Beruflich Dokumente
Kultur Dokumente
Summary of LearningThe Transport lag increases with increase in distance from the heater.
The Transfer lag remains constant for the entire length of the tube.
In a two-step control, more is the set value implies more is the time required to
reach the steady state.
As gain increases, the time required to reach the steady state also increases.
As overlap increases, the frequency of the output wave decreases.
In the dynamic behaviour of the output, we observed that as gain increases the
output wave reaches the input wave more.
Characteristics of the system1. Transport Lag - It is the time lag we get in the output wave from the input
wave due to the distance that the heated air has to travel between the heater
and the point where we are measuring the temperature (output).
The values of transport lag as we move away from the heater are tabulated as
follows
Distance from the
heater
1.5 inches
6.5 inches
11.5 inches
Transport Lag
120ms
180ms
280ms
12.5 inches/sec
36.11 inches/sec
41.07 inches/sec
2. Transfer Lag-It is the time required by the output wave to reach the value
which is equal to 63.2 per cent of the amplitude of the input wave. Ideally it
remains constant throughout the length of the tube.
The values of transfer lag as we move away from the heater are tabulated as
follows
Distance from the
heater
1.5 inches
6.5 inches
11.5 inches
Input amplitude
2.64V
2.64V
2.64V
Transport Lag
800ms
760ms
700ms
As it can be seen from the above pictures the value of transfer lag remains
almost constant through the length of the tube.
On/Off ControlBefore this point our system was in an open loop. Now we give the output back as
feedback and see the time the output takes to reach approximately the
proportional band in steady state.
Observation- We observe that as we increase the set value the time taken by
the output wave to reach approximately equal to the proportional band
increases. Since this is a two-step control, as soon as the air is heated to the
required temperature the heater is switched off and again switched on when its
temperature goes below the set point and finally goes to steady state.
Explanation- This is so because more is the set value implies more is the
temperature we want for the heated gas. So since the temperature required is
higher, the heater takes more time to heat the air to the required value.
Set value= 30
Set value=70
Block Diagram-
Input Air
Temperature
On/Off
Control
Heater
Output Air
Temperature
Proportional controlNow we take different value of gain and see its effect on the time taken by the
output wave to reach approximately the set value in steady state.
GAIN= 100/PROPORTIONAL BAND
The values of proportional band and gain which we used are tabulated as
Follows
GAIN
PROPORTIONAL BAND
0.5
200
1
100
2
50
5
20
10
10
20
5
We took 18 reading (3 for each gain value at distances 1.5 inches,6.5 inches and
11.5 inches respectively).
Fig 1 to 18 respectively showing proportional control. 1-6 ,7-12 and 13-18 represent the output waves and input waves for
distances 11.5 inches(gains increasing as shown in the table),6.5 inches(gains increasing as shown in the table) and 1.5
inches(gains increasing as shown in the table) respectively
Explanation and Learning- As we can see in the pictures above as the value of
gain increases the time required by the output wave to reach the steady state as
the temperature required to be achieved by the output air is higher as a result of
which heater takes longer time to heat the air. At high values of gain it starts
acting like a switch due to the fact that output fluctuations are large.
Block Diagram-
Input Air
Temperature
Proportional
Control
Heater
Output Air
Temperature
Dynamic Behaviour of the SystemWe recorded the output waveforms at different gain values with varying the input
waves as step, ramp and sine waves.
Observation- As the value of gain increased from 0.5 to 3, the output waveform
followed the same shape more closely but with increased fluctuations.
Gain =0.5
Gain =1
Gain =3
Description- More value of gain implies more time required to reach the steady
state and hence we get more number of fluctuations. At very high value of gains
the output behaves almost like a step function in the above case.
Ramp Input-
Output waveforms for ramp input at gains 0.5,1 and 3 at a distance 6.5 inches
Output waveforms for ramp input at gains 0.5,1 and 3 at a distance 11.5 inches
Explanation- As the distance from the heater increases the transport lag increases
as the air has to travel more before it reaches the sensor.
Also, as the gain is increased from 0.5 to 3 the output waveform follows the input
waveform more closely.
Sine Wave Input-
Output and Input waveforms at different gain values from 0.5 to 3(left to right)
Explanation- The reason for the asymmetrical nature is due to phase lag because
of the nature of sine wave. As the input wave reaches its peak and starts to go
back down, a phase lag is introduced in the output wave thereby giving
asymmetrical output wave.