7
39.3 31.5
OPD
110
110
50
50
110
110
50
50
110
110
50
45
100
100
FLA
94.0
89.5
45.0
39.0
93.9
89.5
45.0
39.0
94.0
89.3
44.8
35.4
80.6
78.4
39.2 31.6
53.3
42.0 101.0
53.3
42.0
87.7
85.5
42.7 34.4
60
45
110
110
077
7.5
48.5
60
112.1 107.2
53.9
41
101.4
96
49.2
53.9
41
74.8
73.8
37.6 27.9
66.2
53.3
66.2
50.3
82.8
81.8
41.7 30.9
70
50
110
110
1.
2.
3.
4.
5.
50
125
50
40
69.0
56.1
69.0
52.5
88.9
87.4
44.5 33.1
70
50
110
110
60
45
99.5
98
46
34.5
150
150
70
50
125
125
70
50
150
150
127.5 122.1
59.5
57.6
59.5
45.4
72.5
62.4
72.5
175
150
80
60
175
150
80
60
175
150
80
60
150
125
70
50
135.0 128.9
62.9
61.0
62.9
75.9
65.8
75.9
OPD
175
175
80
FLA
145
138.4
64.4
64.0
64.4
77.8
69.2
77.8
200
175
90
60
70
175
200
175
175
80
80
60
70
175
175
175
175
80
90
60
70
150
175
150
175
70
70
50
60
151.6 144.4
67.4
67.0
67.4
80.8
72.2
80.8
200
200
177.4 170.2
90
88.4
70
200
200
90
88.4
70
200
175
90
84.5
70
175
66.1 150.8
175
148
80
60
76.8 61.0
WSA 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 204.7 201.3 102.1 79.9 165.8 163.0 84.7 67.3
250
225
192.3 184.2
125
100
95.4
250
225
125
100
95.4
225
225
110
91.5
90
225
200
110
90
WSA 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 220.1 215.3 109.1 85.9 181.2 177.0 91.7 73.3
250
250
125
100
125
100
84.5
77.7
85.6
169.9 166.6
225
225
185.3 180.6
110
91.5
90
250
225
250
225
110
84.7
92.6
24
250
250
125
100
225
225
110
90
225
225
84.5
90
200
200 100 80
72.1 153.3 149.1 73.1 58
79.5 220.1 215.3 109.1 85.9 168.3 164.1 81 64.3
100 250
250
125 100 225
200 110 80
69.6 185.3 180.6
OPD 250
250
125 100 250
225
110
Reduced reheat for 028, 035, and 042 models is 10kW.
Reduced reheat for 053, 070, and 077 models is 15kW.
Consult local representative for SCR reheat values.
Reduced reheat for 105 kW models is 20kW.
SCCR - Short Circuit Current Rating 65,000 amps rms symmetrical maximum.
Liebert DS
150
40.4 30.1
FLA
15.0
60
79.4
OPD
105V
125
80.9
FLA
10.0
125
45
43.2
OPD
105V
50
50
56.7
FLA
15.0
110
OPD
105U
70
125
52.0
FLA
10.0
125
50
OPD
105U
150
110
56.7
FLA
10.0
125
118.2 112.8
OPD
077
40
110
FLA
7.5
50
30
96.6
OPD
070
40
25
125
FLA
5.0
35
25
50
OPD
070
30
575
60
FLA
5.0
None
460
OPD
053
None
230
FLA
3.0
None
208
OPD
053
Electric, Std. kW
110
91.5
Electrical Data
Table 16
Reheat Options
Humidifier Options
Model
Motor, hp
Volts
FLA
028
2.0
WSA
OPD
FLA
028
3.0
WSA
OPD
FLA
035
3.0
WSA
OPD
FLA
035
5.0
WSA
OPD
FLA
042
5.0
WSA
OPD
FLA
042
7.5
WSA
OPD
FLA
053
3.0
WSA
OPD
FLA
053
5.0
WSA
OPD
FLA
070
5.0
WSA
OPD
FLA
070
7.5
WSA
OPD
FLA
077
7.5
WSA
OPD
FLA
077
10.0
WSA
OPD
FLA
105U
10.0
WSA
OPD
FLA
105U
15.0
WSA
OPD
FLA
105V
10.0
WSA
OPD
FLA
105V
15.0
WSA
OPD
1.
2.
3.
4.
5.
Electric, Downsized kW
Infrared or Steam Generating Canister
208
230
460
575
208
55.4
52.5
26.6
23.9
52.6
63.9
61.2
30.8
25.6
63.9
70
70
35
30
70
58.5
55.3
28
25.1
55.7
67.0
64.0
32.2
26.8
67.0
80
70
35
30
70
65.3
62.1
30.6
26.1
59.1
71.2
68.2
33.8
28.0
71.2
90
80
40
35
80
71.4
67.7
33.4
28.3
65.2
77.3
73.8
36.6
30.2
77.3
90
90
45
35
90
86.4
82.7
41.6
36.1
73.1
93.5
89.8
45.1
38.9
86.7
110
110
50
50
100
93.9
89.5
45.0
39.0
80.6
101.0
96.6
48.5
41.8
94.2
125
110
60
50
110
101.4
96.0
49.2
39.5
84.3
109.4
104.0
53.3
42.5
102.7
125
125
60
50
110
107.5
101.6
52.0
41.7
90.4
115.5
109.6
56.1
44.7
108.8
125
125
70
50
125
126.1
120.2
57.6
46.1
99.7
136.5
130.6
62.4
49.7
120.5
175
150
80
60
150
133.6
127.0
61.0
49.0
107.2
144.0
137.4
65.8
52.6
128.0
175
175
80
60
150
145
138.4
64.0
52.6
118.4
156.8
150.2
69.2
56.6
135.1
200
175
80
70
175
151.6
144.4
67.0
54.6
125.0
163.4
156.2
72.2
58.6
141.7
200
200
90
70
175
177.4
170.2
88.4
72.6
150.8
192.4
185.2
96.3
78.9
175.2
250
225
125
100
225
192.8
184.2
95.4
78.6
166.2
207.8
199.2
103.3
84.9
190.6
250
250
125
100
225
164.5
157.3
77.7
63.6
146.3
179.5
172.3
86
69.9
175.2
225
225
110
90
200
179.9
171.3
84.7
69.6
161.7
194.9
186.3
93
75.9
190.6
250
225
110
100
225
None
230
50.3
61.2
70
53.1
64.0
70
56.5
68.2
80
62.1
73.8
80
71.6
83.2
100
78.4
90.0
110
80.8
98.6
110
86.4
104.2
125
98
115.8
125
104.8
122.6
150
116.2
129.8
175
122.2
135.8
175
148
168.6
200
162.0
182.6
225
140.5
168.6
200
154.5
182.6
225
460
25.3
30.8
35
26.7
32.2
35
28.0
33.8
40
30.8
36.6
40
35.8
41.7
50
39.2
45.1
50
40.9
49.9
60
43.7
52.7
60
46.5
56.2
70
49.9
59.6
70
52.4
61.5
70
55.4
64.5
80
76.8
86.0
110
83.8
93.0
110
71.6
86
110
78.6
93
110
575
19.6
23.8
25
20.8
25.0
25
21.3
25.7
30
23.5
27.9
30
28.7
32.7
40
31.6
35.6
45
31
37.8
45
33.2
40.0
45
35.4
42.7
50
38.3
45.6
50
41.0
47.9
60
43.0
49.9
60
61.0
67.4
90
67.0
73.4
90
56.1
67.4
80
62.1
73.4
90
25
Liebert DS
7.0
Table 17
Model #
Compressor
Type
Scroll or
Digital Scroll
DS028-042
Semi-Hermetic
Scroll or
Digital Scroll
DS053
Semi-Hermetic
Scroll or
Digital Scroll
DS070
Semi-Hermetic
Scroll or
Digital Scroll
DS077
Semi-Hermetic
Scroll or
Digital Scroll
DS105
Semi-Hermetic
Liebert DS
Upflow
Cooling Type
EC Fan Unit
Weight lb (kg)
EC Fan Unit
Weight lb (kg)
Forward-Curved
Unit Weight, lb (kg)
Air Cooled
1470 (668)
1370 (621)
1520 (689)
Dual Cool
1620 (736)
1520 (689)
1670 (758)
Water/Glycol
1780 (809)
1680 (762)
1830 (830)
1930 (877)
1830 (830)
1980 (898)
Air Cooled
1780 (809)
1680 (762)
1830 (830)
Dual Cool
1930 (877)
1830 (830)
1980 (898)
Water/Glycol
1930 (877)
1830 (830)
1980 (898)
2080 (945)
1980 (898)
2130 (966)
Air Cooled
1920 (871)
1900 (862)
2070 (939)
Dual Cool
2100 (953)
2080 (943)
2250 (1021)
Water/Glycol
2220 (1010)
2200 (998)
2370 (1075)
2400 (1091)
2380 (1080)
2550 (1157)
Air Cooled
2350 (1069)
2180 (989)
2350 (1069)
Dual Cool
2530 (1150)
2360 (1070)
2530 (1150)
Water/Glycol
2650 (1205)
2480 (1125)
2650 (1205)
2830 (1287)
2660 (1207)
2830 (1287)
Air Cooled
1970 (894)
1900 (862)
2070 (939)
Dual Cool
2150 (975)
2080 (943)
2250 (1021)
Water/Glycol
2270 (1032)
2200 (998)
2370 (1075)
2450 (1114)
2380 (1080)
2550 (1157)
Air Cooled
2400 (1091)
2330 (1057)
2500 (1134)
Dual Cool
2580 (1173)
2510 (1139)
2680 (1216)
Water/Glycol
2700 (1228)
2630 (1193)
2800 (1270)
2880 (1310)
2810 (1275)
2980 (1352)
Air Cooled
2020 (916)
1900 (862)
2070 (939)
Dual Cool
2200 (998)
2080 (943)
2250 (1021)
Water/Glycol
2320 (1055)
2200 (998)
2370 (1075)
2500 (1137)
2380 (1080)
2550 (1157)
Air Cooled
2450 (1114)
2330 (1057)
2500 (1134)
Dual Cool
2630 (1196)
2510 (1139)
2680 (1216)
Water/Glycol
2750 (1250)
2630 (1193)
2800 (1270)
2930 (1332)
2810 (1275)
2980 (1352)
Air Cooled
2660 (1207)
2640 (1197)
2880 (1306)
Dual Cool
3015 (1368)
2970 (1347)
3210 (1456)
Water/Glycol
3030 (1374)
3010 (1365)
3250 (1474)
3385 (1535)
3340 (1515)
3580 (1624)
Air Cooled
2780 (1261)
2760 (1252)
3000 (1361)
Dual Cool
3135 (1422)
3090 (1402)
3330 (1510)
Water/Glycol
3150 (1429)
3130 (1420)
3370 (1529)
3505 (1590)
3460 (1569)
3700 (1678)
26
Figure 8
Cabinet and floor planning dimensionsDownflow, air-cooled, 28-42kW (8-12 tons), scroll or
digital scroll compressors with EC fans
Secondary Refrigerant
Piping Entrance
56-7/8" (1445mm)
Opening
33"
(838mm)
35"
(889mm)
5/16"
Bezel
(8mm)
Secondary Entrance
High-Voltage Connection(s)
TOP VIEW
Secondary Entrance
Low-Voltage Connection(s)
Minimum required
for filter replacement
73" (1854mm)
5"
(127mm)
76"
(1930mm)
34" (864mm)
2"
(51mm)
72" (1829mm)
DPN003131
Rev. 1
FRONT VIEW
27
Liebert DS
Figure 9
NOTES:
A
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
A
FRONT VIEW
SECTION A-A
R
4" (102mm)
L1 L2 G1 G2
11.19"
(284mm)
35"
(889mm)
BLOWER
OUTLET
ECS
LV1
LV2
LV3
HUM
CD
B
E1 E2 ECR
4.5"
(114mm)
73" (1854mm)
FRONT OF UNIT
Point
R
L1
L2
G1
G2
CD
HUM
ECS
ECR
HS
HR
E1
E2
LV1
LV2
LV3
B
Description
Refrigerant Access
Liquid Line System 1
Liquid Line System 2
Hot Gas Discharge 1
Hot Gas Discharge 2
Condensate Drain 1
(Infrared Humidifier or No Humidifier)
Condensate Drain 1
(Steam Generating Humidifier)
w/Optional Pump
Humidifier Supply Line
Econ-O-Coil Supply
Econ-O-Coil Return
Hot Water Reheat Supply
Hot Water Reheat Return
Electrical Connection (High-Voltage)
Electrical Connection (High-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Blower Outlet
DPN003239
Rev. 0
59-5/16 (1507)
69-15/16 (1776)
67-5/8 (1718)
65-1/2 (1664)
62-7/16 (1586)
14-3/4 (375)
16-13/16 (411)
16-13/16 (411)
16-13/16 (411)
16-13/16 (411)
46 (1168)
29-1/2 (749)
3/4" FPT
46 (1168)
29-1/2 (749)
1-1/4" FPT
46 (1168)
53-1/2 (1359)
54-7/8 (1394)
49-3/8 (1254)
55-1/2 (1410)
52-7/16 (1332)
2-1/4 (57)
2-1/4 (57)
2-1/4 (57)
4-1/2 (114)
29-1/2 (749)
1/2" Cu Sweat
29 (737)
1/4" Cu Sweat
22-9/16 (573)
1-5/8" Cu Sweat
30-3/4 (781)
1-5/8" Cu Sweat
Consult Factory
Consult Factory
31-1/4 (794)
2-1/2"
31-1/4 (794)
2-1/2"
27 (686)
7/8"
29 (737)
7/8"
31 (787)
7/8"
33 (838)
31 x 31 (787 x 787)
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Source: DPN003239, Rev. 0
Liebert DS
28
Figure 10
33"
(838mm)
35"
(889mm)
56-7/8"
Opening
(1445mm)
24-3/8"
(619mm)
Opening
5/16"
(8mm) Bezel
Secondary Entrance
High-Voltage Connection(s)
TOP VIEW
Secondary Entrance
Low-Voltage Connections
Minimum required
for filter replacement
86" (2184mm)
5"
(127mm)
76"
(1930mm)
34"
(864mm)
2"
(51mm)
85" (2159mm)
DPN003130
Rev. 1
FRONT VIEW
29
Liebert DS
Figure 11
NOTES:
A
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
A
FRONT VIEW
O
R
L1 L2 G1 G2
35"
(889mm)
BLOWER
OUTLET
4" (102mm)
16-7/16"
(418mm)
ECS
LV1
HUM
LV2
CD
E1 E2 ECR
SECTION A-A
FRONT OF UNIT
86"
(2184mm)
LV3
4.5"
(114mm)
DPN003598
Rev. 0
Point
R
L1
L2
G1
G2
CD
HUM
ECS 2
ECR 2
E1
E2
LV1
LV2
LV3
B
Description
Refrigerant Access
Liquid Line System 1
Liquid Line System 2
Hot Gas Discharge 1
Hot Gas Discharge 2
Condensate Drain 1
(Infrared Humidifier or No Humidifier)
Condensate Drain 1
(Steam Generating Humidifier)
w/Optional Pump
Humidifier Supply Line
Econ-O-Coil Supply
Econ-O-Coil Return
Electrical Connection (High-Voltage)
Electrical Connection (High-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Blower Outlet
X
in. (mm)
Y
in. (mm)
63 (1600)
79-3/16 (2011)
76-1/2 (1943)
73-7/8 (1876)
70-1/8 (1780)
13-13/16 (351)
16-3/4 (425)
16-3/4 (425)
16-3/4 (425)
16-3/4 (425)
46 (1168)
29-1/2 (749)
3/4 FPT
46 (1168)
29-1/2 (749)
1-1/4 FPT
46 (1168)
53-1/2 (1359)
54-7/8 (1394)
49-3/8 (1254)
55-1/2 (1410)
52-7/16 (1332)
2-1/4 (57)
2-1/4 (57)
2-1/4 (57)
4-1/2 (114)
29-1/2 (749)
29 (737)
22-9/16 (573)
30-3/4 (781)
31-1/4 (794)
31-1/4 (794)
27 (686)
29 (737)
31 (787)
33 (838)
1/2 Cu Sweat
1/4 Cu Sweat
1-5/8 Cu Sweat
1-5/8 Cu Sweat
2-1/2
2-1/2
7/8
7/8
7/8
31 x 31 (787 x 787)
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cooling systems only (four-pipe system).
3. Source: DPN003598, Rev. 0
Liebert DS
30
Figure 12
Cabinet and floor planning dimensionsDownflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressors with EC fans
Digital scroll compressors
not available on 077 models.
Second Refrigerant
Piping Entrance
80" (2032mm)
Opening
33"
(838mm)
35"
(889mm)
Secondary Entrance
High-Voltage Connection(s)
1-3/4"
(44mm) Handle
TOP VIEW
Downflow electrical
connections can be made
from top or bottom of unit.
5/16"
(8mm)
Minimum required
Bezel
for filter replacement
Secondary Entrance
Low-Voltage Connections
5"
(127mm)
98" (2489mm)
76"
(1930mm)
34"
(864mm)
2"
(51mm)
97" (2464mm)
FRONT VIEW
31
Liebert DS
Figure 13
A
FRONT VIEW
SECTION A-A
X
O
R
4" (102mm)
L1 L2
BLOWER
OUTLET
G1 G2
35"
(889mm)
12-3/16"
(310mm)
ECS ECR
CD
E1 E2
B1
LV1
LV2
LV3
HUM
98" (2489mm)
DPN002182
Rev. 3
FRONT OF UNIT
Point
R
Description
Refrigerant Access
X in. (mm)
Y in. (mm)
81-3/4 (2076)
14-3/4 (374)
12-3/16x4 (310x102)
94-11/16 (2405)
16-3/4 (425)
L2
91-7/8 (2334)
16-3/4 (425)
G1
88-3/4 (2254)
16-3/8 (416)
G2
85-9/16 (2173)
16-3/8 (416)
Condensate Drain
(Infrared Humidifier or No Humidifier)
68-3/8 (1737)
31-3/8 (797)
3/4 FPT
W/ Optional Pump
68-3/8 (1737)
31-3/8 (797)
1/2 Cu Sweat
76-1/2 (1943)
29 (736)
1/4 Cu Sweat
CD 1
HUM
Econ-O-Coil Supply
78-5/8 (1997)
22-1/4 (565)
2-1/8 Cu Sweat
ECR 2
Econ-O-Coil Return
73-15/16 (1862)
26-9/16 (675)
2-1/8 Cu Sweat
ECS
E1
78-1/2 (1994)
31-1/8 (790)
2-1/2
E2
75-3/8 (1915)
31-1/8 (790)
2-1/2
LV1
2 (51)
29 (737)
7/8
LV2
2 (51)
30-7/8 (784)
7/8
LV3
2 (51)
32 (813)
7/8
B1
Blower Outlet
4-1/2 (114)
33 (838)
58-3/8x30 (1483x762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Digital scroll compressors not available on 077 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
5. Source: DPN002182, Rev. 3
Liebert DS
32
Figure 14
33"
(838mm)
35"
(889mm)
Secondary Entrance
High-Voltage Connection(s)
24-5/8"
(625mm)
Opening
1-3/4"
(44mm) Handle
TOP VIEW
5/16"
(8mm)
Bezel
Secondary Entrance
Low-Voltage Connections
Minimum required
for filter replacement
109" (2769mm)
5"
(125mm)
76"
(1930mm)
108" (2743mm)
2"
(51mm)
FRONT VIEW
33
34"
(864mm)
DPN003137
Rev. 2
Liebert DS
Figure 15
NOTE
A
Drawing not to scale.
Tolerance on all piping
dimensions is 1/2" (13mm).
A
FRONT VIEW
SECTION A-A
R
L1 L2
4" (102mm)
G1 G2
35"
(889mm)
BLOWER
OUTLET
16-7/16"
(418mm)
ECS ECR
CD
E1
B1
LV1
LV2
LV3
HUM
109" (2769mm)
DPN002179
Rev. 1
FRONT OF UNIT
Point
R
Description
Refrigerant Access
X
in. (mm)
Y
in. (mm)
82-3/4 (2102)
13-7/8 (352)
16-7/16 x 4 (4181x102)
97 (2464)
16-7/8 (428)
L2
93-5/16 (2370)
16-7/8 (428)
G1
90-5/8 (2302)
16-5/8 (422)
G2
88 (2235)
16-5/8 (422)
Condensate Drain
(Infrared Humidifier or No Humidifier)
68-3/8 (1737)
31-3/8 (797)
3/4 FPT
W/ Optional Pump
68-3/8 (1737)
31-3/8 (797)
1/2 Cu Sweat
76-1/2 (1943)
29 (736)
1/4 Cu Sweat
CD 1
HUM
2
Econ-O-Coil Supply
78-5/8 (1997)
22-1/4 (565)
2-1/8 Cu Sweat
ECR 2
Econ-O-Coil Return
73-15/16 (1862)
26-9/16 (675)
2-1/8 Cu Sweat
ECS
E1
78-1/2 (1994)
31-1/8 (790)
2-1/2
E2
75-3/8 (1915)
31-1/8 (790)
2-1/2
LV1
2 (51)
29 (737)
7/8
LV2
2 (51)
30-7/8 (784)
7/8
LV3
2 (51)
32 (813)
7/8
B1
Blower Outlet
4-1/2 (114)
33 (838)
58-3/8 x 30 (1483x762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
4. Source: DPN002179, Rev. 1
Liebert DS
34
Figure 16
Cabinet and floor planning dimensionsDownflow, air-cooled, 105kW (30 tons), standard
scroll and semi-hermetic compressors with EC fans
Secondary Refrigerant
Piping Entrance
33"
(838mm)
35"
(889mm)
Secondary Entrance
High-Voltage Connection(s)
102-13/16"
(2611mm) Opening
TOP VIEW
1-3/4"
(44mm) Handle
24-3/8"
(619mm)
Opening
5/16"
(8mm)
Bezels
Secondary Entrance
Low-Voltage Connections
Minimum required
for filter replacement
132" (3353mm)
5"
(127mm)
76"
(1930mm)
34" (864mm)
Shaded area indicates the
minimum clearance
required from floor to
top of unit and plenum for
component access.
131" (3327mm)
FRONT VIEW
Filters are accessible through top of unit only.
Downflow electrical connections can be made
from top or bottom of unit.
35
DPN0003145
Rev. 2
Liebert DS
Figure 17
Primary connection locationsDownflow, air-cooled, 105kW (30 tons), standard scroll and
semi-hermetic compressors with EC fans
Digital scroll compressors not
available on 105 models.
NOTE
A
Drawing not to scale.
Tolerance on all piping
dimensions is 1/2" (13mm).
FRONT OF UNIT
SECTION A-A
Y
G1 G2 R
4" (102mm)
L1 L2
16-7/16"
(418mm)
35"
(889mm)
BLOWER
OUTLET
ECS ECR
CD
E1
E2
B1
LV1
LV2
LV3
HUM
132" (3353mm)
DPN002154
Rev. 1
FRONT VIEW
X
in. (mm)
Y
in. (mm)
109 (2769)
15-3/4 (400)
121-3/4 (3092)
16-3/4 (425)
5/8 Cu Sweat
118-1/8 (3000)
16-3/4 (425)
5/8 Cu Sweat
G1
118-1/4 (3004)
14-1/4 (362)
1-1/8 Cu Sweat
G2
115-5/8 (2937)
14-1/4 (362)
1-1/8 Cu Sweat
CD 1
Condensate Drain
(Infrared Humidifier or No Humidifier)
87-3/8 (2220)
31 (787)
3/4 FPT
W/ Optional Pump
83-13/16 (2129)
30 (762)
1/2 Cu Sweat
HUM
85-5/16 (2167)
32-1/2 (825)
1/4 Cu Sweat
ECS 2
Econ-O-Coil Supply
101-7/8 (2588)
29 (737)
2-5/8 Cu Sweat
ECR 2
Econ-O-Coil Return
94-9/16 (2402)
29 (737)
2-5/8 Cu Sweat
E1
98-1/8 (2492)
31 (788)
2-1/2
E2
91 (2311)
31 (788)
2-1/2
LV1
2 (51)
29 (737)
7/8
LV2
2 (51)
30-7/8 (784)
7/8
LV3
2 (51)
32 (813)
7/8
B1
Blower Outlet
4-1/2 (114)
33 (838)
Point
Description
Refrigerant Access
L1
L2
1. Field-pitch condensate drain line a minimum of 1/8" (3.2mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system)
3. Digital scroll compressors not available on DS105
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
5. Source: DPN002154, Rev. 1
Liebert DS
36
7.1
Figure 18
56-7/8" (1445mm)
Opening
35"
(889mm)
33"
(838mm)
1-3/4"
(44mm) Handle
24-3/8"
(619mm)
Opening
5/16
(8mm)
Bezel
TOP VIEW
Secondary Entrance
High-Voltage Connection(s)
Secondary Entrance
Low-Voltage Connections
86" (2184mm)
Required for
condenser cleanout
24"
(610mm)
Minimum required
for filter replacement
15"
(381mm)
76"
(1930mm)
2"
(51mm)
85" (2159mm)
FRONT VIEW
37
34"
(864mm)
DPN003135
Rev. 2
Liebert DS
Figure 19
NOTE
1. Drawing not to scale.
2. Tolerance on all
piping dimensions
is 1/2" (13mm).
FRONT VIEW
SECTION A-A
Y
8"
(203mm)
35"
(889mm)
BLOWER
OUTLET
ECS
3-1/2"
(89mm)
HUM
CD
E1 E2 ECR
LV1
LV2
LV3
4-1/2"
(114mm)
86" (2184mm)
FRONT
Description
Point
X
in. (mm)
DPN003530
Rev. 0
Y
in. (mm)
Water/Glycol/GLYCOOL Access
79-15/16 (2030)
9-1/16 (230)
WS
Water/Glycol/GLYCOOL Supply
82-15/16 (2107)
10-15/16 (278)
WR
Water/Glycol/GLYCOOL Return
82-15/16 (2107)
14-1/16 (357)
ECS
Econ-O-Coil Supply
54-7/8 (1394)
22-9/16 (573)
Econ-O-Coil Return
49-13/16 (1265)
28-1/2 (724)
46 (1168)
29-1/2 (749)
3/4 FPT
Condensate Drain
(Steam Generating Humidifier)
46 (1168)
29-1/2 (749)
1-1/4 FPT
W/ Optional Pump
46 (1168)
29-1/2 (749)
1/2 Cu Sweat
53-1/2 (1359)
29 (737)
ECR
Condensate Drain 1
(Infrared Humidifier Or No Humidifier)
CD
HUM
HS
1/4 Cu Sweat
Consult Factory
HR
E1
55-1/2 (1410)
31-1/4 (794)
Consult Factory
2-1/2
E2
52-7/16 (1332)
31-1/4 (794)
2-1/2
LV1
2-1/4 (57)
27 (686)
7/8
LV2
2-1/4 (57)
29 (737)
7/8
LV3
2-1/4 (57)
31 (787)
7/8
Blower Outlet
4-1/2 (114)
33 (838)
31 x 31 (787 x 787)
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only (four-pipe systems).
