UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN

BMS NARRATIVE (STAGE 1 BUILDING 3a)

HVAC SYSTEM 3A / C6 BUILDING


Introduction:
Definition of Terms;
Alarm changing green background color of text box to red color when alarm is initiated and
warning message shall appear on the screen of Operator Work Station until Operator acknowledge.
Warning Warning message shall appear on the screen of Operator Work Station until Operator
acknowledge.
Command The operator can overide the command from Operator Work Station and start / stop
the equipment / device.
Control Program has control over the equipment / device. (Auto Mode)

AHU- Type-1 (Recirculation VAV-AHU with Air Purge Serving Zones


with VAV-R.H. Air Terminals )
Control Sequnce - (CS-5) Drawing Ref no. 01-SD-M-GG-AC-SC-02-61963

Air Handling Unit:1. C6-AHU-L2-01


2. C6-AHU-L2-03
3. C6-AHU-L3-04
4. C6-AHU-L3-05
5. C6-AHU-L3-06
6. C6-AHU-L2-07
7. C6-AHU-L2-08

Monitor & Alarm:-

Supply Fan VFD Feedback (Monitor)


Return Fan VFD Feedback (Monitor)
Revision 4

Page 1

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Supply Air Temperature ( TS-2108-PH-10-AA ) (High and Low Limit Alarm)
Supply Fan VFD Trip Status (VFC from MCC) (Alarm)
Supply Air Motorized Fire Damper status (VFC from Damper Actuator) (Alarm)
Supply Fan Automatic and Manual Position (VFC from MCC) (Monitor)
Supply fan On/Off status. (VFC from MCC) (Monitor)
Supply Fan Air Flow status ( Diff. Pressure Sensor) (Alarm)
Filter status ( Diff. Pressure switch) (Alarm)
Return Air Temperature. ( TS-2108-PH-10-AA ) (Monitor)
Return fan On/Off status. (VFC from MCC) (Monitor)
Return Fan Automatic and Manual Position (VFC from MCC) (Monitor)
Return Fan VFD Trip Status (VFC from MCC) (Alarm)
Return Air Motorized Fire Damper status (VFC from Damper Actuator) (Alarm)
Fire Signal (Software Point) (Alarm)
Duct Pressure Sensor (Monitor)
Outdoor Condition (Temperature, Humidity and CO2) (Monitor)
Return Air Quality (CO2 Sensor) (Monitor)
Return Fan Airflow Status ( Diff. Pressure Sensor) (Alarm)
Return Air Humidity Sensor (Monitor)

Control :

Fresh, Return & Exhaust Air Damper Actuator Control


Supply fan Variable Speed Drive Control
Return Fan Variable Speed Drive Control
Supply fan On/Off Command
Return Fan On/Off Command
Cooling Valve Control

Revision 4

Page 2

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Sequence of Operation:-

1) Normal Operation (Summer is when outside air Temperature is above 15 Deg. C):
Supply Fan Operation:
a) Supply fan of AHU-X shall be controlled automatically based on adjustable time program
or as per demand of the operator. Duty time is dependent on supply duct pressure sensor
and unnocupied shall be minimum speed (20Hz).
b) Warning shall be initiated for fan status absence or low flow at multi level according to
speed (from differential pressure sensor measurement). Multi level according to speed
means that the pressure difference across the fan at 4 levels (say 20, 30, 40 and 50 HZ)
goes below the predetemined pressure setpoint, alarm for LOW FLOW shall be initiated
i.e, when belt is loose RPM is dropped, this will create low pressure on fan chamber that
needs to be check by the operator. Also speed of the motor can be high, but airflow is less
due to this loose belt. Alarm for VFD trip indication.
c) Supply Fan (S) runs in accordance with VAV/RH zones demand. Full speed when all
zones VAV/RH are in cooling mode and duct pressure sensor (A) give low pressure
signal. When 1, 2 or more VAV/RH terminals closes (VAV terminal minimum open is
30%), supply fan (S) shall drop its speed upon receiving increase in signal from differential
pressure sensor (A). When pressure signal from DPS (A) drop to minimum setting, supply
fan (S) shall increase speed to sustain the minimum required duct system pressure. Electric
Duct heater shall be de-activated during summer.
Return Fan Operation:
a) Return fan of AHU-X shall be controlled automatically based on adjustable time program
used for Supply Fan or as per demand of the operator. Duty time is dependent on supply
duct pressure sensor and unnocupied shall be minimum speed (20Hz).
b) Warning shall be initiated for fan status absence or low flow at multi level according to
speed (from differential pressure sensor measurement). Multi level according to speed
means that the pressure difference across the fan at 4 levels (say 20, 30, 40 and 50 HZ)
goes below the predetemined pressure setpoint, alarm for LOW FLOW shall be initiated
i.e, when belt is loose RPM is dropped, this will create low pressure on fan chamber that

