Beruflich Dokumente
Kultur Dokumente
ACC 75D/DR
ACC 100D/DR
ACC - D- 2005
Ceiling Concealed
Split Systems
CONTENTS
1. NOMENECLATURE ................................................................................................... 2
2. FEATURES ................................................................................................................ 4
3. PRODUCT LINE UP ..................................................................................................... 5
4. SPECIFICATIONS ............................................................................................... 8
5. OPERATING RANGE ......................................................................................... 22
6. SOUND DATA ................................................................................ 23
7. PERFORMANCE TABLE .................................................................... 25
8. OUTLINES AND DIMENSIONS................................................................................................ 35
9. REFRIGERANT CIRCUIT ......................................................................................................... 37
10. WIRING DIAGRAMS ....................................................................................................... 38
11. INSTALLATION ......................................................................... 40
12. SERVICING AND MAINTENANCE ............................................................................................ 43
13. TROUBLESHOOTING ......................................................................... 45
14. EXPLODED VIEW AND PARTS LIST ......................................................................... 51
1. NOMENCLATURE
INDOOR
Product Specification Variation
A : First Issue
Type of Connection
B : For Brazed
Electrical Characteristic
A : 50Hz / 1Ph / 220-240V
CC
75
Model Type
R : Heatpump
Omitted if Cooling Only
Series
D : D Series
Capacity
75 : 75,000 Btu/h
Model Name
CC : Ceiling Concealed
Refrigerant
Blank : R22
4 : R407C
Brand
A : Acson
OUTDOOR
Product Specification Variation
A : First issue
Type of Connection
B : For Brazed
Electrical Characteristic
F : 50Hz / 3Ph / 220-240V
P : 60Hz / 3Ph / 208-230V
Q : 60Hz / 3Ph / 460V
MC
75
Model Type
R : Heatpump
Omitted if Cooling Only
Series
E : E Series
D : D Series
Capacity
75 : 75,000 Btu/h
Model Name
MC : Single Split Condensin g Unit
Refrigerant
Blank : R22
4 : R407C
Brand
A : Acson
2. FEATURES
Invisible Operation
The unit is installed concealed above the ceiling. ACC-D is designed to intelligently create a
comfortable and healthy indoor air climate, while remaining invisible. This allows user to enjoy
conditioned air without sacrificing room space or interior design creativity.
The unit offers fan motor that can operate up to 4 speeds, thus provide choices of external static
pressure for designing ducting system.
Easy Serviceability
With the concept of easy serviceability in mind, ACC-D series is designed for easy access to
internal components. The internal components, such as fan motor or blower, can be easily
accessed for servicing through both sides or bottom of the unit.
The unit is incorporated with a unique safety feature, i.e. a float switch, to provide an additional
protection from possible problems of condensate water over flow inside the unit. Once the
condensate water reaches critical level, the level switch will be activated and signal will be sent to
the microprocessor controller to stop the compressor as well as sending an error message to the
wired controller, alerting the user, for further action.
The standard unit comes with the Netware III controller, which offers wide range of control
features that, includes 7 days and 24 hours timer setting and more. The ACC-D series is able to
communicate with the versatile NIM network control module and offers the opportunity of one
centralized control for a system of multiple indoor units in a building.
Auto random restart function allows the unit to automatic restart as the last setting condition when
the power supply is resumed after power failure. However, the compressor will restart randomly if
more than one unit is installed and sharing the same phase of power.