3. Source: DPN003530, Rev. 0
Liebert DS
38
Figure 20
24-5/8"
(625mm)
Opening
35"
(889mm
1-3/4"
Secondary Condenser
(44mm) Handle
Fluid Piping Entrance
TOP VIEW
Secondary Entrance
High-Voltage Connection(s)
Secondary Entrance
Low-Voltage Connections
24"
(610mm)
109"
(2769mm)
Required for
condenser cleanout
Minimum
required
for filter
replacement
5"
(127mm)
76"
(1930mm)
2"
(51mm)
34"
Shaded area indicates a
(864mm)
recommended minimum
clearance from floor to top
DPN003142
of unit and plenum
Rev. 2
for component access.
108" (2743mm)
FRONT VIEW
39
Liebert DS
Figure 21
FRONT VIEW
SECTION A-A
3-1/2"
(89mm)
W
WS
WR
8"
(203mm)
35"
(889mm)
ECS ECR
CD
B1
LV1
LV2
LV3
E1 E2 HUM
109" (2769mm)
DPN002183
Rev. 1
FRONT OF UNIT
X
in. (mm)
Y
in. (mm)
Water/Glycol/GLYCOOL Access
103 (2616)
9 (229)
WS
Water/Glycol/GLYCOOL Supply
104-3/4 (2661)
11 (279)
2-1/8 Cu Sweat
WR
Water/Glycol/GLYCOOL Return
104-3/4 (2661)
15 (381)
2-1/8 Cu Sweat
CD
Condensate Drain
(Infrared Humidifier or No Humidifier)*
69-1/4 (1759)
30 (762)
3/4 FPT
W/ Optional Pump
69-1/4 (1759)
30 (762)
1/2 Cu Sweat
HUM
76-1/2 (1943)
29 (736)
1/4 Cu Sweat
ECS 3
Econ-O-Coil Supply
78-5/8 (1997)
22-1/4 (565)
2-1/8 Cu Sweat
ECR 3
Econ-O-Coil Return
73-15/16 (1862)
26-9/16 (675)
2-1/8 Cu Sweat
E1
78-1/2 (1994)
31-1/8 (790)
2-1/2
E2
75-3/8 (1915)
31-1/8 (790)
2-1/2
LV1
2 (51)
28-1/2 (724)
7/8
LV2
2 (51)
30-1/4 (768)
7/8
LV3
2 (51)
32 (813)
7/8
B1
Blower Outlet
4-1/28 (114)
133 (838)
Point
Description
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Digital scroll compressors not available on DS077.
3. Supplied on dual-cool systems only (four-pipe system).
4. Source: DPN002183, Rev. 0
Liebert DS
40
Figure 22
35"
(889mm)
Secondary Condenser
Fluid Entrance
Secondary Entrance
High-Voltage Connection(s)
1-3/4"
(44mm) Handle
Secondary Entrance
Low-Voltage Connections
TOP VIEW
24"
(610mm)
132" (3353mm)
Required for
condenser
cleanout
Minimum required
for filter replacement
5"
(127mm)
76"
(1930mm)
34" (864mm)
Shaded area indicates a
recommended minimum
clearance from floor
to top of unit and plenum
for component access.
131" (3327mm)
FRONT VIEW
41
DPN003146
Rev. 2
Liebert DS
Figure 23
NOTES
Drawing not to scale.
Tolerance on
all piping dimensions
is 1/2" (13mm).
FRONT VIEW
Including panels
X
SECTION A-A
W
WS
WR
8"
(203mm)
Y
35"
(889mm)
BLOWER
OUTLET
3-1/2"
(89mm)
ECS ECR
CD
E1
E2
B1
LV1
LV2
LV3
HUM
132" (3353mm)
FRONT OF UNIT
Point
Description
DPN002153
Rev. 1
X
in. (mm)
Y
in. (mm)
Water/Glycol/GLYCOOL Access
125-15/16 (3199)
9 (229)
3-1/2 x 8 (89x203)
WS
Water/Glycol/GLYCOOL Supply
127-7/8 (3248)
10-1/16 (256)
2-1/8 Cu Sweat
WR
Water/Glycol/GLYCOOL Return
127-7/8 (3248)
13-1/4 (337)
2-1/8 Cu Sweat
CD
Condensate Drain
(Infrared Humidifier or No Humidifier) 1
87-3/8 (2220)
31 (787)
3/4 FPT
W/ Optional Pump
83-13/16 (2129)
30 (762)
1/2 Cu Sweat
HUM
85-5/16 (2167)
32-1/2 (825)
1/4 Cu Sweat
ECS 2
Econ-O-Coil Supply
101-7/8 (2588)
29 (737)
2-5/8 Cu Sweat
ECR 2
Econ-O-Coil Return
94-9/16 (2402)
29 (737)
2-5/8 Cu Sweat
E1
98-1/8 (2492)
31 (788)
2-1/2
E2
91 (2311)
31 (788)
2-1/2
LV1
2 (51)
29 (737)
7/8
LV2
2 (51)
30-7/8 (784)
7/8
LV3
2 (51)
32 (813)
7/8
B1
Blower Outlet
4-1/2 (114)
33 (838)
77-3/8 x 30 (1965x762)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Digital scroll compressors not available on 105 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
5. Source: DPN002153, Rev. 1
Liebert DS
42
7.2
Figure 24
Cabinet and floor planning dimensionsDownflow, 28-42kW (8-12 tons), front and/or rear
discharge models with EC fans
Secondary Refrigerant
Piping Entrance
24" (610mm)
56-7/8" (1445mm)
Opening
33"
(838mm)
35"
(889mm)
Secondary Entrance
High-Voltage Connection(s)
Minimum required
for filter replacement.
5"
(127mm)
24-3/8"
(619mm)
Opening
1-3/4"
(44mm) Handle
5/16"
(8mm) Bezels
Secondary Entrance
Low-Voltage Connections
TOP VIEW
A
34"
(864mm)
76"
(1930mm)
33-1/2"
(851mm)
19"
(483mm) Air Outlet
Opening
2"
(51mm)
3-1/4"
(81mm)
B
3"
(76mm)
3"
(77mm)
33-3/8"
(848mm)
19"
(483mm)
Air Outlet
FRONT VIEW
43
Opening
3-1/4"
(81mm)
DPN003180
Rev. 1
Liebert DS
Figure 25
Cabinet and floor planning dimensionsDownflow, 53-77kW (15-22 tons), front and/or rear
discharge models with EC fans
Secondary Refrigerant
Piping Entrance
35"
(889mm)
24" (610mm)
80" (2032mm)
Opening
1-34"
(44mm) Handle
5/16"
(619mm) Bezel
Secondary Entrance
Low-Voltage Connections
TOP VIEW
Secondary Entrance
High-Voltage Connection(s)
Minimum required
for filter replacement.
5"
(127mm)
25-5/8"
(619mm)
Opening
33"
(838mm)
34"
(864mm)
76"
(1930mm)
15-1/8"
(384mm)
29-1/4"
(743mm)
Air Outlet
Opening
2"
(51mm)
FRONT VIEW
15-1/8"
(384mm)
29-5/8"
(752mm)
15-1/8"
(384mm)
29-5/8"
(752mm)
Air Outlet
Opening
3-1/4"
(83mm)
Liebert DS
3-1/8"
(79mm)
Air Outlet
Opening
3"
(76mm)
DPN003181
Rev. 1
44
3-1/4"
(83mm)
15-1/8"
(384mm)
29-1/4"
(743mm)
Air Outlet
Opening
REAR VIEW
Figure 26
Cabinet and floor planning dimensionsDownflow, air-cooled, 105kW (30 tons), front
discharge models with EC fans
Secondary Refrigerant
Piping Entrance
102-7/8" (2611mm)
Opening
33"
(838mm)
24-3/8"
(619mm)
Opening
35"
(889mm)
Secondary Entrance
High-Voltage Connection(s)
1-34"
(44mm)
Handle
5/16"
(619mm)
Secondary Entrance
Bezel
Low-Voltage Connections
TOP VIEW
132" (3353mm)
24"
(610mm)
Minimum required
for filter replacement.
5"
(127mm)
76"
(1930mm)
16-1/8"
(410mm)
16-1/8"
(410mm)
25-5/8"
(649mm)
Air Outlet
Opening
24-7/8"
(649mm)
Air Outlet
Opening
131" (3326mm)
16-1/8"
(410mm)
28-1/4"
(718mm)
Air Outlet
Opening
30-7/8"
(783mm)
57-1/2"
(1459mm)
FRONT VIEW
Filters are accessible through top of unit only.
Downflow electrical connections can be made
from top or bottom of unit.
Customer Piping and Wiring Connections
1. For primary connection locations see standard submittals.
A floor stand at least 9" high is recommended if primary
connections locations are to be used.
2. Contact the factory to relocate connection locations.
45
3/4"
(19mm)
34"
DPN003182
Rev. 1
Liebert DS
7.3
Figure 27
39"
(991mm)
76"
(1930mm)
Assembled
Height
Compressor Assembly
76"
(1930mm)
59-7/16"
(1509mm)
37"
(940mm)
33"
(838mm)
13"
(330mm)
59" (1499mm)
72" (1829mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Dry Weight, Approximate, lb. (kg)
Air-Cooled
Dual-Cool
Compressor Assembly
490 (223)
490 (223)
210 (96)
210 (96)
770 (350)
920 (418)
Component
Liebert DS
46
DPN003133
Rev. 1
Figure 28
39"
(991mm)
76"
(1930mm)
Assembled
Height
Compressor Assembly
76"
(1930mm)
59-7/16"
(1509mm)
37"
(940mm)
33"
(838mm)
26"
(660mm)
59" (1499mm)
85" (2159mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003132
Rev. 1
Dual-Cooled
Compressor Assembly
800 (364)
800 (364)
210 (96)
210 (96)
770 (350)
920 (418)
Component
47
Liebert DS
Figure 29
39"
(991mm)
76"
(1930mm)
Assembled
Height
Compressor Assembly
Blower & Coil Assembly
76"
(1930mm)
59-7/16"
(1509mm)
37"
(940mm)
33"
(838mm)
DS053-DS077 =
15" (381mm)
82" (2083mm)
Assembled Length
DS053-DS077 = 97" (2464mm)
Drawing views are simplified with panels removed to show over all dimensions.
See disassembly and handling instructions in installation manual.
DPN003140
Rev. 1
Dual-Cool
Compressor Assembly
540 (246)
540 (246)
250 (114)
250 (114)
1230 (560)
1410 (641)
Component
Liebert DS
48
Figure 30
39"
(991mm)
76"
(1930mm)
Assembled
Height
Compressor Assembly
Blower & Coil
Assembly
76"
(1930mm)
59-3/8"
(1507mm)
37"
(940mm)
33"
(838mm)
26"
(660mm)
82" (2083mm)
108" (2743mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003139
Rev. 1
Air-Cooled
Dual-Cool
Compressor Assembly
970 (441)
970 (441)
250 (114)
250 (114)
1230 (560)
1410 (641)
49
Liebert DS
Figure 31
39"
(991mm)
41-11/16"
(1059mm)
Compressor Assembly
76"
(1930mm)
Assembled Height
76"
(1930mm)
59-7/16"
(1510mm)
37"
(940mm)
33"
(838mm)
105" (2667mm)
26"
(660mm)
131" (3327mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003148
Rev. 2
Dual-Cool
Compressor Assembly
830 (377)
830 (377)
270 (123)
270 (123)
1560 (708)
1915 (870)
Component
Liebert DS
50
Figure 32
39"
(991mm)
41-11/16"
(1059mm)
Compressor
Assembly
76"
(1930mm)
Assembled
Height
76"
(1930mm)
59 7/16"
(1510mm)
37"
(940mm)
33"
(838mm)
26"
(660mm)
105" (2667mm)
DPN003147
Rev. 1
131" (3327mm)
Assembled Length
Dry Weight, Approximate, Including Panels, lb (kg)
EC Fans
Component
Compressor Assembly
Air-Cooled
Dual-Cool
950 (432)
950 (432)
270 (123)
270 (123)
1560 (708)
1915 (870)
51
Liebert DS
7.4
Figure 33
39"
(991mm)
Compressor Assembly
76"
(1930mm)
Assembled
Height
76"
(1930mm)
59-7/16"
(1509mm)
37"
(940mm)
33"
(838mm)
26"
(660mm)
59" (1499mm)
85" (2159mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003136
Rev. 1
Water/Glycol
GLYCOOL/Dual-Cool
Water/Glycol
GLYCOOL/Dual-Cool
Compressor Assembly
950 (432)
950 (432)
800 (364)
800 (364)
210 (96)
210 (96)
210 (96)
210 (96)
770 (350)
920 (418)
770 (350)
920 (418)
Component
Liebert DS
52
Figure 34
39"
(991mm)
76"
(1930mm)
Assembled
Height
Compressor Assembly
Blower & Coil
Assembly
76"
(1930mm)
59-7/16"
(1509mm)
37"
(940mm)
26"
(660mm)
33"
(838mm)
82" (2083mm)
108" (2743mm)
Assembled Length
DPN003143
Rev. 1
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Dry Weight, Approximate, Including Panels, lb (kg)
Semi-Hermetic Compressor
Component
Compressor Assembly
Water/Glycol GLYCOOL/Dual-Cool
1270 (578)
1270 (578)
GLYCOOL/Dual-Cool
840 (382)
840 (382)
250 (114)
250 (114)
250 (114)
250 (114)
1230 (560)
1410 (641)
1230 (560)
1410 (641)
53
Liebert DS
Figure 35
39"
(991mm)
41-11/16"
(1059mm)
Compressor Assembly
76" (1930mm)
Assembled
Height
76"
(1930mm)
59-7/16"
(1510mm)
37"
(940mm)
33"
(838mm)
26"
(660mm)
105" (2667mm)
131" Assembled Length
(3327mm)
DPN003150
Rev. 1
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Water/Glycol
GLYCOOL/Dual-Cool
Water/Glycol
GLYCOOL/Dual-Cool
Compressor Assembly
1320 (600)
1320 (600)
1200 (545)
1200 (545)
270 (123)
270 (123)
270 (123)
270 (123)
1560 (708)
1915 (870)
1560 (708)
1915 (870)
Component
Liebert DS
54
7.5
Figure 36
Cabinet and floor planning dimensionsUpflow, air-cooled, 28-42kW (8-12 tons), scroll or
digital scroll compressors with EC fans
Alternate refrigerant
piping entrance
33"
(838mm)
34-3/4"
(883mm)
5/16"
(8mm)
Bezel
High-Voltage
Connection(s)
3-1/24"
(90mm)
1-3/4"
(44mm)
Handle
TOP VIEW
Low-Voltage
Connection(s)
73-1/16" 1856mm)
75"
(1924mm)
36"
(914mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.
1-3/4"
(44mm)
72" (1829mm)
FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately. DPN003495
Rev. 0
See DPN002747 for unit dimensions with EC fans plenum mounted
55
Liebert DS
Figure 37
Primary connection locationsUpflow, air-cooled, 28-42kW (8-12 tons), scroll or digital scroll
compressors with EC fans
All dimensions from
rear corner of unit
X
including panels
10-1/8"
(257mm)
4-1/8" (105mm)
NOTES
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
3. Field-routed alternatives for refrigerant
gas and liquid line connection points.
4. See submittal page DPN002747
for plenum dimensional data.
3. R1
R2
35"
(889mm)
ECR
ECS
HUM
CPD
4.
L1 L2 G1 G2
4"
(102mm)
Y
11-13/16"
(300mm)
3.
E1
LV2
E2
LV1
LV3
73" (1854mm)
Front of Unit
17-3/16"
(437mm)
R3
17-1/16"
(434mm)
3.
L1 L2 G1 G2
CGD*
14-1/4"
(362mm)
15-7/8"
(403mm)
3-7/8"
(98mm)
CGD*
Factory Location
DPN002740
Rev. 0
Point
R1
R2
X
in. (mm)
Y
in. (mm)
60-5/8 (1539)
2-13/16 (71)
63 (1600)
13-13/16 (351)
L1
79-3/16 (2011)
16-3/4 (425)
1/2 Cu Sweat
L2
76-1/2 (1943)
16-3/4 (425)
1/2 Cu Sweat
G1
73-7/8 (1876)
16-5/8 (422)
5/8 Cu Sweat
G2
70-1/8 (1780)
16-5/8 (422)
5/8 Cu Sweat
R3
CGD 1
3/4 FPT
CPD
56-1/4 (1429)
11-1/8 (283)
1/2 Cu Sweat
HUM
56-1/4 (1429)
9-1/8 (233)
1/4 Cu Sweat
56 (1423)
7-5/16 (186)
1-5/8 Cu Sweat
ECS 2
2
Econ-O-Coil Supply
56 (1423)
4-1/2 (114)
1-5/8 Cu Sweat
E1
52-3/8 (1331)
29-15/16 (760)
2-1/2
E2
47-3/8 (1204)
29-15/16 (760)
2-1/2
LV1
8-1/8 (207)
29-9/16 (751)
7/8
LV2
8-1/8 (207)
31 (787)
7/8
LV3
8-1/8 (207)
32-7/16 (824)
7/8
ECR
Econ-O-Coil Return
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap.
Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must
comply with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002740, Rev. 0
Liebert DS
56
Figure 38
33"
(838mm)
34-3/4"
(883mm)
5/16"
(8mm)
Bezel
High-Voltage
Connection(s)
3-1/4"
(83mm)
Low-Voltage
Connection(s)
86-1/16" (2186mm)
76"
(1930mm)
Shaded area indicates a
required minimum clearance
from floor to top of unit and
plenum for component access.
84-15/16" (2158mm)
2"
(50mm)
FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
See DPN002747 for unit dimensions with EC fans plenum mounted
57
36"
(914mm)
DPN003494
Rev. 0
Liebert DS
Figure 39
22-1/2"
(572mm)
R1
15-3/16"
(386mm)
35"
NOTES:
(889mm)
1. Drawing not to scale.
2. Tolerance on all piping dimensions
4"
is 1/2" (13mm).
(102mm)
3. Field-routed alternatives for refrigerant
3.
gas and liquid line connection points.
3.
R2
ECR
ECS
HUM
CPD
4.
L1 L2 G1 G2
16-7/16"
(418mm)
E1
LV1
LV2 LV3
E2
86" (2184mm)
TOP VIEW OF UNIT
6"
(152mm)
R3
20-1/16"
(509mm)
3.
17-3/16"
(437mm)
Front of Unit
G1 G2
L1 L2
CGD*
14-1/4"
(362mm)
3-7/8"
(98mm)
CGD*
Factory Location
15-7/8"
(403mm)
Description
Point
R1
R2
X
in. (mm)
DPN002739
Rev. 0
Y
in. (mm)
60-11/16 (1542)
1-7/8 (48)
63 (1600)
13-13/16 (351)
L1
79-3/16 (2011)
16-3/4 (425)
1/2 Cu Sweat
L2
76-1/2 (1943)
16-3/4 (425)
1/2 Cu Sweat
G1
73-7/8 (1876)
16-3/4 (425)
5/8 Cu Sweat
G2
70-1/8 (1780)
16-3/4 (425)
5/8 Cu Sweat
R3
CGD 1
3/4 FPT
CPD
56-1/4 (1429)
11-1/8 (283)
1/2 Cu Sweat
HUM
56-1/4 (1429)
9-1/8 (233)
1/4 Cu Sweat
ECS 2
Econ-O-coil Supply
56 (1423)
7-5/16 (186)
1-5/8 Cu Sweat
ECR**
Econ-O-coil Return
56 (1423)
4-1/2 (114)
1-5/8 Cu Sweat
E1
52-3/8 (1331)
29-15/16 (760)
2-1/2
E2
47-3/8 (1204)
29-15/16 (760)
2-1/2
LV1
8-1/8 (207)
29-9/16 (751)
7/8
LV2
8-1/8 (207)
31 (787)
7/8
LV3
8-1/8 (207)
32-7/16 (824)
7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002739, Rev. 0
Liebert DS
58
Figure 40
Cabinet and floor planning dimensionsUpflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressor models with EC fans
Digital scroll compressors not
available on 077 models.
Alternate Refrigerant
Piping Entrance
33"
(838mm)
5/16"
(8mm)
Bezel
34-3/4"
(883mm)
High-Voltage
Connection(s)
3-1/4"
(83mm)
1-3/4"
(44mm)
Handle
TOP VIEW
Low-Voltage
Connection(s)
98" (2489mm)
76"
(1930mm)
36"
(914mm)
Shaded area indicates a
required minimum clearance
from floor to top of unit and
plenum for component access.
96-15/16" (2462mm)
2"
(50mm)
FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
See DPN002748 for unit dimensions with EC fans plenum mounted
59
DPN003498
Rev. 0
Liebert DS
Figure 41
Primary connection locationsUpflow, air cooled, 53-77kW (15-22 tons) with EC fans, scroll or
digital scroll compressor models with EC fans
12"
(305mm)
4" (102mm)
R2
3.
12-13/16"
(325mm)
ECR
ECS
HUM
CPD
3. R1
L1 L2G1G2
4"
(102mm)
35"
(889mm)
LV1
LV2
LV3
E1
E2
98" (2489mm)
TOP VIEW OF UNIT
Front of Unit
6" (152mm)
R3
17-3/16"
(437mm)
3.
CGD*
17-1/16"
(433mm)
L1 L2G1G2
14-1/4"
(362mm)
15-7/8"
(403mm)
3-7/8"
(98mm)
Factory Location
CGD*
DPN002743
Rev. 0
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed
condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system
materials. The drain line must comply with all local codes.
** Supplied on dual cool systems only
Description
Point
R1 3
R2 3
L1
L2
G1
G2
R3 3
CGD 1
CPD
HUM
ECS 1
ECR 1
E1
E2
LV1
LV2
LV3
X
in. (mm)
83-5/8 (2124)
82-3/4 (2102)
94-11/16 (2405)
91-7/8 (2334)
88-3/4 (2254)
85-9/16 (2173)
79-5/16 (2015)
79-5-16 (2015)
78-5/8 (1998)
78-5/8 (1998)
78-1/8 (1984)
74-3/8 (1889)
2-5/8 (66)
2-5/8 (66)
2-5/8 (66)
Y
in. (mm)
2 (51)
12 x 4 (305 x 102)
14-3/4 (374)
12-3/16 x 4 (310 x 102)
53kW (15 Tons) / 70 and 77kW (20 and 22 Tons)
16-3/4 (425)
16-3/4 (425)
16-3/8 (416)
16-3/8 (416)
11-7/8 (302)
9-7/8 (251)
7-7/8 (200)
4-5/8 (117)
30 (762)
30 (762)
28-9/16 (726)
30 (762)
31-7/16 (799)
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cooling systems only
3. Source: DPN002743, Rev. 0
Liebert DS
60
Figure 42
34-3/4"
(883mm)
5/16"
(8mm)
Bezel
High-Voltage
Connection(s)
3-1/4"
(83mm)
1-3/4"
(44mm)
Handle
TOP VIEW
Low-Voltage
Connection(s)
109" (2769mm)
76"
(1930mm)
36"
(914mm)
108" (2743mm)
2"
(50mm)
FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
See DPN002748 for unit dimensions with EC fans plenum mounted
61
DPN003497
Rev. 0
Liebert DS
Figure 43
22-1/2"
(572mm)
NOTES:
1. Drawing not to scale.
15-3/16"
2. Tolerance on all piping dimensions
35"
(386mm)
is 1/2" (13mm).
(889mm)
3. Field-routed alternatives for
4"
refrigerant gas and liquid
(102mm) 3.
line connections.
R1 ECR
3.
R2
ECS
HUM
CPD
4.
L1 L2 G1 G2
16-7/16"
(418mm)
Y
E1 E2
LV1
LV2
LV3
109" 2760mm)
6"
(152mm)
Front of Unit
17-3/16"
(437mm)
3.
CGD*
14-1/4"
(362mm)
3-7/8"
(98mm)
20-1/16"
(509mm)
15-7/8"
(403mm)
G1 G2
LV1 LV2
CGD*
FACTORYLOCATION
Description
Point
R1
R2
DPN002742
Rev. 0
X
in. (mm)
Y
in. (mm)
83-3/4 (2127)
1-7/8 (48)
86 (2184)
13-7/8 (352)
97 (2464)
16-3/4 (425)
L2
93-5/16 (2370)
16-3/4 (425)
G1
90-5/8 (2302)
16-5/8 (422)
G2
88 (2235)
16-5/8 (422)
R3
CGD 1
3/4 FPT
CPD
79-5/16 (2015)
11-7/8 (302)
1/2 Cu Sweat
HUM
79-5/16 (2015)
9-7/8 (251)
1/4 Cu Sweat
Econ-O-Coil Supply
78-5/8 (1998)
7-7/8 (200)
2-1/8 Cu Sweat
ECS
ECR
Econ-O-Coil Return
78-5/8 (1998)
4-5/8 (117)
2-1/8 Cu Sweat
E1
78-1/8 (1984)
30 (762)
2-1/2
E2
74-3/8 (1889)
30 (762)
2-1/2
LV1
2-5/8 (66)
28-9/16 (726)
7/8
LV2
2-5/8 (66)
30 (762)
7/8
LV3
2-5/8 (66)
31-7/16 (799)
7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002742, Rev. 0
Liebert DS
62
Figure 44
Cabinet and floor planning dimensionsUpflow, air-cooled, 105kW (30 tons), all compressor
models with EC fans
Digital scroll compressors
not available on 105 models.
Alternate Refrigerant
Piping Entrance
33"
(838mm)
34-3/4"
(882mm)
High-Voltage
Connection(s)
3-3/16"
(81mm)
Typical
TOP VIEW
Low-Voltage
Connection(s)
5/16"
(8mm)
Bezel
132-1/16" (3354mm)
76"
(1931mm)
2"
(51mm)
Shaded area indicates a
recommended minimum
clearance from floor to
ceiling for component access.
130-15/16" (3325mm)
FRONT VIEW
Note:
1. Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196.
2. EC fans plenum is not shown. EC fans and plenum are shipped
separately. See DPN002749 for unit dimensions with EC fans
plenum mounted
63
36"
(914mm)
DPN003500
Rev. 0
Liebert DS
Figure 45
Primary connection locationsUpflow, air-cooled 105kW (30 tons), all compressor models
with EC fans
22-1/2"
(572mm)
R1
15-3/16"
(386mm)
NOTES
35"
1. Drawing not to scale.
(889mm)
2. Tolerance on all piping
dimensions is 1/2" (13mm).
4"
(102mm)
3. Field-routed alternatives for
refrigerant gas and liquid
line connections.
4. See submittal page DPN002749 for
plenums dimensions.
3. R2
ECR
ECS
HUM
CPD
4.
L1L2 G1G2
16-7/16"
(418mm)
E1
3.
LV1
LV2
E2
LV3
LV3
132" (3353mm)
Front of Unit
6" (152mm)
R3
17-3/16"
(437mm)
3.
