Sie sind auf Seite 1von 20

Data sheet

Description / Application

Manual presetting valve MSV-C


MSV-C is used for balancing the flow in cooling,
heating and domestic water systems.
MSV-C is a combined manual presetting valve
with following features:
Fixed measurement orifice.
Supplied with 2 pcs. of measuring nipples
for needles.
Handwheel with shut-off function and clear
360 o reading
Digital scale with lock function
Measuring accuracy of fixed orifice 5%
MSV-C is supplied with internal thread.
MSV-C is made in standard brass and CR brass
(CR - Corrosion Resistant).

MSV-C
Fan
Coil

MSV-C

Fan coil terminals for cooling and heating.

MSV-C or MSV-F2

MSV-C or MSV-F2

MSV-C or MSV-F2

Secondary circuit for cooling or heating in distribution systems .

HEC

VDB1C602 Danfoss 09/2008

Data sheet

Manual presetting valve MSV-C

Ordering

MSV-C valve with measuring nipples


Type

Material

CR brass,
with measuring
nipples (2 pcs.)

Brass,
with measuring
nipples (2 pcs.)

Size
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50

kvs
1.8
3.8
7.0
15.8
21.1
43.9
1.8
3.8
7.0
15.8
21.1
43.9

Connection
Rp "
Rp "
Rp 1"
Rp 1"
Rp 1"
Rp 2"
Rp "
Rp "
Rp 1"
Rp 1"
Rp 1"
Rp 2"

Code no.
003Z3001
003Z3002
003Z3003
003Z3004
003Z3005
003Z3006
003Z3020
003Z3021
003Z3022
003Z3023
003Z3024
003Z3025

Size
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50

kvs
1.8
3.8
7.0
15.8
21.1
43.9
3.9
7.3
11.8
21.6
28.5
50.5

Connection
Rp "
Rp "
Rp 1"
Rp 1"
Rp 1"
Rp 2"
Rp "
Rp "
Rp 1"
Rp 1"
Rp 1"
Rp 2"

Code no.
003Z3010
003Z3012
003Z3013
003Z3014
003Z3015
003Z3016
003Z3030
003Z3031
003Z3032
003Z3033
003Z3034
003Z3035

MSV-C valve without measuring nipples


Type

Material

Brass,
without nipples
(with plug)

CR brass,
without measuring
station

Note for commissioning: kvs for measuring orifice is explained on page 4 and 5.
MSV-C valve with draincock and measuring nipples
Type

Material
CR brass,
draincock,
with measuring
nipples (2 pcs.)

Brass, draincock,
with measuring
nipples (2 pcs.)

Size
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50

VDB1C602 Danfoss 09/2008

kvs
1.8
3.8
7.0
15.8
21.1
43.9
1.8
3.8
7.0
15.8
21.1
43.9

Connection
Rp "
Rp "
Rp 1"
Rp 1"
Rp 1"
Rp 2"
Rp "
Rp "
Rp 1"
Rp 1"
Rp 1"
Rp 2"

Code no.
003Z3800
003Z3801
003Z3802
003Z3803
003Z3804
003Z3805
003Z3811
003Z3812
003Z3813
003Z3814
003Z3815
003Z3816

HEC

Data sheet

Manual presetting valve MSV-C

Accessories
Type
Measuring nipples for needles, 2 pcs.
Extended nipples for needles, 2 pcs.
Measuring needles, 2 pcs.
Drain cook
Measuring connector for drain cook
Measuring equipment PFM 3000
Handwheel, for valve size
Handwheel, for valve size
Handwheel, for valve size
Handwheel, for valve size
Handwheel, for valve size
Handwheel, for valve size

Code no.
003Z0100
003Z0106
003Z0107
003L8141
003L8143
003L8230
003Z3050
003Z3051
003Z3052
003Z3053
003Z3054
003Z3055

Size
36 mm "
60 mm "
3.0 mm
" - "
" - Rectus
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50

Insulation caps

Design

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.

The insulation caps are made of polyurethane


foam with a polystyrene shield, and they are
designed for temperatures from -30 oC to +120 oC
( = 0.028 W/mK).

Code no.
003Z3040
003Z3041
003Z3042
003Z3043
003Z3044
003Z3045

Type
DN 15
DN 20
DN 25
DN 32
DN 40
DN 50

Valve body (CR brass)


Bonnet
Setting spindle
Valve cone
O-ring
O-ring
Pos. indicator
Retaining ring
Handle
Lock setting screw
Knob
Pin
Valve information cap
Fixed orifice
Label
Digital scale
Valve seal

15

8
7

13

10

5
11

16

12
9

17

14

Locking and shut-off


Informations on the label:
Type: . . . . . . . . . MSV-C
kVS: . . . . . . . . . max. kVS
Dimension: . . . . . . DN 15