Self Diagnosis
The microprocessor provides the possibility to detect and diagnose any fault or malfunction that
occurs in the system. The error will be reflected by the wired remote controller with a series of
error code.
Handset
Control Module
Filtration
Marking
Refrigerant
Control
NETWARE III
Air Filter
CE Mark
Cap. Tube
Level Switch
L2
ABAA
X
X
X
X
X
X
X
X
ABAA
X
X
X
X
X
X
X
X
TXV
NONMENCLATURE
75DR
ACC
100DR
3. PRODUCT LINE UP
INDOOR UNIT
ACC-D SERIES PRODUCT LINE UP
Classification
A4MC
75D
100D
FBAA
FBAA
FCAA
FCAB
FBAA
FBAA
FCAA
FCAB
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
6
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
With Accumulator
X
X
X
X
X
Refrigerant
Control
ETL
X
X
X
X
X
Refrigerant
Control
Compressor
Phase Protector
With Accumulator
TXV
Scroll-Copeland
Without Marking
Marking
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
CE Mark
Without Contactor
Controller
TXV
Compressor
X
X
Scroll-Copeland
Marking
X
X
CE Mark
Auto HP/LP
Controller
100D
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
With Contactor
75D
FBAF
FBAG
FBAH
FCAA
FCAB
PBAB
PBAC
PCAA
QBAB
QBAC
QCAB
FBAF
FBAG
FBAH
FCAA
FCAB
PBAB
PBAC
PCAA
QBAB
QBAC
QCAB
With Contactor
Nomenclature
AMC
Nomenclature
OUTDOOR UNIT
AMC-D Series Product Line Up
Classification
Others
1/2
1
X
5/8
1-1/8
Others
1/2
5/8
1-1/8
Heatpump Models
4MSS
75ER
100ER
125ER
150ER
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
7
X
X
X
X
X
Phase Sequencer
Check valve
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
With Accumulator
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
TXV
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Scroll-Copeland
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Compressor
CE Mark
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Refrigerant
Control
Marking
Controller
With Contactor
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
TXV
X
X
X
X
X
X
X
X
Refrigerant
Control
Compressor
Scroll-Copeland
FBAA
FCAA
FBAA
FCAA
FBAA
FCAA
FBAA
FCAA
Marking
150ER
CE Mark
125ER
Controller
100ER
FBAA
FBAB
FBAC
FCAA
FBAA
FBAB
FBAC
FCAA
FBAA
FBAB
FBAC
FCAA
FBAA
FBAB
FCAA
With Contactor
75ER
Nomenclature
MSS
Nomenclature
HEATPUMP MODLES
Outdoor Unit
AMC-ER Series Product Line Up
Classification
Others
1/2
1
5/8
1-1/8
5/8
1-3/8
5/8
1-3/8
Others
1/2
5/8
1-1/8
5/8
1-3/8
5/8
1-3/8
4. SPECIFICATIONS
General Data - Cooling Only (R22)
MODEL
INDOOR UNIT
ACC 75D
ACC 100D
OUTDOOR UNIT
AMC 75D
AMC 100D
Btu/h
75,000
95,000
21,960
27,820
8,471
10,822
16.3
NOMINAL CAPACITY
NOMINAL TOTAL INPUT POWER
NOMINAL RUNNING CURRENT
POWER SOURCE
CFM / L/s
2420 / 1142
3150 / 1487
HIGH
CFM / L/s
2450 / 1156
3130 / 1477
MEDIUM
CFM / L/s
2000 / 944
2840 / 1340
LOW
CFM / L/s
1680 / 793
2240 / 1057
AIR FLOW
INDOOR UNIT
PACKING DIMENSION
mmAq(Pa)
dBA
52 / 52 / 48 / 43
HEIGHT
mm/in
430 / 16.9
430 / 16.9
WIDTH
mm/in
1426 / 56.1
1655 / 65.2
826 / 32.5
DEPTH
mm/in
826 / 32.5
mm/in
612 / 24.1
612 / 24.1
WIDTH
mm/in
1535 / 60.4
1765 / 69.5
DEPTH
mm/in
974 / 38.3
974 / 38.3
kg/lb
92 / 203
119 / 262
mm/in
25.4 / 1.0
dBA
64
HEIGHT
mm/in
1041 / 40.98
PACKING DIMENSION
WIDTH
mm/in
981 / 38.62
DEPTH
mm/in
981 / 38.62
HEIGHT
mm/in
1224 / 48.2
WIDTH
mm/in
1175 / 46.3
DEPTH
mm/in
UNIT WEIGHT
1150 / 45.3
170 / 374
kg/lb
REFRIGERANT CHARGE
SIZE
184 / 405
BRAZING
TYPE
PIPE CONNECTION
25.4 / 1.0
7000 / 3304
CFM / L/s
UNIT DIMENSION
55 / 54 / 52 / 48
HEIGHT
UNIT WEIGHT
OUTDOOR UNIT
19.4
380 - 415 / 3 / 50
V/Ph/Hz
LIQUID
mm/in
12.70 / 1/2
15.88 / 5/8
GAS
mm/in
25.40 / 1
28.57 / 1-1/8
kg/lb
6.7 / 14.77
10.5 / 23.15
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 26.7C DB / 19.4C WB INDOOR AND 35.0C DB / 23.9C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
INDOOR UNIT
ACC 75D
ACC 100D
OUTDOOR UNIT
AMC 75D
AMC 100D
INDUCTION
TYPE
CLASS B
INSULATION GRADE
POWER SOURCE
INDOOR MOTOR
220 - 240 / 1 / 50
V/Ph/Hz
1061
4.51
5.79
MOTOR OUTPUT
750
1000
POLES
CLASS F
INSULATION GRADE
V/Ph/Hz
380 - 415 / 3 / 50
600
1.2
MOTOR OUTPUT
350
POWER SOURCE
SCROLL
TYPE
INSULATION GRADE
POWER SOURCE
COMPRESSOR
4
INDUCTION
TYPE
OUTDOOR MOTOR
1254
N/A
N/A
380 - 415 / 3 / 50
V/Ph/Hz
CAPACITOR
NIL
6810
8968
13.6
16.3
95
125
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/230-94.