3-7/8"
(98mm)
14-1/4"
(362mm)
15-7/8"
(403mm)
CGD*
20-1/16"
(509mm)
G1G2
L1L2
CGD*
Factory Location
Description
Point
DPN002745
Rev. 0
X
in. (mm)
Y
in. (mm)
R1
106-7/8 (2715)
1-7/8 (48)
R2
109-1/8 (2772)
13-7/8 (352)
L1
121-3/4 (3092)
16-3/4 (425)
5/8 Cu Sweat
L2
118-1/8 (3000)
16-3/4 (425)
5/8 Cu Sweat
G1
118-1/4 (3004)
14-1/4 (362)
1-1/8 Cu Sweat
G2
115-5/8 (2937)
14-1/4 (362)
1-1/8 Cu Sweat
R3
3
1
CGD
CPD
HUM
ECS
ECR
3/4 FPT
102-3/8 (2600)
13-5/8 (346)
1/2 Cu Sweat
101-1/8 (2569)
13-1/8 (333)
1/4 Cu Sweat
Econ-O-Coil Supply
101-1/8 (2569)
10-1/4 (260)
2-5/8 Cu Sweat
Econ-O-Coil Return
101-1/8 (2569)
5-1/4 (133)
2-5/8 Cu Sweat
E1
101-5/8 (2581)
30 (762)
2-1/2
E2
97-7/8 (2486)
30 (762)
2-1/2
LV1
34-1/8 (867)
30-1/4 (769)
7/8
LV2
34-1/8 (867)
31-3/4 (807)
7/8
LV3
32-5/8 (829)
28-15/16 (734)
7/8
LV4
32-5/8 (829)
30-7/16 (772)
7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Digital scroll compressors not available on 105 models.
4. Source: DPN002745, Rev. 0
Liebert DS
64
7.6
Figure 46
33"
(838mm)
34-3/4"
(883mm)
5/16"
(8mm)
Bezel
1-3/4"
(44mm)
Handle
TOP VIEW
Required for
Condenser Cleanout
Low-Voltage
Connection(s)
86-1/16" (2186mm)
76"
(1930mm)
36"
(914mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.
2"
(50mm)
84-15/16" (2158mm)
FRONT VIEW
Notes:
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fan plenum is not shown. EC fans and plenum are shipped separately.
See DPN002747 for unit dimensions with EC fans plenum mounted
65
DPN003496
Rev. 0
Liebert DS
Figure 47
W1, W2 3.
8"
(203mm)
2-7/8"
35" (73mm)
(889mm)
17-3/16"
(437mm)
Y
3-1/2"
(89mm)
3-7/8"
(98mm)
LV2
E1 E2
86" 2184mm)
3.
6"
(152mm)
W3
WS
WR
ECR
ECS
HUM
CPD
LV1
LV3
Front of Unit
CGD*
14-1/4"
(362mm)
15-7/8"
(403mm)
CGD*
Description
X
in. (mm)
Y
in. (mm)
79-15/16 (2030)
9 (229)
Point
W1
W2
79-15/16 (2030)
9 (229)
W3
WS
Water/Glycol/GLYCOOL Supply
WR
ECS 2
Econ-O-Coil Supply
Water/Glycol/GLYCOOL Return
56 (1423)
7-5/16 (186)
ECR
Econ-O-Coil Return
56 (1423)
4-1/2 (114)
CGD
3/4 FPT
CPD
56-1/4 (1429)
11-1/8 (282)
1/2 Cu Sweat
HUM
56-1/4 (1429)
9-1/8 (232)
1/4 Cu Sweat
E1
52-3/8 (1331)
29-15/16 (760)
2-1/2
E2
47-3/8 (1204)
29-15/16 (760)
2-1/2
LV1
8-1/8 (207)
29-9/16 (751)
7/8
LV2
8-1/8 (207)
31 (787)
7/8
LV3
8-1/8 (207)
32-7/16 (824)
7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only (four-pipe system).
3. Source: DPN002741, Rev. 1
Liebert DS
66
Figure 48
33"
(838mm)
5/16"
(8mm)
Bezels
35"
(889mm)
Alternate Refrigerant
Piping Entrance
High-Voltage Connection(s)
3-1/4"
(83mm)
1-3/4" TOP
(44mm)
Handle
Required for
condenser cleanout
24"
(610mm)
VIEW
Low-Voltage
Connection(s)
109" (2769mm)
76"
(1930mm)
36"
Shaded area indicates a
(914mm)
recommended minimum
clearance from floor to top
of unit for component access.
2"
(50mm)
108" (2743mm)
FRONT VIEW
NOTES
1. Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
2. EC fans plenum is not shown. EC fans and plenum are shipped separately.
See DPN002748 for unit dimensions with EC fans plenum mounted
67
DPN003499
Rev. 0
Liebert DS
Figure 49
8"
(203mm)
ECR
ECS
HUM
CPD
W1, W2
NOTES
35"
1. Drawing not to scale.
(889mm)
2. Tolerance on all piping
dimensions
is 1/2" (13mm).
3-1/2"
3. Field-routed alternatives for
(89mm)
water/glycol connections.
4. See submittal page DPN002748
for plenum dimensions.
3.
4.
2-7/8"
(73mm)
Y
E1 E2
LV1
LV2
LV3
109" (2769mm)
Front of Unit
6" (152mm)
17-3/16"
(437mm)
3-7/8"
(98mm)
W3
WS
WR
3. CGD*
14-1/4"
(362mm)
15-7/8"
(403mm)
CGD*
DPN002744
Rev. 0
* Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed
condensate trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system
materials. The drain line must comply with all local codes. Supplied on dual cool systems only.
** Supplied on dual cool systems only.
Point
Description
X
in. (mm)
Y
in. (mm)
W1
102-15/16 (2615)
9 (229)
W2
102-15/16 (2615)
9 (229)
W3
WS
Water/Glycol/GLYCOOL Supply
2-1/8 Cu Sweat
WR
Water/Glycol/GLYCOOL Return
2-1/8 Cu Sweat
CGD
CPD
HUM
ECS
ECR
3/4 Fpt
79-5/16 (2015)
11-7/8 (302)
1/2 Cu Sweat
79-5/16 (2015)
9-7/8 (251)
1/4 Cu Sweat
Econ-O-Coil Supply
78-5/8 (1998)
7-7/8 (200)
2-1/8 Cu Sweat
Econ-O-Coil Return
78-5/8 (1998)
4-5/8 (117)
2-1/8 Cu Sweat
E1
78-1/8 (1984)
30 (762)
2-1/2
E2
74-3/8 (1889)
30 (762)
2-1/2
LV1
2-5/8 (66)
28-9/16 (726)
7/8
LV2
2-5/8 (66)
30 (762)
7/8
LV3
2-5/8 (66)
31-7/16 (799)
7/8
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Digital scroll compressors not available on 077 models.
4. Source: DPN002744, Rev. 0
Liebert DS
68
Figure 50
Alternate Refrigeration
Piping Entrance
33"
(838mm)
34-3/4"
(883mm)
Alternate Condenser
Fluid Piping Entrance
High-Voltage
Connection(s)
3-3/16"
(81mm)
Typical
5/16"
(8mm)
Bezel
Low-Voltage
Connection(s)
Required for
condenser cleanout
132-1/16" (3354mm)
76"
(1931mm)
34"
(864mm)
1-15/16"
(50mm)
130-15/16" (3325mm)
FRONT VIEW
NOTES
1. Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196.
2. EC fans plenum not shown. EC fans and plenum shipped separately.
See DPN002749 for plenum dimensions.
69
DPN003501
Rev. 0
Liebert DS
Figure 51
8"
(203mm)
W1, W2 3.
35"
(889mm)
NOTES
1. Drawing not to scale.
2. Tolerance on all piping
3-1/2"
dimensions is 1/2" (13mm).
ECR
ECS
HUM
CPD
4.
2-7/8"
(73mm)
E1
E2
(89mm)
LV2
LV1 LV3
Y
LV4
132" (3353mm)
Front of Unit
TOP VIEW OF UNIT
6" (152mm)
W3
WS
WR
3.
CGD*
17-3/16"
(437mm)
14-1/4"
(362mm)
15-7/8"
(403mm)
3-7/8"
(98mm)
CGD*
DPN002746
Rev. 0
Description
Point
W1
X
In. (mm)
Y
In. (mm)
126-1/8 (3204)
9 (229)
W2
126-1/8 (3204)
9 (229)
W3
WS
Water/Glycol/GLYCOOL Supply
2-1/8 Cu Sweat
WR
Water/Glycol/GLYCOOL Return
2-1/8 Cu Sweat
CGD 1
3/4 FPT
CPD
102-3/8 (2600)
13-5/8 (346)
1/2 Cu Sweat
HUM
101-1/8 (2569)
13-1/8 (333)
1/4 Cu Sweat
Econ-O-Coil Supply
101-1/8 (2569)
10-1/4 (260)
2-5/8 Cu Sweat
ECR 2
Econ-O-Coil Return
101-1/8 (2569)
5-1/4 (133)
2-5/8 Cu Sweat
E1
101-5/8 (2581)
30 (762)
2-1/2
E2
97-7/8 (2486)
30 (762)
2-1/2
LV1
34-1/8 (867)
30-1/4 (769)
7/8
LV2
34-1/8 (867)
31-3/4 (807)
7/8
LV3
32-5/8 (829)
28-15/16 (734)
7/8
LV4
32-5/8 (829)
30-7/16 (772)
7/8
ECS
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN002746, Rev. 0
Liebert DS
70
7.7
Figure 52
33"
(838mm)
5/16"
(8mm)
Bezel
35"
(889mm)
Minimum required
for blower replacement
High-Voltage
Connection(s)
1-1/2"
(38mm)
1-3/4"
(44mm) TOP
Handle VIEW
Low-Voltage
Connection(s)
73" (1854mm)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.
2"
(51mm)
72" (1829mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
71
DPN003154
Rev. 1
Liebert DS
Figure 53
10-1/8"
(257mm)
3.
R1
ECR
ECS
HUM
CPD
BLOWER
OUTLET
R2
L1 L2 G1 G2
4.
Y
11-1/8"
(283mm)
LV1
LV2
LV3
E1 E2
73" (1854mm)
R3
17-3/16"
(437mm)
3.
CGD*
3-7/8"
(98mm)
Front
TOP VIEW
6"
(152mm)
17-1/16"
(434mm)
14-1/4"
(362mm)
15-7/8"
(403mm)
L1 L2 G1 G2
CGD*
FRONT SECTION
Point
Description
R1
R2
Factory Location
(Left Front Panel Not Shown)
DPN001119
Rev. 3
X
in. (mm)
Y
in. (mm)
60-5/8 (1539)
2-13/16 (71)
63 (1600)
13-13/16 (351)
L1
79-3/16 (2011)
16-3/4 (425)
1/2" Cu Sweat
L2
76-1/2 (1943)
16-3/4 (425)
1/2" Cu Sweat
G1
73-7/8 (1876)
16-5/8 (422)
5/8" Cu Sweat
G2
70-1/8 (1780)
16-5/8 (422)
5/8" Cu Sweat
R3
CGD*
3/4" FPT
CPD
56-1/4 (1429)
11-1/8 (283)
1/2" Cu Sweat
HUM
56-1/4 (1429)
9-1/8 (233)
1/4" Cu Sweat
ECS *
Econ-O-Coil Supply
56 (1423)
7-5/16 (186)
1-5/8" Cu Sweat
ECR 2*
Econ-O-Coil Return
56 (1423)
4-1/2 (114)
1-5/8" Cu Sweat
E1
52-3/8 (1330)
30 (762)
2-1/2"
E2
46-7/8 (1191)
30 (762)
2-1/2"
LV1
19-1/2 (495)
29-1/16 (738)
7/8"
LV2
19-1/2 (495)
30-1/2 (775)
7/8"
LV3
19-1/2 (495)
31-15/16 (811)
7/8"
1. Field pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual cool systems only.
3. Source: DPN001119, Rev. 3
Liebert DS
72
Figure 54
Cabinet and floor planning dimensionsUpflow, air-cooled 28-42kW (8-12 tons) semi-hermetic
compressor models with forward-curved blowers
Alternate Refrigerant
Piping Entrance
33"
(838mm)
5/16"
(8mm)
Bezel
35"
(889mm)
High-Voltage
Connection(s)
1-1/2"
(38mm)
TOP
VIEW
1-3/4"
(44mm)
Handle
Minimum required
for blower replacement
Low-Voltage
Connection(s)
24"
(610mm)
86" (2184mm)
76"
(1930mm)
34"
(864mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.
85" (2159mm)
2"
(51mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
73
DPN003153
Rev. 1
Liebert DS
Figure 55
22-1/2"
(572mm)
NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
15-3/16"
3 Field-routed alternatives for refrigerant
35" (386mm)
gas and liquid line connection points.
(889mm)
4 Forwad-curved blower shown. See
4"
submittal page DPN001120 for
(102mm)
blower outlet and deck dimensions.
R2
ECR
ECS
HUM
CPD
Blower
Outlet
4
L1 L2 G1 G2
16-7/16"
(418mm)
E1
LV1
LV2
LV3
E2
86" (2184mm)
TOP VIEW
6"
(152mm)
17-3/16"
(437mm)
R3
G1 G2
CGD *
3-7/8"
(98mm)
Point
Front of Unit
14-1/4"
(362mm)
15-7/8"
(403mm)
LEFT SIDE SECTION VIEW
Description
R1
R2
20-1/16"
(509mm)
L1 L2
CGD *
Factory Location
FRONT SECTION VIEW
(Left Front Panel Not Shown)
X
in. (mm)
DPN001114
Rev. 3
Y
in. (mm)
60-11/16 (1542)
1-7/8 (48)
63 (1600)
13-13/16 (351)
L1
79-3/16 (2011)
16-3/4 (425)
1/2" Cu Sweat
L2
76-1/2 (1943)
16-3/4 (425)
1/2" Cu Sweat
G1
73-7/8 (1876)
16-3/4 (425)
5/8" Cu Sweat
70-1/8 (1780)
16-3/4 (425)
5/8" Cu Sweat
G2
R3
CGD 1
3/4" FPT
CPD
56-1/4 (1429)
11-1/8 (283)
1/2" Cu Sweat
56-1/4 (1429)
9-1/8 (233)
1/4" Cu Sweat
HUM
2
Econ-O-Coil Supply
56 (1423)
7-5/16 (186)
1-5/8" Cu Sweat
ECR 2
Econ-O-Coil Return
56 (1423)
4-1/2 (114)
1-5/8" Cu Sweat
E1
52-3/8 (1330)
30 (762mm)
2-1/2"
E2
46-7/8 (1191)
30 (762mm)
2-1/2"
LV1
19-1/2 (495)
29-1/16 (738)
7/8"
LV2
19-1/2 (495)
30-1/2 (775)
7/8"
LV3
19-1/2 (495)
31-15/16 (811)
7/8"
ECS
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
4. Source: DPN001114, Rev. 3
Liebert DS
74
Figure 56
Cabinet and floor planning dimensionsUpflow, air-cooled, 53-77kW (15-22 tons), scroll or
digital scroll compressors with forward-curved blowers
Alternate Refrigerant
Piping Entrance
33"
(838mm)
35"
(889mm)
High-Voltage
Connection(s)
5/16"
(8mm)
Bezel
1-3/4"
(44mm)
Handle
Low-Voltage
Connection(s)
TOP VIEW
1-1/2"
(38mm)
Minimum required
for blower replacement
98" (2489mm)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
2"
(51mm)
97" (2464mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
75
DPN003157
Rev. 1
Liebert DS
Figure 57
NOTES:
12" (305mm)
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
4"
3. Field-routed alternatives for refrigerant
(102mm)
gas and liquid line connection points.
4"
35"
4. Forward-curved blowers shown. See
(102mm)
(889mm)
submittal page DPN001191 for
blower outlet and deck dimensions.
Blower
Outlet
12-13/16"
(325mm)
6" (152mm)
98" (2489mm)
Front of Unit
3-7/8"
(98mm)
17-1/16"
(433mm)
15-7/8"
(403mm)
CGD *
Factory
Location
DPN001213
Rev. 2
X
in. (mm)
Y
in. (mm)
83-5/8 (2124)
2 (51)
12 x 4 (305 x 102)
82-3/4 (2102)
14-3/4 (374)
Point
Description
R1
R2
94-11/16 (2405)
16-3/4 (425)
L2
91-7/8 (2334)
16-3/4 (425)
G1
88-3/4 (2254)
16-3/8 (416)
G2
85-9/16 (2173)
16-3/8 (416)
R3
CGD 1
3/4 FPT
CPD
79-5/16 (2015)
11-7/8 (302)
1/2 Cu Sweat
HUM
79-5-16 (2015)
9-7/8 (251)
1/4 Cu Sweat
Econ-O-Coil Supply
78-5/8 (1998)
7-7/8 (200)
2-1/8 Cu Sweat
ECR 2
Econ-O-Coil Return
78-5/8 (1998)
4-5/8 (117)
2-1/8 Cu Sweat
E1
75-3/8 (1915)
30 (762)
2-1/2
E2
69-7/8 (1775)
30 (762)
2-1/2
LV1
19-1/2 (495)
29-1/16 (738)
7/8
LV2
19-1/2 (495)
30-1/2 (775)
7/8
LV3
19-1/2 (495)
31-15/16 (811)
7/8
ECS
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Digital scroll compressors not available on 077 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different depending, on distance. Refer to user manual,
SL-18826.
5. Source: DPN001213, Rev. 2
Liebert DS
76
Figure 58
33"
(838mm)
5/16"
(8mm)
Bezel
35"
(889mm)
High-Voltage
Connection(s)
1-1/2"
(38mm)
1-3/4"
(44mm)
Handle
TOP
VIEW
Low-Voltage
Connection(s)
Minimum required
for blower replacement
109" (2769mm)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
2"
(51mm)
108" (2743mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
77
DPN003156
Rev. 1
Liebert DS
Figure 59
22-1/2"
(572mm)
NOTES:
1. Drawing not to scale.
2. Tolerance on all piping dimensions
is 1/2" (13mm).
15-3/16"
(386mm)
3. Field-routed alternatives for refrigerant 35"
gas and liquid line connection points. (889mm)
4"
4. Forward-curved fans shown. See
(102mm)
submittal page DPN001191 for
blower outlet and deck dimensions.
Blower
Outlet
Blower
Outlet
16-7/16"
(418mm)
6"
(152mm)
109" (2769mm)
Front of Unit
17-3/16"
(437mm)
3-7/8"
(98mm)
14-1/4"
(362mm)
20-1/16"
(509mm)
15-7/8"
(403mm)
CGD *
Point
Description
R1
R2
Factory Location
DPN001212
Rev. 3
X
in. (mm)
Y
in. (mm)
83-3/4 (2127)
1-7/8 (48)
86 (2184)
13-7/8 (352)
97 (2464)
16-3/4 (425)
L2
93-5/16 (2370)
16-3/4 (425)
G1
90-5/8 (2302)
16-5/8 (422)
G2
88 (2235)
16-5/8 (422)
R3
CGD 1
3/4" FPT
CPD
79-5/16 (2015)
11-7/8 (302)
1/2" Cu Sweat
HUM
79-5/16 (2015)
9-7/8 (251)
1/4" Cu Sweat
ECS 2
Econ-O-Coil Supply
78-5/8 (1998)
7-7/8 (200)
2-1/8" Cu Sweat
ECR 2
Econ-O-Coil Return
78-5/8 (1998)
4-5/8 (117)
2-1/8" Cu Sweat
E1
75-3/8 (1915)
30 (762)
2-1/2"
E2
69-7/8 (1775)
30 (762)
2-1/2"
LV1
19-1/2 (495)
29-1/16 (738)
7/8"
LV2
19-1/2 (495)
30-1/2 (775)
7/8"
LV3
19-1/2 (495)
31-15/16 (811)
7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
4. Source: DPN001212, Rev. 3
Liebert DS
78
Figure 60
Cabinet and floor planning dimensionsUpflow, air-cooled, 105kW (30 tons), all compressor
models with forward-curved blowers
Digital scroll compressors
not available on 105 models.
Alternate Refrigerant
Piping Entrance
33"
(838mm)
35"
(889mm)
High-Voltage
Connection(s)
1-1/2"
(38mm)
5/16"
(8mm)
Bezel
1-3/4"
(44mm)
TOP VIEW Handle
Low-Voltage
Connection(s)
Minimum required
for blower replacement
132" (3353mm)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
2"
(51mm)
131" (3327mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
79
Liebert DS
Figure 61
Primary connection locationsUpflow, air-cooled, 105kW (30 tons), semi-hermetic and scroll
compressor models with forward-curved blowers
22-1/2"
(572mm)
15-3/16"
(386mm)
R2
35"
(889mm)
ECR
ECS
HUM
CPD
Blower
Outlet
Blower
Outlet
16-7/16"
(418mm)
NOTES:
4"
1. Drawing not to scale.
(102mm)
2. Tolerance on all piping dimensions
is 1/2" (13mm).
3. Field-routed alternatives for refrigerant
gas and liquid line connection points.
4. Forward-curved fans shown. See submittal
page DPN001192 for blower outlet and
deck dimensions.
5. EC fans are field-installed in plenum.
Blower
Outlet
LV1 LV3
LV2
E1 E2
Y
LV4
132" (3353mm)
TOP VIEW
Front Of Unit
6"
(152mm)
R3
20-1/16"
(509mm)
17-3/16"
(437mm)
G2
L1 L2G1
CGD*
3-7/8"
(98mm)
14-1/4"
(362mm)
15-7/8"
(403mm)
CGD*
Factory Location
DPN001257
Rev. 1
X, in. (mm)
Y, in. (mm)
106-7/8 (2715)
1-7/8 (48)
Point
Description
R1
R2
109-1/8 (2772)
13-7/8 (352)
L1
121-3/4 (3092)
16-3/4 (425)
5/8" Cu Sweat
L2
118-1/8 (3000)
16-3/4 (425)
5/8" Cu Sweat
G1
118-1/4 (3004)
14-1/4 (362)
1-1/8" Cu Sweat
G2
115-5/8 (2937)
14-1/4 (362)
1-1/8" Cu Sweat
R3
CGD*
3/4" FPT
CPD
102-3/8 (2600)
13-5/8 (346)
1/2" Cu Sweat
HUM
101-1/8 (2569)
13-1/8 (333)
1/4" Cu Sweat
Econ-O-Coil Supply
101-1/8 (2569)
10-1/4 (260)
2-5/8" Cu Sweat
ECR 2
Econ-O-Coil Return
101-1/8 (2569)
5-1/4 (133)
2-5/8" Cu Sweat
E1
98-1/2 (2502)
30 (762)
2-1/2"
E2
93 (2362)
30 (762)
2-1/2"
LV1
41-1/8 (1045)
30-3/8 (772)
7/8"
LV2
38-7/8 (987)
30-3/8 (772)
7/8"
LV3
35-1/8 (892)
30-3/8 (772)
7/8"
LV4
31-5/8 (803)
30-3/8 (772)
7/8"
ECS
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only.
3. Digital scroll compressors not available on 105 models.
4. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
5. Source: DPN001257, Rev. 1
Liebert DS
80
7.8
Figure 62
33"
(838mm)
5/16"
(8mm)
Bezel Required for
condenser cleanout
Minimum required
for blower replacement
35"
(889mm)
1-3/4"
(44mm)
Handle
Low-Voltage
Connection(s)
TOP VIEW
24"
(610mm)
86" (2184mm)
76"
(1930mm)
34"
(864mm)
Shaded area indicates a
required minimum clearance from floor
to top of unit and plenum for component
access.
2"
(51mm)
85" (2159mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
81
DPN003155
Rev. 1
Liebert DS
Figure 63
W1, W2 3
8"
(203mm)
Blower
Outlet
ECS
ECR
HUM
CPD
35"
(889mm)
2-7/8"
(73mm)
3-1/2"
(89mm)
E2
86" (2184mm)
6"
(152mm)
Front
W3
WS
WR
17-3/16"
(437mm)
3-7/8"
(98mm)
E1
LV1
LV2
LV3
CGD*
14-1/4"
(362mm)
15-7/8"
(403mm)
CGD*
DPN001179
Rev. 6
X
in. (mm)
Y
in. (mm)
79-15/16 (2030)
79-15/16 (2030)
9 (229)
9 (229)
56 (1423)
56 (1423)
56-1/4 (1429)
56-1/4 (1429)
52-3/8 (1330)
46-7/8 (1191)
19-1/2 (495)
19-1/2 (495)
19-1/2 (495)
7-5/16 (186)
4-1/2 (114)
11-1/8 (282)
9-1/8 (232)
30 (762)
30 (762)
29-1/16 (738)
30-1/2 (775)
31-15/16 (811)
Point
W1 3
W2 3
W3 3
WS 3
WR 3
ECS 2
2
ECR
CGD 1
CPD
HUM
E1
E2
LV1
LV2
LV3
Econ-O-Coil Supply
Econ-O-Coil Return
Condensate Gravity Drain
Condensate Pump Discharge (Opt)
Humidifier Supply Line
Electrical Connection (High-Voltage)
Electrical Connection (High-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
Electrical Connection (Low-Voltage)
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate trap. Do
not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain line must comply
with all local codes.
2. Supplied on dual-cool systems only (four-pipe system).
3. Piping dimensions shown are connection sizes; field piping sizes may be different, depending on distance. Refer to user manual,
SL-18826.
4. Source: DPN001179, Rev. 6
Liebert DS
82
Figure 64
Cabinet and floor planning dimensionsUpflow, water/glycol-cooled, 53-77kW (15-22 tons), all
compressor models with forward-curved blowers
Digital scroll compressors
not available on 077 models.
33"
(838mm)
5/16"
(8mm)
Bezel
35"
(889mm)
Alternate Condenser Fluid
Piping Entra
High-Voltage
Connection(s)
1-1/2"
(38mm)
1-3/4"
(44mm)
Handle
Required for
condenser cleanout
Minimum required
for blower replacement
Low-Voltage
Connection(s)
TOP VIEW
109" (2769mm)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
2"
(51mm)
108" (2743mm)
FRONT VIEW
Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
83
DPN003158
Rev. 1
Liebert DS
Figure 65
ECR
ECS
HUM
CPD
W1, W2
8"
(203mm)
35"
(889mm)
2-7/8"
(73mm)
3.
BLOWER
OUTLET
BLOWER
OUTLET
4.
4.
Y
3-1/2"
(89mm)
LV1
LV2
LV3
E1 E2
109" (2769mm)
Front
6"
(152mm)
TOP VIEW
W3
WS
WR
17-3/16"
(437mm)
3.