Revision 4

Page 3

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
needs to be check by the operator. Also speed of the motor can be high, but airflow is less
due to this loose belt.
c) Return Fan shall modulate to increase / decrease following the supply fan speed
adjustments and alarm for VFD trip indication.
Motorized Damper I, J and H operation:
a) Motorized dampers I , J & H will modulate depending on signal receive from CO2 sensor
(M), when CO2 level goes above minimum setting (above 500 ppm) motorized damper (I)
shall start to close and motorized damper (J) shall start to open for purge mode, motorized
damper (H) shall open in direct proportion with damper (J). When CO2 level reaches the
minimum (500 ppm), motorized dampers shall return to balanced position.
b) Example:
CO2 Level

Fresh air Damper

Return Damper

Exhaust Damper

50 %

50 %

50 %

600 ppm

60 %

40 %

60 %

700 ppm

70 %

30 %

70 %

800 ppm

80 %

20 %

80 %

900 ppm

90 %

10 %

90 %

1000 ppm

Full open 100%

Full closed 0%

Full open 100%

500 ppm and below


(Balanced Position)

c) Motorized Damper (J) and (H) shall closed when supply and return fan is Off.
d) Motorized Damper (I) is open when supply Fan is Off.
Cooling Valve (E):
a) Constant supply temperature of air shall be maintained by two way control valve (E) via
signal from temperature sensor (C) at 15 deg.C. Warning shall be initiated above and
below 3 degrees from the supply duct temperature setpoint.
b) Cooling Valve is off when Supply Fan is Off.
Supply Fan Filter:
a) Warning message for filter block indication shall be initiated in the Operator Work Station
until Operator acknowledge.

Revision 4

Page 4

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
2) Winter normal Operation (Winter is when outside air Temperature is 15 Deg. C and
below): During winter, electric duct reheat coil shall be energized to maintain the internal
room/space condition according to heating demand from space room thermostat controller
(R.TH). When relative humidity increases, RH sensor (N) shall send signal to open the cooling
coil valve (E) to drop the supply air temperature to balance the space air temperature. It is
recommended to use VAV action during summer and winter, and electric re-heat action
during winter. Winter mode will be activated if the outside air temperature is 15 degrees and
below. VAV shall close up to 30% if the room temperature is below the set point temperature
at the same time, electric duct heater shall activate to increase the room temperature to reach
set point temperature. This is to avoid duplication/over-lapping of energy usage.

3) BMS (Auto) Mode: When MCC selector switch is in "Auto" mode the BMS operator shall
be able to view all trends, and values , changing setpoints or adjusting schedule using BMS
operator-work-station (OWS) or the Hand Held Operator Terminal(HHOT) under software
protection.

4) In Fire Mode: Upon receipt of signal from Fire Alarm Control panel, all VAV units shall be
fully closed except VAV Units serving the corridors which will be fully opened. Accordingly,
Supply Fan (S) shall reduce its speed proportionally due to the increase in pressure in Duct
Pressure Sensor (A). Supply Fan (S) will delay 180 seconds before it shutdown upon receipt
of signal from Fire Alarm Panel, this is to maintain positive pressure in the corridor area.
Motorized damper (I) shall close to prevent smoke re-entering the building. Motorized Fire
Damper (M) (Supply Fan MFD) shall close at same time with Supply Fan (S) considering the
180 sec time delay (Motorized Fire damper is provided only when main duct is penetrating fire
rated wall above 1.5 hours). RAF-X shall shutdown immediately upon receipt of signal from
FACP at the same time, motorized fire damper (M) (Return Fan MFD) shall close.