NIL
INDOOR UNIT
ACC 75D
OUTDOOR UNIT
AMC 75D
ACC 100D
ALC 100D
CENTRIFUGAL
TYPE
Q'TY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIRECT
DIRECT
DIAMETER
mm/in
228.6 / 9.0
228.6 / 9.0
LENGTH
mm/in
177.8 / 7.0
228.6 / 9.0
INDUCTION
TYPE
Q'TY
INDEX OF PROTECTION (IP)
N/A
N/A
TYPE
PROPELLER
Q'TY
1
ALUMINIUM
DIRECT
DRIVE
DIAMETER
812.8 / 32.0
mm/in
INDUCTION
TYPE
OUTDOOR FAN
Q'TY
MOTOR
INDEX OF PROTECTION (IP)
1
N/A
N/A
SCROLL
TYPE
COMPRESSOR
OIL TYPE
OIL AMOUNT
cm
SONTEX 200 LT
SONTEX 200 LT
2513
3253
SEAMLESS COPPER
MATERIAL
TUBE
DIAMETER
mm/in
9.52 / 3/8
THICKNESS
mm/in
0.35 / 0.013
MATERIAL
INDOOR COIL
FIN
ALUMINIUM
ALUMINIUM
THICKNESS
mm/in
0.127 / 0.005
0.127 / 0.005
FACE AREA
m2/ft2
0.45 / 4.89
0.55 / 5.89
ROW
12
14
SEAMLESS COPPER
MATERIAL
TUBE
DIAMETER
mm/in
THICKNESS
mm/in
9.52 / 3/8
0.35 / 0.013
MATERIAL
OUTDOOR COIL
FIN
ALUMINIUM
ALUMINIUM
THICKNESS
mm/in
0.127 / 0.005
0.127 / 0.005
FACE AREA
m2/ft2
2.29 / 24.72
2.29 / 24.72
ROW
20
16
WASHABLE SARANET FILTER
TYPE
FILTRATION
SIZE
WIDTH
mm/in
665 / 26.1
780 / 30.7
HEIGHT
mm/in
345 / 13.9
345 / 13.9
pc
QUANTITY
INDOOR UNIT
CASING
OUTDOOR UNIT
MATERIAL
FINSIHING
COLOUR
MATERIAL
FINISHING
COLOUR
WHITE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
10
INDOOR UNIT
ACC 75DR
OUTDOOR UNIT
ACC 100DR
AMC 75ER
AMC 100ER
Btu/h
75000
100000
21960
29280
Btu/h
84000
110000
24600
32210
7356
10200
7206
9800
13.6
17.9
13.3
CFM / L/s
2420 / 1142
3150 / 1487
HIGH
CFM / L/s
2450 / 1156
3130 / 1477
MEDIUM
CFM / L/s
2000 / 944
2840 / 1340
LOW
CFM / L/s
1680 / 793
2240 / 1057
AIR FLOW
INDOOR UNIT
PACKING DIMENSION
mmAq(Pa)
dBA
52 / 52 / 48 / 43
HEIGHT
mm/in
430 / 16.9
430 / 16.9
WIDTH
mm/in
1426 / 56.1
1655 / 65.2
826 / 32.5
DEPTH
mm/in
826 / 32.5
mm/in
612 / 24.1
612 / 24.1
WIDTH
mm/in
1535 / 60.4
1765 / 69.5
DEPTH
mm/in
974 / 38.3
974 / 38.3
kg/lb
92 / 203
119 / 262
mm/in
25.4 / 1.0
dBA
64
HEIGHT
mm/in
1041 / 40.98
PACKING DIMENSION
WIDTH
mm/in
981 / 38.62
DEPTH
mm/in
981 / 38.62
HEIGHT
mm/in
1224 / 48.2
WIDTH
mm/in
1175 / 46.3
DEPTH
mm/in
UNIT WEIGHT
1150 / 45.3
170 / 374
kg/lb
REFRIGERANT CHARGE
SIZE
184 / 405
BRAZING
TYPE
PIPE CONNECTION
25.4 / 1.0
7000 / 3304
CFM / L/s
UNIT DIMENSION
55 / 54 / 52 / 48
HEIGHT
UNIT WEIGHT
OUTDOOR UNIT
17.2
380 - 415 / 3 / 50
V/Ph/Hz
LIQUID
mm/in
12.70 / 1/2
15.88 / 5/8
GAS
mm/in
28.58 / 1-1/8
28.58 / 1-1/8
kg/lb
6.80 / 14.99
7.50 / 16.54
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7C DB / 19.4C WB INDOOR AND 35.0C DB / 23.9C WB OUTDOOR
b) HEATING - 21.1C DB INDOOR AND 8.3C DB / 6.1C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
11
INDOOR UNIT
ACC 75DR
ACC 100DR
OUTDOOR UNIT
AMC 75ER
AMC 100ER
INDUCTION
TYPE
CLASS B
INSULATION GRADE
POWER SOURCE
INDOOR MOTOR
220 - 240 / 1 / 50
V/Ph/Hz
1061
4.51
5.79
MOTOR OUTPUT
750
1000
POLES
CLASS F
INSULATION GRADE
V/Ph/Hz
380 - 415 / 3 / 50
600
1.2
350
POWER SOURCE
MOTOR OUTPUT
SCROLL
TYPE
INSULATION GRADE
POWER SOURCE
COMPRESSOR
4
INDUCTION
TYPE
OUTDOOR MOTOR
1254
N/A
N/A
380 - 415 / 3 / 50
V/Ph/Hz
CAPACITOR
NIL
NIL
5695
8346
5545
7966
10.9
14.8
10.6
14.1
95
125
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.