CGD*
14-1/4"
(362mm)
3-7/8"
(98mm)
15-7/8"
(403mm)
CGD*
Point
DPN001214
Rev. 2
Description
X
in. (mm)
Y
in. (mm)
W1
102-15/16 (2615)
9 (229)
W2
102-15/16 (2615)
9 (229)
W3
WS
Water/Glycol/GLYCOOL Supply
2-1/8" Cu Sweat
WR
3
1
Water/Glycol/GLYCOOL Return
2-1/8" Cu Sweat
CGD
3/4" FPT
CPD
78-5/8 (1998)
11-1/8 (282)
1/2" Cu Sweat
HUM
78-5/8 (1998)
9-7/8 (251)
1/4" Cu Sweat
ECS
Econ-O-Coil Supply
79-5/16 (2015)
7-7/8 (200)
2-1/8" Cu Sweat
ECR
Econ-O-Coil Return
79-5/16 (2015)
4-5/8 (117)
2-1/8" Cu Sweat
E1
75-3/8 (1915)
30 (762)
2-1/2"
E2
69-7/8 (1775)
30 (762)
2-1/2"
LV1
19-1/2 (495)
29-1/16 (738)
7/8"
LV2
19-1/2 (495)
30-1/2 (775)
7/8"
LV3
19-1/2 (495)
31-15/16 (811)
7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate
trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain
line must comply with all local codes.
2. Supplied on dual-cool systems only.
3. Source: DPN001214, Rev. 2
Liebert DS
84
Figure 66
Cabinet and floor planning dimensionsUpflow, water/glycol-cooled, 105kW (30 tons), all
compressor models with forward-curved blowers
Alternate Refrigerant
Piping Entrance
33"
(838mm)
35"
(889mm)
Alternate Condenser Fluid
Piping Entrance
High-Voltage
Connection(s)
1-1/2"
(38mm)
5/16"
(8mm)
Bezel
1-3/4"
(44mm)
TOP VIEW Handle
Low-Voltage
Connection(s)
Required for
condenser cleanout
Minimum required
for blower replacement
132" (3353mm)
24"
(610mm)
76"
(1930mm)
34"
(864mm)
2"
(51mm)
131" (3327mm)
FRONT VIEW
85
Liebert DS
Figure 67
8"
35"
(203mm)
(889mm)
2-7/8"
NOTES:
(73mm)
1. Drawing not to scale.
3-1/2"
2. Tolerance on all piping dimensions
(89mm)
is 1/2" (13mm).
3. Field routed alternatives for water/glycol
connections.
4. Forward-curved blowers shown.
See submittal page DPN001192 for
blower outlet and deck dimensional data.
Blower
Outlet
Blower
Outlet
LV1 LV3
LV2
LV4
132"
(3353mm)
Front Of Unit
6"
(152mm)
W3
WS
WR
17-3/16"
(437mm)
CGD*
3-7/8"
(98mm)
CGD*
14-1/4"
(362mm)
15-7/8"
(403mm)
DPN001258
Rev. 1
Description
X
in. (mm)
Y
in. (mm)
W1
126-1/8 (3204)
9 (229)
W2
126-1/8 (3204)
9 (229)
W3
WS
Water/Glycol/GLYCOOL Supply
2-1/8" Cu Sweat
WR
3
1
Water/Glycol/GLYCOOL Return
2-1/8" Cu Sweat
CGD
3/4" FPT
CPD
102-3/8 (2600)
13-5/8 (346)
1/2" Cu Sweat
101-1/8 (2569)
13-1/8 (333)
1/4" Cu Sweat
HUM
ECS
Econ-O-Coil Supply
101-1/8 (2569)
10-1/4 (260
2-5/8" Cu Sweat
ECR
Econ-O-Coil Return
101-1/8 (2569)
5-1/4 (133)
2-5/8" Cu Sweat
E1
98-1/2 (2502)
30 (762)
2-1/2"
E2
93 (2362)
30 (762)
2-1/2"
LV1
41-1/8 (1045)
30-3/8 (772)
7/8"
LV2
38-7/8 (987)
30-3/8 (772)
7/8"
LV3
35-1/8 (892)
30-3/8 (772)
7/8"
LV4
31-5/8 (803)
30-3/8 (772)
7/8"
1. Field-pitch condensate drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory-installed condensate
trap. Do not trap external to the unit. Drain line may contain boiling water. Select appropriate drain system materials. The drain
line must comply with all local codes.
2. Supplied on dual-cool systems only.
3. Source: DPN001258, Rev. 1
Liebert DS
86
8.0
Figure 68
Blower outlet and deck dimensionsUpflow, 28-42kW (8-12 tons) with forward-curved blowers
73" (1854mm) or 86" (2184mm) Ref
E
Blower Outlet *
35"
(889mm)
Ref
Front of Unit
Top of Unit
Blower Deck
1-1/2"
(38mm)
76"
(1930mm)
Ref
DPN001120
Rev. 3
28-42kW
(8-12 Tons)
Blower
15 x 15
15 x 15
Supply
Front Throw
15-7/8 (404)
Rear Throw
15-7/8 (404)
18-5/8 (472)
2-1/8 (54)
25-5/8 (651)
25 (635)
18-5/8 (472)
11-5/8 (295)
25-5/8 (651)
25 (635)
Front Throw
15-7/8 (404)
14-1/2 (368)
2-1/8 (54)
25-5/8 (651)
25 (635)
Rear Throw
15-7/8 (404)
14-1/2 (368)
11-5/8 (295)
25-5/8 (651)
25 (635)
87
Liebert DS
Figure 69
Blower outlet and deck dimensionsUpflow, 53-77kW (15-22 tons) with forward-curved
blowers
35"
(889mm)
Ref
Front of Unit
Top of Unit
Blower Deck
D
1-1/2"
(38mm)
76"
(1930mm)
Ref.
DPN001191
Rev. 6
53-77kW
(15-22
tons)
Blower
15 x 15
15 x 11
Supply
18-5/8 (472)
2-1/8 (54)
18-5/8 (472)
55-1/2 (1410)
55-1/2 (1410)
2-1/8 (54)
Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 31-3/8 (797) 58-7/16 (1484)
Liebert DS
88
Figure 70
Blower outlet and deck dimensionsUpflow, 105kW (30 tons), forward-curved blowers
132" (3353mm)
G
Blower Outlets *
F
E
A
35"
(889mm)
Ref
Front of Unit
TOP OF UNIT
Blower Deck
1-1/2"
(38mm)
76"
(1930mm)
Ref
DPN001192
Rev. 1
SUPPLY
2-1/8 (54)
Rear Throw 15-7/8 (404) 14-11/16 (373) 11-5/8 (295) 25-5/8 (651) 30-3/4 (781) 54-1/2 (1384) 78-1/8 (1984)
89
Liebert DS
8.1
Figure 71
31-1/4"
(794mm)
Compressor Assembly
76" (1930mm)
Assembled
Height
45-13/16"
(1163mm)
33"
(838mm)
13"
(330mm)
59" (1499mm)
72" (1829mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003162
Rev. 1
Dual-Cool
Compressor Assembly
490 (223)
490 (223)
510 (231)
510 (231)
EC Fan 1
360 (163)
360 (163)
520 (236)
670 (304)
Component
1. Fan weight not included in this weight. Fan is installed in plenum. See 313221 for plenum weight.
2. Source: DPN003162, Rev. 2
Liebert DS
90
Figure 72
31-1/4"
(794mm)
Compressor Assembly
76"
(1930mm)
Assembled
Height
76"
(1930mm)
45-13/16"
(1163mm)
33"
(838mm)
26"
(660mm)
85" (2159mm)
Assembled Length
59"
(1499mm)
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003161
Rev. 1
Dual-Cool
800 (364)
800 (364)
510 (231)
510 (231)
360 (163)
360 (163)
520 (236)
670 (304)
Component
Compressor Assembly
Blower and Electric Box Assembly (Forward-Curved Fans)
1
1. Fan weight not included in this weight. Fan is installed in plenum. See 313221 for plenum weight.
2. Source: DPN003161, Rev. 1
91
Liebert DS
Figure 73
31-1/4"
(794mm)
Compressor Assembly
76"
(1930mm)
Assembled
Height
45-13/16"
(1163mm)
33"
(838mm)
15"
(381mm)
82" (2083mm)
97" (2464mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Model #
Compressor
Component
Compressor Assembly
Blower and Electric Box Assembly
EC Fans 2
Blower and Electic Box Assembly
(Forward-Curved Blowers)
Filter and Coil Assembly
DPN003166
Rev. 1
Air-Cooled
Dual-Cool
540 (246)
540 (246)
600 (272)
600 (272)
770 (349)
770 (349)
760 (345)
940 (426)
Liebert DS
92
Figure 74
31-1/4"
(794mm)
Compressor Assembly
76" (1930mm)
Assembled Height
76"
(1930mm)
45-13/16"
(1163mm)
33"
(838mm)
26"
(660mm)
82" (2083mm)
108" (2743mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003165
Rev. 2
Dual-Cool
Compressor Assembly
970 (441)
970 (441)
770 (349)
770 (349)
EC Fans 1
600 (231)
600 (231)
760 (345)
940 (426)
Component
1. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
2. Source: DPN003165, Rev. 2
93
Liebert DS
Figure 75
31-1/4"
(794mm)
Compressor
Assembly
76"
(1930mm)
Assembled
Height
Filter & Coil Assembly
76"
(1930mm)
45-13/16"
(1164mm)
33"
(838mm)
26"
(660mm)
105" (2667mm)
131" (3327mm
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
Seee disassembly and handling instructions in installation manual.
DPN003169
Rev. 1
Dual-Cool
Compressor Assembly
830 (376)
830 (376)
1080 (490)
1080 (490)
EC Fans 2
840 (381)
840 (381)
970 (440)
1300 (590)
Component
Liebert DS
94
Figure 76
31-1/4"
(794mm)
Compressor
Assembly
76"
(1930mm)
Assembled
Height
45-13/16"
(1164mm)
33"
(838mm)
26"
(660mm)
105" (2667mm)
131" (3327mm
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003168
Rev. 1
Dual-Cool
Compressor Assembly
950 (431)
950 (431)
1080 (490)
1080 (490)
EC Fans 1
840 (381)
840 (381)
970 (440)
1300 (590)
Component
1. Fan weight not included in this weight. Fans are installed in plenum. See 313221 for plenum weight.
2. Source: DPN001254, Rev. 1
95
Liebert DS
8.2
Figure 77
31-1/4"
(794mm)
Compressor Assembly
76" (1930mm)
Assembled
Height
76"
(1930mm)
45-13/16"
(1163mm)
33"
(838mm)
26"
(660mm)
59" (1499mm)
85" (2159mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003163
Rev. 1
Water/Glycol
GLYCOOL/Dual-Cool
Water/Glycol
GLYCOOL/Dual-Cool
Compressor Assembly
950 (432)
950 (432)
800 (364)
800 (364)
510 (231)
510 (231)
510 (231)
510 (231)
360 (163)
360 (163)
360 (163)
360 (163)
520 (236)
670 (304)
520 (236)
670 (304)
Component
Liebert DS
96
Figure 78
31-1/4"
(794mm)
Compressor Assembly
76"
(1930mm)
Assembled
Height
Filter & Coil
Assembly
76"
(1930mm)
45-13/16"
(1163mm)
33"
(838mm)
26"
(660mm)
82" (2083mm)
108" (2743mm)
Assembled Length
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
DPN003167
Rev. 1
Water/Glycol
GLYCOOL/Dual-cool
Water/Glycol
GLYCOOL/Dual-Cool
Compressor Assembly
1270 (578)
1270 (578)
840 (382)
840 (382)
770 (349)
770 (349)
770 (349)
770 (349)
600 (272)
600 (272)
600 (272)
600 (272)
760 (345)
940 (426)
760 (345)
940 (426)
Component
97
Liebert DS
Figure 79
31-1/4"
(794mm)
Compressor Assembly
76" (1930mm)
Assembled Height
45-13/16"
(1164mm)
33"
(838mm)
26"
(660mm)
105" (2667mm)
131" (3327mm)
Assembled Length
DPN003170
Rev. 1
Drawing views are simplified with panels removed to show overall dimensions.
See disassembly and handling instructions in installation manual.
Water/Glycol
GLYCOOL/Dual-cool
Water/Glycol
GLYCOOL/Dual-Cool
Compressor Assembly
1320 (599)
1320 (599)
1200 (544)
1200 (544)
1080 (490)
1080 (490)
1080 (490)
1080 (490)
840 (381)
840 (381)
840 (381)
840 (381)
970 (440)
1300 (590)
970 (440)
1300 (590)
Component
1. Fan weight not included in this weight; fans are installed in plenum. See 313221 for plenum weight.
2. Digital scroll compressors not available on 105 models.
3. Source: DPN003170, Rev. 1
Liebert DS
98
Ancillary Items
9.0
ANCILLARY ITEMS
9.1
Floor Stands
Figure 80
Floor stand dimensions, downflow, 28-42kW (8-12 tons) models with EC fans
33"
(838mm)
34-1/2"
876mm
(With Feet)
1"
(35mm)
Typical
Right side of paneled unit is flush with right side of floor stand.
All other paneled sides overhang floor stand 1" (25mm).
* Leveling feet are provided with 1-1/2" (38mm) adjustment
from nominal height C.
C*
1
7/8"
(23mm)
8"
(203mm)
3"
(76mm)
DPN003240
Rev. 1
Floor Stand
Height C*
in. (mm)
85 (2159)
27 (686)
24 (610)
72 (1829)
14 (356)
30 (762)
Model
36 (914)
42 (1069)
48 (1219)
99
Liebert DS
Ancillary Items
Figure 81
Floor stand dimensions, downflow, 53-77kW (15-22 tons) models with EC fans
A
B
Piping Access Area
3/4"
(19mm)
32"
(813mm)
Center Feet
31-1/2"
(800mm)
3/4"
(19mm)
32-3/4"
(832mm)
C
Support Feet Centers
See Note 4
24" FLOOR STAND SHOWN
3/4"
(19mm)
1"
(25mm)
7/8"
(23mm)
33"
(838mm)
F*
3"
(76mm)
E
Notes
1. This floor stand should be used when EC fans are intended to be lowered under
a raised floor. The standard Liebert DS floor stand can be used if the fans are to
remain in their original raised position.
2. Right side of paneled unit is flush with right side of floor stand. All other paneled sides
overhang floor stand 1" (25mm).
3) The floor stand used with EC units is not symmetrical, and its orientation to the
Liebert DSE is critical for lowering the EC fans. The blowers will not lower into the
floor stand unless the floor stand is installed in the correct position.
4. Jack and jack support are shipped loose and are intended to be placed into position
under each fan and utilized to lower or raise that fan as needed.
* Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height F.
35" (889mm)
Overall Depth
DPN003173
Rev. 1
Leg
Height
F, in.
(mm)
Height
G, in.
(mm)
108
(2743)
26
(660)
106.5
(2705)
108
(2743)
109.5
(2781)
24 (610)
97
(2464)
15
(381)
95.5
(2426)
97
(2464)
98.5
(2502)
30 (762)
Liebert DS Model
Liebert DS
100
36 (914)
42 (1067)
11
48 (1219)
17
Ancillary Items
Figure 82
Floor stand dimensionsDownflow, 105kW (30 tons) models with EC fans, standard scroll and
semi-hermetic compressors
Digital scroll compressors
not available on 105 models.
25"
(635mm)
34-1/2"
33"
(876mm)
(with feet) (838mm)
Typ. Both Ends
132-1/2" (3366mm)
(with feet)
131" (3327mm)
35" (889mm)
(with feet)
Typ. (2) Places
74" (1880mm)
1"
(25mm Typ.)
5
19-1/4"
(489mm)
See
Note 4
Notes
7/8"
(23mm)
3" (76mm)
35"
(889mm)
Overall Depth
1. This floor stand should be used when EC fans are intended to be lowered
under a raised floor. The standard Liebert DS floor stand can be used
if the fans are to remain in their original raised position.
Height - A
in. (mm)
24 (610)
30 (762)
2. Right side of paneled unit is flush with right side of floor stand. All other paneled
sides overhang floor stand 1" (25mm).
36 (914)
3. The floor stand used with EC units is not symmetrical and its orientation to the
Liebert DS is critical for lowering the EC fans. The blowers will not lower into the floor stand
unless the floor stand is installed in the correct position.
42 (1067)
48 (1219)
4. Jack and jack support are shipped loose and are intended to be placed into
position under each fan and utilized to lower or raise that fan as needed.
5. Not applicable to 24' (610mm) x 30" (762) tall floor stands.
*Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height A.
101
DPN003174
Rev. 2
Liebert DS
Ancillary Items
9.2
Plenums
Figure 83
m)
32.1"
(815mm)
m
63
.6"
(14
57
19.7"
(500mm)
Plenum
Height
4.3" (109mm)
0.88"
(2.2mm)
m)
0m
.7"
4
(14
1.3"
(33mm)
2
56
m)
" (1
"
1.3 m)
m
(33
33.75"
(857mm)
m
05
5
9.2
Plenum Type
Height
In. (mm)
24 (610)
30 (762)
36 (914)
Liebert DS
DPN002747
Rev. 1
102
Ancillary Items
Figure 84
32"
(813mm)
m)
7m
"
81
5
(20
20"
(508mm)
4" (102mm)
1"
(25mm)
Plenum
Height
Both top duct opening
and grilles shown. See
specification sheet
for specific application.
0.88"
(2.2mm)
0.88"
(2.2mm)
m)
m
32
" (2
80
mm
3
08
" (2
82
1"
(25mm)
34"
(864mm)
DPN002748
Rev. 3
Plenum Type
Height
In. (mm)
24 (610)
30 (762)
36 (914)
103
Liebert DS
Ancillary Items
Figure 85
32"
(813mm)
m)
m
(51 m)
2"
9m
5
" (5
22
Plenum
Height
0.88"
(2.2mm)
4" (102mm)
1"
(25mm)
2
m)
2m
"
80
3
(20
m)
3m
5"
10
34"
(864mm)
7
(26
1"
(25mm)
DPN002749
Rev. 1
Plenum Type
Height
In. (mm)
24 (610)
30 (762)
36 (914)
Liebert DS
104
Ancillary Items
Figure 86
Without Grille
34"
(864mm)
Without Grille
A
1"
(25mm)
With
Grille
With Grille
76"
(1930mm)
Without
Grille
Without Grille
SIDE VIEW - UNIT WITH PLENUM
B
in. (mm)
Front/Rear
Grilles
Side Grille
59-1/4
(1505)
13-3/4
(349)
18 x 55
(457 x 1397)
18 x 20
(457 x 508)
59-1/4
(1505)
26-3/4
(679)
18 x 55
(457 x 1397)
18 x 20
(457 x 508)
82-1/4
(2089)
15-3/4
(400)
18 x 78
(457 x 1981)
18 x 20
(457 x 508)
82-1/4
(2089)
26-3/4
(679)
18 x 78
(457 x 1981)
18 x 20
(457 x 508)
105-1/4
(2673)
26-3/4
(679)
(1) 18 x 20
(457 x 508)
(1) 18 x 78
(457 x 1981)
18 x 20
(457 x 508)
Model
Non-grilled
24 (610)
36 (914)
Non-grilled
105
Liebert DS
Ancillary Items
9.3
Figure 87
Rear return filter box dimensionsUpflow, air cooled 28-105kW (8-30 tons), all compressors
Digital scroll compressors not
available on 077 or 105 models.
Filter Access
Door
Filter Access
Door
7-15/16"
(202mm)
40"
(1016mm)
38-1/4"
(971mm)
Duct Size
76"
(1930mm)
3-1/2" (89mm)
D Duct Size
A
B
NOTES
1. Filters can be accessed from either side.
2. 25" (635mm) minimum clearance provided on one side for filter access.
3. Filter boxes are shipped flat and must be field assembled.
DPN001196
Rev. 1
A
in. (mm)
B
in. (mm)
C
in. (mm)
D
in. (mm)
# Filters
4-1/4 (108)
50-3/4 (1289)
18 (457)
47-5/8 (1210)
4-1/4 (108)
50-3/4 (1289)
31 (787)
47-5/8 (1210)
3-1/4 (83)
75-1/2 (1918)
19-1/4 (489)
72-3/8 (1838)
3-1/4 (83)
75-1/2 (1918)
30-1/4 (768)
72-3/8 (1838)
2-1/4 (57)
100-1/4 (2546)
29-1/2 (749)
97-1/8 (2467)
Model #
Liebert DS
106
Piping
10.0 PIPING
Table 18
028
035
042
053
070
077
105
Hot
Hot
Hot
Hot
Hot
Hot
Hot
Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid
Length
Line Line Line Line Line Line Line Line Line Line Line Line Line Line
50 ft (15m)
7/8
1/2
7/8
1/2
7/8
1/2
7/8
5/8
1-1/8
7/8
1-1/8
7/8
1-3/8
7/8
100 ft (30m)
7/8
5/8
7/8
5/8
7/8
5/8
1-1/8
7/8
1-1/8
7/8
1-1/8
7/8
1-3/8
7/8
150 ft (45 m)
7/8
5/8
7/8
5/8
7/8
5/8
1-1/8
7/8
1-1/8
7/8
1-1/8
7/8
1-3/8 1-1/8
028
035
042
053
077 2
070
105 2
Hot
Hot
Hot
Hot
Hot
Hot
Hot
Equivalent Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid Gas Liquid
Line Line Line Line Line Line Line Line Line Line Line Line Line Line
Length
50 ft (15m)
3/4
100 ft (30m)
1/2
3/4
150 ft (45 m)
5/8
7/8
5/8
3/4
1/2
7/8
7/8
5/8
7/8
5/8
5/8
7/8
1-1/8
5/8
1
5/8
7/8
1
1-1/8
1-1/8
7/8
1-1/81
7/8
1-1/8
7/8
1-3/8
7/8
7/8
7/8
1-1/8
7/8
1-3/8
7/8
7/8
1-1/8
7/8
1-3/8 1-1/8
7/8
1-1/8
1-1/8
Table 19
R-407C Charge
per Circuit, lb. (kg)
5.5 (2.5)
8.0 (3.6)
105
9.5 (4.3)
System Type
Air-Cooled
Table 20
Line Size,
O.D., in.
1/2
6.7 (3.0)
5/8
10.8 (4.8)
0.8 (0.4)
3/4
16.1 (7.2)
1.2 (0.5)
7/8
22.3 (10.0)
1.7 (0.8)
1-1/8
38.0 (17.0)
2.9 (1.3)
1-3/8
57.9 (25.9)
4.4 (2.0)
107
Liebert DS
Piping
Table 21
Condensers without
Liebert Lee-Temp
Condensers with
Liebert Lee-Temp
2.2 (1.0)
21.0 (9.5)
MCM080
3.0 (1.4)
21.8 (9.9)
MCM160
7.5 (3.4)
44.5 (20.2)
MCL110
5.1 (2.3)
26.0 (11.8)
MCL220
12.2 (5.6)
53.8 (24.4)
Table 22
Standard
Condenser
Models
FSC or VFD
Lee-Temp
(includes receiver)
CD*/TCDV205
7 (3.2)
54 (24.4)
CD*/TCDV251
10 (4.6)
36 (16.3)
CD*/TCDV308
11 (5.0)
55 (24.9)
CD*/TCDV415
24 (10.9)
102 (46.2)
CD*/TCDV616
26 (11.8)
108 (49.0)
N/A
77 (34.9)
DCD*286
N/A
119 (54.0)
DCD*409
N/A
148 (67.2)
DCD*572
N/A
186 (84.4)
Liebert DS
108
Piping
10.1
Piping Schematics
CONDENSERS
Figure 88 shows a single refrigeration circuit diagram, displaying the indoor air conditioning unit,
the outdoor condenser (with or without Liebert Lee-Temp) and field-supplied interconnection piping.
Figure 88
Check Valve
Relief Valve
Service
Valve Liquid Return
Head Pressure
Control Valve
Liebert Lee-Temp Receiver
Check
Valve
Condenser
Coil
Condenser
Coil
Optional Field-Installed
Fusible Plug
Liebert Lee-Temp
Internal
Inverted Trap
Liquid
Sensing
Bulb
Service
Valve
Check
Valve
Evaporator
Coil
Suction
Service
External
Valve
Equalizer
Compressor
*Isolation
Valve
Hot Gas Discharge
Expansion Solenoid
Valve
Valve
Sight
Glass
Liquid Line
Filter Drier
Refrigerant Piping
Field Piping
Service/Schrader (Access) Connection No Valve Core
Service/Schrader (Access) Connection With Valve Core
NOTES
Single refrigeration circuit shown for clarity.
Schematic representation shown. Do not use for specific connection locations.
109
*Isolation
Valve
Trap at base
of risers
over 5ft. (1.5m)*
DPN002188
Rev. 3
Liebert DS
Piping
Liquid Return
Optional
Subcooling
Coil
Head Pressure
Control Valve
Optional
Sub-Cooling
Coil
CONDENSER
COIL
(FAN SPEED or VFD)
CONDENSER
COIL
(Liebert Lee-Temp)
Optional Field-Installed
Fusible Plug
LIQUID
Service
Valve
Sensing
Bulb
Cylinder
Unloader(s)
EVAPORATOR
COIL
SUCTION
Muffler
**Muffler
*Isolation
Valve
Sight
Glass
Liquid Return
Filter Drier
Liebert DS
*Isolation
Valve
110
Piping
Figure 90
Piping schematic, air-cooled with scroll or digital scroll compressor with fin/tube condenser
Relief
Valve
Check
Valve
Service
Valve
Head Pressure
Liebert Lee-Temp Receiver Control Valve
Optional
Field-Installed
Fusible Plug
LIQUID
Sensing
Bulb
Optional
Sub-Cooling
Coil
CONDENSER
COIL
(Liebert Lee-Temp)
Liquid Return
EVAPORATOR
COIL
SUCTION
Service
Valve
Check
External
Service
Valve
Equalizer
COMPRESSOR Valve
Expansion
Valve
Solenoid Sight
Filter Drier
Valve
Glass
NOTES: Two refrigeration circuits provided.
Single refrigeration circuit shown for clarity.
Schematic representation shown.
Do not use for specific connection locations.
Liquid Return
* Components are not supplied by
Emerson but are required for
proper circuit operation and
maintenance.
REFRIGERANT PIPING
FIELD PIPING
*Isolation
Valve Trap at base of risers
over 5ft. (1.5m)*
DPN000798
Rev. 7
111
Liebert DS
Piping
Figure 91
LIEBERT
HEAT REJECTION
CUSTOMER
HEAT REJECTION
* Check Valves
(on Dual Pump
Systems only)
DRYCOOLER
(Glycol)
COOLING TOWER
AND PUMP
SYSTEM
BY OTHERS
GLYCOL
PUMPS
* Pressure
Port
Aquastat
Sensing
Bulbs
* Hose
Bib * Shutoff Valve
* Gate Valves
* Pressure Port
Flow Switch
Supplied with Dual
Pump Systems
RETURN
* Shutoff Valve
SUPPLY
* Flow-Regulating
Valve
RETURN
LIEBERT DS
(and associated piping)
RETURN
SUPPLY
LIQUID
Sensing Bulb
Cylinder
Unloader(s)
Service
Valve
SUPPLY
Optional
3-Way
Regulating
Valve
EVAPORATOR
COIL
* Shutoff Valve
* Shutoff Valve
* Hose
Bib
SUCTION
* Hose
Bib
Muffler
COMPRESSOR
Service External
Check
Valve Equalizer
Valve
Two-Way
Regulating
Valve
DISCHARGE
Bypass Valve
PARADENSER
CONDENSER
Filter Drier
Relief valve(s) supplied
TO SECOND
with 50 Hz EU CE units rated
maximum 480 PSIG (33 Bar). REFRIGERATION
Sensor
CIRCUIT
FACTORY PIPING
FIELD PIPING
OPTIONAL FACTORY PIPING
Service / Schrader (Access) Connection No Valve Core
Service / Schrader (Access) Connection With Valve Core
NOTES: Two refrigeration circuits provided.