MSV-C valve can shut-off the flow by turning the


handwheel clockwise to the stop.
HEC

VDB1C602 Danfoss 09/2008

The presetting can be locked with an 6 mm Allen


key.
3

Data sheet

Manual presetting valve MSV-C

Measuring

Fixed orifice (kVS) and differential pressure will be


used in the measuring equipment to define the
flow.
Measuring on a fixed orifice valve i.e. MSV-C is
very fast and easy. The amount of information
entered into the measuring equipment is low.
The Danfoss measuring equipment PFM 3000:
Type:

Danfoss MSV-C
Dimension: DN 20
Now presetting scale can be turned to the desired
position and at the same time the exact flow can
be read at the measuring equipment.
The flow running through the MSV-C valve can
be measured by using the Danfoss measuring
equipment PFM 3000 or other brands of measuring
equipment.
The MSV-C valve is supplied with two measuring
nipples for 3 mm needles.

The other brands of measuring equipment.


kVS: 4.1 (orifice DN 20 MSV-C)
Now presetting scale can be turned to the desired
flow and at the same time the exact flow can be
read at the measuring equipment.

The measuring nipples are placed across a fixed


orifice and the differential pressure can be measured across this orifice.

Fixed orifice

The fixed orifice is a very presise way to define the


flow running through a presetting valve.
Our fixed orifice is created in the valve body and
has a fixed and stable kvs. Sizing depends on valve
dimension.
On a fixed orifice valve i.e. MSV-C the orifice is
fixed and stable because it is created in the valve
body.
Measuring accuracy 5%.

Setting / adjustment

The flow can be adjusted with the presetting


hand-wheel.
The digital presetting scale indicates the value of
setting. Turn the presetting hand-wheel clockwise.
The Kv value will be smaller and finally shut-off
the flow.
Turn the presetting hand-wheel counter-clockwise
and Kv will increase.
The digital presetting scale indicates:
0.0 Closed setting orifice.
8.0 Completly opened setting orifice.
At page 6 - 17, the valve diagram shows the digital
presetting scale setting no. and Kv.

VDB1C602 Danfoss 09/2008

HEC

Data sheet

Manual presetting valve MSV-C

Valve selection table


Size

*Minimum flow rate


(l/s)

Max balancing pressure


(kPa)

kVS orifice

kVS

DN 15

0.055

2366 Q2

1.8

1.8

DN 20

0.11

1250 Q2

4.1

3.8

DN 25

0.21

1203 Q

7.5

7.0

DN 32

0.46

284 Q2

16.6

15.8

DN 40

0.7

203 Q2

23.0

21.1

DN 50

1.3

49 Q2

47.4

43.9

* Minimum flow rate at 1kPa pressure drop across orifices.

KVS orifice

KVS valve

kvs orifice
kvs valve
kvs

KVS

- kvs across orifices


- kvs across the cone
- kvs include orifice and cone.

Example:
Wanted:

Correct valve size and presetting.

Given:


Max. pipe flow


pr = 15 kPa
pa = 40 kPa
pm = 10 kPa

Q= 0.80 m3/h

Solution: MSV-C size and presetting:





The differential pressure across MSV-C


can be calculated:

pi = 45 kPa - 15 kPa - 10KPa = 20 kPa

The correct valve size on presetting


can be found in the graph (page 7).

Q= 0.80 m3/h and pi = 20 kPa

pi = pa - pv - pm

pi
pm
pr
pa

Pressure drop across MSV-C valve


Pressure drop across valve
Necessary pressure for the riser
Available pressure for the riser

Setting can be also calculated from the formula:



Technical data

Intersect the setting lines at point 'A'


- presetting 3.2 on valve size DN 20.

Q[m3/h]
pi [bar]

0.8
0.20

= 1.7 m3/h

what corespondent presetting 3.2.

Max. static working


pressure

16 bar

Material of parts in contact with water

Static test pressure

25 bar

Valve body,
spindle, cone, etc.

Corrosion Resistant
(CR) or standard
brass

O-rings

HMBR

Max. differential pressure 1.5 bar (150 kPa)


across valve

HEC

kv =

Max. flow temperature

120 C

Min. temperature

-10C

Cooling liquids

Glycol and HYCOOL

VDB1C602 Danfoss 09/2008

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 15 with measuring station

Flow characteristics DN 15 with meas. station

DN 15 with measuring station


Handwheel rotations

kV-value

0.5

0.8

1.2

1.4

1.6

1.7

1.8

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

VDB1C602 Danfoss 09/2008

HEC

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 15 without measuring station

Flow characteristics DN 15 without meas. station

DN 15 without measuring station


Handwheel rotations

kV-value

0.6

1.1

1.6

2.1

2.8

3.2

3.9

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

HEC

VDB1C602 Danfoss 09/2008

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 20 with measuring station

Flow characteristics DN 20 with meas. station

DN 20 with measuring station


Handwheel rotations

kV-value

0.8

1.6

2.5

3.1

3.5

3.7

3.8

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

VDB1C602 Danfoss 09/2008

HEC

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 20 without measuring station