5) Purge Mode: Two purge cycle will occur, first during high CO2 level (as mentioned in item 1)
which is done automatically by program and second for smoke clearing after Return to
Normal Operation (Item 6) shall be done by operator from Operator Work Station (OWS).

Revision 4

Page 5

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
6) Return to Normal Operation: After fire situation, all HVAC equipment in fire zone can only
be started upon resetting manually the FACP and BMS program by the operator.

7) Power Failure Mode: In the event of Power failure, BMS system will have all the
information saved in the server during any abnormal power failure condition irrespective any
accidental shut down of the BMS PC directly/manually. BMS shall start the normal operation
as soon as the power supply is available.

8) Hand mode: The unit can be controlled from the MCC panel by switching on the push
buttons available on the panel.Respective indications also will be provided in the MCC
panel.BMS will have all the details/control/data points saved in the server during the switching
from remote mode to hand mode. As soon it is switched back to remote mode, BMS will
return to normal operating condition.

9) Graphics: Graphics shall monitor, control and generate alarm as indicated in this sequence of
operation including all the control points.

AHU- Type-2 Air Handling Unit with Run Around Coil and Return
Fan
Control Sequnce - (CS-8) ( Drawing Ref no. 01-SD-M-GG-AC-SC-02-61963 )

Air Handling Unit:-

1. C6-AHU-L2-02

Monitor & Alarm:-

Supply Fan VFD Feedback (Monitor)


Return Fan VFD Feedback (Monitor)
Supply Air Temperature ( TS-2108-PH-10-AA ) (High and Low Limit Alarm)
Supply Air Motorized Fire Damper status (VFC from Damper Actuator) (Alarm)
Revision 4

Page 6

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Supply fan On/Off status. (VFC from MCC) (Monitor)
Supply Fan Air Flow status ( Diff. Pressure Switch) (Alarm)
Supply Fan VFD Trip Status (VFC from MCC) (Alarm)
Supply Fan Automatic and Manual Position (VFC from MCC) (Monitor)
Supply Fan Filter status ( Diff. Pressure switch) (Alarm)
Filter Bank status (Fresh Air) ( Diff. Pressure switch) (Alarm)
Return Air Quality (Air Quality CO2 Sensor) (Monitor)
Return Air On/Off Fan Status (VFC from MCC) (Monitor)
Return Air Fan VFD Trip (VFC from MCC) (Alarm)
Return Air Fan Air Flow Status ( Diff. Pressure Switch) (Alarm)
Run Around the Cycle Pump On/ Off Status (VFC from MCC) (Monitor)
Return Fan Automatic and Manual Position (VFC from MCC) (Monitor)
Fire Signal (Software Point) (Alarm)
Out door Air (Temp and Humidity) conditions (Monitor)

Control and Command:

Supply Air Fan VFD Speed Control


Supply Fan Start/Stop Command
Chilled Water Cooling Valve Control
Fresh and Return Air Damper Control
Return Fan Start/Stop Command
Run Around Cycle Pump Start/Stop Command
Return Air Fan VFD Speed Control

Sequence of Operation:-

1) Normal Operation (Summer is when outside air Temperature is above 15 Deg. C):
Supply Fan Operation:
a) Supply fan of AHU-X shall be controlled automatically based on adjustable time program
used for Supply Fan or as per demand of the operator. Duty time is full speed (50Hz) and
unnocupied shall be minimum speed (20Hz).
Revision 4