12
INDOOR UNIT
ACC 75DR
ACC 100DR
OUTDOOR UNIT
AMC 75ER
AMC 100ER
CENTRIFUGAL
TYPE
Q'TY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIRECT
DIRECT
DIAMETER
mm/in
228.6 / 9.0
228.6 / 9.0
LENGTH
mm/in
177.8 / 7.0
228.6 / 9.0
INDUCTION
TYPE
Q'TY
N/A
N/A
PROPELLER
TYPE
Q'TY
ALUMINIUM
DIRECT
DRIVE
DIAMETER
812.8 / 32.0
mm/in
INDUCTION
TYPE
OUTDOOR FAN
Q'TY
MOTOR
INDEX OF PROTECTION (IP)
1
N/A
N/A
SCROLL
TYPE
COMPRESSOR
OIL TYPE
Sontex 200 LT
OIL AMOUNT
cm3
3253
SEAMLESS COPPER
MATERIAL
TUBE
DIAMETER
mm/in
9.52 / 3/8
THICKNESS
mm/in
0.35 / 0.013
MATERIAL
INDOOR COIL
FIN
ALUMINIUM
ALUMINIUM
THICKNESS
mm/in
0.127 / 0.005
0.127 / 0.005
FACE AREA
m2/ft2
0.45 / 4.89
0.55 / 5.89
ROW
12
14
MATERIAL
TUBE
DIAMETER
mm/in
9.52 / 3/8
THICKNESS
mm/in
0.35 / 0.013
MATERIAL
OUTDOOR COIL
FIN
ALUMINIUM
SIZE
ALUMINIUM
THICKNESS
mm/in
0.127 / 0.005
0.127 / 0.005
FACE AREA
2.29 / 24.72
2.29 / 24.72
m /ft
ROW
20
16
WASHABLE SARANET FILTER
TYPE
FILTRATION
Sontex 200 LT
2513
WIDTH
mm/in
665 / 26.1
780 / 30.7
HEIGHT
mm/in
345 / 13.9
345 / 13.9
pc
QUANTITY
INDOOR UNIT
CASING
OUTDOOR UNIT
MATERIAL
FINSIHING
N/A
COLOUR
N/A
MATERIAL
FINISHING
COLOUR
WHITE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
13
Safety Devices
MODEL
INDOOR UNIT
ACC 75D
ACC 100D
OUTDOOR UNIT
AMC 75D
AMC 100D
AUTO RESET
AUTO RESET
TYPE
SETTING
TYPE
AUTO RESET
AUTO RESET
SETTING
PHASE SEQUENCER
18 psi OFF
18 psi OFF
AVAILABLE
AVAILABLE
130 C
130
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
MODEL
INDOOR UNIT
ACC 75DR
ACC 100DR
OUTDOOR UNIT
AMC 75ER
AMC 100ER
AUTO RESET
AUTO RESET
TYPE
SETTING
TYPE
AUTO RESET
AUTO RESET
SETTING
PHASE SEQUENCER
7 psi OFF
7 psi OFF
AVAILABLE
AVAILABLE
130 C
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
14
130
INDOOR UNIT
ACC 75D
ACC 100D
OUTDOOR UNIT
A4MC 75D
A4MC 100D
Btu/h
75000
100000
NOMINAL CAPACITY
21980
29310
8892
10833
16.0
POWER SOURCE
CFM / L/s
2520 / 1189
3070 / 1449
HIGH
CFM / L/s
2320 / 1095
2620 / 1237
MEDIUM
CFM / L/s
2095 / 989
2350 / 1109
CFM / L/s
1660 / 783
2150 / 1015
AIR FLOW
LOW
INDOOR UNIT
PACKING DIMENSION
dBA
52 / 52 / 48 / 43
mm/in
430 / 16.9
430 / 16.9
WIDTH
mm/in
1426 / 56.1
1655 / 65.2
DEPTH
mm/in
826 / 32.5
826 / 32.5
mm/in
612 / 24.1
612 / 24.1
WIDTH
mm/in
1535 / 60.4
1765 / 69.5
DEPTH
mm/in
974 / 38.3
974 / 38.3
kg/lb
92 / 203
119 / 262
mm/in
25.4 / 1.0
AIR FLOW
dBA
64
HEIGHT
mm/in
1041 / 40.98
PACKING DIMENSION
WIDTH
mm/in
981 / 38.62
DEPTH
mm/in
981 / 38.62
HEIGHT
mm/in
1224 / 48.2
WIDTH
mm/in
1175 / 46.3
DEPTH
mm/in
UNIT WEIGHT
1150 / 45.3
kg/lb
TYPE
REFRIGERANT CHARGE
SIZE
25.4 / 1.0
7000 / 3304
CFM / L/s
UNIT DIMENSION
55 / 54 / 52 / 48
HEIGHT
OUTDOOR UNIT
mmAq(Pa)
HEIGHT
UNIT WEIGHT
PIPE CONNECTION
19.0
380 - 415 / 3 / 50
V/Ph/Hz
170 / 374
184 / 405
BRAZING
BRAZING
LIQUID
mm/in
12.70 / 1/2
15.88 / 5/8
GAS
mm/in
25.40 / 1
28.57 / 1-1/8
kg/lb
7.00 / 15.43
7.80 / 17.20
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
COOLING - 26.7C DB / 19.4C WB INDOOR AND 35.0C DB / 23.9C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
15
INDOOR UNIT
OUTDOOR UNIT
ACC 75D
ACC 100D
A4MC 75D
A4MC 100D
INDUCTION
TYPE
CLASS B
INSULATION GRADE
POWER SOURCE
INDOOR MOTOR
220 - 240 / 1 / 50
V/Ph/Hz
1061
4.51
5.79
MOTOR OUTPUT
750
1000
POLES
INDUCTION
CLASS F
INSULATION GRADE
V/Ph/Hz
380 - 415 / 3 / 50
600
1.2
MOTOR OUTPUT
350
POWER SOURCE
SCROLL
TYPE
INSULATION GRADE
POWER SOURCE
COMPRESSOR
TYPE
OUTDOOR MOTOR
1254
N/A
N/A
380 - 415 / 3 / 50
V/Ph/Hz
CAPACITOR
NIL
NIL
7231
8979
13.34
15.82
95
125
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.
