Beruflich Dokumente
Kultur Dokumente
'0'\00
~j\~IJ
t..~,:..\IJ J~)L\
~I
~;'.~\~Iw~I~\
SECTION 15955:
31/01/06
REV
DATE
KINGDOM
OFSAUDIARABIA
RoyalCommission
forJubail&Yanbu
DESCRIPTION
PREPARED BY
c4~~1
cw.
RC APPROVED
~}iJ1 i61ooJ1
4 W 4#JoJ Id4fJ 1
SECTION 15955
TESTING, ADJUSTING AND BALANCING
TABLE OF CONTENTS
Item No
Title
PART 1
GENERAL............................................................................................................ 1
1.01
1.02
1.03
1.04
REFERENCES..................................................................................................... 2
1.05
DEFINITIONS ...................................................................................................... 3
1.06
SUBMITTALS....................................................................................................... 3
1.07
1.08
1.09
DESIGN CRITERIA6
1.10
JOB CONDITIONS............................................................................................... 6
1.11
PART 2
PRODUCTS ......................................................................................................... 8
2.10
INSTRUMENTS ................................................................................................... 8
2.11
MATERIALS......................................................................................................... 9
PART 3
EXECUTION ...................................................................................................... 11
3.01
PROCEDURE .................................................................................................... 11
3.02
PREPARATION ................................................................................................. 12
3.03
3.04
3.05
3.06
3.07
INSTRUCTIONS ................................................................................................ 25
3.08
Rev 0
Page No
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
PART 1
GENERAL
Testing, adjusting, and balancing (TAB) is the process of checking and adjusting all
environmental systems in a building to produce the design objectives. This process
includes balancing air and water distribution systems, adjusting the total system to
provide design quantities, electrical measurement, establishing quantitative
performance of all equipment, verifying automatic control system operation and
sequences of operation and sound and vibration measurement. These procedures
are accomplished by checking installations for conformity to design, measuring and
establishing the fluid quantities of the system as required meeting design
specifications, and recording and reporting the results.
B.
This Section covers the measurement and setting of air and water flow facilities
provided or specified for the systems, recording data, making tests and preparing
reports. The work in this Section shall not be commenced until the completion of the
air and water systems.
Testing, Adjusting and Balancing of Air Systems: All pressures ranges including
supply air, return air, make-up fresh air, exhaust air, for constant volume, variable
volume, single duct and dual duct system.
B.
C.
Rev 0
A.
Section 01320
B.
Section 01330
Submittal Procedures
C.
Section 01410
Regulatory Requirements
D.
Section 01450
Quality Control
E.
Section 01650
F.
Section 01660
G.
Section 15070
H.
Section 15180
I.
Section 15620
J.
Section 15670
1 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
K.
Section 15730
L.
Section 15810
Duct
M.
Section 15820
Duct Accessories
N.
Section 15830
Fan
O.
Section 15840
P.
Section 15850
Q.
Section 15860
R.
Section 15900
1.04 REFERENCES
A.
The referred codes and standards are intended to provide an acceptable level of
quality for materials, products and workmanship. In case of conflict between these
standards and the text of this Specification, the Specification text shall govern.
B.
The latest revision of the referred codes and standards shall be used wherever
applicable. In case of conflict, the Contractor shall propose equipment, materials and
processes conforming to one group of codes and standards.
C.
SASO
D.
1.
SASO 381
2.
SASO 382
3.
SASO 385
AABC
1.
E.
Rev 0
ASHRAE
1.
ASHRAE 111
2.
ASHVE
3.
ASHRAE
Handbook of Fundamentals
2 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
4.
F.
G.
ANSI
HVAC Applications
American National Standards Institute
1.
ANSI S1.4
2.
ANSI S1.11
NEBB
1.
H.
ASHRAE
SMACNA
1.
SMACNA
Air
Conditioning
Contractors
National
1.05 DEFINITIONS
A.
adjust: To regulate the specified fluid flow rate and air patterns at the terminal
equipment, (e.g., reduce fan speed, throttling).