Page 7

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
b) AHU-X is running, RAF-X shall be running simultanuously.when AHU-X supply fan is
off, circulating pump CP-X & RAF-X are off.
c) Warning shall be initiated for fan status absence via differential pressure switch and alarm
for VFD fault.
d) RAC pump shall start whenever the return air temperature (High Select from room
temperature) is lower than the outside air temperature and stop when the outside air
temperature and return air temperature (High Select from room temperature) are same or
outside air temp. is lower. Also, RAC pump shall stop when supply fan is off.
Return Fan Operation:
a) Return fan of AHU-X shall be controlled automatically based on adjustable time program
used for Supply Fan or as per demand of the operator. Duty time is full speed (50Hz) and
unnocupied shall be minimum speed (20Hz).
b) Warning shall be initiated for fan status absence via differential pressure switch.
c) Return Fan shall modulate to increase / decrease following the supply fan speed
adjustments and alarm for VFD trip indication.
Motorized Damper operation:
a) Motorized Damper (C) shall closed when supply fan is Off and Open before supply fan
start (120 sec. time delay).
b) Return fan Motorized damper (M) shall open before return fan start (120sec. time delay)
and close when return fan is Off. During Fire mode damper is closed same time with the
return Fan.
c) Supply Fan Motorized Fire Damper shall close only during Fire Mode via fire alarm.

Cooling Valve (E):


a) Constant supply temperature of air shall be maintained by two way control valve (E) via
signal from high select from all zones served. Warning shall be initiated above and below
3 degrees from the supply duct temperature setpoint. High select means that cooling valve
will open if any of the temperature in the room served by the airhandling unit is above the
room temperature setpoint and the rest of the room will be maintaned by corresponding
Electric Duct heater.
b) Cooling Valve is shut off when Supply Fan is Off.
Supply Fan and Fresh Air Filter Bank:
Revision 4

Page 8

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
a) Warning message for filter block indication shall be initiated in the Operator Work Station
until Operator acknowledge.

2) Purge Cycle (Unoccupied Only): Depending on quantity of CO2 (P) present in return air, the
supply fan of AHU-X shall maintain its speed upon sensing CO2 level below the minimum
setpoint at 500 ppm (unoccupied period). When CO2 level goes above minimum setting at 500
ppm supply fan and return fan of AHU-X shall rise up speed to the maximum flow gradually.
Full speed at CO2 level of 1000 ppm.
NOTE:
The gradual operation of S.F. and R.F. are as follows:
SN

CO2

Hz

500

20

650

30

800

40

1000

50

3) Winter Normal Operation (Winter is when outside air Temperature is below 15 Deg. C):
Room temperature is maintained by electric duct heater serving each space/zone. Room
temperature pre-determined setpoint shall be 23C. when room temp. goes below 20C its
corresponding duct heater shall be energized and modulate the KW output (via thyristor) until
achieving room temperature setpoint, heater KW shall ramp down when temperature rise
above maximum temp. setpoint. When outdoor air temperature is lower than, say 15C,
cooling coil valve (E) shall be closed and open when outdoor air temperature is higher than
15C or as per demand of operator.

4) BMS (Auto) mode: When MCC selector switch is in "Auto" mode the BMS operator shall be
able to view all trends, and values , changing setpoints or adjusting schedule using BMS
operator-work-station (OWS) or the Hand Held Operator Terminal(HHOT) under software
protection.

5) Fire mode: When signal is received from fire alarm control panel AHU-X shall shutdown
immediately. It cannot be started until the fire alarm is reset in the corresponding Fire Alarm
Revision 4

Page 9

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Panel. Motorized Fire Damper (M) shall close in fire mode (motorized fire damper is provided
only on the supply duct of AHU when main duct is penetrating fire rated wall or slab above
1.5 hours). Return Air Fan (X ) shall run at its full speed via BMS control overriding existing
program and toilet exhaust fan will also run overriding existing program for 180 sec.

6) Return to Normal Operation: After fire situation, all HVAC equipment in fire zone can only
be started upon resetting manually the FACP and BMS program by the operator.

7) Graphics: Graphics shall monitor, control and generate alarm as indicated in this sequence of
operation.

8) Hand mode: The unit can be controlled from the MCC panel by switching on the push buttons
available on the panel.Respective indications also will be provided in the MCC panel. BMS
will have all the details/control/data points saved in the server during the switching from
remote mode to hand mode. As soon it is switched back to remote mode, BMS will return to
normal operating condition.