16
INDOOR UNIT
OUTDOOR UNIT
ACC 75D
ACC 100D
A4MC 75D
A4MC 100D
CENTRIFUGAL
TYPE
Q'TY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DRIVE
DIRECT
DIRECT
DIAMETER
mm/in
228.6 / 9.0
228.6 / 9.0
LENGTH
mm/in
177.8 / 7.0
Q'TY
N/A
N/A
PROPELLER
TYPE
Q'TY
ALUMINIUM
DIRECT
DRIVE
DIAMETER
812.8 / 32.0
mm/in
INDUCTION
TYPE
OUTDOOR FAN
Q'TY
MOTOR
INDEX OF PROTECTION (IP)
1
N/A
N/A
SCROLL
TYPE
COMPRESSOR
OIL TYPE
SONTEX 200 LT
OIL AMOUNT
cm3
MATERIAL
TUBE
FIN
FIN
SEAMLESS COPPER
mm/in
9.52 / 3/8
9.52 / 3/8
mm/in
0.35 / 0.013
0.35 / 0.013
ALUMINIUM
mm/in
0.127 / 0.005
0.127 / 0.005
FACE AREA
0.45 / 4.89
0.55 / 5.89
m /ft
ROW
12
14
S. I. G. C.
SEAMLESS COPPER
DIAMETER
mm/in
9.52 / 3/8
9.52 / 3/8
THICKNESS
mm/in
0.35 / 0.013
0.35 / 0.013
ALUMINIUM
SIZE
ALUMINIUM
THICKNESS
mm/in
0.127 / 0.005
0.127 / 0.005
FACE AREA
2.29 / 24.72
2.29 / 24.72
ROW
20
m /ft
16
WASHABLE SARANET FILTER
TYPE
FILTRATION
ALUMINIUM
THICKNESS
MATERIAL
OUTDOOR COIL
3253
S. I. G. C.
THICKNESS
MATERIAL
TUBE
SONTEX 200 LT
2513
DIAMETER
MATERIAL
INDOOR COIL
228.6 / 9.0
INDUCTION
TYPE
WIDTH
mm/in
665 / 26.1
780 / 30.7
HEIGHT
mm/in
345 / 13.9
345 / 13.9
pc
QUANTITY
INDOOR UNIT
CASING
OUTDOOR UNIT
MATERIAL
FINSIHING
COLOUR
MATERIAL
FINISHING
COLOUR
WHITE
17
ACC 75DR
ACC 100DR
OUTDOOR UNIT
A4MC 75ER
A4MC 100ER
Btu/h
75000
100000
21980
29310
Btu/h
84000
110000
24620
32240
7827
11040
7827
9279
13.9
19.0
13.9
MODEL
NOMINAL COOLING CAPACITY
NOMINAL HEATING CAPACITY
POWER SOURCE
CFM / L/s
2520 / 1189
3070 / 1449
HIGH
CFM / L/s
2320 / 1095
2620 / 1237
MEDIUM
CFM / L/s
2095 / 989
2350 / 1109
LOW
CFM / L/s
1660 / 783
2150 / 1015
AIR FLOW
INDOOR UNIT
PACKING DIMENSION
mmAq(Pa)
52 / 52 / 48 / 43
dBA
mm/in
430 / 16.9
430 / 16.9
WIDTH
mm/in
1426 / 56.1
1655 / 65.2
826 / 32.5
DEPTH
mm/in
826 / 32.5
HEIGHT
mm/in
612 / 24.1
612 / 24.1
WIDTH
mm/in
1535 / 60.4
1765 / 69.5
DEPTH
mm/in
974 / 38.3
974 / 38.3
kg/lb
92 / 203
119 / 262
mm/in
25.4 / 1.0
25.4 / 1.0
7000 / 3304
CFM / L/s
dBA
64
HEIGHT
mm/in
1041 / 40.98
PACKING DIMENSION
WIDTH
mm/in
981 / 38.62
DEPTH
mm/in
981 / 38.62
HEIGHT
mm/in
1224 / 48.2
WIDTH
mm/in
1175 / 46.3
DEPTH
mm/in
UNIT WEIGHT
1150 / 45.3
170 / 374
kg/lb
REFRIGERANT CHARGE
SIZE
184 / 405
BRAZING
TYPE
PIPE CONNECTION
55 / 54 / 52 / 48
HEIGHT
UNIT WEIGHT
OUTDOOR UNIT
19.6
380 - 415 / 3 / 50
V/Ph/Hz
LIQUID
mm/in
12.70 / 1/2
15.88 / 5/8
GAS
mm/in
28.58 / 1-1/8
28.58 / 1-1/8
kg/lb
7.00 / 15.43
7.80 / 17.20
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI 210/240-94.
