: CONTROL & MONITORING POINT LIST OF BUILDING AUTOMATION SYSTEM


: DISTRIK 8 - TOWER - 2
: PT. ARNAN PRATAMA CONSULTANTS
: MARET 16th, 2015
:0
NUMBER

NO.

DESCRIPTION

OF
UNITS

I.

VAC SYSTEM

MISCELLANEOUS FANS
a. Exhaust Fan

BINARY
IN

OUT

ANALOG
IN

OUT

HIGH
TRANSDUCER & ACTUATOR
NUMBER
LEVEL
SUPPLY
INSTALL
INTERFACE OF POINTS

TYPE OF
TRANSDUCER/ACTUATOR

REMARKS

(Above 1 HP/0.76 kW)


Lantai Basement-1 = EF-B1/PR.1 (1 Unit)
Lantai 30 = EF-REF/JAN (1 unit)
Lantai 50 = EF-50/LND (1 Unit)
Lantai Atap = EF-RF/JAN 1 (1 unit)
Start/Stop

PANEL

PANEL

Dry contact

Dry contact

Air Flow Switch

Motor Trip Alarm

PANEL

PANEL

Air Flow Status

BAS

BAS

b. Supply Fan

(Above 1 HP/0.76 kW)


Lantai Basement-1 = SF-BS1/PR (1 unit)
Lantai 30 = SF-REF/1 (! Unit)
Lantai Atap = SF-TRF/1 (1 Unit)
Start/Stop

PANEL

PANEL

Dry contact

Motor Trip Alarm

PANEL

PANEL

Dry contact

Air Flow Status

BAS

BAS

Air Flow Switch

Motor Trip Alarm

PANEL

PANEL

Dry contact

Air Flow Status

BAS

BAS

Air Flow Switch

Motor Trip Alarm

PANEL

PANEL

Dry contact

Air Flow Status

BAS

BAS

Air Flow Switch

c. Pressurization Fans

Lantai 30 = PF-REF/1~2 (2 Uniit)


Lantai Atap = PF-TRF/1~2 (2 Unit)

d. Smoke Extract Fans & Smoke Make up Fan

Lantai 30 = SEF-REF (1 Unit), MUF-REF (1 Unit)


Lantai Atap = SEF-RF (1 Unit), MUF-RF (1 Unit)

T O T A L VAC

30

Page 1 Tower 2

37

NUMBER
NO.

DESCRIPTION

OF
UNITS

II.

BINARY
IN

OUT

ANALOG
IN

OUT

HIGH
TRANSDUCER & ACTUATOR
NUMBER
LEVEL
SUPPLY
INSTALL
INTERFACE OF POINTS

TYPE OF
TRANSDUCER/ACTUATOR

REMARKS

PLUMBING
A. FIRE FIGHTING SYSTEM

Fire Pump ( DFP, JFP, EFP)


(1 Electric Pump, 1 Diesel Pump, 1 Jockey Pump)

Motor status

PANEL

PANEL

Dry contact

Motor Trip alarm

PANEL

PANEL

Dry contact

BAS

BAS

Water Pressure Sensor

BAS

BAS

Dry contact

Riser Water Pressure Sensor

MCPFA Status

3
1

B. CLEAN WATER SYSTEM


1

Transfer Pump (Located at Basement 4 Floor)

(TP.1102-1-2-T2.A/B) (4 Unit)

Motor status

PANEL

PANEL

Dry contact

Motor Trip alarm

PANEL

PANEL

Dry contact

Motor status

12

PANEL

PANEL

Dry contact

Motor Trip alarm

12

PANEL

PANEL

Dry contact

HH Level Alarm

BAS

BAS

Water Level Switch

LO Level Alarm

BAS

BAS

Water Level Switch

HH Level Alarm

BAS

BAS

Level Switch

LO Level Alarm

BAS

BAS

Level Switch

Booster Pump (Located at Roof & 30th Floor)

12

(DP.1101-1-T2 A/B/C) (12 Unit)

Elevated Water Tank (Located at Roof Floor)

(RT.1102.1~2-T2) (360m3 & 130 m3) (2 Unit)

C. SEWAGE & WASHING SYSTEM


1

Greasetrap (Located at Basement-2 Floor)

(GT.1103-T2.A/B) (65m3) (1 Unit)

Greasetrap Pump (Located at Basement-2 Floor)

(GT.1103-T2.A/B) (2 Unit)
Motor status

PANEL

PANEL

Dry contact

Motor Trip Alarm

PANEL

PANEL

Dry contact

Page 2 Tower 2

NUMBER
NO.

DESCRIPTION

OF
UNITS

BINARY
IN

OUT

ANALOG
IN

OUT

HIGH
TRANSDUCER & ACTUATOR
NUMBER
LEVEL
SUPPLY
INSTALL
INTERFACE OF POINTS

TYPE OF
TRANSDUCER/ACTUATOR

REMARKS

D. FUEL OIL SYSTEM


1

Fuel Oil Daily Tank (Located at Basement-1 (Cap. 1 x 2000 litre)

HH Level Alarm

BAS

BAS

Oil Level Switch

LO Level Alarm

BAS

BAS

Oil Level Switch

Fuel Oil Weekly Tank (Located at Genset Room) (Cap.1 X 3000 litre)

HH Level Alarm

BAS

BAS

Oil Level Switch

LO Level Alarm

BAS

BAS

Oil Level Switch

PANEL

PANEL

Dry contact

Status

PANEL

PANEL

Dry contact

Trip Alarm

PANEL

PANEL

Dry contact

PANEL

PANEL

Digital KWH (ModBus Protocol)

