Beruflich Dokumente
Kultur Dokumente
Slots
Slots
Term.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
Function Description
Power supply
Power supply
Status out COM PPU, System Healthy
Status out NO PPU, System Healthy
Relay 1 NO Open Breaker
Relay 1 COM Open Breaker
Relay 1 NC
Relay 2 NO Emergency Stop
Relay 2 COM Emergency Stop
Relay 2 NC Emergency Stop Relay 3 NO Circuit breaker trip
Relay 3 COM Circuit breaker trip
Relay 3 NC Circuit breaker trip Relay 4 NO Spare
Relay 4 COM Spare
Relay 4 NC Spare
Relay 5 NO Close Breaker
Relay 5 COM Close Breaker
Relay 5 NC
Optocoupler COM Spare Optocoupler OP 1 Spare Optocoupler OP 2 Spare Digital input CB Tripped
Digital input Emergency Stop Energized
Digital input CB Closed
Digital input CB Open
Digital input Air Flaps
Common J2 (0V)
Ferrule
K3
J2
K3
K102
GY12
GY3
K799
K905
C2
C1
GY10
GY3
K55
K797
X2
X3
K793
J2
Inputs
Input 24:
Input 25:
CB Closed, is energized high when the circuit breaker is in the closed position.
Input 26:
Emergency stop, will be energized high when the system is running normally,
this signal is required to keep relay 2 energized.
CB Open, is energized high when the circuit breaker is in the open position.
Input 27:
Air Flaps, this is energized high when the air flaps are closed.
Relays
5 relays are mounted in the power supply and binary I/O board in
slot #1.
The relays 1-5 are pre-configured.
Relay 1:
Relay 2:
Circuit Breaker Trip: This relay is energized closed to maintain the circuit breaker
under-voltage trip loop; if a circuit breaker trip is required by the PPU this will deenergize the contacts and trip the breaker
Relay 4:
Emergency Stop: This relay is energized closed to maintain the emergency stop loop;
if an emergency stop is required the PPU will de-energize these contacts and stop the
engine.
Relay 3:
Open Breaker, this relay will open the circuit breaker immediately when required
Spare.
Relay 5:
Circuit Breaker Open, this relay will close the circuit breaker if the conditions set in the
PPU are met.
Function Description
Can-H
GND
Can-L
Can-H
GND
Can-L
Not used
Not used
Term.
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
Function
Description Ferrule
Term.
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
Function
Description
Ferrule
Input 44
ECM Common Shutdown, this is an input from the ECM indicating a
common shutdown (not used on G3)
Input 45
AVR Over voltage, this is an input from the AVR indicating an over
voltage, normally this is set in the AVR.
Input 46
Excitation Loss, this is an input from the ACB indicating an excitation
loss on the stator.
Input 48
Engine Start, if the conditions are met energizing this input
momentarily (300ms+) will begin the engine starting cycle.
Input 49
Open Breaker Request, energizing this input will energize Relay 1
immediately; this function is not inhibited by any other component or
logic.
Input 50
Close Breaker request, this will begin synch and check synch the
generator as required and if programmed allow closing onto a
dead/black Busbar. Note: regardless of the operation of the panel
Manual/Auto/Remote etc, the PPU will always be in control of the
genset during the closing cycle of the breaker, thus preventing
uncontrolled breaker closing.
Input 51
Input 52
Speed Increase, energizing this input will increase the speed bias output from
the PPU, this is only possible if the Local Control is enabled.
Input 55
Manual/Auto Switch, this is the key switch input from the control panel that
allows the user to run the machine fully automatically.
Input 54
Remote Start, when the set is switched to auto and Local Control Off/ Remote
On , energizing this input will start the generator, subsequent loss of this signal
will then stop the machine.
Input 53
Local Control On, this input is used to allow remote control of the panel, either
via a SCADA system, or AT control system.
Speed decrease, energizing this input will decrease the speed bias output from
the PPU, this is only possible if the Local Control is enabled.
Input 56
Relay 7
Alarm Reset, this resets the alarms in the ECM
Relay 8
Close Air Flaps, this relay will energize the air flaps, when this close
signal is returned or the engine speed drops below 30Hz then the relay
will de-energize.
Term.
65
66
67
68
69
70
71
72
Function
Not used
+/-20 mA out
0
Not used
Not used
+/-20 mA out
0
Not used
Description
Speed governor set-point output
The current outputs are converted to voltage using a resistor across the terminals
(200ohm will convert the +/-20 mA into +/-4 VDC, for volts control),
(10 ohm will convert the +/-20 mA into +/ 0.2V for Barber Coleman Speed control with
the Cummins ECM)
For different governor control interface requirements please refer to Aggreko
international Product Support department for advise.