3) NOMINAL COOLING AND HEATING CAPACITY ARE BASED ON THE CONDITIONS BELOW :
a) COOLING - 26.7C DB / 19.4C WB INDOOR AND 35.0C DB / 23.9C WB OUTDOOR
b) HEATING - 21.1C DB INDOOR AND 8.3C DB / 6.1C WB OUTDOOR
4) SOUND PRESSURE LEVEL ARE ACCORDING TO JIS B 8615 STANDARD. POSITION OF THE MEASUREMENT POINT IS 1m IN FRONT AND
1m BELOW THE UNIT.
18
INDOOR UNIT
OUTDOOR UNIT
ACC 75DR
ACC 100DR
A4MC 75ER
A4MC 100ER
INDUCTION
TYPE
CLASS B
INSULATION GRADE
POWER SOURCE
INDOOR MOTOR
220 - 240 / 1 / 50
V/Ph/Hz
1061
4.51
5.79
MOTOR OUTPUT
750
1000
POLES
CLASS F
INSULATION GRADE
V/Ph/Hz
380 - 415 / 3 / 50
600
1.2
MOTOR OUTPUT
350
POWER SOURCE
SCROLL
TYPE
INSULATION GRADE
POWER SOURCE
COMPRESSOR
4
INDUCTION
TYPE
OUTDOOR MOTOR
1254
N/A
N/A
380 - 415 / 3 / 50
V/Ph/Hz
CAPACITOR
NIL
6045
9186
6045
7425
11.1
15.9
11.1
16.5
95
125
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ARI210/240-94.
19
NIL
INDOOR UNIT
OUTDOOR UNIT
ACC 75DR
ACC 100DR
A4MC 75ER
A4MC 100ER
CENTRIFUGAL
TYPE
Q'TY
INDOOR FAN
INDOOR FAN
MOTOR
MATERIAL
DIRECT
DIRECT
228.6 / 9.0
DRIVE
DIAMETER
mm/in
228.6 / 9.0
LENGTH
mm/in
177.8 / 7.0
228.6 / 9.0
INDUCTION
TYPE
Q'TY
INDEX OF PROTECTION (IP)
N/A
N/A
PROPELLER
TYPE
Q'TY
ALUMINIUM
DIRECT
DRIVE
DIAMETER
812.8 / 32.0
mm/in
INDUCTION
TYPE
OUTDOOR FAN
Q'TY
MOTOR
INDEX OF PROTECTION (IP)
1
N/A
N/A
SCROLL
TYPE
COMPRESSOR
OIL TYPE
SONTEX 200 LT
OIL AMOUNT
cm3
MATERIAL
TUBE
DIAMETER
THICKNESS
FIN
9.52 / 3/8
9.52 / 3/8
mm/in
0.35 / 0.013
ALUMINIUM
FIN
mm/in
0.127 / 0.005
0.127 / 0.005
FACE AREA
m2/ft2
0.45 / 4.89
0.55 / 5.89
ROW
12
14
S. I. G. C.
SEAMLESS COPPER
DIAMETER
mm/in
9.52 / 3/8
9.52 / 3/8
THICKNESS
mm/in
0.35 / 0.013
0.35 / 0.013
ALUMINIUM
SIZE
ALUMINIUM
THICKNESS
mm/in
0.127 / 0.005
0.127 / 0.005
FACE AREA
m2/ft2
2.29 / 24.72
2.29 / 24.72
ROW
20
16
WASHABLE SARANET FILTER
TYPE
FILTRATION
ALUMINIUM
THICKNESS
MATERIAL
OUTDOOR COIL
SEAMLESS COPPER
0.35 / 0.013
MATERIAL
TUBE
3253
S. I. G. C.
mm/in
MATERIAL
INDOOR COIL
SONTEX 200 LT
2513
WIDTH
mm/in
665 / 26.1
780 / 30.7
HEIGHT
mm/in
345 / 13.9
345 / 13.9
pc
QUANTITY
INDOOR UNIT
CASING
OUTDOOR UNIT
MATERIAL
FINSIHING
COLOUR
MATERIAL
FINISHING
COLOUR
WHITE
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
20
Safety Devices
MODEL
INDOOR UNIT
OUTDOOR UNIT
HIGH PRESSURE SWITCH
SAFETY DEVICE
TYPE
ACC 75D
ACC 100D
A4MC 75D
A4MC 100D
AUTO RESET
AUTO RESET
SETTING
TYPE
AUTO RESET
AUTO RESET
SETTING
PHASE SEQUENCER
18 psi OFF
18 psi OFF
AVAILABLE
AVAILABLE
130 C
130
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
MODEL
INDOOR UNIT
OUTDOOR UNIT
HIGH PRESSURE SWITCH
SAFETY DEVICE
TYPE
ACC 75DR
ACC 100DR
A4MC 75ER
A4MC 100ER
AUTO RESET
AUTO RESET
SETTING
TYPE
AUTO RESET
AUTO RESET
SETTING
PHASE SEQUENCER
7 psi OFF
7 psi OFF
AVAILABLE
AVAILABLE
130 C
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
21
130
5. OPERATING RANGE
Ensure the operating temperature is in allowable range.