B.
balance: To proportion flows within the distribution system (sub-mains, branches and
terminals) in accordance with specified design quantities.
C.
D.
E.
main: Duct or pipe containing the systems major or entire fluid flow.
F.
G.
report forms: The data sheets arranged for collection of test data in logical order for
submission and review. Data should also form the permanent record which shall be
used as the basis for any future testing, adjusting and balancing required.
H.
sub-main: Duct or pipe containing part of the systems capacity and serving two or
more branch-mains.
I.
1.06 SUBMITTALS
A.
Rev 0
The Contractor shall submit to the Royal Commission, under the provisions of
SECTION 01330, the following items for review and approval before commencing
Work:
3 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
1.
2.
Testing Organization
a)
The Contractor shall submit the name of the independent testing and
balancing organization he proposes to employ within 60 days after
Contract award.
b)
Preliminary Report
a)
3.
Agenda
a)
4.
General description of each air and water system with its associated equipment and operation cycles for heating, intermediate
and cooling. Where different cycles are used for day and night,
they shall be described separately.
2)
A complete listing of all air and water flow and air terminal
measurements to be performed e.g. P & I Diagram, Schematic
Diagram, etc.
3)
4)
Procedure Reporting
a)
Rev 0
The Contractor shall submit specific test procedures for measuring air
and water quantities at terminals shall specify type of instrument to be
used, method of instrument application (by sketch) and factors for:
1)
2)
3)
Velocity corrections.
4)
4 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
5)
5.
6.
7.
Density correction
elsewhere).
(unless
applicable
data
are
covered
Report Forms
a)
b)
Forms shall be letter size paper for loose leaf binding, with blanks for
listing of the required test ratings and for certification of report.
c)
Final Report
a)
b)
The Contractor shall be responsible for the quality of work and shall develop and
propose programs and methods of construction and testing such as to achieve the
specified quality to the approval of the Royal Commission in accordance with
SECTION 01450.
B.
The Contractor shall maintain a qualified representative on-site during all operations,
in accordance with SECTION 01450.
C.
The codes and standards as specified in par. 1.04 are intended to provide an
acceptable level of quality for materials and products. The Contractor may propose
alternative codes and standards provided they give an equivalent degree of quality
as the referenced codes and standards and are submitted for the Royal Commission
review and approval in advance of their use.
Rev 0
5 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
1.
2.
3.
Contractor
a)
B.
In the absence of any of the above, best accepted industry practice shall be
employed throughout.
Rev 0
General Criteria
1.
2.
3.
B.
C.
Qualification
1.
2.
6 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
3.
D.
Procedures
1.
2.
System Operation
1.
B.
Re-adjustments
1.
2.
Corrective measures, other than the above, shall be made only as directed by
and at no additional expense to the Royal Commission.
Rev 0
The Contractor shall deliver, handle and store equipment and material units in
accordance with SECTIONS 01650 and 01660, as well as the following
requirements:
1.
2.
Store equipment and control devices in their factory shipping boxes to prevent
equipment damage and to eliminate dirt and moisture from equipment.
3.
4.
Do not operate units until ductwork is clean, filters are in place, bearings
lubricated and fan has been test run under observation.
7 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
PART 2
PRODUCTS
2.01 INSTRUMENTS
Rev 0
A.
All goods and products covered by these Specifications shall be procured, when
available, from an in-Kingdom manufacturer. Procurement of all goods manufactured
out-of-Kingdom must be approved by the Royal Commission.
B.
The minimum instrumentation for adjusting, testing, and balancing shall be the
"AABC Approved Minimum Field Instrumentation."
C.
2.
3.
4.
5.
6.
7.
Flow hood.
8.
9.
Sound level meter with octave band filter set, calibrator and microphone.
10.
Vibration analyzer
acceleration.
11.
12.
Compound gage.
13.
Test gages; 690 kPa (100 psi) and 2070 kPa (300 psi).