Single refrigeration circuit shown for clarity.
DPN000895
Rev. 5
Liebert DS
112
Piping
Figure 92
CUSTOMER
HEAT REJECTION
** EXPANSION
TANK
GLYCOL
PUMPS
* Check Valves
(on Dual Pump
Systems only)
* Gate Valves
DRYCOOLER
(Glycol)
COOLING TOWER
AND PUMP
SYSTEM
BY OTHERS
* Pressure
Port
Aquastat
Sensing
Bulbs
* Hose
* Shutoff Valve
Bib
* Pressure Port
Flow Switch
Supplied with Dual
Pump Systems
* Shutoff Valve
RETURN
* Flow-Regulating
Valve
SUPPLY
RETURN
LIEBERT DS
(and associated piping)
RETURN
LIQUID
Sensing Bulb
Optional
3-Way
Regulating
Valve
EVAPORATOR
COIL
* Shutoff Valve
* Hose
Bib
SUCTION
SUPPLY
SUPPLY
* Shutoff Valve
* Hose
Bib
Service
Valve
Service
CheckCOMPRESSOR Valve
Valve
External
Equalizer
Two-Way
Regulating
Valve
DISCHARGE
Bypass Valve
PARADENSER
CONDENSER
Filter Drier
Relief valve(s) supplied
with 50 Hz EU CE units rated
maximum 480 PSIG (33 Bar).
Sensor
To Second
Refrigeration
Circuit
FACTORY PIPING
FIELD PIPING
OPTIONAL FACTORY PIPING
Service / Schrader (Access) Connection No Valve Core
Service / Schrader (Access) Connection With Valve Core
NOTES: Two refrigeration circuits provided.
Single refrigeration circuit shown for clarity.
DPN000896
Rev. 5
113
Liebert DS
Piping
Figure 93
LIEBERT
HEAT REJECTION
CUSTOMER
HEAT REJECTION
GLYCOL
PUMPS
Check Valves*
(on Dual Pump
Systems only)
DRYCOOLER
(Glycol)
COOLING TOWER
AND PUMP
SYSTEM
BY OTHERS
EXPANSION
TANK**
Pressure
Port*
Gate Valves*
Aquastat
Sensing
Bulbs
Hose
Bib* Shut-Off Valve*
Air Vents
(typical)***
Pressure Port*
Flow Switch
Supplied with Dual
Pump Systems
LIEBERT DS
(and associated piping)
LIQUID
28-42kW Digital Solenoid Valve Sensing Bulb
53-70kW Digital
Solenoid Valve
Flow-Regulating
Valve*
Shut-Off Valve*
RETURN SUPPLY
RETURN
SUPPLY
RETURN
SUPPLY
Shut-Off Valve*
Hose
Bib*
EVAPORATOR
COIL
Shut-Off Valve*
Hose
Bib*
SUCTION
Hot Gas Reheat
Valve
Service
Valve
Service
Valve
Check
COMPRESSOR
Valve
External
Equalizer
2-Way
Motorized
Ball Valve
Check Valve
DISCHARGE
From
Liebert
iCOM
Control
PARADENSER
CONDENSER
Expansion Solenoid Sight
Filter Drier
Valve
Valve
Pressure
Glass
Relief valve(s) supplied Transducer
with 50 Hz EU CE units rated
maximum 480 PSIG (33 Bar).
To
Liebert
iCOM
Control
To Second
Refrigeration
Circuit
*
FACTORY PIPING
FIELD PIPING
OPTIONAL FACTORY PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
NOTE: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity
Schematic representation shown. This schematic does not imply or define elevations and
component location, unless specifically noted.
Liebert DS
114
DPN001430
Rev. 1
Piping
Figure 94
LIEBERT
HEAT REJECTION
EXPANSION
TANK**
GLYCOL
PUMPS
Check Valves*
(on Dual Pump
Systems only)
Pressure
Port*
DRYCOOLER
(Glycol)
Gate Valves*
Aquastat
Sensing
Bulbs
Hose
Bib* Shutoff Valve*
Air Vents
(typical)***
Pressure Port*
Flow Switch
Supplied with Dual
Pump Systems
Flow-Regulating
Valve*
Shutoff Valve*
RETURN
LIEBERT DS
(and associated piping)
SUPPLY
Shutoff Valve*
Sensing Bulb
Cylinder
Unloader(s)
RETURN
ECON-O-COIL
LIQUID
Service
Valve
SUPPLY
EVAPORATOR
COIL
3-Way
Chilled Glycol
Valve
Thermistor
Shutoff Valve*
Hose
Bib*
Hose
Bib*
SUCTION
External
Equalizer
Muffler
COMPRESSOR
Service
Valve
Check Valve
DISCHARGE
Service
Valve
PARADENSER
CONDENSER
Expansion Solenoid Sight
Valve
Glass
Valve
Filter
Dryer
Relief valve(s) supplied
with 50Hz EU CE units rated
maximum 480 PSIG (33 Bar).
3-Way
Regulating
Valve
Sensor
To Second
Refrigeration
Circuit
Factory Piping
Field Piping
Service/Schrader (Access) Connection No Valve Core
Service/Schrader (Access) Connections With Valve Core
Notes: Schematic representation shown. This schematic does not imply or define elevations and
component location unless specifically noted.
Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
115
DPN000897
Rev. 4
Liebert DS
Piping
Figure 95
EXPANSION
TANK**
LIEBERT
HEAT REJECTION
DRYCOOLER
(Glycol)
Pressure
Port*
Aquastat
Sensing
Bulbs
Hose
Bib*
Shutoff Valve*
Gate Valves*
Air Vents
(typical)***
Pressure Port*
Flow Switch
Supplied with Dual
Pump Systems
Flow-Regulating
Valve*
Shutoff Valve*
RETURN
LIEBERT DS UNIT
(and associated piping)
ECON-O-COIL
RETURN
LIQUID
Sensing Bulb
Service
Valve
SUCTION
EVAPORATOR
COIL
3-Way
Chilled Glycol
Valve
Thermistor
SUPPLY
SUPPLY
Shutoff Valve*
Shutoff Valve*
Hose
Bib*
Hose
Bib*
Check
Valve
Service
Valve External
Equalizer
COMPRESSOR
DISCHARGE
Paradenser
Condenser
Expansion Solenoid Sight
Valve
Valve
Glass
3-Way
Regulating
Valve
Filter Dryer
Relief valve(s) supplied
with 50 Hz EU CE units rated To Second
maximum 480 PSIG (33 Bar). Refrigeration
Circuit
Sensor
FIELD PIPING
FACTORY PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
NOTES: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
Schematic representation shown. This schematic does not imply or define elevations and
component location, unless specifically noted.
Liebert DS
116
Piping
Figure 96
LIEBERT
HEAT REJECTION
EXPANSION
TANK**
GLYCOL
PUMPS
Check Valves*
(on Dual Pimp
Systems only)
Gate Valves*
Pressure
Port*
DRYCOOLER
(Glycol)
Aquastat
Sensing
Bulb
Hose
Bib*
Shutoff Valve*
Air Vents
(typical)***
Pressure Port*
Flow Switch
Supplied with Dual
Pump Systems
Flow-Regulating
Valve*
Shutoff Valve*
LIEBERT DS
(and associated piping)
LIQUID
28-42kW Digital Solenoid Valve
53-70kW Digital
Solenoid Valve
ECON-O-COIL
RETURN
SUPPLY
RETURN
SUPPLY
Shutoff Valve*
Sensing Bulb
EVAPORATOR
COIL
3-Way
Chilled Glycol
Valve
Thermistor
Hose
Bib*
Shutoff Valve*
Hose
Bib*
SUCTION
Service
Valve
Check
Valve COMPRESSOR
3-Way
Motorized
Ball Valve
External
Equalizer
DISCHARGE
From
Liebert
iCOM
Control
PARADENSER
CONDENSER
Expansion Solenoid Sight
Filter Drier
Valve
Valve
Pressure
Glass
Relief valve(s) supplied Transducer
with 50Hz EU CE units rated
maximum 480 PSIG (33 Bar).
To
Liebert
iCOM
Control
To Second
Refrigeration
Circuit
FACTORY PIPING
FIELD PIPING
SERVICE / SCHRADER (ACCESS) CONNECTION NO VALVE CORE
SERVICE / SCHRADER (ACCESS) CONNECTION WITH VALVE CORE
NOTE: Two refrigeration circuits provided. Single refrigeration circuit shown for clarity.
Schematic representation shown. This schematic does not imply or define elevations and
Component location, unless specifically noted.
117
DPN001432
Rev. 1
Liebert DS
Piping
Figure 97
Return Supply
Thermistor*
Thermistor*
Actuator
Return
Return
Supply
Supply
Econ-O-Coil
Econ-O-Coil
Actuator
DPN000805
2
Liebert DS
118
Electrical field connectionsUpflow and downflow models, single molded case switch
disconnect with main fuses
See 11.1 - Standard Electrical Field Connections, 11.2 Optional Electrical Connections, 11.2 - Optional Electrical
Connections and 11.3 - Optional Low-Voltage Terminal
Package Connections for keys to numbered components.
15
Liebert
IntelliSlot
Housing
Alternate
Location
P64
CONTACTORS
P67
60Hz
13
17 18
82 83 88 89
24 23
58 59 84 85
Downflow
16
22
19
NOTICE
75 76 94 95 96 97 91 92 93 80 81 11 12
21
10
20
11
49-3
49-1
SH
UPFLOW
3
12
E
DPN000807
Pg. 3, Rev. 13
119
Liebert DS
Figure 99
15
14
60Hz
Liebert
IntelliSlot
Housing
Alternate
Alternate
Location
Location
15
P64
CONTACTORS
PRIMARY
P67
SECONDARY
13
CONTACTORS, RELAYS and
OVERLOAD PROTECTORS
E
1
17 18
82 83 88 89
22
16
58 59 84 85
NOTICE
Risk of broken or shorted low-voltage
wiring. Field-installed low-voltage wiring
must be routed with loop as shown
to allow electric box to swing.
20
10
11
49-3
49-1
SH
UPFLOW
3
B
21
19
75 76 94 95 96 97 91 92 93 80 81 11 12
A
24 23
DOWNFLOW
12
Liebert DS
120
11.1
121
Liebert DS
11.2
11.3
Liebert DS
122
Heat RejectionLiebert MC
Liebert MC Selections
Table 23
Model #
95F (35C)
100F (38C)
105F (41C)
110F (43C)
115F (46C)
120F (49C)
DS/VS028A
MCM056_8
MCM056_8
MCM080_8
MCL110_8
MCL110_8
MCL110_8
DS/VS035A
MCM056_8
MCM080_8
MCM080_8
MCL110_8
MCL110_8
MCL110_8
DS/VS042A
MCM056_8
MCM080_8
MCL110_8
MCL110_8
MCL110_8
MCL110_8
DS/VS053A
MCM056_8
MCM080_8
MCL110_8
MCM160_8
MCM160_8
MCL220_8
DS/VS070A
MCM080_8
MCL110_8
MCL110_8
MCM160_8
MCM160_8
MCL220_8
DS/VS077A
MCM080_8
MCL110_8
MCL110_8
MCM160_8
MCM160_8
MCL220_8
DS/VS105A
MCL110_8
MCM160_8
MCM160_8
MCL220_8
MCL220_8
MCL220_8
Table 24
Model #
95F (35C)
100F (38C)
105F (41C)
110F (43C)
115F (46C)
120F (49C)
DS/VS028A
MCM056_8
MCM080_8
MCL110_8
MCL110_8
MCL110_8
MCM160_8
DS/VS035A
MCM056_8
MCM080_8
MCL110_8
MCL110_8
MCM160_8
MCM160_8
DS/VS042A
MCM080_8
MCL110_8
MCL110_8
MCM160_8
MCM160_8
MCM160_8
DS/VS053A
MCL110_8
MCL110_8
MCM160_8
MCL220_8
MCL220_8
MCL220_8
DS/VS070A
MCL110_8
MCM160_8
MCM160_8
MCL220_8
MCL220_8
MCL220_8
DS/VS077A
MCL110_8
MCM160_8
MCM160_8
MCL220_8
MCL220_8
MCL220_8
DS/VS105A
MCM160_8
MCL220_8
MCL220_8
MCL220_8
MCL220_8
Table 25
T75F/45RH return air conditions Liebert QuietLine for lower sound levels
Outdoor Design Ambient Temperature
Liebert DS
Model #
95F (35C)
100F (38C)
105F (41C)
110F (43C)
115F (46C)
DS/VS028A
MCM080E8
MCM080E8
MCL110E8
MCL110E8
MCL110E8
DS/VS035A
MCM080E8
MCL110E8
MCL110E8
MCM160E8
MCM160E8
DS/VS042A
MCM080E8
MCL110E8
MCL110E8
MCM160E8
MCM160E8
DS/VS053A
MCL110E8
MCL110E8
MCM160E8
MCL220E8
MCL220E8
DS/VS070A
MCL110E8
MCM160E8
MCL220E8
MCL220E8
MCL220E8
DS/VS077A
MCL110E8
MCM160E8
MCL220E8
MCL220E8
MCL220E8
DS/VS105A
MCM160E8
MCL220E8
Consult Factory
123
Liebert DS
Heat RejectionLiebert MC
12.2
Table 26
Condenser Dry
Weight, lb (kg)
MCS056
2
18" Leg
270 (122)
36" Leg
419 (190)
48" Leg
451 (205)
60" Leg
482 (219)
Table 27
110 (50)
8 (4)
63 (29)
MCM080
MCM160
18" Leg
441 (200)
860 (390)
36" Leg
590 (268)
1066 (484)
48" Leg
622 (282)
1114 (505)
60" Leg
653 (296)
1160 (526)
110 (50)
220 (100)
Coated Coil
10 (5)
20 (9)
575 Transformer
63 (29)
76 (34)
Refrigeration Circuits
Condenser Dry
Weight, lb (kg)
Table 28
MCL110
MCL220
18" Leg
602 (273)
1186 (538)
36" Leg
766 (347)
1453 (659)
48" Leg
798 (362)
1501 (681)
60" Leg
829 (376)
1547 (702)
120 (54)
240 (109)
16 (7)
32 (15)
90 (41)
134 (61)
Refrigeration Circuits
Condenser Dry
Weight, lb (kg)
Liebert DS
124
Heat RejectionLiebert MC
12.3
Table 29
Liebert MC
Model #
63
125
250
500
1000
2000
4000
8000
Total
MCS056
53
73
69
73
76
74
67
61
81
MCM80
52
70
76
79
81
79
72
65
85
MCM160
55
73
79
82
84
82
75
68
89
MCL110
65
74
78
83
85
83
76
69
89
MCL220
68
77
81
86
88
86
79
72
92
12.4
Electrical DataLiebert MC
Table 30
Liebert MC electrical data, three-phase, 60Hz condenser, Premium Version (EC control)
Power Requirements
FLA
WSA
Model #
Number
of Fans
208/230V
460V
575V
208/230V
460V
OPD
575V
208/230V
460V
575V
MCS056
6.0
2.8
2.3
6.8
3.3
2.8
15
15
15
MCM080
4.6
2.8
2.3
5.5
3.3
2.8
15
15
15
MCM160
9.2
5.6
4.7
9.8
6.0
5.0
15
15
15
MCL110
11.4
5.6
4.7
12.8
6.3
5.3
15
15
15
MCL220
22.8
11.2
9.3
24.2
11.9
9.9
25
15
15
1.
2.
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device.
208V460V premium models must be connected to Wye 3-phase systems.
125
Liebert DS
Heat RejectionLiebert MC
12.5
Liebert MC Dimensions
575V
Option
G
A*
H
Top of
Fan Guard
Liebert Lee-Temp
Entering Hot Gas
and Leaving
Liquid Piping
C
D
Anchor
Plan
Main
Electric
Box
End
1/2" x 1"
(13mm x 25mm)
Obround Typical
DETAIL A
Typical of all Legs
MCS056
MCM080
MCL110
FRONT VIEW
(Liebert Lee-Temp Shown)
1-7/8" (48mm)
Typical
7"
(178mm)
Typical
Liebert
Model No.
6-1/2"
(165mm) Ref
6-1/2"
Dual Circuit Only
(165mm) Ref
15-1/4"
15-1/4"
K
(387mm)
(387mm)
Dual Circuit Only
J
Liebert Lee-Temp Only
3-5/8"
(93mm)
Typical
13/16"
(21mm)
Typical
M L K
DPN003437
Rev. 1
A
in. (mm)
A*
(575V Only)
in. (mm)
C
in. (mm)
D
in. (mm)
J
Liebert Lee-Temp
Only
K
in. (mm)
L
in. (mm)
M
in. (mm)
94-7/8
(2411)
105-1/4
(2674)
124-1/8
(3152)
103-1/8
(2619)
113-7/16
(2882)
133-1/8
(3381)
88-3/8
(2245)
96-1/16
(2440)
112-1/8
(2848)
86-3/4
(2203)
94-7/16
(2398)
110-1/2
(2806)
42-1/2
(1079)
46-5/16
(1177)
54-3/8
(1381)
42-1/2
(1080)
46
(1168)
55-1/2
(1410)
40-7/8
(1038)
44-3/8
(1127)
53-7/8
(1368)
35-7/8
(910)
39-5/16
(999)
48-3/4
(1238)
36 (914)
49-5/8 (1260)
57-5/8 (1464)
36 (914)
49-5/8 (1260)
57-5/8 (1464)
48 (1219)
61-5/8 (1565)
69-5/8 (1768)
48 (1219)
61-5/8 (1565)
69-5/8 (1768)
60 (1524)
73-5/8 (1870)
81-5/8 (2073)
60 (1524)
73-5/8 (1870)
81-5/8 (2073)
35-7/8 (911)
43-5/8 (1108)
53-7/8 (1368)
61-5/8 (1565)
65-7/8 (1673)
73-5/8 (1870)
77-7/8 (1978)
85-5/8 (2175)
1. Cross-bracing required for legs longer than 18". Number of legs varies per model and options.
2. Source: DPN003437, Rev. 1
Liebert DS
126
Heat RejectionLiebert MC
575V
Option
Lifting Eyebolts
Typ. (4) Places
A*
A
H
Top of
Fan Guard
Liebert Lee-Temp
Receiver
Entering Hot Gas
and Leaving
Liquid Piping
C
E
54-3/16
(1376mm)
Typical
A
Full height leg
supplied for each
Liebert Lee-Temp
Receiver Required
Anchor
Plan
Main
Electric
Box
End
M L K
6-1/2"
(165mm) Ref
13/16"
(21mm)
Typical
3-5/8"
(93mm)
Typical
15-1/4"
(387mm)
FRONT VIEW
7"
(178mm)
Typical
6-1/2"
(165mm) Ref.
Dual Circuit Only
15-1/4"
(387mm)
Liebert Lee-Temp
Only
1-7/8"
(48mm)
Typical
1/2" x 1"
(13mm x 25mm)
Obround Typical
DETAIL A
Typical of all Legs
DPN003439
Rev. 1
Liebert
Model No.
A
in. (mm)
A*
(575V Only)
in. (mm)
B
in. (mm)
C
D
E
in. (mm) in. (mm) in. (mm)
J
Liebert Lee-Temp
Receivers Only
MCM160
202-7/16
(5142)
210-5/8
(5350)
113-1/2
(2883)
46-5/16
(1177)
46
(1168)
44-3/8
(1127)
39-5/16
(999)
MCL220
236-5/16
(6003)
245-5/16
(6231)
54-3/8
(1381)
55-1/2
(1410)
53-7/8
(1368)
48-3/4
(1238)
K
L
M
in. (mm) in. (mm) in. (mm)
18 (457)
36 (914)
48 (1219)
60 (1524)
31-5/8 (803)
49-5/8 (1260)
61-5/8 (1565)
73-5/8 (1870)
39-5/8 (1006
57-5/8 (1464)
69-5/8 1768)
81-5/8 (2073)
35-7/8 (911)
53-7/8 (1368)
65-7/8 (1673)
77-7/8 (1978)
43-5/8 (1108)
61-5/8 (1565)
73-5/8 (1870)
85-5/8 (2175)
MCL220
1. Cross-bracing required for legs longer than 18". Number of legs varies per model and options.
2. Source: DPN003439, Rev. 1
127
Liebert DS
Heat RejectionLiebert MC
12.6
Piping Connections
* Cover
Vertical
Inverted traps
are factory provided
inside condenser
Leaving Liquid
Line
Field Piping
Horizontal
Entering Hot
Gas Line
DETAIL A
Circuit #1
Circuit #2
Table 31
DPN002425
Rev. 5
Model #
# of
Fans
Liquid Line
MCS056
7/8
5/8
MCM080
7/8
5/8
MCL110
1-1/8
7/8
MCM160
1-1/8
7/8
MCL220
1-3/8
1-1/8
Liebert DS
128
Heat RejectionLiebert MC
C View
B View
* Cover
* Shipping cover is not necessary for proper
condenser operation and may be recycled if field
piping interferes with proper reattachment
Position elbow to
direct relief valve
downward
Leaving
Liquid Line
B View
Liquid Line
From Condenser
Isolator
Detail AA
GENERAL ARRANGEMENT
Entering Hot
Gas Line
Liquid Line
From Condenser
Leaving
Liquid Line
Position elbow to
direct relief valve
downward
C View
Note:
1. The following materials are supplied by Emerson for each circuit (shipped loose with condenser)
for field installation: insulated Liebert Lee-Temp receiver tank with sight glasses, piping assembly
with head pressure control valve, check valve, rotalock valve and pressure relief valve. All other piping
and electrical wiring to be supplied and installed by others. An additional condenser leg per circuit
to be shipped with the condenser.
2. Consult factory for proper line sizing for runs longer than 150ft. (45.7m) equivalent length.
Table 32
DPN002426
Rev. 6
Receiver Out
Rotalock
IDS, in.
Model #
Circuit No.
Hot Gas
Liquid
MCS056
7/8
5/8
7/8
5/8
5/8
MCM080
7/8
5/8
7/8
5/8
5/8
MCL110
1-1/8
7/8
1-1/8
7/8
7/8
MCM160
1-1/8
7/8
1-1/8
7/8
1-1/8
MCL220
1-3/8
1-1/8
1-3/8
1-1/8
1-1/8
129
Liebert DS
Heat RejectionLiebert MC
12.7
Figure 104 Electrical field connectionsLiebert MC premium efficiency control, with and without Liebert
Lee-Temp
Fan 2
Fan 2
Liebert Lee-Temp receiver tank 1 per circuit).
NOTE: Heater pad voltage available for
120V/1ph/60Hz or 230V/1ph/60Hz
150 or 300 watt, varies by condenser.
Fan 1
Fan 1
Electrical connection
box; cover removed
for clarity
Without Liebert
Lee-Temp
Electrical service connection.
With Liebert
Lee-Temp
1
+
5A
5B
+
xxxxxxx
xxxxxxx
xxxxxxxxxxxxxx
xxxxxxx
xxxxxxx
xxxxxxxxxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
5C
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxxxxxxxxxxxxxxxxx
xxxxxxxxxxxxxxxxxxxxxx
8
12
13
Liebert DS
11
Left Knockout
3
Right Two
Knockouts
70
71
230
NOTICE!
THIS HOLE FOR FIELD
SUPPLIED EXTRA LOW
VOLTAGE CONTROL WIRING
xxxxxxx
xxxxxxx
xxxxxxx
xxxxxxx
10
DPN002169
Pg. 1, Rev. 7
DPN002374
Pg. 1, Rev. 6
130
Heat RejectionLiebert MC
131
Liebert DS
Heat RejectionLiebert MC
Notes
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
Conductors 22-18AWG stranded tinned copper
Twisted pair (minimum 4 twists per foot)
Braided shield or foil shield with drain wire
Shield must be wired to ground at indoor unit
Low Capacitance (15pf/ft or less)
UL approved temperature rated to 75C
UL approved voltage rated to 300V
UV-resistant and moisture-resistant if not run in conduit
Examples: Belden part number 89207(plenum rated) or Alpha Wire part number 6454 (UV
resistant outdoor rated) Category 5, 5e or higher. Do not run the CANbus cable in the same
conduit, raceway or chase as high-voltage.
3. Do not run the CANbus cable in the same conduit, raceway or chase as high-voltage.
4. No special considerations are required when the total external cable connection between the
indoor unit and outdoor unit(s) is less than 450ft. (137m). For total external cable connections
greater than 450ft. (137m) but less than 800ft. (243m), a CANbus isolator is required.
5. All wiring must be sized and selected for insulation case per NEC and other local codes.
6. Do not bend cables to less than four times the diameter of the cable.
7. Do not deform cables when securing in bundles or when hanging them.
8. Avoid running the cables by devices that may introduce noise, such as machines, fluorescent
lights and electronics.
9. Avoid stretching cables.
10. Separate high volt wires and other high-voltage sources from CAN wires by 12 inches.
11. The electrically commutated (EC) motors included in the Liebert MC Condenser are suitable for
connection to power supplies with a solidly grounded neutral. (Some platforms can accept power
supplies listed under Item b below. Contact the factory for more information.)
a. Acceptable power supplies for 208 to 575V nominal units
208V wye with solidly grounded neutral and 120V line to ground;
380V wye with solidly grounded neutral and 220V line to ground;
480V wye with solidly grounded neutral and 277V line to ground.
575V wye with solidly grounded neutral and 332V line to ground. (uses step-down
transformer)
b. Non-acceptable power supplies for 208V to 575V nominal units
wye with high resistance (or impedance) ground;
delta without ground or with floating ground;
delta with corner ground; or
delta with grounded center tap.
Liebert DS
132
Liebert DS
Model
95 (35)
100 (38)
105 (41)
95 (35)
100 (38)
105 (41)
028
TCDV/CD*-205
TCDV/CD*-205
TCDV/CD*-251
TCDV/CD*-214
TCDV/CD*-214
TCDV/CD*-286
035
TCDV/CD*-205
TCDV/CD*-205
TCDV/CD*-251
TCDV/CD*-214
TCDV/CD*-214
TCDV/CD*-286
042
TCDV/CD*-205
TCDV/CD*-251
TCDV/CD*-308
TCDV/CD*-286
TCDV/CD*-286
TCDV/CD*-409
053
TCDV/CD*-251
TCDV/CD*-308
TCDV/CD*-415
TCDV/CD*-286
TCDV/CD*-409
TCDV/CD*-409
070
TCDV/CD*-308
TCDV/CD*-415
TCDV/CD*-415
TCDV/CD*-409
TCDV/CD*-572
TCDV/CD*-572
077
TCDV/CD*-308
TCDV/CD*-415
TCDV/CD*-616
TCDV/CD*-409
TCDV/CD*-572
TCDV/CD*-572
105
TCDV/CD*-415
TCDV/CD*-616
TCDV/CD*-616
TCDV/CD*-572
N/A
N/A
Table 34
Fin/tube condenser physical data and R-407C refrigerant required per condenser circuit
Connection Size,
OD, In.