Cooling only
54
High ambient
unit
46
Standard
point
35
Caution :
The use of your air conditioner
outside the range of working
temperature and humidity can
result in serious failure.
19
-5
24
15
Heatpump
Cooling
Heating
54
18
Standard
point
-9
High ambient
unit
46
Standard
point
35
19
-5
15
21
27
15
24
Note :
Standard operating range.
22
6. SOUND DATA
Ext. Static
(mmAq)
20
14
10
7
Speed
Ext. Static
(mmAq)
20
14
10
7
Speed
SH
Hi
Me
Lo
SH
Hi
Me
Lo
Microphone position:
125
52
51
48
43
ACC 75D/DR
1/1 Octave sound Pressure Level (dB, reference 20 Pa)
250
500
1000
2000
4000
8000
49
49
48
45
40
33
49
48
47
44
40
33
46
46
45
40
34
26
40
42
38
36
30
19
Overall
(dBA)
52
52
48
43
Noise
Criteria
47
46
44
37
125
60
59
55
55
ACC 100D/DR
1/1 Octave sound Pressure Level (dB, reference 20 Pa)
250
500
1000
2000
4000
8000
54
51
51
49
44
37
52
50
50
48
42
36
51
49
47
44
38
31
47
47
43
40
33
26
Overall
(dBA)
55
54
52
48
Noise
Criteria
50
49
46
43
23
NC CURVES
ACC 75D/DR NC CURVES
70
60
50
NC-50
SH FAN
NC-45
HI FAN
40
NC-40
ME FAN
NC-35
LO FAN
30
NC-30
NC-25
20
NC-20
10
0
125
250
500
1000
2000
4000
8000
70
60
SH FAN
50
NC-50
HI FAN
NC-45
ME FAN
NC-40
40
LO FAN
NC-35
NC-30
30
NC-25
20
NC-20
10
0
125
250
500
1000
24
2000
4000
8000
5.
5.
7.PERFORMANCE
PERFORMANCE
PERFORMANCETABLE
TABLE
TABLE
Interpolation and Extrapolation method can be used to get the total capacity, TC and sensible capacity,
SC at those temperatures which are not stated out in the table.
Example:
Model: ACC 75D AMC 75D
Indoor Condition: 23C DB, 15C WB
Outdoor Condition: 37C DB
Solution:
Overall
Based on the Performance table on Pg. 29,
1. Refer to the Indoor DB column,
- 23C is located between 20C and 24C (Thus, Interpolation need to be applied)
2. Refer to the Indoor WB column,
- 15C only available in the case of Indoor DB = 20C. (Thus, Extrapolation between 16C
WB and 17C WB during 24C indoor DB is required)
3. Refer to the Outdoor DB column,
- 37C is located between 35C and 40C. (Thus, Interpolation need to be applied)
Please follow the steps below in order to get the required capacity.
1st Step
2nd Step
3rd Step
Extrapolation of Indoor WB
Interpolation of Indoor DB
25
Interpolation of Outdoor DB
Details:
1st Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 24C DB, 15C WB
Outdoor Condition: 35C DB
Indoor DB
C
Indoor WB
C
24
15
16
17
Outdoor DB, C
35
TC (kW)
SC (kW)
x1
20.229
20.744
y1
15.040
14.517
Total capacity, TC
x1 = 19.713kW (Same as Total capacity at 20C Indoor DB / 15C Indoor WB & 35C Outdoor WB)*
Sensible capacity, SC
Extrapolation Method:
14.517kW - y 1
17 C - 15 C
17 C - 16 C
14.517kW - 15.040kW
y1 = 15.563kW
Indoor WB
C
24
15
16
17
Outdoor DB, C
40
TC (kW)
SC (kW)
x2
18.776
19.366
y2
13.808
13.463
Total capacity, TC
x 2 = 18.186kW (Same as Total capacity at 20C Indoor DB / 15C Indoor WB & 40C Outdoor WB)*
Sensible capacity, SC
Extrapolation Method:
13.463kW - y 2
17 C - 15 C
17C - 16 C
13.463kW - 13.808kW
y 2 = 14.153kW
* This is due to 2 different conditions with same WB temperature, will have the same level of enthalpy. For
more details, please refer to psychrometrics chart
26
2nd Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23C DB, 15C WB
Outdoor Condition: 35C DB
Indoor DB
C
Indoor WB
C
20
23
24
15
15
15
Outdoor DB, C
35
TC (kW)
SC (kW)
19.173
x3
19.173
11.110
y3
15.563
Total capacity, TC
x 3 = 19.173kW (Same as Total capacity at 20C Indoor DB / 15C Indoor WB & 35C Outdoor WB)*
Sensible capacity, SC
Interpolation Method:
24 C - 20 C 15.563kW - 11.110kW
24C - 23 C
15.563kW - y 3
y 3 = 14.450kW
Indoor WB
C
20
23
24
15
15
15
Outdoor DB, C
40
TC (kW)
SC (kW)
18.186
x4
18.186
9.698
y4
14.153