14.
Sling psychrometer.
15.
16.
Hygrometers.
17.
18.
Velometer.
capable
of
8 of 38
measuring
displacement
velocity
Contract No:
and
SECTION 15955
TESTING, ADJUSTING AND BALANCING
D.
The devices needed to successfully balance hydronic system may consist of all or
some of the following:
1.
2.
3.
4.
5.
6.
Balancing valve with a factory-rated flow coefficient Cv, a flow versus handle
position and pressure drop table or a slide rule flow calculator.
7.
8.
E.
Instruments used for adjusting, testing and balancing must have been calibrated
within a period of 6 months and checked for accuracy prior to start of work.
F.
G.
Balancing Devices
1.
2.
3.
Pressure drop across equipment is not an accurate flow measurement but can
be used to determine if the manufacturer design pressure is within specified
limits.
4.
2.02 MATERIALS
Rev 0
A.
B.
9 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Rev 0
physical
Complete descriptive literature, such as drawings, specifications and rating data shall
be submitted for approval prior to purchasing.
10 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
PART 3
EXECUTION
3.01 PROCEDURE
A.
Methodology
1.
B.
Requirements
1.
2.
3.
4.
5.
6.
7.
Accuracy of all thermometers shall be plus or minus graduation at the temperatures to be measured. Graduation shall conform to the following schedule:
TABLE 3A: THERMOMETER GRADUATIONS
Medium
Air
Water
Rev 0
Design Temperature
Differential (C)
5
>5
<5
5 - 10
> 10
11 of 38
5
/100
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
C.
Test Duration
1.
Operating tests of heating and cooling coils, fans and other equipment shall be
of not less than 4 hours duration after stabilized operating conditions have
been established.
2.
3.02 PREPARATION
A.
Air System
1.
B.
Prior to system adjusting, testing and balancing, the Contractor shall do the
following:
a)
b)
c)
d)
e)
Determine best locations in main and branch ductwork for most accurate
duct traverses.
f)
Ensure dampers of outlet and inlet devices are in the full open position.
g)
h)
i)
j)
Hydronic System
1.
Prior to system adjusting, testing and balancing, the Contractor shall do the
following:
a)
Rev 0
2)
3)
12 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
4)
5)
6)
7)
8)
2.
Open all valves to full position. Close coil bypass stop valves set mixing valves
to full coil flow.
3.
4.
Examine water in system and determine if water has been treated and
cleaned.
5.
6.
Clean and set automatic fill valves for required system pressure.
7.
Check expansion tanks to determine that they are not air bound and the
system is completely full of water.
8.
Check air vents at high points of water systems and determine if all are
installed and operating freely.
9.
Set all temperature controls of all coils requiring full cooling. Execute similar
procedures when balancing hot water coils set for full heating.
10.
11.
12.
13.
14.
Ensure that the testing and balancing engineer review execution reports to
check that the water and pneumatic piping were tested for leakage.
Air Systems
1.
Place all supply, return and exhaust fans in operation and check
the following:
(a)
Rev 0
13 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Rev 0
(b)
Fan rotation.
(c)
(d)
(e)
(f)
(g)
(h)
2)
3)
Set the system for balance with outdoor air dampers positioned
for minimum outdoor air.
4)
(b)
(c)
(d)
(e)
(f)
14 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
2.
3.
Rev 0
Check the leaving air temperature at the nearest terminal to verify that
the hot and cold damper inlet leakage is not greater than the maximum
allowable leakage established.
b)
c)
d)
e)
Put the control settings to full heating and check the proper functioning
of the controls and dual-duct boxes. Spot-check the airflow at several
outlets. Check for stratification.
f)
Establish the ratio of the design volume through the cooling coil to the
total fan volume to achieve the desired diversity factor. Keep the
proportion of cold to total air constant during the balance. Check each
zone or branch with this component on full cooling. If the design calls for
full flow through the cooling coil, the entire system should be set to full
flow through the cooling side while making tests. Perform the same
procedure for hot air side.
b)
Fan curves.