Technical data
Ferrule
Description
73
74
I L1 s1
I L1 s2
Generator current
L1
CR
CR2
1/5A AC input
75
76
I L2 s1
IL2 s2
Generator current
L2
CY3
CY2
1/5 A AC input
77
78
I L3 s1
I L3 s2
Generator current
L3
CB
CB2
1/5 A AC input
79
U L1
Generator voltage L1
GR3
80
81
Not used U L2
Generator voltageL2
GY3
82
83
Not used U L3
Generator voltageL3
GB3
Max. 690
VACphase
- phase value
84
U neutral
Generator voltage
neutral
GN2
For land-based
85
applications only
U L1
Bus voltage L1
LR2
86
87
Not used U L2
Bus voltage L2
LY2
Max. 690
VACphase
- phase value
88
89
Not used U L3
Bus voltage L3
LB2
Term.
90
91
92
93
94
95
96
97
Function
Common
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Description
Ferrule
Digital Input Common J2
Low Oil Level
K1048
Low Oil Pressure
K1050
High Water Temp
K1052
Volts Up
K1038
Volts Down
K1040
Mode Enable
K1036
Alarm reset
Term.
90
91
92
93
94
95
96
97
Function
Common
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Digital input
Description
Digital Input Common
High Water temp
Low Oil Pressure
Low Water press.
Volts Up
Volts Down
Mode Enable
Alarm reset
Ferrule
J2
K1048
K1050
K1052
K1038
K1040
K1036
Input 94-95
Energizing these inputs will instruct the PPU to vary the voltage level
accordingly, by changing the bias output on terminals 70 and 71 to the
AVR.
Input 96
Mode Enable, this changes the control from Manual to automatic, all
volts, speed, power and circuit breaker control are mode by the PPU
the logic is determined by the mode selection.
An engine interface board is mounted in slot #7. It consists of configurable inputs and outputs.
The configuration is done through the utility software and the default settings can be changed to the
relevant settings.
To configure the inputs, upload the parameter list from the PPU and select the input to be
configured. A configuration dialog box appears and the settings can be changed. The standard title
(e.g. 4-20mA in no. 1) can be changed, and the new title will also be shown in the display.
The minimum and maximum values of the 4-20mA input can be adjusted:
The inverse proportional function is used when the input has inverse proportionality according to
the measured value. This could for instance be when measuring a negative value.
The inputs can be used as a high or low alarm. As a high alarm the alarm appears when the
measured value is higher than the alarm limit, and as a low alarm the alarm appears when the
measured values are lower than the alarm limit.
The binary inputs use 24-volt constant signal. They are not pulse inputs.
S10
Function
Analogue input
Description
Ferrule
Analogue input
Analogue input
Analogue input
Analogue input
Analogue input
Analogue input
Analogue input
Pt100
Pt101
Pt102
Pt103
Pt104
Pt105
Function
Description
Ferrule
112
113
114
115
116
117
118
119
120
121
122
123
124
125
Tacho input
Tacho input
Digital input
Digital input
Digital input
Digital input
Digital input
Common
Relay 10 COM
Relay 10 NO
Relay 11 COM
Relay 11 NO
Relay 12 COM
Com.
Engine Speed
Engine Speed
Extern/intern set-point power
Extern/intern set-point voltage
Engine Stop
Fan Fail
Spare
Common
Speed Selection
Speed Selection
Engine Run
Engine Run
Engine Start/Crank
MP1
MP2
FF
J2
K725
K723
K705
K1062
K725
Input 114
Input 115
Fan Fail, this will go high if the engine cooling fan circuit breaker trips.
Input 118
Engine Stop, when energized this will begin the engine stopping cycle; the
genset will de-load (if this is not possible then the breaker will open after a set
period 30 seconds plus de-load time); the breaker will open; then the engine will
run for the preset cooling time, default 5 minutes before stopping.
Input 117
Extern/inter set-point voltage, when energized the unit will base its nominal
voltage level on a percentage of a 0-10V input on terminal 42.
Input 116
Extern/inter set-point power, when energized the unit will base its nominal power
level on a percentage of a 0-10V input on terminal 40.
Spare
Input 119
Relay 11
Engine Run, this is the engine run control relay, will close when the
engine is required to run, equivalent to the fuel control relay.
Relay 12
Engine Start/Crank Relay, required to start/crank the diesel generator
starter motor.