ELECTRIC DUCT HEATER (EDH)


1. C6-EDH- L1-1
2. C6-EDH- L1-2
3. C6-EDH- L1-3
4. C6-EDH- L1-4
5. C6-EDH- L1-5
6. C6-EDH- L1-6
7. C6-EDH- L1-7
8. C6-EDH- L1-8

Control:-

Revision 4

Page 10

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Electric Duct Heater control - DDC will provide Analog Output to Thyristor based on demand. (
Heater is modulated based on demand)
Electric Duct Heater on / off control (without thyristor)

Monitor & Alarm:-

Space Temperature - via Wall Plate Temperature Sensor (TS-1101-WA-10-AA) (Monitor)


High Temperature Cut-Off (General Alarm)
Heater Trip Status - VFC from Heater Control Panel (Alarm)

Control Sequence:-

Electric Duct heater shall maintain the laboratory room temperature via room mounted temperature
sensor. Warning messages are initiated if Heater Temperature is very high (High Temperature cut-off
/ General Alarm) & Heater trip status.

Graphics:

Graphics shall monitor, control and generate alarm as indicated in this sequence of operation.

Fire detection:

Upon receipt of signal from FACP, all energized Electric Duct Heater shall de-energized.

Power failure:

BMS will have all the information saved in the server during any abnormal power failure condition
irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start the normal
operation as soon as the power supply is available.

Revision 4

Page 11

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)

EXHAUST FAN (EF)


1. C6-EF-L4-01
2. C6-EF-L4-02
3. C6-EF-L3-03
4. C6-EF-L4-04
5. C6-EF-L3-05
6. C6-EF-L4-06
7. C6-EF-L3-07
8. C6-EF-L4-08
9. C6-EF-L4-09
10.C6-EF-L3-10

Control and Command:

Exhaust Fan On/Off Command

Monitor & Alarm:-

Exhaust Fan trip status (Alarm)


Air Flow status - (Diff. Pressure switch) (Alarm)
Fan Automatic position (Monitor)

Control Sequence:

Exhaust Fan shall Start /Stop automatically based on adjustable time program or as per demand of the
operator. Warning shall be initiated for fan status absence (via differential pressure switch) and alarm
for exhaust fan trip status.

Graphics:

Revision 4

Page 12

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Graphics shall monitor, control and generate alarm as indicated in this sequence of operation including
all the control points.

Fire detection:

Exhaust fan shall run upon receipt of signal from FACP.

Power failure:

BMS will have all the information saved in the server during any abnormal power failure condition
irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start the normal
operation as soon as the power supply is available.

Hand mode:

The unit can be controlled and monitored from the MCC panel via push buttons available on the
panel.Trip,Start/Stop,Running indications are provided in the MCC panel.BMS will have all the
details/control/data points saved in the server during the switching from remote mode to hand mode.
As soon it is switched back to remote mode, BMS will return to normal operating condition.

FUME CUPBOARDS
1. C6-FC-L1-01
2. C6-FC-L1-02
3. C6-FC-L1-03
4. C6-FC-L1-04

Control:-

Fume Exhaust Fan On/Off Command

Revision 4

Page 13

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Monitor & Alarm:-

Fume Exhaust Fan Trip Status


Fume Cupboard Fault indication (including no airflow)

Control Sequence:

Fume exhaust fan shall start automatically based on adjustable time program used for C6-AHU-L2-02
to ensure room pressure is maintained. Warning messages are initiated for Fume Exhaust Fan trip
status and Fume Cupboards Fault indication including no airflow.

Graphics:

Graphics shall monitor, control and generate alarm as indicated in this sequence of operation.

Fire detection:

Receiving signal from FACP in Fire Mode Condition during Fire. Fume Cupboard Exhaust fans are in
running mode over ride the existing programmed.

Power failure:

BMS will have all the information saved in the server during any abnormal power failure condition
irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start the normal
operation as soon as the power supply is available.