2)
3)
Data pertaining to the de-aeration of the fan when used with inlet
vortex damper.
4)
5)
c)
d)
Position the terminal boxes to the proportion of the maximum fan air
volume to total installed terminal maximum volume.
15 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
4.
B.
f)
Run a total air traverse with a Pitot tube. Increase the speed if static
pressure and/or volume are low. If the volume is correct, but the static
pressure is high, reduce the speed. If the volume is low but the static
pressure is correct or high, check for the system effect at the fan. If
there is no system effect, adjust all boxes to the proper volume.
g)
Proportion the outlets and verify the design volume with VAV boxes on
the maximum flow setting. Verify the minimum flow setting. Set the
terminals to the minimum and adjust the inlet vane or speed controller
until minimum static pressure and airflow are obtained.
h)
Ensure that the final placement of the static pressure controller sensor
shall be in representative location in the supply duct to sense the
average maximum and minimum static pressures in the system, this
location shall be agreed by testing and balancing engineer and design
engineer.
i)
Check the return air fan speed or its inlet vane damper that tracks or
adjusts to the supply fan airflow to ensure proper outside air volume.
j)
Operate the system on 100% outside air and check supply and return
fans for proper power and static pressure.
Induction System
a)
b)
Determine the primary airflow at each terminal unit by reading the unit
plenum pressure with a manometer and locating the point on the
manufacturer charts or curves of air quantity versus static pressure.
c)
d)
Adjust the fan to run at the lowest speed that provides sufficient nozzle
pressure to all units with minimum throttling of all units and riser
dampers to provide quietest possible operation.
e)
Hydronic System
1.
Rev 0
e)
16 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
referenced standard.
2.
3.
4.
b)
c)
d)
Rev 0
The system has been flashed out, cleaned and all air is out.
2)
All manual valves are open or are in operating positions and all
automatic valves are in their proper position and operative.
3)
b)
c)
Examine the flow diagram and piping for obvious short circuits, check
flow and adjust balancing valves.
d)
e)
Record the readings of each pump motor amperage and voltage, and
determine approximate power.
f)
For each pump establish pump curve and determine the approximate
flow rate.
g)
If total flow station exists determine the flow and compare it with pump
curve flow.
h)
Set the total flow (if possible) 10% high using the total flow station first
and the pump differential pressure second; then maintain pumped flow
to a constant value as balance proceeds by adjusting the pump throttle
valve.
17 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
C.
Rev 0
i)
If branch main flow stations exist, these shall be tested and set, starting
by setting the shortest runs low as balancing proceeds to the longer
branch runs.
j)
k)
Perform sound and vibration tests for all mechanical equipment and systems
including standby equipment for both summer and winter operations in
accordance with referenced standard and the following general procedure.
2.
b)
c)
d)
Before final sound measurements for any particular area, survey all
areas using an A-weighted scale reading (dBA) to determine the
location of highest sound pressure level. Indicate this location on testing
form and use it for test measurements. Restrict the preliminary survey to
determine location of test measurements to areas, which will be
occupied by standing or sitting persons. Measurements shall not be
made directly close to ceiling air outlets but as close to the outlets as
standing or sitting persons might be situated.
e)
f)
g)
18 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
3.
4.
5.
Rev 0
Both vibration levels of the equipment and their isolation system shall be
tested to insure that equipment is operating within satisfactory vibration
level and the objectionable vibration and noise are not transmitted to the
building structure.
b)
Make a visual check of all equipment for obvious errors that must
be corrected immediately.
2)
Make sure that all isolation systems are free floating and not short
circuited by any obstruction between equipment or equipment
base and building structure.
3)
4)
5)
6)
b)
c)
d)
Operate equipment and make visual and aural checks for any apparent
rough operation. Bearing or any other component defect shall be
corrected before the equipment is considered acceptable.
e)
Measure and record on the test form vibration at bearing of driving and
driven components in horizontal, vertical and if possible axial directions.
