OLYMPIC CABLE COMPANY SDN. BHD.

11KV SINGLE CORE CROSS-LINKED POLYETHYLENE (XLPE) INSULATED, PVC INNER SHEATHED, ALUMINIUM WIRE ARMOURED, PE OVERSHEATHED CABLE

REF
1
2
3
4

5
6
7

8
9

10

11

12

13

TECHNICAL DATA
UNIT

DESCRIPTION
Reference standard
Voltage (Uo / U)
Number of cores
Conductor
- Material
- Cross sectional area
- Number of strands
- Conductor shape
- Conductor's outermost lay direction
Conductor Screen
-Material
Insulation
- Material
- Nominal thickness
Insulation Screen
-Material
-Method of application
-Diameter over insulation screen (Approx.)
Metallic Screen
-Material
-Nominal thickness
Inner sheatlh
- Material
- Nominal thickness
- Overall diameter over inner shealth
Armouring
- Material
- No of wire (approx.) / size
- Diameter over armouring
Outer Sheath
- Material
- Nominal thickness
- Overall diameter over outer shealth (approx.)
Completed Cable
- Approx. overall diameter
- Approx. weight per kilometer
- Approx. cable length per drum
Condition Upon Which Current Carrying
Capacities are Based
- Soil thermal resistivity
- Ground temperature
- Ambient air temperature
- Burial depth
- Type of earth bonding-Trefoil
- Load factor
- Number of circuit

Page 1 of 2

kV

mm2
Nos.

630 mm x 1C
IEC 60502-2:1998
6.35 / 11
1
Plain Annealed Copper wires
630
Min. 53
Compacted circular
Right-handed ( Z)
Semi-conducting compound

mm

Cross-linked Polyethylene
3.4

mm

Semi-conducting compound
Extrusion
37.70

mm

Copper Tape
0.08

mm
mm

Black PE
1.4
40.66

Nos/mm
mm

Hard Drawn Round Aluminium Wire


52 2.52
45.70

mm
mm

Black PE
2.6
51.60

mm
kg
m

51.60
7819
1000 2.5%

K-m/w
o
C
o
C
mm

1.2
25
40
800
Bonding at both ends
100
1

OLYMPIC CABLE COMPANY SDN. BHD.


11KV SINGLE CORE CROSS-LINKED POLYETHYLENE (XLPE) INSULATED, PVC INNER SHEATHED, ALUMINIUM WIRE ARMOURED, PVC OVERSHEATHED CABLE

TECHNICAL DATA
REF DESCRIPTION
14 Minimum Radius of Bend
- Laid direct in ground
- Laid in duct
- Laid in air
15 Minimum interal diameter of duct
o
16 Maximum DC Resistance of Conductor at 20 C
17 Maximum Conductor Temperature
- Laid direct in ground
- Drawn into duct
- Laid in air
18 Maximum Current Carrying Capacity Based
on condition Specified (See Ref : 16)
- Laid in ground
- Drawn into duct
- Laid in air
19 Conductor Short Time Current Rating
-Initial temperature
-Maximum conductor short time temperature
Short circuit current rating:-For 1 second
-For 3 second
20 Copper Tape Earth Fault Current Rating
- Initial temperature
- Maximum conductor fault teperature
- Short circuit current rating:- For 1 second
- For 3 second
21 Maximum Volt Drop at Maximum Conductor
Temperature
- For 1 - phase circuits
- For 3 - phase circuits

Page 2 of 2

UNIT
mm
mm
mm
mm
ohm/km
0

2
630 mm x 1C

619
619
619
82
0.0283

C
C
0
C

90
90
90

Amp
Amp
Amp

707
661
955

C
C

90
250

kA
kA

90.06
51.99

0
0

C
C

80
200

kA
kA

0.92
0.53

mV/A.m
mV/A.m

0.18