Flow characteristics DN 20 without meas. station

DN 20 without measuring station


Handwheel rotations

kV-value

0.9

1.8

2.8

3.9

5.2

6.3

7.3

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

HEC

VDB1C602 Danfoss 09/2008

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 25 with measuring station

Flow characteristics DN 25 with meas. station

DN 25 with measuring station


Handwheel rotations

kV-value

0.9

2.0

3.5

5.0

6.1

6.7

7.0

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

10

VDB1C602 Danfoss 09/2008

HEC

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 25 without measuring station

Flow characteristics DN 25 without meas. station

DN 25 without measuring station


Handwheel rotations

kV-value

0.8

1.8

3.3

5.5

8.3

10.2

11.8

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

HEC

VDB1C602 Danfoss 09/2008

11

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 32 with measuring station

Flow characteristics DN 32 with meas. station

DN 32 with measuring station


Handwheel rotations

kV-value

1.3

3.0

5.8

9.2

12.3

14.6

15.8

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

12

VDB1C602 Danfoss 09/2008

HEC

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 32 without measuring station

Flow characteristics DN 32 without meas. station

DN 32 without measuring station


Handwheel rotations

kV-value

2.6

5.1

8.9

14.0

17.0

20.0

21.6

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

HEC

VDB1C602 Danfoss 09/2008

13

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 40 with measuring station

Flow characteristics DN 40 with meas. station

DN 40 with measuring station


Handwheel rotations

kV-value

2.2

4.7

8.9

13.2

16.4

19.3

21.1

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

14

VDB1C602 Danfoss 09/2008

HEC

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 40 without measuring station

Flow characteristics DN 40 without meas. station

DN 40 without measuring station


Handwheel rotations

kV-value

3.1

7.2

13.5

18.5

24.0

26.0

28.5

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

HEC

VDB1C602 Danfoss 09/2008

15

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 50 with measuring station

Flow characteristics DN 50 with meas. station

DN 50 with measuring station


Handwheel rotations

kV-value

2.5

8.8

17.0

26.2

34.5

40.2

43.9

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

16

VDB1C602 Danfoss 09/2008

HEC

Data sheet

Manual presetting valve MSV-C

Sizing diagram
DN 50 without measuring station

Flow characteristics DN 50 without meas. station

DN 50 without measuring station


Handwheel rotations

kV-value

5.4

13.8

24.5

33.0

41.0

49.0

50.5

Max. permissible differential pressure in


throttling function 2.0 bar.

Condition:
The flow must be free of cavitation.

Max. permissible flow speed:


Liquids 4 m/s,
Gas and vapours 60 m/s

HEC

VDB1C602 Danfoss 09/2008

17

Data sheet

Dimensions

Manual presetting valve MSV-C

without nipples (with plug)

with 2 pcs. measuring nipples

E
B

SW

SW

D
C

Size
(DN)

Thread

15
20

A
(mm)

Rp

28

161

125

85

15

184.5

52

0.610

0.68

Rp
Rp 1

33

185

145.5

97

16.3

215.5

52

0.860

0.93

40

186

158.5

113

19.1

224

52

1.060

1.13

51

207

168.5

144

21.4

245.5

52

1.665

1.73

40

Rp 1
Rp 1

56

259.5

212

163

21.4

309

58

2.435

2.50

50

Rp 2

71

281

230

193

25.7

337.5

58

3.645

3.72

25
32

B
(mm)

C
(mm)

D
(mm)

E
(mm)

F
(mm)

Weight (kg)
without
with
nipples
nipples

SW

Size
(DN)

Thread

SW

A
(mm)

15

Rp

28

20

Rp

33

25

40

160

51

171

40

Rp 1
Rp 1
Rp 1

56

212

50

Rp 2

71

231

32

18

SW

D
A

B
(mm)

C
(mm)

D
(mm)

E
(mm)

F
(mm)

Weight
(kg)

137.5

119

157

138.5

68

15

162.5

52

0.47

77

16.3

189.5

52

0.64

154

91

19.1

201.5

52

0.86

168.5

108

21.4

220

52

1.27

211

116

21.4

276

58

1.89

230

143

25.7

301.6

58

2.80

VDB1C602 Danfoss 09/2008

HEC

Data sheet

HEC

Manual presetting valve MSV-C

VDB1C602 Danfoss 09/2008

19

Data sheet

Manual presetting valve MSV-C

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products
already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed.
All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

Danfoss Trata d.o.o.

Danfoss A/S
Comfort Division

Joeta Jame 16, P.O.B. 4820


1210 Ljubljana - entvid
Slovenia
Tel.: +386 1/58 20 200
Fax: + 386 1/51 99 824

http://www.hydronicbalancing.com

http://www.danfoss-trata.si

Hrupvnget 11
Hrup
DK-8600 Silkeborg
Denmark
Tel.: +45 86 80 36 66
Fax: +45 86 80 19 66

20

VDB1C602 Danfoss 09/2008

HEC

Das könnte Ihnen auch gefallen