There shall be at least one axial measurement for each rotating
component.
f)
19 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
6.
7.
2)
3)
Perform testing, adjusting and balancing procedures on each air or water system
identified, in accordance with the detailed procedures described in the referenced
standards.
B.
Cut insulation, ductwork and piping for installation of test probes to minimum extent
necessary to allow adequate performance of procedures.
C.
Patch insulation, ductwork and housings using materials identical to those removed.
D.
Seal ducts and piping, and test for and repair leaks. Seal insulation to re-establish
integrity of the vapor barrier.
E.
Mark with paint or other suitable permanent identification materials to show final
settings of equipment, dampers control positions, valves indicators, fans speed.
F.
Air system balancing report shall include at least the following information:
1.
Rev 0
Design
a)
b)
c)
Motor power.
d)
Outside air percentage under minimum conditions for each air handling
unit.
20 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
2.
3.
4.
5.
Rev 0
e)
Fan speed.
f)
Installation
a)
b)
c)
d)
Fan class.
e)
Field Tests
a)
Fan speed.
b)
c)
d)
e)
f)
Terminal Outlets
a)
b)
c)
d)
e)
b)
c)
21 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
6.
B.
d)
Filter type and static pressure at the initial use and full load time to
replace.
e)
f)
b)
Branch duct static readings in the double duct and induction system.
c)
d)
e)
f)
Water system balancing report shall include at least the following information:
1.
Pumps
a)
b)
c)
Rev 0
Installation Data
1)
2)
Size.
3)
Type drive.
4)
Design Data
1)
Flow in L/s.
2)
Head.
3)
R/min.
4)
Recorded Data
1)
2)
Suction.
3)
Operating head.
4)
22 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
2.
b)
Full-flow amps.
7)
No-flow amps.
Installation Data
1)
2)
Flow in L/s.
3)
4)
Recorded Data
1)
2)
3)
4)
5)
Design Data
1)
2)
3)
4)
5)
6)
b)
Rev 0
6)
4.
3.
5)
Installation Data
1)
2)
3)
4)
2)
23 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
C.
3)
4)
Amperes.
The certified report shall record data on sound levels, taken at each selected
location, as follows:
a)
b)
c)
d)
2.
2)
2)
e)
f)
Re-Test
a)
3.
1)
The certified report shall record all sound data, and their locations, after final
adjustments of air and water systems involved.
Scope
1.
Rev 0
B.
At the time of final inspection, the Contractor shall recheck, in the presence of the
Royal Commission, random selections of data (water and air quantities, air motion
and sound levels) recorded in the certified report. In addition, all courtrooms,
auditoriums and conference rooms shall be rechecked. All laboratories shall be
rechecked for satisfactory air flow and motion in vicinity of and through hoods.
C.
Points and areas for recheck shall be selected by the Royal Commission.
24 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
D.
Measurement and test procedures shall be the same as approved for work forming
basis of certified report.
E.
Selections for recheck (specific plus random), in general, will not exceed 25% of the
total number tabulated in the report, except that special air systems may require a
complete recheck for safety reasons.
F.
Re-Tests
G.
1.
2.
In the event the report is rejected, all systems shall be readjusted and tested,
new data recorded, new certified reports submitted and new inspection tests
made, all at no additional cost to the Royal Commission.
Marking of Settings
1.
2.
3.
Checkout cards shall be standard 127 x 203 mm index cards enclosed in clear
film card holder securely attached to equipment or wall in immediate area.
4.
3.07 INSTRUCTIONS
Rev 0
A.
The testing and commissioning engineer shall instruct the Royal Commission's
personnel in the proper setting and adjustment of the equipment.
B.
Train owners maintenance staff on testing, adjusting and balancing procedures and
troubleshooting procedures. Review with the staff operating and maintenance
specified in Divisions 1 and 15.
C.
Permanently installed instruments used for tests (e.g. gages and thermometers) shall
be installed just prior to the tests to avoid damage and changes in calibration.