FAN COIL UNITS


1. C6-FCU-L0-01
Revision 4

2. C6-FCU-L1-26
Page 14

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
3. C6-FCU-L0-02

4. C6-FCU-L2-11

5. C6-FCU-L0-03

6. C6-FCU-L2-12

7. C6-FCU-L0-04

8. C6-FCU-L2-13

9. C6-FCU-L0-05

10. C6-FCU-L2-14

11. C6-FCU-L0-06

12. C6-FCU-L2-15

13. C6-FCU-L0-07

14. C6-FCU-L2-16

15. C6-FCU-L0-08

16. C6-FCU-L2-17

17. C6-FCU-L0-25A

18. C6-FCU-L2-18

19. C6-FCU-L0-25B

20. C6-FCU-L2-25M

21. C6-FCU-L0-25C

22. C6-FCU-L2-25L

23. C6-FCU-L0-25D

24. C6-FCU-L2-25K

25. C6-FCU-L1-09

26. C6-FCU-L3-19

27. C6-FCU-L1-10

28. C6-FCU-L3-20

29. C6-FCU-L1-25F

30. C6-FCU-L3-21

31. C6-FCU-L1-25G

32. C6-FCU-L3-22

33. C6-FCU-L1-25H

34. C6-FCU-L3-23

35. C6-FCU-L1-25J

36. C6-FCU-L3-24

Monitor, Alarm and Control:-

The space temperature of fan coil units are monitored by Thermostat (Microset II MS-2000BT) (Monitor)
Cooling Valve open / close Control
Supply Fan On/Off command and fan speed Command (low, medium and High)
Differential pressure switch for filter and supply fan (Alarm)
End of line measurement (Differential pressure sensor) ( 1 no. FCU) (Monitor)

Control Sequence:-

The temperature set point (22 deg) can be adjusted through thermostat. The three speeds of fan can
also be selected through thermostat. Through digital display of the thermostat we can monitor the

Revision 4

Page 15

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
space temperature, temperature set point, the selected fan speed, outside air temperature and outside
air humidity.
The difference between the set point and space temperature is used to produce a cooling signal.The
two port valve (VCZAF1100/E) in the chilled water line is Open/ Closed by the valve actuator
(VC2011ZZ00/E) in response with cooling signal by the controller.The valve will be fully closed when
FCU is stopped. Fan Coil Unit shall automatically start /stop based on an adjustable time program or
by operator request.
For Fan Coil Units serving Server room, MTR, FTR and switch Room.
Provide alarm for room temperature 3 degrees above setpoint.
Shall be programmed to operate 24hrs a day and 7 days a week.
Repeatable warning message for filter block indication and no airflow

Remote monitoring/control:The temperature set point and the speeds can be adjusted from the BMS PC also the fan run time can
also be displayed.

Graphics:-

Graphics shall monitor and generate alarm as indicated in this sequence of operation.

Power failure:-

BMS will have all the information saved in the server during any abnormal power failure condition
irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start the normal
operation as soon as the power supply is available.

VAV,VAV-H & CAV

Building Name

VAV (Qty in Nos)

VAV- H

CAV without Heater (Qty in


Nos)

Revision 4

Page 16

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
BLDG. 3A

27

157

Control:-

Damper Open/Close Command


Heater On/off Command

Monitor & Alarm:-

Room Temperaturer Sensor (Microset II)


Heater General Alarm
Heater Trip Status

Control Sequence:

VAV Operation:
a) Modulate to open when the room temperature is above room setpoint.
b) Modulate to close (at 70% close or 30% open) when the room temperature is below room
setpoint.
c) When VAV is closed manually via thermostat, VAV shall be fully closed.
Heater Operation.
a) Activated only during Winter and deactivated during summer.
b) During winter, when the VAV Damper closed (30%) due to room temperature is below
room setpoint, electric duct heater shall be activated to maintain the room setpoint and
room temperature same.
c) Heater shall be de-actvated during unoccupied period by program.
CAV Operation:
a) CAV Damper shall maintain the specified airflow.