Table 35
Model #
Liquid
Net Weight
lb (kg)
FSC or VFD
Liebert Lee-Temp
(includes receiver)
1-1/8
1-1/8
1-3/8
1-3/8
1-5/8
7/8
7/8
1-1/8
1-1/8
1-1/8
495 (225)
500 (227)
670 (304)
840 (381)
1380 (626)
7 (3.2)
10 (4.6)
11 (5.0)
24 (10.9)
26 (11.8)
54 (24.4)
36 (16.3)
55 (24.9)
102 (46.2)
108 (49.0)
1-1/8
1-1/8
1-5/8
2-1/8
7/8
7/8
1-1/8
1-1/8
840 (381)
1105 (501)
1380 (626)
2430 (1102)
N/A
N/A
N/A
N/A
77 (34.9)
119 (54.0)
148 (67.2)
186 (84.4)
Number
of Fans
Number
of Circuits
Hot Gas
2
3
3
4
6
2
2
2
2
2
3
4
6
8
2
2
2
2
Model #
Standard Models
TCDV/CD*205
TCDV/CD*251
TCDV/CD*308
TCDV/CD*415
TCDV/CD*616
Quiet-Line Models
TCDV/DCD*214
TCDV/DCD*286
TCDV/DCD*409
TCDV/DCD*572
Dual-Circuit
lb/circuit (kg/circuit)
Horsepower
CFM
Sound Power
LwA
Sound Pressure
dBA 3
Standard Models
205
3/4
10300
91.0
75.5
251
3/4
17950
94.0
77.3
308
3/4
16650
93.8
77.3
415
3/4
20650
94.4
78.5
616
3/4
33300
96.8
80.3
1/4
6400
74.8
61.3
Quiet-Line Models
214
286
1/4
8275
76.2
62.5
409
1/4
13750
78.4
64.3
572
1/4
17050
79.9
65.5
133
Liebert DS
13.1
Dimensions
43-9/16"
(1106mm)
Emerson recommends a
clearance of 36" (915mm) on
each side for proper operation
and component access.
91-1/2"
(2324mm)
37-7/8"
(962mm)
18"
(457mm)
84"
(2134mm)
43-3/16"
(1097mm)
131-1/2"
(3340mm)
37-7/8"
(962mm)
43-9/16"
(1106mm)
171-1/2"
(4356mm)
18"
(457mm)
124"
(3150mm)
70"
(1778mm)
37-7/8"
(962mm)
Eyebolts
for Lifting
43-3/16"
(1097mm)
18"
(457mm)
Note:
Overall height to the top of fan guard
43-1/8" (1095mm)
164"
(4166mm)
43-3/16"
(1097mm)
Liebert DS
134
131-1/2"
(3340mm)
87-1/8"
(2213mm)
171-1/2"
(4356mm)
37-7/8"
(962mm)
37-7/8"
(962mm)
59"
(1499mm)
18"
(457mm)
86-3/4"
(2203mm)
18"
(457mm)
124"
(3150mm)
70" (1778mm)
1-1/2" (38mm)
diameter hole for
rigging (typ.4)
164"
(4166mm)
86-3/4"
(2203mm)
135
Liebert DS
13.2
Electrical Data
Model #
Input
Voltage
ph
205
251, 308
415
616
2 Fans
3 Fans
4 Fans
6 Fans
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
8.3
9.5
15
11.8
13.0
15
15.3
16.5
20
23.6
24.8
30
4.2
4.8
15
5.9
6.5
15
7.6
8.2
15
11.8
12.4
15
3.3
3.8
15
4.7
5.2
15
6.1
6.6
15
9.4
9.9
15
7.2
8.1
15
10.7
11.6
15
14.2
15.1
20
N/A
N/A
N/A
3.5
4.0
15
5.2
5.7
15
6.9
7.4
15
N/A
N/A
N/A
575
VFD Controlled
208/230
460
Lee-Temp Controlled/Fan-Cycling
208/230
460
575
7.0
7.9
15
10.5
11.4
15
14.0
14.9
20
21.0
21.9
25
3.4
3.8
15
5.1
5.5
15
6.8
7.2
15
10.2
10.6
15
2.8
3.2
15
4.2
4.6
15
5.6
6.0
15
8.4
8.8
15
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device
Table 37
Model #
Input
Voltage
208/230
460
575
(Liebert Lee-Temp
286
409
572
3 Fans
4 Fans
6 Fans
8 Fans
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
5.4
5.9
15
7.2
7.7
15
10.8
11.3
15
14.4
14.9
20
2.7
2.9
15
3.6
3.8
15
5.4
5.6
15
7.2
7.4
15
2.1
2.3
15
2.8
3.0
15
4.2
4.4
15
5.6
5.8
15
120
150
200/208/230
300
150
300
1.25
2.5
0.7
1.4
1.56
3.1
0.9
1.8
15
15
15
15
Maximum Overcurrent
Protection Device, Amps
The Liebert Lee-Temp receiver requires a separate power feed for heaters. The
condenser is not designed to supply power to the receiver.
Liebert DS
controlled/fan-cycling), 60Hz
214
FLA = Full Load Amps; WSA = Wire Size Amps; OPD = Maximum Overcurrent Protection Device
Table 38
136
71
Factory-installed disconnect
switch (optional).
Factory-wired to components on
electric panel.
Electric Service Entrance.
A 7/8 in. (22.2mm) diameter hole in
a 1-1/18 in. (28.6mm) knockout
provided in bottom of electric box.
137
DPN000666
Rev. 1
Liebert DS
Figure 109 Electrical field connections for VFD control fin/tube condensers
Factory-wired to 24V
control circuit.
Heat Rjection
Connection 70, 71
Field-supplied
Class 1 wiring to
interlock condenser 24V
controls to Liebert indoor
unit (70, 71). Reference the
condenser and indoor unit
electrical schematics for
termination. 7/8" (22.2mm)
diameter hole provided in
bottom of electric box.
70
71
11
12
13
14
V
F
D
SPD
Factory-wired to components
on electric panel.
Earth Ground BAR (optional
on 50Hz only).
Connection terminals with factory
ground from each high-voltage
component for field-supplied
earth grounding wire.
Refer to specification sheet
for full load amp and wire size amp ratings
Earth Ground Connection (60Hz)
Connection terminal for fieldsupplied earth grounding wire
when factory disconnect is supplied.
Liebert DS
Factory-installed
disconnect switch
138
Electric service,
not by Emerson
DPN001051
Rev. 2
Figure 110 Electrical field connections for Liebert Lee-Temp control fin/tube condensers
70
71
Factory-wired to components on
electric panel
Factory-installed disconnect
switch (optional).
139
DPN000683
Rev. 1
Electric Service,
not by Emerson.
Liebert DS
13.3
Piping Connections
Figure 111 VFD and Fan Speed Control condenser pipingFin/tube condensers
Leaving
Liquid Line
Vertical
Horizontal
See
Detail
A-A
Liebert DS
140
Isolator
Detail A-A
DPN001065
Rev. 1
Figure 112 Liebert Lee-Temp head pressure control condenser pipingFin/tube condensers
Metal
Clamp
Isolator
Detail A-A
Discharge Line
from Unit
(field-supplied)
Position elbow to direct
relief valve downward
Liquid Return
Line to Unit
(field-supplied)
Hot Gas Line
(field-supplied)
Liquid Line
(field-supplied)
DPN000669
Rev. 4
141
Liebert DS
Ambient
Temp. F (C)
028
035
042
053
070
077
105
95 (35)
PB-925
PB-925
PB-1100
PB-1350
N/A
N/A
N/A
100 (38)
PB-1100
PB-1100
PB-1350
N/A
N/A
N/A
N/A
105 (41)
PB-1100
PB-1350
N/A
N/A
N/A
N/A
N/A
Piggyback
Table 40
Liebert DS Size
Model
Liquid
PB-350
5/8
1/2
18 8.2)
PB-550
5/8
1/2
17 (7.8)
PB-675
7/8
1/2
25 (11.2)
PB-925
7/8
1/2
22 (9.9)
PB-1100
1-1/8
5/8
34 (15.5)
PB-1350
1-1/8
5/8
34 (15.5)
Table 41
Model
No.
of Fans
CFM / m / hr
0.25 (62.3)
0.50 (125)
0.75 (187)
1.0 (249)
PB-350A
7600/12,920
2/580
3/650
3/720
3/790
PB-550A
6600/11,200
2/575
3/650
3/725
3/800
PB-675A
6900/11,730
2/605
3/680
3/750
3/820
PB-925A
12,500/21,250
7.5/760
7.5/810
7.5/870
7.5/920
PB-1100A
12,300/20,910
7.5/780
7.5/830
7.5/890
7.5/940
PB-1350A
16,500/28,050
10/640
10/695
10/740
15/790
Values are without filter box. External Static Pressure = filter pressure drop + other static drops.
Source: DPN000695, Rev. 1
Table 42
208
hp
230
FLA
460
FLA
LRA
LRA
FLA
2.0
7.5
55
6.8
50
3.0
10.6
71
9.6
64.0
5.0
16.7
102
15.2
92
7.5
24.2
140
22.0
127
10.0
30.8
179
28.0
162.0
14.0
575
LRA
FLA
LRA
3.4
25
2.7
20
4.8
32.0
3.9
25.6
7.6
46
6.1
36.8
11.0
63.5
9.0
50.8
81
11.0
64.8
15.0
46.2
257
42.0
232
21.0
116.0
17.0
93.0
1. See Table 43 for separate power feed needed for Lee-Temp receiver heaters.
2. FLA: Full Load Amps; LRA: Lock Rotor Amps
3. Source: DPN000695, Rev. 1
Table 43
Voltage
120
120
208/230
208/230
Watts/Receiver
150
300
150
300
FLA
2.5
5.0
1.4
2.8
WSA
3.1
6.2
1.8
3.6
OPD
15
15
15
15
Only one independent input power supply is needed per piggyback unit; connect to Terminals 90 & 91.
Liebert DS
142
14.1
Dimensions
1-1/8"
(29mm)
Overa
ll Dim
ensio
ns
sions
Dimen
Overall
Optional Fan
Discharge
Disconnect
Switch (optional)
S
H
J
35-1/8"
(892mm)
72"
(1829mm)
R
Fan Discharge
Shaded areas
indicate a recommended
clearance of 34" (864mm)
for component access.
5"
(127mm)
G
Drain Outlet
Opening
C
Unit Base
10" (254mm)
1"
(25.4mm)
A
Unit Base
Floor Level
A
DPN000695
Rev. 1
Model
PB-350A
72
(1829)
74
(1880)
31
(787)
32
(813)
1-1/8
(29)
33
(838)
60
(1524)
8-5/8
(219)
50-3/16
(1275)
16-1/16
(408)
13-3/16
(335)
14-11/16
(373)
PB-550A
72
(1829)
74
(1880)
31
(787)
32
(813)
1-1/8
(29)
33
(838)
60
(1564)
8-5/8
(219)
50-3/16
(1275)
16-1/16
(408)
13-3/16
(335)
14-11/16
(373)
PB-675A
72
(1829)
74
(1880)
31
(787)
32
(813)
1-1/8
(29)
33
(838)
60
(1564)
8-5/8
(219)
50-3/16
(1275)
16-1/16
(408)
13-3/16
(335)
14-11/16
(373)
PB-925A
97
(2464)
99
(2515)
33
(838)
34
(864)
3-1/8
(79)
45-1/2
(1156)
85
(2159)
23-5/16
(592)
50-3/16
(1275)
16-1/16
(408)
23-1/2
(597)
14-11/16
(373)
PB-1100A
97
(2464)
99
(2515)
33
(838)
34
(864)
3-1/8
(79)
45-1/2
(1156)
85
(2159)
23-5/16
(592)
50-3/16
(1275)
16-1/16
(408)
23-1/2
(597)
14-11/16
(373)
PB-1350A
97
(2464)
99
(2515)
33
(838)
34
(864)
3-1/8
(79)
45-1/2
(1156)
85
(2159)
16-5/16
(421)
63-7/8
(1622)
19-1/8
(486)
16-13/16
(427)
11-5/8
(295)
143
Liebert DS
Figure 114 Floor stand dimensions, piggyback condensers with forward-curved blowers
B
A
1"
(25.4mm)
* H 1-1/2" (38mm)
For height selection
refer to chart.
Center Leg Provided
on 99" Cabinets
Table 45
Model
72 (1829)
36 (914)
31 (787)
97 (2464)
48-1/2 (1232)
33 (838)
Table 46
Nominal
9 (229)
12 (305)
15 (381)
18 (458)
21 (553)
24 (610)
1. Leveling feet are provided with 1-1/2" (38mm) adjustment from nominal height H.
2. Source: DPN000727, Rev. 0
Liebert DS
144
DPN000727
Rev. 0
14.2
Factory-installed unit
disconnect switch (optional)
Field-supplied disconnect
switch when factory-installed
unit disconnect switch is not provided.
Three phase electric
service not by
Emerson
Three-phase connection.
Electric service
connection terminals
when factory disconnect
switch is not supplied
Factory-installed disconnect
switch (optional)
Electric conduit knockouts
on bottom of wire raceway
Knockout sizes 1-3/8"
(34.9mm) or 1-3/4" (44.5mm)
or 2 1/2" (63.5mm)
Three-phase electric
service not by Emerson
Factory-wired to
Earth ground connection (60Hz).
components
Connection terminal for field-supplied
on electric panel.
earth grounding wire.
Liebert Lee-Temp electric
Factory-wired to components
service connection to
on electric panel
terminals supplied from
factory-wired Liebert
Control interlock Field-supplied, Class 2 wiring to
Lee-Temp heater pads
Terminals 70 & 71 to interlock condenser 24V
for field connection of separate
controls to Liebert room unit; 7/8 in. (22.2mm)
continuous electrical source,
diameter knockout provided in bottom of box
not supplied by Emerson.
DPN000697
Rev. 0
Refer to specification sheet for full load amp and wire size amp ratings.
71
70
91
90
145
Liebert DS
14.3
See Note 2
See
Note 2
See Note 1
See
Note 1
A
1-13/16"
(46mm)
B
C
G
1-13
/16"
(46m
m)
E
See Note 3
D
F
D
See Note 2
3" (76mm)
3" (76mm)
1" (25mm)
Panel
1" (25mm)
Panel
3" (76mm)
3" (76mm)
See Note 2
See Note 2
3" (76mm)
See Note 1
3" (76mm)
E See Note 3
See Note 1
E See Note 3
12-5/8"
(321mm)
9-11/16"
(246mm)
12-5/8"
(321mm)
4-1/2" (114mm)
4-1/2"
(114mm)
9-11/16"
(246mm)
7-7/8"
(200mm)
7-7/8"
(200mm)
MODEL PB-1350A
5-1/2" (140mm) See Note 1
3-1/4" (85mm) See Note 2
Drain Outlet
Location
1-1/4" (32mm) F.P.T.
3"
(76mm)
8"
(203mm)
6"
(152mm)
3"
(76mm)
See Note 3
ALL MODELS
1-1/2"
(38mm)
1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and 2-1/2" (64mm) for main power supply (typical).
2. 7/8" (22.2mm) knockouts for Liebert Lee-Temp power supply (typical).
3. Cover plate for access of liquid line and hot gas line.
Table 47
DPN00696
Rev. 1
Model
PB-350A
27-1/4 (692)
2-1/2 (64)
6 (152)
10-1/8 (267)
28-3/4 (730)
PB-550A
27-1/4 (692)
2-1/2 (64)
6 (152)
10-1/8 (267)
28-3/4 (730)
PB-675A
27-1/4 (692)
2-1/2 (64)
6 (152)
10-1/8 (267)
28-3/4 (730)
PB-925A
27-1/4 (692)
2-1/2 (64)
6 (152)
10-1/8 (267)
28-3/4 (730)
PB-1100A
27-1/4 (692)
2-1/2 (64)
6 (152)
10-1/8 (267)
28-3/4 (730)
PB-1350A
11-1/4 (286)
24 (610)
26-1/2 (673)
7 (178)
6 (152)
Table 48
Model
Liquid Line
Drain
PB-350A
2 @ 1/2 (13)
2 @ 5/8 (16)
1-1/4 (32)
PB-550A
2 @ 1/2 (13)
2 @ 5/8 (16)
1-1/4 (32)
PB-675A
2 @ 1/2 (13)
2 @ 7/8 (22)
1-1/4 (32)
PB-925A
2 @ 1/2 (13)
2 @ 7/8 (22)
1-1/4 (32)
PB-1100A
2 @ 5/8 (16)
2 @ 1-1/8 (29)
1-1/4 (32)
PB-1350A
2 @ 5/8 (16)
2 @ 1-1/8 (29)
1-1/4 (32)
See Figures 89 and 90 for piggyback condenser piping schematic with Liebert Lee-Temp .
Liebert DS
146
Table 49
Liebert DS
Model
95F (35C)
100F (38C)
105F (41C)
95F (35C)
100F (38C)
105F (41C)
028
D-174
D-225-16
D-310-16
D-173-16
D-205-16
D-356-32
035
D-174
D-225-16
D-350-16
D-178-16
D-205-16
D-356-32
042
D-225-16
D-310
D-419
D-205
D-347-32
D-453-32
053
D-260
D-350
D-491-32
DD-248
D-347-32
D-453-32
070
D-310
D-419
D-620-32
D-347-32
D-453-32
D-453-32
077
D-350
D-466
D-650-40
D-347-32
D-453-32
N/A
105
D-466
D-620-32
D-880-52
D-453
N/A
N/A
15.2
Table 50
Model #
-174
-225
-260
-310
-350
-419
-466
-491
-620
-650
-880
6
8
Internal
Volume,
gal. (L)
Dry Weight
lb. (kg)
CFM, (l/s)
60Hz
Sound Power
LwA
Sound
Pressure
dBA
6.9 (26.2)
540 (245)
13265 (6261)
91.0
75.5
11.1 (42.1)
620 (281)
12177 (5748)
91.1
75.5
10.0 (37.8)
735 (333)
19898 (9392)
94.0
77.3
13.1 (50.0)
795 (361)
18965 (8951)
94.0
77.3
19.4 (73.3)
855 (388
17398 (8212)
94.0
77.3
17.4 (65.9)
1020 (463)
23650 (11163)
94.4
78.5
22.0 (83.3)
1050 (476)
22770 (10747)
94.4
78.5
26.3 (99.6)
1100 (499)
21700 (10242)
94.4
78.5
27.0 (102.2)
1780 (808)
37930 (17901)
96.8
80.3
33.0 (124.9)
1780 (808)
36531 (17241)
96.8
80.3
44.0 (166.5)
2330 (1058)
45500 (21474)
97.4
81.5
Sound Power
LwA
Sound
Pressure
dBA
Table 51
Model #
-173
-178
-205
-248
-347
-356
-453
Internal
Volume,
gal. (L)
Dry Weight
lb. (kg)
CFM, l/s
60Hz
13.1 (50.0)
795 (361)
8520 (14477)
74.8
61.3
19.4 (73.3)
855 (388)
7440 (12642)
74.8
61.3
13.1 (50.0)
940 (426)
11680 (19847)
76.2
62.5
17.4 (65.9)
1020 (463)
11360 (19303)
76.2
62.5
27.0 (102.2)
1780 (808)
17040 (8042)
78.4
64.3
39.3 (148.8)
1880 (854)
14880 (7023)
78.4
64.3
35.0 (132.5)
2250 (1022)
22720 (10723)
79.9
65.5
147
Liebert DS
15.3
Dimensional Information
37-7/8"
(962mm)
18"
(457mm)
84"
(2134mm)
43-3/16"
(1097mm)
Emerson recommends a
clearance of 36" (915mm) on
each side for proper operation
and component access.
43-9/16"
(1106mm)
171-1/2"
(4356mm)
18"
(457mm)
124"
(3150mm)
70"
(1778mm)
37-7/8"
(962mm)
Eyebolts
for Lifting
43-3/16"
(1097mm)
18"
(457mm)
Note:
Overall height to the top of fan guard
43-1/8" (1095mm)
164"
(4166mm)
43-3/16"
(1097mm)
Liebert DS
148
Emerson recommends a
clearance of 36" (915mm) on
each side for proper operation
and component access.
131-1/2"
(3340mm)
87-1/8"
(2213mm)
87-1/8"
(2213mm)
171-1/2"
(4356mm)
37-7/8"
(962mm)
37-7/8"
(962mm)
59"
(1499mm)
18"
(457mm)
86-3/4"
(2203mm)
18"
(457mm)
124"
(3150mm)
70" (1778mm)
1-1/2" (38mm)
diameter hole for
rigging (typ.4)
86-3/4"
(2203mm)
149
164"
(4166mm)
Emerson recommends a
clearance of 36" (915mm) on
each side for proper
operation and component
Liebert DS
15.4
Electrical Data
Phase
208/230
460
575
Table 53
Electrical
Value
174, 225
2 Fans
620, 650
6 Fan
880
8 Fans
FLA
7.0
10.5
14.0
21.0
28.0
WSA
7.9
11.4
14.9
21.9
28.9
OPD
15
15
20
25
35
FLA
3.4
5.1
6.8
10.2
13.6
WSA
3.8
5.5
7.2
10.6
14.0
OPD
15
15
15
15
20
FLA
2.8
4.2
5.6
8.4
11.2
WSA
3.2
4.6
6.0
8.8
11.6
OPD
15
15
15
15
15
60Hz electrical valuesProp fan drycoolers without pump controls, Liebert Quiet-Line
models
Drycooler Model
Voltage
Phase
Electrical
Value
173, 178
3 Fans
205, 248
4 Fans
347, 356
6 Fans
453
8 Fans
FLA
5.4
7.2
10.8
14.4
WSA
5.9
7.7
11.3
14.9
OPD
15
15
15
20
FLA
2.7
3.6
5.4
7.2
WSA
2.9
3.8
5.6
7.4
OPD
15
15
15
15
FLA
2.1
2.8
4.2
5.6
WSA
2.3
3.0
4.4
5.8
OPD
15
15
15
15
208/230
460
575
Liebert DS
150
Table 54
60Hz electrical valuesStandard prop fan drycoolers with integral pump controls
Number of Fans
Model #
Pump HP
FLA
174, 225
620, 650
880
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
208/230/3/60
0.75
10.5
11.4
15
14.0
14.9
20
17.5
18.4
25
24.5
25.4
30
31.5
32.4
40
1.5
13.6
15.3
20
17.1
18.8
25
20.6
22.3
25
27.6
29.3
35
34.6
36.3
40
2.0
14.5
16.4
20
18.0
19.9
25
21.5
23.4
30
28.5
30.4
35
35.5
37.4
45
3.0
17.6
20.3
30
21.1
23.8
30
24.6
27.3
35
31.6
34.3
40
38.6
41.3
50
5.0
23.7
27.9
40
27.2
31.4
45
30.7
34.9
50
37.7
41.9
50
44.7
48.9
60
7.5
31.2
37.3
60
34.7
40.8
60
38.2
44.3
60
45.2
51.3
70
52.2
58.3
80
10.0
37.8
45.5
70
41.3
49.0
70
44.8
52.5
80
51.8
59.5
90
58.8
66.5
90
15
53.2
64.8
110
56.7
68.3
110
60.2
71.8
110
67.2
78.8
110
74.2
85.8
125
0.75
5.0
5.4
15
6.7
7.1
15
8.4
8.8
15
11.8
12.2
15
15.2
15.6
20
1.5
6.4
7.2
15
8.1
8.9
15
9.8
10.6
15
13.2
14.0
20
16.6
17.4
20
2.0
6.8
7.7
15
8.5
9.4
15
10.2
11.1
15
13.6
14.5
20
17.0
17.9
20
460/3/60
3.0
8.2
9.4
15
9.9
11.1
15
11.6
12.8
15
15.0
16.2
20
18.4
19.6
25
5.0
11.0
12.9
20
12.7
14.6
20
14.4
16.3
20
17.8
19.7
25
21.2
23.1
30
7.5
14.4
17.2
25
16.1
18.9
25
17.8
20.6
30
21.2
24.0
30
24.6
27.4
35
10.0
17.4
20.9
30
19.1
22.6
35
20.8
24.3
35
24.2
27.7
40
27.6
31.1
45
15
24.4
29.7
50
26.1
31.4
50
27.8
33.1
50
31.2
36.5
50
34.6
39.9
60
0.75
4.1
4.5
15
5.5
5.9
15
6.9
7.3
15
9.7
10.1
15
12.5
12.9
15
1.5
5.2
5.8
15
6.6
7.2
15
8.0
8.6
15
10.8
11.4
15
13.6
14.2
20
2.0
5.5
6.2
15
6.9
7.6
15
8.3
9.0
15
11.1
11.8
15
13.9
14.6
20
3.0
6.7
7.7
15
8.1
9.1
15
9.5
10.5
15
12.3
13.3
15
15.1
16.1
20
5.0
8.9
10.4
15
10.3
11.8
15
11.7
13.2
15
14.5
16.0
20
17.3
18.8
20
7.5
11.8
14.1
20
13.2
15.5
20
14.6
16.9
25
17.4
19.7
25
20.2
22.5
30
575/3/60
10.0
13.8
16.6
25
15.2
18.0
25
16.6
19.4
30
19.4
22.2
30
22.2
25.0
35
15
19.8
24.1
40
21.2
25.5
40
22.6
26.9
40
25.4
29.7
45
28.2
32.5
45
151
Liebert DS
Table 55
Number of Fans
Model #
Pump H.P.