D.
Schedule training with owner through the engineer with at least 7days prior notice.
25 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Rev 0
Cover Sheet.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
Octave Band Sound Pressure Levels Associated with the Noise Criterion (NC)
Curves.
26 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
CONTRACT NO:
_________________________
CONTRACT TITLE:
_________________________
ARCHITECT/ENGINEER :
_________________________
Rev 0
27 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Form No. 1
Address___________________________________
Specified
Actual
Specified
Actual
Specified
Actual
Specified
Actual
Rated
Running
Rated
Running
Rated
Running
Rated
Running
Total L/s
Return Air L/s
O.S.A L/s
Total Static Pressure
Pa
Suction Pressure Pa
Discharge Pressure
Pa
Fan Sheave
Belts
Motor Manufacturer
Size
Voltage
Phase
RPM Motor
Amperage
RPM
Entering Dry bulb C
Entering Wet bulb C
Leaving Dry bulb C
Leaving Wet bulb C
Rev 0
28 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Form No. 2
Fan No.
Mfg.
Size
Motor HP
Voltage
Actual Voltage
Amp Rating
Actual Amps
Actual r/min
Actual RPM
Required SP
Actual SP
Required L/s
Actual L/s
Fan Sheave
Motor Sheave
Belts
Rev 0
29 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Form No. 3
Job Name____________________________
Date________________
Sheet No. ___________
Address_______________________________
Room
No.
Rev 0
Outlet
No.
Size
AK Factor
Design Data
m/s
L/s
Vel
30 of 38
Test Data
m/s
Vel
L/s
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Form No. 4
Address________________________________
Design Condition
Unit
Final Balance
Cooling
ENT
ENT
LV
LV
AIR
AIR
AIR
AIR
D.B
W.B
D.B
W.B
ENT
WATER
Rev 0
Heating
LV
WATER
O.S.A
TEMP
ENT
LV
AIR
AIR
D.B
D.B
ENT
WATER
Cooling
LV.
WATER
ENT
ENT
LV
LV
AIR
AIR
AIR
AIR
D.B
W.B
D.B
W.B
31 of 38
ENT.
WATER
Heating
LV
O.S.A
ENT.
LV
ENT.
LV.
WATER
TEMP
.
AIR
AIR
WATER
WATER
D.B.
D.B.
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Form No. 5
Address____________________________________________________
Rev 0
Serving
Pump
Mfg.
Model
No.
Motor
Mfg
H.P.
32 of 38
Volts
Ph.
Amps
Tested By:__________________________________________________
Specs. Req.
L/s
T.D.H.
Running
Amps
Contract No:
Pressure
Diff.
Final
T.D.H.
Meters
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Form No. 6
PUMP AND COOLING TOWER DATA SHEET
Testing and Balancing Agency:_____________________________________________
Pump: ______________________________ Date: _____________________________________
Contract No:__________________________ Contract Name: ____________________________
Pump #: _____________________________ Data: ____________________________________
Manufacturer: __________________________________________________________________
Model: ______________________________ Serial: ____________________________________
Size: _______________________________ Capacity: L/s _____________ Head ____________
Motor Manufacturer: _____________________________________________________________
Motor HP: ______________________ r/min: ________________ Phase: ___________________
Voltage: 480 __________ 440 __________ 220___________ 208 __________ Other__________
Full Load Amps: _______________________ Rating: ________________ to ________________
Discharge Head: ____________________kPa.