PANEL

PANEL

Dry contact

Status

PANEL

PANEL

Dry contact

Trip Alarm

PANEL

PANEL

Dry contact

PANEL

PANEL

Digital KWH (ModBus Protocol)

TOTAL PLUMBING
III.
1

49

52

ELECTRICAL SYSTEM
Medium Voltage Main Dist. Panel
(MVMDP-T.2/LZ) (Located at Basement 2 Floor)
a. Main Incoming

Status
b. Main Outgoing

c. PMCU (Digital Protection, Metering, Monitoring and Control Unit)


2

Medium Voltage Main Dist. Panel


(MVDP-T.2/HZ) (Located at Basement 2 Floor)
a. Main Incoming

Status
b. Main Outgoing

c. PMCU (Digital Protection, Metering, Monitoring and Control Unit)


3

Low Voltage Distribution Panel


(LVDP-T2/LZ) (Located at Basement 2 Floor)
Low Voltage Incoming

Status

PANEL

PANEL

Dry contact

Trip Alarm

PANEL

PANEL

Dry contact

11

PANEL

PANEL

Dry contact

PANEL

PANEL

Digital KWH (ModBus Protocol)

Main Outgoing

11

DPM (Digital Power Meter)

Page 3 Tower 2

NUMBER
NO.

DESCRIPTION

OF
UNITS

BINARY
IN

ANALOG

OUT

IN

OUT

HIGH
TRANSDUCER & ACTUATOR
NUMBER
LEVEL
SUPPLY
INSTALL
INTERFACE OF POINTS

TYPE OF
TRANSDUCER/ACTUATOR

REMARKS

Low Voltage Distribution Panel


(LVDP-T2/HZ.1) (Located at 30th Floor)
Low Voltage Incoming

Status

PANEL

PANEL

Dry contact

Trip Alarm

PANEL

PANEL

Dry contact

PANEL

PANEL

Dry contact

PANEL

PANEL

Digital KWH (ModBus Protocol)

Main Outgoing

DPM (Digital Power Meter)

Low Voltage Distribution Panel


(LVDP-T.2/MZ.2) (Located at 30th Floor)
Low Voltage Incoming

Status

PANEL

PANEL

Dry contact

Trip Alarm

PANEL

PANEL

Dry contact

PANEL

PANEL

Dry contact

PANEL

PANEL

Digital KWH (ModBus Protocol)

BAS

BAS

Dry contact

BAS

BAS

Room Temperature Sensor

PANEL

PANEL

Dry contact

Main Outgoing

DPM (Digital Power Meter)

Transformer

(TR-SD-TM2/LZ) (1 Unit), (TR-SD-T2/HZ.1~2) (2 Unit)


(Dry Type) (Located at 30th Floor)
Geenral Alrm
7

Transformer Room

3
2

(Located at 2 Floor & 30th Floor) (2 Unit)


High Temp. Alarm
8

Lighting Panel
LP-BS3/APT2 (1 Unit), LP-BS2/APT2 (1 Unit), LP-BS1/APT2 (1 Unit), LP-SB/APT2 (1 Unit)
LP-LOB.LD/APT2 (1 Unit), LP-L3/APT2 (2 Unit), LP-L4/APT.2 (2 Unit), LP-L5/APT.2 (2 Unit)
LP.L6/APT2 (2 Unit), LP-L7/APT2 (2 Unit), LP-LOB.L8/APT2 (1 Unit), LP-LOB.L9/APT2 (1 Unit)
LP-LOB.L10~29/APT2 (20 Unit), LP-LOB.31~L49 (19 Unit), LP-LOB.L50/APT2 (1 Unit)
Corridor Zones

57

Start/Stop

57

Status

57

PANEL

PANEL

Dry contact

Trip Alarm

57

PANEL

PANEL

Dry contact

TOTAL ELECTRICAL

TOTAL POINT LIST BAS


TOTAL POINT LIST BAS (+ 10% Spare)

147

57

226

64

295

249

70

325

Page 4 Tower 2

NUMBER
NO.

DESCRIPTION

OF
UNITS

KWH Meter for Billing System for office 1

BINARY
IN

OUT

ANALOG
IN

OUT

HIGH
TRANSDUCER & ACTUATOR
NUMBER
LEVEL
SUPPLY
INSTALL
INTERFACE OF POINTS

TYPE OF
TRANSDUCER/ACTUATOR

382

DP-L8/T2 (7 Unit), DP-L9/T2 (3 Unit), MC-L10~29/APT2 (200 Unit)


MC-L31~L49/APT2 (171 Unit), MC-L50/APT2 (1 Unit)
KWH 3 Phase
Status

LEGEND

382

BAS/PANEL

TOTAL POINT LIST BILLING SYSTEM

382

382

TOTAL POINT LIST BILLING SYSTEM (+ 10% Spare)

420

420

BAS

= Building Automation System

VAC

= Ventilation & Air Conditioning

= Control

= Monitoring

NOTE :
- BAS Contractor should be coordinate with all related contractor
- Starting of Pressurization Fan should be operated automatically by Fire alarm
- Starting all pump should be operated by Pump Panel, BAS only monitoring status & trip alarm
- Starting of Smoke Extract Fan (SEF) should be operated automatically by Fire alarm
- KWH Billing software included conversion to rate (Rupiah)
- BAS system operation to be based on fast field network communication speed at least 78.6 Kbps for field network and
10Mbps for central backbone network
- Open BAS system : Modbus, LONWorks

Page 5 Tower 2

BAS/PANEL

Digital KWH (ModBus Protocol)

REMARKS