FLA
173, 178
205, 248
347, 356
453
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
FLA
WSA
OPD
208/230/3/60
0.75
8.9
9.8
15.0
10.7
11.6
15.0
14.3
15.2
20.0
17.9
18.8
25.0
1.5
12.0
13.7
20.0
13.8
15.5
20.0
17.4
19.1
25.0
21.0
22.7
25.0
2.0
12.9
14.8
20.0
14.7
16.6
20.0
18.3
20.2
25.0
21.9
23.8
30.0
3.0
16.0
18.7
25.0
17.8
20.5
30.0
21.4
24.1
30.0
25.0
27.7
35.0
5.0
22.1
26.3
40.0
23.9
28.1
40.0
27.5
31.7
45.0
31.1
35.3
50.0
7.5 *
29.6
35.7
50.0
31.4
37.5
60.0
35.0
41.1
60.0
38.6
44.7
60.0
36.2
43.9
70.0
38.0
45.7
70.0
41.6
49.3
80.0
45.2
52.9
80.0
51.6
63.2
100.0
53.4
65.0
110.0
57.0
68.6
110.0
60.6
72.2
110.0
0.75
4.3
4.7
15.0
5.2
5.6
15.0
7.0
7.4
15.0
8.8
9.2
15.0
1.5
5.7
6.5
15.0
6.6
7.4
15.0
8.4
9.2
15.0
10.2
11.0
15.0
2.0
6.1
7.0
15.0
7.0
7.9
15.0
8.8
9.7
15.0
10.6
11.5
15.0
10.0
15
460/3/60
3.0
7.5
8.7
15.0
8.4
9.6
15.0
10.2
11.4
15.0
12.0
13.2
15.0
5.0
10.3
12.2
15.0
11.2
13.1
20.0
13.0
14.9
20.0
14.8
16.7
20.0
13.7
16.5
25.0
14.6
17.4
25.0
16.4
19.2
30.0
18.2
21.0
30.0
16.7
20.2
30.0
17.6
21.1
35.0
19.4
22.9
35.0
21.2
24.7
35.0
23.7
29.0
45.0
24.6
29.9
50.0
26.4
31.7
50.0
28.2
33.5
50.0
0.75
3.4
3.7
15.0
4.1
4.4
15.0
5.5
5.8
15.0
6.9
7.2
15.0
1.5
4.5
5.1
15.0
5.2
5.8
15.0
6.6
7.2
15.0
8.0
8.6
15.0
2.0
4.8
5.5
15.0
5.5
6.2
15.0
6.9
7.6
15.0
8.3
9.0
15.0
3.0
6.0
7.0
15.0
6.7
7.7
15.0
8.1
9.1
15.0
9.5
10.5
15.0
5.0
8.2
9.7
15.0
8.9
10.4
15.0
10.3
11.8
15.0
11.7
13.2
15.0
11.1
13.4
20.0
11.8
14.1
20.0
13.2
15.5
20.0
14.6
16.9
25.0
13.1
15.9
25.0
13.8
16.6
25.0
15.2
18.0
25.0
16.6
19.4
30.0
19.1
23.4
40.0
19.8
24.1
40.0
21.2
25.5
40.0
22.6
26.9
40.0
7.5 *
10.0
15
575/3/60
7.5
10.0
15 2
1. Values are calculated per UL 1995. Pump FLA values used are based on NEC tables for motor horsepower. OPD values may be
adjusted higher than calculations to compensate for maximum anticipated application temperatures.
2. May require electrical component(s) with higher capacity in the drycooler. Consult factory representatives for assistance before
ordering.
Liebert DS
152
Figure 120 Electrical field connections for fluid temperature control, direct-drive Drycoolers
Factory-wired to 24V
Class 2 control circuit
Factory-wired to components
on electric panel
Control interlock
Field-supplied
Class 2 wiring to
interlock drycooler
24V controls to
Liebert room unit
(Not required on
CSU 3000). 7/8"
(22.2mm) diameter
hole provided in
bottom of electric box.
Flow switch connection
(Dual pump controls only)
Field-supplied 24V Class 2
wiring from terminals 74 +
77 to field mounted flow
switch.
Refer to specification sheet for full load amp and wire size amp ratings.
153
Electric service.
not by Emerson.
(Field-wired to Liebert
CSU 3000.
Interconnecting wiring
not by Emerson).
DPN000276
Rev. 1
Liebert DS
15.5
Piping Connections
Table 56
Drycooler
No. of
Fans
Model #
No. of Internal
Coil Circuits
174
16*
225
16
260
24*
310
16
13.1 (50.0)
1/1
2-1/8
350
16
19.4 (73.3)
1/1
2-1/8
419
32*
17.4 (65.9)
1/1
2-1/8
466
40*
22.0 (83.3)
1/1
2-5/8
Internal Volume,
gal. (L)
No. of
Inlets/Outlets
OD Copper, in.
ID Sweat, in.
6.9 (26.2)
1/1
2-1/8
11.1 (42.1)
1/1
2-1/8
10.0 (37.8)
1/1
2-1/8
491
32
26.3 (99.6)
1/1
2-1/8
620
32
27.0 (102.2)
2/2
2-1/8
650
40
33.0 (124.9)
2/2
2-1/8
880
52
44.0 (166.5)
2/2
2-1/8
6
8
* = Standard Circuiting
Table 57
Liebert Quiet-Line
Drycooler
No. of Internal
Coil Circuits
No. of
Fans
173
16, 32*
178
16, 32*
205
16
248
32*
347
32
356
32
453
32
Model #
4
6
8
Internal Volume
gal. (L)
ID Sweat, in.
13.1 (50.0)
1/1
2-1/8
19.4 (73.3)
1/1
2-1/8
13.1 (50.0)
1/1
2-1/8
17.4 (65.9)
1/1
2-1/8
27.0 (102.2)
2/2
2-1/8
39.3 (148.8)
2/2
2-1/8
35.0 (132.5)
2/2
2-1/8
* = Standard circuiting
Liebert DS
No. of
Inlets/Outlets
154
Inlet Connection
(Upper Header)
Outlet Connection
(Lower Header)
DPN000275
Rev. 3
Inlet
Connections
(4 Inlet, 4 Outlet
Connections Shown)
See table for actual
number provided.
DPN002429
Rev. 0
Outlet Connections
155
Liebert DS
Figure 123 Typical piping arrangement, multiple prop fan drycoolers and multiple indoor units
Expansion Tank
Gal. (L)
FS
Drycooler No. 1 Model
P:
GPM (L/s)
Ft (kPA)
See Note 3
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Total
GPM
(L/s):
Pipe
Diam.:
In. (mm)
P: Ft.
(kPa)
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Ft (kPA)
LEGEND
Gate Valve
Check Valve
Butterfly Valve
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Relief Valve
Union
Ball Or Flow Control Valve
FS
Flow Switch
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
P:Pressure Drop
Strainer Filter
Notes:
1. Pressure and temperature gauges (or ports for same) are recommended to monitor
component pressure drops and performance.
2. Flow measuring devices, drain and balancing valves to be supplied by others and
located as required.
3. See product literature for installation guidelines and clearance dimensions.
4. Drawing shows dual pump package. Alternate pump packages with more pumps may be
considered, consult supplier
Liebert DS
156
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
Cooling Unit #
Model
GPM (L/s)
P Ft (kPa):
DPN000991
Rev. 0
Table 58
Liebert DS Model
Drycooler Type
028
035
042
053
070
077
Piggyback
Drycooler
95 (35)
100 (38)
105 (41)
PD-133/150
PD-223
PD-333
PD-150
PD-223
PD-333
PD-223
PD-333
PD-333
PD-290
N/A
N/A
PD-333
N/A
N/A
PD-333
N/A
N/A
Table 59
Model
No. of Fans
CFM (m /hr)
0.25 (62.3)
0.50 (125)
0.75 (187)
1.0 (249)
PD-133
PD-150
6900 (11,730
2/605
3/680
3/750
3/820
PD-223
12,500 (21,250
7.5/760
7.5/810
7.5/870
7.5/920
PD-290
12,300 (20,910
7.5/780
7.5/830
7.5/890
7.5/940
PD-333
16,500 (28,050
10/640
10/695
10/740
15/790
1. Values are without filter box. External Static Pressure = filter pressure drop + other static drops.
2. Source: DPN000695, Rev. 0
16.2
Table 60
Model
PD-133
PD-150
PD-223
PD-290
PD-333
Drycooler
Standard Pump Package
Total Unit
Pump Only
Drycooler - Optional
Pump Package
Total Unit
Pump
Only
Total Unit
Voltage
Blower
Motor hp
FLA
WSA
OPD
hp
FLA
FLA
WSA
OPD
hp
FLA
WSA
OPD
208
10.6
13.3
20
1.5
6.6
17.2
19.9
30
18.1
20.8
30
230
9.6
12.0
20
1.5
6.0
15.6
18
25
16.4
18.8
25
460
4.8
6.0
15
1.5
3.0
7.8
15
8.2
9.4
15
575
3.9
4.9
15
1.5
2.4
6.3
7.3
15
6.6
7.6
15
208
10.6
13.3
20
7.5
18.1
20.8
30
21.2
23.9
30
230
9.6
12.0
20
6.8
16.4
18.8
25
19.2
21.6
30
460
4.8
6.0
15
3.4
8.2
9.4
15
9.6
10.8
15
575
3.9
4.9
15
2.7
6.6
7.6
15
7.8
8.8
15
208
7.5
24.2
30.3
50
10.6
34.8
40.9
60
40.9
47
70
230
7.5
22.0
27.5
45
9.6
31.6
37.1
50
37.2
42.7
60
460
7.5
11.0
13.8
20
4.8
15.8
18.6
25
18.6
21.4
30
575
7.5
9.0
11.3
20
3.9
12.9
15.2
20
15.1
17.4
25
208
7.5
24.2
30.3
50
10.6
40.9
47
60
34.8
40.9
60
230
7.5
22.0
27.5
45
9.6
37.2
42.7
30
31.6
37.1
50
460
7.5
11.0
13.8
20
4.8
18.6
21.4
25
15.8
18.6
25
575
7.5
9.0
11.3
20
3.9
15.1
17.4
20
12.9
15.2
20
208
10
30.8
38.5
60
10.6
47.5
55.2
80
41.4
49.1
70
230
10
28.0
35.0
60
9.6
43.2
50.2
70
37.6
44.6
70
460
10
14.0
17.5
30
4.8
21.6
25.1
35
18.8
22.3
35
575
10
11.0
13.8
20
3.9
17.1
19.9
30
14.9
17.7
25
ph = phase; FLA = Full Load Amps; WSA = Wire Size Amp; OPD = Maximum Overcurrent Protection Device
Source: DPN000710, Rev. 0
157
Liebert DS
16.3
J
R
Overall
Optional Fan
Discharge
sions
Dimen
Over
all Dim
ensio
ns
Disconnect
Switch
H
J
35-1/8"
(892mm)
72"
(1829mm)
Fan Discharge
Shaded areas indicate
a recommended
clearance of 34" (864mm)
for component access.
5"
(127mm)
1"
(25.4mm)
C
Unit Base
10"
(254mm)
Drain Outlet
Opening
UNIT DIMENSIONS
FAN DISCHARGE DATA
REAR DISCHARGE
OPTIONAL TOP DISCHARGE
15-7/16"
(392mm)
Floor Level
Rear of
Cabinet
DPN000710
Rev. 2
Table 61
A
Unit Base
PD-133
72
(1829)
74
(1880)
31
(787)
32
(813)
1-1/8
(29)
33
(838)
60
(1524)
8-5/8
(219)
50-3/16
(1275)
16-1/16
(408)
13-3/16
(335)
14-11/16
(373)
PD-150
72
(1829)
74
(1880)
31
(787)
32
(813)
1-1/8
(29)
33
(838)
60
(1524)
8-5/8
(219)
50-3/16
(1275)
16-1/16
(408)
13-3/16
(335)
14-11/16
(373)
PD-223
97
(2464)
99
(2515)
33
(838)
34
(864)
3-1/8
(79)
46-1/2
(1181)
85
(2159)
23-5/16
(592)
50-3/16
(1275)
16-1/16
(408)
23-1/2
(597)
14-11/16
(373)
PD-290
97
(2464)
99
(2515)
33
(838)
34
(864)
3-1/8
(79)
46-1/2
(1181)
85
(2159)
23-5/16
(592)
50-3/16
(1275)
16-1/16
(408)
23-1/2
(597)
14-11/16
(373)
PD-333
97
(2464)
99
(2515)
33
(838)
34
(864)
3-1/8
(79)
46-1/2
(1181)
85
(2159)
16-5/16
(421)
63-7/8
(1622)
19-1/8
(486)
16-13/16
(427)
11-5/8
(295)
Model
1. A 1" (25.4mm) flange is provided on all units for duct connection to coil duct opening and fan air discharge opening.
2. Source: DPN000710, Rev. 1
Liebert DS
158
16.4
Piping
See
Note 4
See
Note 4
See
Note 1
See
Note 1
See Note 2
1-13/16"
(46mm)
1-13/16"
(46mm)
See Note 2
3" (76mm)
See Note 1
See Note 4
3" (76mm)
1" (25mm)
Panel
3" (76mm)
See Note 1
3" (76mm)
See Note 4
1" (25mm)
Panel
3" (76mm)
3" (76mm)
C See Note 2
12-5/8"
(321mm)
12-5/8"
(321mm)
4-1/2"
(114mm)
9-11/16"
(246mm)
See Note 2
4-1/2"
(114mm)
9-11/16"
(246mm)
7-7/8"
(200mm)
7-7/8"
(200mm)
MODEL PD-333
5-1/2" (140mm) See Note 1
3-1/4" (85mm)
See Note 4
Drain Outlet
Location
1-1/4" (32mm) F.P.T.
3"
(76mm)
See
Note 2
NOTES
1. Multiple knockouts of 1-3/8" (35mm), 1-3/4" (45mm) and
2-1/2" (64mm) for main power supply (typical).
2. Cover plate for access of glycol piping inlet and outlet.
3. Piggyback drycooler connection sizes for supply and return
glycol lines are the same as room unit supply and return lines.
FE/FH 110G 1-5/8" (41mm); FE/FH116G - 2-1/8" (54mm).
Note applies to PD-133.
4. 7/8" (22.2mm) knockout provided.
Table 62
Model #
6" (1
52m
3" (7
1-1/2
6mm
" (38
m)
8"
(203mm)
mm)
ALL MODELS
DPN000711
Rev. 1
Table 63
Drain
PD-133 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730)
PD-133
See Note 3
PD-150 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730)
PD-150
2-1/8 (54)
2-1/8 (54)
1-1/4 (32)
PD-223 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730)
PD-223
2-1/8 (54)
2-1/8 (54)
1-1/4 (32)
PD-290 27-1/4 (692) 2-1/2 (64) 6 (152) 9-1/8 (232) 28-3/4 (730)
PD-290
2-1/8 (54)
2-1/8 (54)
1-1/4 (32)
PD-333
2-1/8 (54)
2-1/8 (54)
1-1/4 (32)
6 (152)
24 (610)
159
Liebert DS
2
1
3
19"
(482.6mm)
2-7/8"
(72.9mm)
15-7/8"
(403.2mm)
1-3/4"
(44.4mm)
6-3/8"
(161.9mm)
8-3/4"
(222.3mm)
12-1/4"
(311.1mm)
30"
(762mm)
17"
(431.8mm)
3/4"
(19mm)
C
DPN000278
Rev. 0
Table 64
15-1/4 (387.4)
2-1/2 (63.5)
22-1/2 (571.5)
30-1/4 (768.4)
2-1/2 (63.5)
22-1/2 (571.5)
Dual (7.5hp)
39-5/16 (998.5)
1-3/4 (44.5)
26-7/8 (682.6)
Pump Package
Liebert DS
160
32-1/4"
(819.2mm)
1
2
1
3
15-7/8"
(403.2mm)
4-1/8"
(104.8mm)
6-3/8"
(161.9mm) "
2-7/8"
(73mm)
8-3/4" (222.2mm)
19"
(482.6mm)
1-3/4"
(44.4mm)
12-1/4"
(311.1mm)
30"
(762mm)
23-3/4"
(603.2mm)
27-1/4"
(692.1mm)
32"
(812.8mm)
3
5
41-1/4"
(1047.8mm)
6
5
6
19-15/16
(506.4mm)
11-7/8
(301.6mm)
15-7/8
(403.2mm)
33-3/16"
(843mm)
16-3/8"
(415.9mm)
29-3/16"
(741.4mm)
6-1/2"
(165.1mm)
41"
(1041.4mm)
161
DPN000328
Rev. 0
Liebert DS
30-1/2"
(774.7mm)
9"
(228.6mm)
1/2" F.P.T.
Fitting
2-3/4"
(69.9mm)
2-1/2"
(63.5mm)
1"
(25.4mm)
1-1/2"
(38.1mm)
6-13/16"
(173mm)
1/2" F.P.T.
Fitting
17-1/4"
(438.2mm)
7"
(177.8mm)
4"
(101.6mm)
1"
(25.4mm)
1/2" (12.7mm)
8 Holes
1-1/2"
(38.1mm)
6-1/8"
(155.6mm)
3"
(76.2mm)
DPN000329
Rev. 0
Electric @ 60Hz
Pump
HP
NPT Suction
Connection
Female
Discharge
Connection
ph
208 FLA
230 FLA
460 FLA
575 FLA
3/4
1-1/4"
3/4"
7.6
6.9
N/A
N/A
3/4
1-1/4"
3/4"
3.5
3.2
1.6
1.3
1-1/2
1-1/4"
3/4"
6.6
6.0
3.0
2.4
1-1/4"
3/4"
7.5
6.8
3.4
2.7
1-1/2"
1"
10.6
9.6
4.8
3.9
1-1/2"
1-1/4"
16.7
15.2
7.6
6.1
7-1/2 *
3"
3"
24.2
22.0
11.0
9.0
* May require electrical component(s) with higher capacity in the drycooler. Consult factory representative
for assistance before ordering.
Liebert DS
162
180
Curve
A
B
C
D
E
F
160
140
F
120
D
100
80
60
HP
3/4 (1-ph)
3/4 (3-ph)
1.5
2
3
5
7.5
C
B
A
40
20
0
10
20
30
40
50
60
70
80
120
160
200
250
300
400
163
Liebert DS
Basic Model
Number
Airflow
Configuration
DS028AD*0*
DS028AD*1*
Btu/hr
kW
Btu/hr
kW
CFM
SCOP
Downflow
104499
30.63
94171
27.60
4210
2.42
Downflow
106548
31.23
96218
28.20
4199
2.62
DS028AS*0*
Downflow
104158
30.53
93830
27.50
4210
2.6
DS028AS*1*
Downflow
106207
31.13
95877
28.10
4199
2.83
DS028AU*0*
Downflow
124306
36.43
103725
30.40
4210
2.37
DS028AU*1*
Downflow
126697
37.13
106113
31.10
4199
2.54
DS028DD*0*
Downflow
103816
30.43
93489
27.40
4210
2.36
DS028DD*1*
Downflow
105865
31.03
95536
28.00
4199
2.56
DS028DU*0*
Downflow
123623
36.23
103384
30.30
4210
2.32
DS028DU*1*
Downflow
126014
36.93
105431
30.90
4199
2.48
DS035AD*0*
Downflow
119184
34.93
107137
31.40
4976
2.24
DS035AD*1*
Downflow
122940
36.03
110549
32.40
4976
2.5
DS035AS*0*
Downflow
123623
36.23
109184
32.00
4976
2.38
DS035AS*1*
Downflow
127038
37.23
112596
33.00
4976
2.66
DS035AU*0*
Downflow
124989
36.63
109866
32.20
4976
2.33
DS035AU*1*
Downflow
128746
37.73
113620
33.30
4976
2.59
DS035DD*0*
Downflow
118501
34.73
106113
31.10
4976
2.18
DS035DD*1*
Downflow
121916
35.73
109525
32.10
4976
2.42
DS035DU*0*
Downflow
123965
36.33
108843
31.90
4976
2.26
DS035DU*1*
Downflow
127721
37.43
112596
33.00
4976
2.51
DS042AD*1*
Downflow
138649
40.64
125220
36.70
5957
2.32
DS042AS*0*
Downflow
133185
39.03
120102
35.20
6029
2.1
DS042AS*1*
Downflow
139674
40.94
125903
36.90
5957
2.46
DS042AU*1*
Downflow
146504
42.94
129315
37.90
5957
2.35
DS042DD*1*
Downflow
136942
40.14
124538
36.50
6053
2.22
DS042DU*1*
Downflow
145138
42.54
128632
37.70
6053
2.26
DS053AD*0*
Downflow
184069
53.95
166506
48.80
7177
2.49
DS053AD*1*
Downflow
187484
54.95
173671
50.90
7714
2.63
DS053AS*0*
Downflow
190557
55.85
169918
49.80
7177
2.5
DS053AS*1*
Downflow
193972
56.85
177083
51.90
7714
2.63
DS053AU*0*
Downflow
182020
53.35
165482
48.50
7177
2.54
DS053AU*1*
Downflow
185435
54.35
172306
50.50
7714
2.68
DS053DD*0*
Downflow
182361
53.45
164800
48.30
7177
2.41
DS053DD*1*
Downflow
185776
54.45
171965
50.40
7714
2.54
DS053DU*0*
Downflow
180312
52.85
163776
48.00
7177
2.46
DS053DU*1*
Downflow
183727
53.85
170600
50.00
7714
2.59
DS070AD*0*
Downflow
227098
66.56
198237
58.10
8613
2.16
DS070AD*1*
Downflow
231537
67.86
207450
60.80
9277
2.3
DS070AS*0*
Downflow
231879
67.96
200626
58.80
8613
2.18
DS070AS*1*
Downflow
236318
69.26
209497
61.40
9277
2.32
Liebert DS
164
Table 66
Basic Model
Number
Airflow
Configuration
DS070AU*0*
DS070AU*1*
Btu/hr
kW
Btu/hr
kW
CFM
SCOP
Downflow
216853
63.56
193460
56.70
8613
2.27
Downflow
221634
64.96
202332
59.30
9277
2.43
DS070DD*0*
Downflow
224707
65.86
195849
57.40
8613
2.1
DS070DD*1*
Downflow
228805
67.06
204720
60.00
9277
2.21
DS070DU*0*
Downflow
214462
62.86
190731
55.90
8613
2.18
DS070DU*1*
Downflow
218902
64.16
199943
58.60
9277
2.32
DS077AS*1*
Downflow
252710
74.07
226216
66.30
10644
2.1
DS077AU*1*
Downflow
243490
71.36
221780
65.00
10644
2.15
DS077DU*1*
Downflow
241099
70.66
215638
63.20
10063
2.1
DS105AS*1*
Downflow
328182
96.18
276372
81.00
13111
1.92
DS105AU*1*
Downflow
326474
95.68
283878
83.20
13111
1.9
DS105DU*1*
Downflow
322035
94.38
270572
79.30
13087
1.9
VS028AD*0*
Upflow
105524
30.93
95195
27.90
4210
2.35
VS028AD*1*
Upflow
106548
31.23
96218
28.20
4210
2.45
VS028AS*0*
Upflow
104499
30.63
94854
27.80
4210
2.52
VS028AS*1*
Upflow
105865
31.03
95877
28.10
4210
2.63
VS028AU*0*
Upflow
125672
36.83
105090
30.80
4210
2.31
VS028AU*1*
Upflow
126697
37.13
106113
31.10
4210
2.4
VS028DD*0*
Upflow
104841
30.73
94854
27.80
4210
2.32
VS028DD*1*
Upflow
106207
31.13
95877
28.10
4210
2.42
VS028DU*0*
Upflow
125331
36.73
104748
30.70
4210
2.29
VS028DU*1*
Upflow
126355
37.03
105772
31.00
4210
2.37
VS035AD*0*
Upflow
120550
35.33
108843
31.90
4976
2.21
VS035AD*1*
Upflow
122599
35.93
110890
32.50
4976
2.35
VS035AS*0*
Upflow
127721
37.43
103042
30.20
4976
2.17
VS035AS*1*
Upflow
126697
37.13
112937
33.10
4976
2.49
VS035AU*0*
Upflow
126697
37.13
111914
32.80
4976
2.3
VS035AU*1*
Upflow
128746
37.73
113961
33.40
4976
2.44
VS035DD*0*
Upflow
119867
35.13
110208
32.30
5263
2.16
VS035DD*1*
Upflow
121916
35.73
110208
32.30
4976
2.31
VS035DU*0*
Upflow
126014
36.93
113278
33.20
5263
2.24
VS035DU*1*
Upflow
128063
37.53
113278
33.20
4976
2.4
VS042AD*0*
Upflow
135234
39.63
122491
35.90
5933
2.01
VS042AD*1*
Upflow
138649
40.64
125903
36.90
5933
2.19
VS042AS*0*
Upflow
135917
39.83
122832
36.00
5933
2.13
VS042AS*1*
Upflow
139332
40.84
126244
37.00
5933
2.33
VS042AU*0*
Upflow
143430
42.04
126585
37.10
5933
2.05
VS042AU*1*
Upflow
146845
43.04
129997
38.10
5933
2.23
VS042DD*0*
Upflow
130795
38.33
121808
35.70
6029
1.99
VS042DD*1*
Upflow
137625
40.34
125220
36.70
5933
2.15
VS042DU*0*
Upflow
142747
41.84
125903
36.90
5933
2.01
VS042DU*1*
Upflow
145821
42.74
129315
37.90
5933
2.18
165
Liebert DS
Table 66
Basic Model
Number
Airflow
Configuration
VS053AD*0*
VS053AD*1*
Btu/hr
kW
Btu/hr
kW
CFM
SCOP
Upflow
186118
54.55
172988
50.70
7656
2.45
Upflow
186801
54.75
173671
50.90
7656
2.47
VS053AS*0*
Upflow
192606
56.45
176400
51.70
7656
2.45
VS053AS*1*
Upflow
193289
56.65
177083
51.90
7656
2.48
VS053AU*0*
Upflow
184410
54.05
171965
50.40
7656
2.49
VS053AU*1*
Upflow
184752
54.15
172647
50.60
7656
2.52
VS053DD*0*
Upflow
184752
54.15
171624
50.30
7656
2.37
VS053DD*1*
Upflow
185776
54.45
171624
50.30
7656
2.47
VS053DU*0*
Upflow
182703
53.55
170600
50.00
7656
2.41
VS053DU*1*
Upflow
184069
53.95
172647
50.60
7656
2.43
VS070AD*0*
Upflow
230513
67.56
207450
60.80
9187
2.16
VS070AD*1*
Upflow
231537
67.86
208473
61.10
9187
2.2
VS070AS*0*
Upflow
235635
69.06
209838
61.50
9187
2.18
VS070AS*1*
Upflow
236660
69.36
210862
61.80
9187
2.21
VS070AU*0*
Upflow
220609
64.66
202332
59.30
9187
2.26
VS070AU*1*
Upflow
221634
64.96
203355
59.60
9187
2.3
VS070DD*0*
Upflow
229147
67.16
205744
60.30
9187
2.11
VS070DD*1*
Upflow
230171
67.46
206767
60.60
9187
2.15
VS070DU*0*
Upflow
219243
64.26
200967
58.90
9187
2.21
VS070DU*1*
Upflow
220268
64.56
201990
59.20
9187
2.25
VS077AS*0*
Upflow
253052
74.17
223486
65.50
9953
1.99
VS077AS*1*
Upflow
254076
74.47
224510
65.80
9953
2.02
VS077AU*0*
Upflow
243490
71.36
219050
64.20
9953
2.05
VS077AU*1*
Upflow
244514
71.66
220210
64.54
9953
2.08
VS077DU*0*
Upflow
241441
70.76
217003
63.60
9953
VS077DU*1*
Upflow
243148
71.26
215980
63.30
9570
2.05
VS105AS*0*
Upflow
328865
96.38
277054
81.20
13111
1.84
VS105AS*1*
Upflow
329548
96.58
275007
80.60
12633
1.87
VS105AU*0*
Upflow
326474
95.68
276031
80.90
13111
1.81
VS105AU*1*
Upflow
324425
95.08
273984
80.30
12633
1.84
VS105DU*0*
Upflow
322376
94.48
272278
79.80
13111
1.79
VS105DU*1*
Upflow
325108
95.28
269548
79.00
12250
1.81
Liebert DS
166
Table 67
Basic Model
Number
Airflow
Configuration
DS028WD*0*
DS028WD*1*
Btu/hr
kW
Btu/hr
kW
CFM
SCOP
Downflow
107914
31.63
97583.2
28.60
4210
Downflow
111329
32.63
99971.6
29.30
4210
3.29
DS028WS*0*
Downflow
106889.5
31.33
96559.6
28.30
4210
3.25
DS028WS*1*
Downflow
108938.5
31.93
98948
29.00
4210
3.59
DS028WU*0*
Downflow
129087
37.83
107478
31.50
4210
2.89
DS028WU*1*
Downflow
131477.5
38.53
109866.4
32.20
4210
3.14
DS035WD*0*
Downflow
127038
37.23
112596
33.00
4926
2.63
DS035WD*1*
Downflow
130453
38.23
116008
34.00
4926
2.96
DS035WS*0*
Downflow
122940
36.03
110548.8
32.40
4926
2.83
DS035WS*1*
Downflow
126355
37.03
113960.8
33.40
4926
3.22
DS035WU*0*
Downflow
130453
38.23
114302
33.50
4926
2.83
DS035WU*1*
Downflow
134209.5
39.33
118055.2
34.60
4926
3.2
DS042WD*1*
Downflow
147869.5
43.34
132044.4
38.70
5850
2.83
DS042WS*0*
Downflow
140015
41.04
125902.8
36.90
5950
2.52
DS042WS*1*
Downflow
131477.5
38.53
131362
38.50
5850
3.02
DS042WU*0*
Downflow
150943
44.24
129997.2
38.10
6054
2.5
DS042WU*1*
Downflow
155041
45.44
135456.4
39.70
5850
2.84
DS053WD*0*
Downflow
201826.5
59.15
172647.2
50.60
7177
3.19
DS053WD*1*
Downflow
205241.5
60.15
179471.2
52.60
7714
3.38
DS053WS*0*
Downflow
203875.5
59.75
173670.8
50.90
7177
3.19
DS053WS*1*
Downflow
207290.5
60.75
180494.8
52.90
7714
3.38
DS053WU*0*
Downflow
196704
57.65
170258.8
49.90
7177
3.18
DS053WU*1*
Downflow
200460.5
58.75
177082.8
51.90
7714
3.37
DS070WD*0*
Downflow
246904.5
72.36
205402.4
60.20
8613
2.74
DS070WD*1*
Downflow
252027
73.86
214273.6
62.80
9277
2.92
DS070WS*0*
Downflow
250319.5
73.36
207108.4
60.70
8613
2.75
DS070WS*1*
Downflow
255442
74.87
215979.6
63.30
9277
2.94
DS070WU*0*
Downflow
238025.5
69.76
201308
59.00
8613
2.77
DS070WU*1*
Downflow
243148
71.26
209838
61.50
9277
2.96
DS077WS*0*
Downflow
273883
80.27
225192
66.00
10500
2.5
DS077WS*1*
Downflow
263638
77.27
235428
69.00
10644
2.67
DS077WU*0*
Downflow
266711.5
78.17
221780
65.00
10500
2.5
DS077WU*1*
Downflow
270126.5
79.17
232016
68.00
10644
2.65
DS105WS*1*
Downflow
349013
102.29
288314
84.50
12890
2.43
DS105WU*1*
Downflow
353111
103.49
287972.8
84.40
13000
2.4
VS028WD*0*
Upflow
108597
31.83
97242
28.50
4297
2.856
VS028WD*1*
Upflow
109621.5
32.13
98265.6
28.80
4297
2.99
VS028WS*0*
Upflow
106206.5
31.13
96218.4
28.20
4297
3.092
VS028WS*1*
Upflow
107572.5
31.53
97242
28.50
4297
3.24
VS028WU*0*
Upflow
129087
37.83
107478
31.50
4297
2.78
VS028WU*1*
Upflow
130453
38.23
108501.6
31.80
4297
2.89
VS035WD*0*
Upflow
127038
37.23
112937.2
33.10
5078
2.556
167
Liebert DS
Table 67
Basic Model
Number
Airflow
Configuration
kW
kW
CFM
SCOP
VS035WD*1*
Upflow
129087
37.83
114643.2
33.60
5078
2.72
VS035WS*0*
Upflow
122940
36.03
110548.8
32.40
5078
2.85
VS035WS*1*
Upflow
124989
36.63
112596
33.00
5078
2.94
VS035WU*0*
Upflow
130794.5
38.33
114643.2
33.60
5078
2.75
VS035WU*1*
Upflow
132843.5
38.93
116349.2
34.10
5078
2.93
VS042WD*0*
Upflow
142747
41.84
127267.6
37.30
6054
2.386
VS042WD*1*
Upflow
146162
42.84
130679.6
38.30
6054
2.62
VS042WS*0*
Upflow
126696.5
37.13
126585.2
37.10
6054
2.526
VS042WS*1*
Upflow
144796
42.44
129656
38.00
6054
2.78
VS042WU*0*
Upflow
150260
44.04
130679.6
38.30
6054
2.41
VS042WU*1*
Upflow
153675
45.04
134091.6
39.30
6054
2.64
VS053WD*0*
Upflow
202851
59.45
177082.8
51.90
7812
3.07
VS053WD*1*
Upflow
203534
59.65
177424
52.00
7812
3.11
VS053WS*0*
Upflow
204558.5
59.95
177765.2
52.10
7812
3.066
VS053WS*1*
Upflow
205241.5
60.15
178106.4
52.20
7812
3.1
VS053WU*0*
Upflow