Graphics:

Revision 4

Page 17

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Warning messages are initiated for hi/low temparture. Graphics shall monitor, control and generate
alarm as indicated in this sequence of operation including all the control points.

Fire detection:

Receiving signal from FACP in Fire Mode Condition during Fire . All VAV system will fully shut off
except VAVs serving corridor areas which will fully open to maintain pressure in the corridor. Heater
deactivated.

Power failure:
BMS will have all the information saved in the server during any abnormal power failure condition
irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start the normal
operation as soon as the power supply is available.

ELECTRICAL SYSTEM
Electrical Equipment's

3A

Power Meter

MCC/EMCP/MCP

MDB

Control

BMS only monitors the Panel.

Monitor & Alarm:-

Main Incomming status (Monitor)


Revision 4

Page 18

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Main Incomming Trip status (Alarm)
Main Incomming General Alarm

Graphics:

Graphics shall monitor and generate alarm as indicated in this sequence of operation including all the
control points.

Power failure:

BMS will have all the information saved in the server during any abnormal power failure condition
irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start the normal
operation as soon as the power supply is available.

PLUMBING SYSTEM
Monitor:-

Domestic water flow sensor

Graphics:-

Graphics shall monitor Domestic Water Flow.

Power failure:-

Revision 4

Page 19

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
BMS will have all the information saved in the server during any abnormal power failure condition
irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start the normal
operation as soon as the power supply is available.

FM 200 System:Control:
BMS only monitors the FM200 system.

Monitor & Alarm:-

Status Alarm

Graphics:

Graphics shall monitor and generate alarm as indicated in monitor and alarm.

Power failure:

BMS will have all the information saved in the server during any abnormal power failure condition
irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start the normal
operation as soon as the power supply is available.

CHILLED WATER SYSTEM


Monitor:-

Building Energy Consumption BTU Meter (Monitor)


Chilled Water Supply Pressure and Temperature (Monitor)
Chilled Water Return Pressure and Temperature (Monitor)
Revision 4

Page 20

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Operation:

Energy meter (With display screen and function keys) receive the temperature measurements and
the flow rate from the connected sensing devices and calculate accumulated, peak (via trend), and
actual thermal energy.
BMS network controller shall receive and store all data from DDCs and energy meter then send
these information to building 1C (The signal to tabreed plant from 1C will be sent via IT network
by the External Work Contractor if required).

Graphics:-

Graphics shall monitor as indicated in this sequence of operation.

Power failure:-

BMS will have all the information saved in the server during any abnormal power failure
condition irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start
the normal operation as soon as the power supply is available.

ELEVATOR SYSTEM
BLDG. 3A : 2 nos.

Control:

BMS only monitors the Elevators.

Monitor & Alarm:-

Out of Service - (VFC From Control Panel) (Alarm)


Revision 4

Page 21

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Power Failure - (VFC From Control Panel) (Alarm)
Run Status (Monitor)

Graphics:
Graphics shall monitor and generate alarm as indicated in this sequence of operation including all the
control points.

Fire detection:

Receiving signal from FACP in Fire Mode Condition during Fire . Elevator will homing upon
received signal from FACP

Power failure:

BMS will have all the information saved in the server during any abnormal power failure condition
irrespective any accidental shut down of the BMS PC directly/manually. BMS shall start the normal
operation as soon as the power supply is available.

COMPRESSED AIR SYSTEM


Monitor & Alarm: Compressor # 1 Fault (Alarm)
Compressor # 2 Fault (Alarm)
Pressure fault (Alarm)

VACUUM AIR SYSTEM

Revision 4

Page 22

UAE UNIVERSITY NEW CAMPUS PPP DEVELOPMENT, AL AIN


BMS NARRATIVE (STAGE 1 BUILDING 3a)
Monitor & Alarm: Plant Fault (Alarm)
Plant Emergency (Alarm)
Pressure Fault (Alarm)

L.P.G SYSTEM
Monitor & Alarm:-

Right Bank 50% (Monitor)


Left Bank 50% (Monitor)
Pressure Fault (Alarm)
Gas Leak (Alarm)
...............END..............