Cooling Tower:
Tower identification number: ________________ Model No. ____________ Serial No. _________
Manufacturer:__________________________________ Rated Capacity: ___________________
Entering Air WB temp. (specified): __________ Entering Air WB temperature (actual): _________
Leaving Air WB temp. (specified): ___________Leaving Air WB temperature (actual): _________
Ambient Air DB temperature: ___________________________________
Condenser water entering temp.: ___________ Condenser water leaving temperature: ________
Condenser water flow rate: __________________________ Fan RPM: ____________________
Rev 0
33 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Form No. 7
CHILLER & AIR COOLED CONDITIONING CONDENSER DATA
Date ___________________
Sheet No. _________________
Job Name: ______________________________ Address: _____________________________
Testing & Balancing Agency: _____________________________________________________
Chiller #: _______________Data: ________________ Chiller type: ______________________
Manufacturer: ________________________________________________________________
Model: __________________ Serial #: ________________ Capacity: ____________________
Evaporator entering water temp. (design): _____Evaporator entering water temp. (actual): ____
Evaporator leaving water temp. (design): ______Evaporator leaving water temp. (actual): ____
Evaporator pressure drop (design): _________ Evaporator pressure drop (actual): _________
Evaporator water flow rate (design): ________ Evaporator water flow rate (actual): _________
Condenser entering water temp. (design): ____ Condenser entering water temp.(actual): _____
Condenser pressure drop (design): _________ Condenser pressure drop (actual): __________
Condenser water flow rate (design): _________ Condenser water flow rate (actual): _________
Motor: Manufacturer: __________________ HP: _____________ r/min: __________________
Voltage: ______________________ Phase: ________________ Full Load Amps: __________
Heaters: __________________ Rating: __________to ___________ Fuse Size: ___________
Head Pressure: __________________________ Suction Pressure: ______________________
========================================================================
Air Cooled Condenser #: ______________Data: _______________ Serial #: _______________
Manufacturer: _________________________________________________________________
Model: ___________________________________ Serial #: ____________________________
Motor Manufacturer: _______________________ HP: _______________ r/min: ____________
Voltage: ______________________ Phase: ______________ Full Load Amps: ____________
Operating Amps: ______________________________________________________________
Belt Drive: Motor: ________________ Fan: _________________ Belts: ___________________
Fan Dia.: _______________ Propeller: _____________ Centrifugal: _________r/min: _______
DB Air On Condenser: _____________________ DB Air Off Condenser: _________________
Entering DB air temp. (design): _____________ Entering DB air temp. (actual): _____________
Leaving DB air temp. (design): _____________ Leaving DB air temp. (actual): ______________
Compressor Data: _________________________________ No. of Compressors: ___________
Rev 0
34 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Form No. 8
SOUND LEVEL REPORT
Date ___________________
Sheet No. _______________
Job
Name__________________________________
Address___________________________
Rev 0
Check
Point
Equipment Off
B
35 of 38
Equipment On
B
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Form No. 9:
DUCT TRAVERSE SHEET
ZONE TOTALS
Job Name_________________________________
Date________________
Sheet No. ___________
Address_____________________________
Zone
No.
Rev 0
Duct
Size
Effective
Area
Required
Velocity
Actual
Test
Velocity
Required
L/s
36 of 38
Actual
Test L/s
Average
Vel. pressure
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Address _________________________________
Velocity
Pressure
Velocity
Reading
Duct
Position
Velocity
Pressure
Velocity
Reading
Duct
Position
Velocity
Pressure
Velocity
Reading
Duct
Position
Rev 0
37 of 38
Contract No:
SECTION 15955
TESTING, ADJUSTING AND BALANCING
Address _________________________________
Noise
Criterion
Curve
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
47
51
54
57
60
64
67
71
74
77
80
125 Hz
Data
36
40
44
48
52
56
60
64
67
71
75
250 Hz
500 Hz
1000 Hz
2000 Hz
4000 Hz
Actual Data Actual Data Actual Data Actual Data Actual Data Actual Data Actual
29
33
37
41
45
50
54
58
62
67
71
22
26
31
35
40
45
49
54
58
63
68
17
22
27
31
36
41
46
51
56
61
66
14
19
24
29
34
39
44
49
54
59
64
12
17
22
28
33
38
43
48
53
58
63
END OF SECTION
Rev 0
8000 Hz
38 of 38
Contract No:
11
16
21
27
32
37
42
47
52
57
62