197728.5
57.95
174353.2
51.10
7812
3.05
VS053WU*1*
Upflow
198411.5
58.15
174694.4
51.20
7812
3.09
VS070WD*0*
Upflow
249295
73.06
211544
62.00
9374
2.69
VS070WD*1*
Upflow
250319.5
73.36
212226.4
62.20
9374
2.73
VS070WS*0*
Upflow
252368.5
73.96
213250
62.50
9374
2.7
VS070WS*1*
Upflow
253734.5
74.37
213932.4
62.70
9374
2.74
VS070WU*0*
Upflow
240416
70.46
207108.4
60.70
9374
2.71
VS070WU*1*
Upflow
241440.5
70.76
207790.8
60.90
9374
2.76
VS077WS*0*
Upflow
274566
80.47
228945.2
67.10
10156
2.51
VS077WS*1*
Upflow
276273.5
80.97
229968.8
67.40
10156
2.56
VS077WU*0*
Upflow
267394.5
78.37
225533.2
66.10
10156
2.49
VS077WU*1*
Upflow
268760.5
78.77
226215.6
66.30
10156
2.53
VS105WS*0*
Upflow
348330
102.09
286266.8
83.90
12890
2.29
VS105WS*1*
Upflow
349013
102.29
283537.2
83.10
12890
2.32
VS105WU*0*
Upflow
345256.5
101.19
285925.6
83.80
12500
2.29
VS105WU*1*
Upflow
345256.5
101.19
282854.8
82.90
12500
2.29
Liebert DS
168
Table 68
U.S. DOE performance tableLiebert DS upflow and downflow, water-cooled with a fluid
economizer
Basic Model
Number
Airflow
Configuration
VS028*U*1*
VS028*U*0*
VS028*D*1*
VS028*D*0*
Btu/hr
kW
Btu/hr
kW
CFM
SCOP
Upflow
130111.5
38.13
108160.4
31.70
4297
2.86
Upflow
128745.5
37.73
107136.8
31.40
4297
2.75
Upflow
109280
32.03
97924.4
28.70
4297
2.94
Upflow
108255.5
31.73
96900.8
28.40
4297
2.82
VS035*U*1*
Upflow
132160.5
38.73
116008
34.00
5078
2.88
VS035*U*0*
Upflow
130111.5
38.13
114302
33.50
5078
2.71
VS035*D*1*
Upflow
129087
37.83
113960.8
33.40
5078
2.67
VS035*D*0*
Upflow
126355
37.03
112254.8
32.90
5078
2.52
VS042*U*1*
Upflow
152650.5
44.74
133068
39.00
6054
2.56
VS042*U*0*
Upflow
149577
43.84
129997.2
38.10
6054
2.37
VS042*D*1*
Upflow
145137.5
42.54
129314.8
37.90
6054
2.54
VS042*D*0*
Upflow
142064
41.64
126585.2
37.10
6054
2.34
VS053*U*1*
Upflow
197728.5
57.95
174012
51.00
7812
3.02
VS053*U*0*
Upflow
195679.5
57.35
172306
50.50
7812
2.91
VS053*D*1*
Upflow
202509.5
59.35
176400.4
51.70
7812
3.05
VS053*D*0*
Upflow
200802
58.85
175035.6
51.30
7812
2.93
VS070*U*1*
Upflow
240074.5
70.36
206426
60.50
9374
2.68
VS070*U*0*
Upflow
238708.5
69.96
205743.6
60.30
9374
2.64
VS070*D*1*
Upflow
248953.5
72.96
210861.6
61.80
9374
2.66
VS070*D*0*
Upflow
247587.5
72.56
210179.2
61.60
9374
2.62
VS077*U*1*
Upflow
266370
78.07
222121.2
65.10
9765
2.49
VS077*U*0*
Upflow
265345.5
77.77
223486
65.50
9765
2.42
VS105*U*1*
Upflow
345256.5
101.19
278419.2
81.60
12500
2.24
DS028*U*1*
Downflow
130794.5
38.33
109184
32.00
4210
3.06
DS028*U*0*
Downflow
128404
37.63
106795.6
31.30
4210
2.82
DS028*D*1*
Downflow
110646
32.43
99289.2
29.10
4210
3.2
DS028*D*0*
Downflow
108255.5
31.73
96900.8
28.40
4210
2.92
DS035*U*1*
Downflow
133185
39.03
117031.6
34.30
4976
3.09
DS035*U*0*
Downflow
129428.5
37.93
113278.4
33.20
4976
2.74
DS035*D*1*
Downflow
129428.5
37.93
115325.6
33.80
4976
2.86
DS035*D*0*
Downflow
126013.5
36.93
111572.4
32.70
4976
2.55
DS042*U*1*
Downflow
153675
45.04
134774
39.50
5957
2.72
DS042*D*1*
Downflow
146162
42.84
131362
38.50
5957
2.7
DS053*U*1*
Downflow
198753
58.25
175376.8
51.40
7714
3.23
DS053*U*0*
Downflow
195338
57.25
168552.8
49.40
7177
3.06
DS053*D*1*
Downflow
203534
59.65
177765.2
52.10
7714
3.25
DS053*D*0*
Downflow
200119
58.65
170941.2
50.10
7177
3.07
DS070*U*1*
Downflow
240416
70.46
207449.6
60.80
9277
2.82
DS070*U*0*
Downflow
235635
69.06
198578.4
58.20
8613
2.65
DS070*D*1*
Downflow
249295
73.06
211544
62.00
9277
2.79
DS070*D*0*
Downflow
244514
71.66
203014
59.50
8613
2.62
DS077*U*1*
Downflow
266711.5
78.17
224850.8
65.90
9998
2.56
169
Liebert DS
Guide Specifications
GENERAL
1.1
SUMMARY
These specifications describe requirements for a Mission Critical Cooling system. The system shall be
designed to control temperature and humidity conditions in rooms containing electronic equipment,
with good insulation and vapor barrier. The manufacturer shall design and furnish all equipment to
be fully compatible with heat dissipation requirements of the room.
1.2
DESIGN REQUIREMENTS
The Mission Critical Cooling system shall be a Liebert self-contained, factory-assembled unit with
(upflow) (downflow) air delivery. The system shall have a net total cooling capacity of ____ BTUH
(kW) with a net sensible cooling capacity of ____ BTUH (kW) based on an entering air temperature of
____ F (C) dry bulb and ____ F (C) wet bulb. The unit shall be supplied with ____ volt ____ ph
____ Hz electrical service. Net capacities shall include losses due to fan motor heat. The system
cooling capacity shall be factory-certified per ASHRAE127-2007.
1.3
SUBMITTALS
Submittals shall be provided after the agreement of the proposal and shall include: Single-Line
Diagrams; Dimensional, Electrical and Capacity Data; Piping and Electrical Connection Drawings.
2.0
PRODUCT
2.1
FRAME
The frame shall be MIG welded, formed sheet metal. It shall be protected against corrosion using the
autophoretic coating process. The frame shall be capable of being separated into three parts in the
field to accommodate rigging through small spaces.
2.1.1
Downflow Configurations
2.1.2
Upflow Supply
Liebert DS
170
Guide Specifications
2.1.3
Exterior Panels
The exterior panels shall be insulated with a minimum 1 in. (25mm), 1.5 lb. (0.68 kg) density fiber
insulation. The main front panel shall have captive 1/4 turn fasteners. The main unit color shall be
______.
2.2
FILTERS
The filter chamber shall be located within the cabinet, and filters shall be removable from the top of
the unit.
2.2.1
2.2.1
2.2.2
2.3
FAN SECTION
2.3.1
171
Liebert DS
Guide Specifications
2.3.1.1 Motor
The fan motor shall be ____ hp (kW) at 1750 rpm @ 60Hz (1450 rpm @50Hz), mounted to an
automatic, spring-tensioning base. The motor shall be removable from the front of the cabinet.
2.3.2
Drive Package
The motor sheave and fan pulley shall be double-width fixed pitch. Two belts, sized for 200% of the
fan motor horsepower shall be provided with the drive package. An auto-tension system shall provide
constant tension on the belts. Belts, shaft, blower bearings, sheave and pulley shall be warranted for
five years (parts only).
2.4
HUMIDIFIER
A humidifier shall be factory-installed inside the unit. Bypass air slots shall be included to enable
moisture to be absorbed into the air stream. The humidifier capacity shall be ____lb./hr (kg/hr). The
humidifier shall be removable from the front of the cabinet.
2.4.1
Infrared Humidifier
The humidifier shall be of the infrared type, consisting of high-intensity quartz lamps mounted above
and out of the water supply. The humidifier pan shall be stainless steel and arranged to be removable
without disconnecting high-voltage electrical connections. The complete humidifier section shall be
pre-piped, ready for field connection to the water supply. The humidifier shall be equipped with an
automatic water supply system and shall have an adjustable water-overfeed to prevent mineral
precipitation. A high-water detector shall shut down the humidifier to prevent overflowing. A factoryprovided air-gap shall prevent backflow of the humidifier supply water.
2.4.1
2.5
REHEAT
The environmental control unit shall include a factory-installed reheat to control temperature during
dehumidification.
2.5.1
Liebert DS
172
Guide Specifications
2.5.1
2.5.1
2.6
2.6.1
2.6.1
2.6.1
Scroll Compressors
The compressor shall be scroll-type. The compressor shall be suction gas cooled motor, vibration
isolators, thermal overloads, automatic reset high pressure switch with lockout after three failures,
rotalock service valves, pump down low pressure transducer, suction line strainer and a maximum
operating speed of 3500 RPM.
2.6.2
Evaporator Coil
The evaporator coil shall be A-frame design with offset orientation and have ____sq. ft. (m2) face area,
three rows deep. It shall be constructed of rifled copper tubes and aluminum fins and shall have a
maximum face velocity of ____ ft. per minute (m/s) at ____ CFM (m3). A stainless steel condensate
drain pan shall be provided.
173
Liebert DS
Guide Specifications
2.6.3
Dual-Cooling Source
The dual-cooling source system shall consist of an air-cooled or water-cooled compressorized system
with the addition of a chilled water coil (Liebert Econ-O-Coil), a modulating control valve and a
comparative temperature sensor. The system shall be able to function either as a modulating chilled
water system or as a compressorized system, or a combination of both. The primary cooling mode
shall be chilled water. Switchover between the two cooling modes shall be performed automatically by
the microprocessor control. Four (4) pipes shall be included on water/glycol systems: Liebert Econ-OCoil supply, Liebert Econ-O-Coil return, condenser supply and condenser return.
2.6.4
2.6.5
A 70/30 Cu-Ni Liebert Econ-O-Coil shall be provided on dual-cooling units that are connected to a
cooling tower loop or other open water system. This option shall be required on open cooling tower
applications.
2.6.6
The coil shall be coated with a high performance polymeric coating process to provide corrosion
resistance within 2 to 12 pH range.
2.6.7
R-407C Refrigerant
The system shall be designed for use with R-407C refrigerant, which meets the EPA clean air act for
phase-out of HCFC refrigerants.
Liebert DS
174
Guide Specifications
3.0
CONTROLS
3.1
175
Liebert DS
Guide Specifications
The Service screen shall be designed for service personnel and shall provide access to advanced
control setup features and diagnostic information.
Sensor Calibration - The menus shall allow unit sensors to be calibrated with external
sensors.
Maintenance/Wellness Settings - The menus shall allow reporting of potential component
problems before they occur.
Options Setup - The menus shall provide operation settings for the installed components.
Auxiliary Boards - The menus shall allow setup of optional expansion boards.
Various Sensors: The menus shall allow setup and display of optional custom sensors. The
control shall include four customer accessible analog inputs for field-supplied sensors. The analog
inputs shall accept a 4 to 20mA signal. The user shall be able to change the input to 0 to 5VDC or
0 to 10VDC. The gains for each analog input shall be programmable from the front display. The
analog inputs shall be able to be monitored from the front display.
Diagnostics/Service Mode - The Liebert iCOM control shall be provided with self-diagnostics
to aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not
pass. Control inputs shall be indicated as On or Off at the front display. Control outputs shall be
able to be turned On or Off from the front display without using jumpers or a service terminal.
Each control output shall be indicated by an LED on a circuit board.
3.2
ALARMS
All unit alarms shall be annunciated through both audio and visual cues, clearly displayed on the
screen, automatically recorded in the event log and communicated to the customers Building
Management System/Building Automation System. The Liebert iCOM control shall activate an
audible and visual alarm in event of any of the following conditions:
High Temperature
Low Temperature
High Humidity
Low Humidity
EC Fan Fault
Change Filters
Loss of Air Flow
Loss of Power
Compressor Overload (Optional)
Humidifier Problem
High Head Pressure
Low Suction Pressure
Custom Alarms
Custom alarm inputs shall be provided to indicate facility-specific events. Custom alarms can be
identified with programmable labels. Frequently used alarm inputs include:
Leak Under Floor
Smoke Detected
Standby Unit On
Each alarm (unit and custom) shall be separately enabled or disabled, selected to activate the
common alarm and programmed for a time delay of 0 to 255 seconds.
Liebert DS
176
Guide Specifications
3.3
3.3.1
3.3.2
Temperature Compensation
The Liebert iCOM shall be able to adjust the capacity output based on supply and return temperature
conditions to meet SLA guidelines while operating to highest efficiency.
3.3.3
Humidity Control
Dew point and relative humidity control methods shall be available (based on user preference) for
humidity control within the conditioned space.
3.4
MULTI-UNIT COORDINATION
Liebert iCOM teamwork shall save energy by preventing multiple units in an area from operating in
opposing modes. Teamwork allows the control to optimize a group of connected cooling units equipped
with Liebert iCOM using the U2U (Unit-to-Unit) network. There shall be three modes of teamwork
operation:
Teamwork Mode 1: Is best in small rooms with balanced heat loads. The controlling
temperature and humidity sensor readings of all units in operation (fan On) are collected to be
used for an average or worst-case sensor reading (user-selectable). The master unit shall send the
operating requirements to all operating units in the group. The control band (temperature, fan
and humidity) is divided and shared among the units in the group.
Teamwork Mode 2: The Liebert iCOM calculates the worse-case demand for heating, cooling
humidification and dehumidification. Based on the greatest demand within the group, each unit
operates independently, meaning that the unit may respond to the thermal load and humidity
conditions based on the units controlling sensors.
Teamwork Mode 3 - Optimized Aisle: May be employed in large and small rooms with
varying heat loads. Optimized Aisle is the most efficient teamwork mode that allows the unit to
match cooling capacity with heat load. In the Optimized Aisle mode, the fans operate in parallel.
Fans can be controlled exclusively by remote temperature or using static pressure with a
secondary remote temperature sensor(s) as an override to ensure that the inlet rack temperature
is being met. Cooling (Compressors or Economizer) is controlled through unit supply air
conditions. Liebert iCOM calculates the average or worst-case sensor reading (user-selectable) for
heating, cooling humidification and dehumidification. Based on the demand within the group,
units will be allowed to operate within that mode until room conditions are satisfied.
177
Liebert DS
Guide Specifications
3.5
STANDBY LEAD-LAG
The Liebert iCOM shall allow scheduled rotation to keep equal run time on units and provide
automated emergency rotation of operating and standby units.
3.6
3.7
3.8
VIRTUAL MASTER
As part of the robust architecture of the Liebert iCOM control, it shall allow for a virtual master that
coordinates operation. The Virtual Master function shall provide smooth control operation if the
groups communication is compromised. When the lead unit, which is in charge of component staging
in teamwork, unit staging and standby rotation, becomes disconnected from the network, the Liebert
iCOM shall automatically assign a virtual master. The virtual master shall assume the same
responsibilities as the master until communication is restored.
3.9
3.10
3.11
3.12
3.13
LOW-PRESSURE MONITORING
Units shall ship standard with low-pressure transducers for monitoring individual compressor
suction pressure. If the pressure falls due to loss of charge or other mechanical cause, the
corresponding circuit shall shut down to prevent equipment damage. The user shall be notified of the
low-pressure condition through the local display and remote monitoring.
Liebert DS
178
Guide Specifications
3.14
3.15
3.16
3.17
3.18
3.19
3.20
179
Liebert DS
Guide Specifications
3.21
COMPRESSOR SEQUENCING
A user-selectable compressor sequencing parameter shall be provided and shall be accessible through
the local display. This sequencing parameter shall present the user with three choices:
Always use Compressor 1 as the lead compressor.
Always use Compressor 2 as the lead compressor.
Auto: The unit shall automatically stage compressors to keep each units run time within 8
hours of the others run time.
First priority: If the safety timings are acceptable for only one compressor, then it is the
next to be started/stopped.
Second priority: If both compressors are Off: The compressor with fewer working hours is
the next to start.
Third priority: If both compressors are in operation: the compressor that has been operating
longer since the last start is the next to be stopped.
3.22
3.23
The user shall have the ability to monitor compressor operating temperature and pressure from the
local display to be used as a diagnostic tool.
3.24
3.25
Liebert DS
180
Guide Specifications
3.26
3.27
COMPRESSOR DEHUMIDIFICATION
The control shall permit the user to specify which compressor is used for dehumidification. The
choices shall be 1st compressor, 2nd compressor, 1 or 2, or BOTH.
4.0
MISCELLANEOUS OPTIONS
4.1
4.2
4.3
4.4
SMOKE SENSOROPTIONAL
The smoke sensor shall immediately shut down the environmental control system and activate the
alarm system when activated. The smoke sensor shall be mounted in the electrical panel with the
sensing element in the return air compartment. The smoke sensor is not intended to function as or
replace any room smoke detection system that may be required by local or national codes. The smoke
sensor shall include a supervision contact closure.
4.5
4.6
4.7
4.8
4.9
COMPRESSOR OVERLOADOPTIONAL
A pair of normally open contacts shall be factory-installed and factory-wired to each compressor to
indicate Compressor Overload.
181
Liebert DS
Guide Specifications
4.10
4.11
4.12
Each Liebert iCOM shall have up to four factory-installed and factory-programmed static pressure
transducer(s). The transducer(s) may be used for control of fan speed or reference of the supply
plenum pressure. When used for control, the Liebert iCOM shall be capable of:
Sharing sensor data across multiple units in the U2U network to provide greater flexibility,
visibility and control. Only one transducer shall be required for a group of units however multiple
transducers may be applied per group and aggregated for redundancy.
Offering the user selections to control fan from either the average or lowest pressure reading
collected in the U2U network.
4.13
4.14
REMOTE MONITORINGOPTIONAL
A factory-installed communication card shall be provided for monitoring and/or control. The
communication card shall be capable of connecting to Building Management System/Building
Automation System using the following protocols:
BACnet IPBACnet over Internet Protocol
BACnet MSTPBACnet Master-Slave/Token-Passing (MSTP) communications protocol over
a RS-485 serial network (also known as BACnet MSTP RS-485)
Modbus RTUModbus Remote Terminal Unit (RTU) communication protocol over a RS-485
serial network (also known as Modbus RTU RS-485)
Modbus TCPModbus Transmission Control Protocol over Internet Protocol (also known as
Modbus TCP/IP)
SNMP
YDN23 - YD-T-1363 specification protocol (also known as YD/T 1363)
The communications card shall be capable of connecting to two of these protocols at once.
4.15
POWER MONITORINGOPTIONAL
The unit shall be equipped with factory-programmed/installed power meters to monitor power
characteristics for either individual components or the total unit. These meters shall allow the user to
monitor meter connection status, input undervoltage, input RMS voltage leg-to-leg and leg-to-ground,
input current for each phase, energy consumption in kilowatt hours and instantaneous power in
watts. In multi-unit applications, a phase loss protection routine shall place a unit into standby mode
in the event.
Liebert DS
182
Guide Specifications
4.16
4.16
183
Liebert DS
Guide Specifications
4.16
OPTIONS-WATER/GLYCOL SYSTEMS
4.16
OPTIONS-GLYCOOL SYSTEMS
4.16.4
Cu-Ni Econ-O-Coil
A 70/30 Cu-Ni Econ-O-Coil shall be provided for when the Liebert Econ-O-Coil is cooling tower loop or
other open water system. This option shall be required on open cooling tower applications.
Liebert DS
184
Guide Specifications
4.17 OPTIONS-DRYCOOLER
The drycooler shall be the low profile, slow speed, multiple direct drive, propeller fan type. The
drycooler shall be constructed of aluminum and contain a copper tube aluminum fin coil with an
integral electric control panel and disconnect switch. The drycooler shall be designed for ____ F (C)
ambient.
4.18
The dual pump package shall include pumps, enclosure, field-mounted flow switch and a separate,
factory-wired control box (including a lead-lag switch for the pumps). The standby pump shall
automatically start upon failure of the lead pump. Each pump shall be rated for ____ GPM (l/s) at ____
feet of head (kPa).
Provide ____ (quantity) solid state water sensors under the raised floor.
4.19
FLOOR STAND
The floor stand shall be constructed of a welded steel frame. The floor stand shall have adjustable legs
with vibration isolation pads. The floor stand shall be ____ inches (mm) high.
4.20
4.21
4.22
185
Liebert DS
Guide Specifications
5.0
EXECUTION
5.1
5.1.1
General
Install Thermal Management units in accordance with manufacturers installation instructions.
Install units plumb and level, firmly anchored in locations indicated and maintain manufacturers
recommended clearances.
5.1.2
Electrical Wiring
Install and connect electrical devices furnished by manufacturer but not specified to be factorymounted. Furnish copy of manufacturers electrical connection diagram submittal to electrical
contractor.
5.1.3
Piping Connections
Install and connect devices furnished by manufacturer but not specified to be factory-mounted.
Furnish copy of manufacturers piping connection diagram submittal to piping contractor.
5.2
Liebert DS
186
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
Fax: +39 049 5841 257
Asia
29/F, The Orient Square Building
F. Ortigas Jr. Road, Ortigas Center
Pasig City 1605
Philippines
+63 2 687 6615
Fax: +63 2 730 9572
SL-18827_REV0_12-15
www.EmersonNetworkPower.com