Compressor Selection: 2-stage Semi-hermetic Reciprocating Compressors


Input Values
Compressor model
Refrigerant
Reference temperature
Evaporating SST
Condensing SDT
Operating mode
Suct. gas superheat
Useful superheat
Power supply

S6F-30.2Y
R507A
Dew point temp.
-40.00 C
55.0 C
with sub cooler
10.00 K
100%
380V-3-60Hz

Result
Compressor
Capacity steps
Cooling capacity
Cooling capacity *
Evaporator capacity
Power input
Current (380V)
Voltage range
Condenser Capacity
COP/EER
COP/EER *
Mass flow LP
Mass flow HP
Intermed. pressure
Mean temperature
Liquid temp.

S6F-30.2Y- 35P
100%
25.9 kW
17.53 kW
25.9 kW
26.8 kW
45.5 A
360-400V
52.7 kW
0.97
0.66
723 kg/h
1352 kg/h
5.98 bar(a)
-1.63 C
13.05 C

*According to EN12900 (20C suction gas temp., 0K liquid subcooling)

Application Limits
Legend

15-135-1

BITZER Software v6.4.4 rev1464

06/03/2016 / All data subject to change.

Technical Data: S6F-30.2Y


Dimensions and Connections

Technical Data
Technical Data
Displacement (1450 RPM 50Hz)
Displacement (1750 RPM 60Hz)
No. of cylinder x bore LP/HP x stroke
Weight
Max. pressure (LP/MP/HP)
Connection suction line
Connection discharge line
Oil type R404A/R507A
Oil type R22
Motor data
Motor voltage (more on request)
Max operating current
Winding ratio
Starting current (Rotor locked)
Max. Power input
Extent of delivery (Standard)
Motor protection
Enclosure class
Vibration dampers
TX valve for liquid injection
Sight glass
Filter Drier
Solenoid valve
Oil charge
Available Options
Crankcase heater
Oil pressure monitoring
Oil service valve
Discharge gas temperature sensor
CIC (only for R22,instead of TX valve for LI)
Liquid sub cooler (also mounted)

101.10 / 50.50 m/h


122.02 / 60.95 m/h
6 x 82/ 82 mm x 55 mm
234 kg
19 / 19 / 28 bar
42 mm - 1 5/8''
35 mm - 1 3/8''
BSE32 (Option)
B5.2 (Standard)
360-400V PW-3-60Hz
65.0 A
50/50
171.5 A Y / 280.0 A YY
38.5 kW
SE-B2 (Standard)
IP54 (Standard), IP66 (Option)
Standard
Standard
Standard
Standard
Standard
4.75 dm3
140 W (Option)
MP54 (Option), Delta P II(Option)
Option
Option
Option
Option

2/3

15-135-1

BITZER Software v6.4.4 rev1464

06/03/2016 / All data subject to change.

3/3

2-stage Semi-hermetic Reciprocating Compressors


Condensing capacity:
The condensing capacity can be calculated with or without heat rejection. This option can be set in the menu PROGRAM/
OPTIONS. The heat rejection is constantly 5% of the power consumption. The condensing capacity is to be found in the
line Condensing cap. (with HR) resp. Condensing capacity.
Legend of connection positions according to "Dimensions":
1 High pressure connection (HP)
2 Discharge gas temperature sensor (HP)
3 Low pressure connection (LP)
4 CIC system: spray nozzle (operation without liquid subcooler)
4b CIC sensor (HP)
4c CIC sensor (MP / operation with liquid subcooler)
5 Oil fill plug
6 Oil drain (magnetic screw)
7 Oil filter
8 Oil return (oil separator)
10 Crankcase heater
11 Oil pressure +
12 Oil pressure
14 Intermediate pressure connection (MP)
15 Liquid injection (operation without liquid subcooler and with thermostatic expansion valve)
16 Connection for differential oil pressure switch "Delta-P"
17 Refrigerant inlet at liquid subcooler
18 Refrigerant outlet at liquid subcooler

Das könnte Ihnen auch gefallen