Sie sind auf Seite 1von 3

Equivalent Pipe Length Method Calculating Pressure Loss in Piping

Systems
Calculating pressure loss in piping systems with the
Equivalent Pipe Length Method
An efficient and simple way to calculate the pressure loss in a piping system is the "Equivalent Pipe
Length Method".

1. Make a Diagram of the Piping System


Make a diagram where the system is structured with nodes as shown below.

In the very simply circulating system used in this example the first node (0) is the pump. The next node
is the tees (2) where the piping system splits up. The other nodes are the heating radiators.
In many systems the structure can be simplified as above since the piping in both directions are of
same size. If a more fine grained approach is required, additional nodes can be added in both
directions as shown below.

2. Make a calculation table


With the most simplified nodes structure above a calculation table can be made as shown below. Each
section from node to node is calculated by supplying length, volume flow, pipe size, pressure loss from
diagrams or tables for the actual pipes and components in the sections and their individual equivalent
length substituting the the minor loss.

An excel template with the table above can be downloaded here:

Equivalent Pipe Length Method - Excel Template

Note! The flow and pressure units must be adjusted to the data available for your piping system.

3. Add Volume flow, Pipe Size and Pressure Loss for each Section
Add actual pipe size and in each section. Use tabulated data or a diagrams.
The pressure loss may alternatively be calculated with the Hazen-Williams Equation or the DarcyWeisbach Formula.

Pressure loss for many types of pipes can be found here.

4. Add Equivalent Length of all Valves, Fittings and Straight Pipes


Add the equivalent length of all valves, components, fittings and straight pipes in the sections.

5. Summarize the Pressure Loss in each Section


Calculate and summarize the pressure loss in each section.

6. Summarize the Pressure Loss in all Paths


Finally, add up the pressure loss in all sections that form unique paths. In the example above there are
two unique paths - one is section 0 - 2 - 3, the other is section 0 - 2 - 4. Add extra columns for
additional paths in more complicated systems.
The highest pressure loss determines the pump head.

7. Add Balancing Valves


Add valves where it is necessary to balance the system. In the example above a balancing valve is
added in section 2-4.
Note! The Equivalent Pipe Length Method can be adapted to most piping systems - like water supply
systems, gravity heating systems and similar.

Das könnte Ihnen auch gefallen