Total capacity, TC
x 4 = 18.186kW (Same as Total capacity at 20C Indoor DB / 15C Indoor WB & 40C Outdoor WB)*
Sensible capacity, SC
Interpolation Method:
24 C - 20 C 14.153kW - 9.698kW
24C - 23 C
14.153kW - y 1
y 4 = 13.039kW
* This is due to 2 different conditions with same WB temperature will have the same level of enthalpy. For
more details, please refer to psychrometrics chart
27
3rd Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23C DB, 15C WB
Outdoor Condition: 37C DB
Indoor DB
C
Indoor WB
C
23
15
TC (kW)
19.713
35
Outdoor DB, C
37
SC (kW)
TC (kW)
SC (kW)
14.450
Total capacity, TC
Interpolation Method:
40 C - 35 C 18.186kW - 19.713kW
40C - 37 C
18.186kW - x
x = 19.102kW
Sensible capacity, SC
Interpolation Method:
40 C - 35 C 13.039kW - 14.450kW
40C - 37 C
13.039kW - y
y = 13.886kW
28
TC (kW)
18.186
40
SC (kW)
13.039
R22 MODELS
(COOLING ONLY)
MODEL : ACC 75D / AMC 75D
ID DBC ID WBC
20
24
28
30
15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24
20
TC(kW) SC(kW)
24.294 15.345
24.586 14.284
24.586 18.738
24.877 17.677
25.169 16.616
25.461 15.555
25.750 14.484
25.169 21.069
25.461 20.008
25.750 18.938
26.038 17.860
26.325 16.783
26.612 15.706
26.899 14.629
25.750 21.164
26.038 20.087
26.325 19.010
26.612 17.933
26.899 16.855
25
TC(kW) SC(kW)
22.767 13.934
23.133 13.052
23.133 17.505
23.500 16.623
23.866 15.742
24.233 14.860
24.572 13.887
23.866 20.195
24.233 19.313
24.572 18.341
24.893 17.308
25.214 16.274
25.535 15.241
25.856 14.208
24.572 20.567
24.893 19.534
25.214 18.501
25.535 17.468
25.856 16.435
Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
21.240 12.522 19.713 11.110
21.681 11.819 20.229 10.587
21.681 16.273 20.229 15.040
22.122 15.570 20.744 14.517
22.563 14.867 21.260 13.993
23.004 14.164 21.775 13.469
23.393 13.290 22.215 12.693
22.563 19.321 21.260 18.447
23.004 18.618 21.775 17.923
23.393 17.744 22.215 17.147
23.748 16.755 22.603 16.202
24.103 15.766 22.992 15.257
24.458 14.777 23.381 14.313
24.813 13.788 23.770 13.368
23.393 19.971 22.215 19.374
23.748 18.982 22.603 18.429
24.103 17.993 22.992 17.484
24.458 17.004 23.381 16.539
24.813 16.015 23.770 15.595
40
TC(kW) SC(kW)
18.186 9.698
18.776 9.354
18.776 13.808
19.366 13.463
19.956 13.119
20.546 12.774
21.036 12.096
19.956 17.572
20.546 17.228
21.036 16.550
21.459 15.649
21.882 14.749
22.304 13.848
22.727 12.948
21.036 18.777
21.459 17.876
21.882 16.976
22.304 16.075
22.727 15.174
46
TC(kW) SC(kW)
16.354 8.004
17.033 7.875
17.033 12.329
17.713 12.199
18.392 12.070
19.072 11.940
19.622 11.380
18.392 16.523
19.072 16.394
19.622 15.833
20.085 14.986
20.549 14.138
21.012 13.291
21.476 12.443
19.622 18.060
20.085 17.213
20.549 16.365
21.012 15.518
21.476 14.670
25
TC(kW) SC(kW)
28.908 18.136
29.695 17.179
29.695 22.464
30.483 21.507
31.270 20.549
32.057 19.592
32.801 18.482
31.270 25.835
32.057 24.877
32.801 23.767
33.515 22.555
34.230 21.343
34.944 20.131
35.659 18.919
32.801 26.410
33.515 25.198
34.230 23.986
34.944 22.774
35.659 21.562
Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
27.224 16.650 25.540 15.163
28.046 15.906 26.396 14.634
28.046 21.192 26.396 19.919
28.868 20.448 27.253 19.390
29.690 19.705 28.109 18.861
30.512 18.962 28.966 18.332
31.251 17.930 29.700 17.378
29.690 24.991 28.109 24.146
30.512 24.247 28.966 23.617
31.251 23.215 29.700 22.663
31.935 21.990 30.354 21.425
32.618 20.765 31.007 20.186
33.302 19.539 31.660 18.948
33.986 18.314 32.314 17.709
31.251 25.858 29.700 25.306
31.935 24.632 30.354 24.067
32.618 23.407 31.007 22.829
33.302 22.182 31.660 21.590
33.986 20.957 32.314 20.352
40
TC(kW) SC(kW)
23.856 13.676
24.747 13.362
24.747 18.647
25.638 18.332
26.529 18.017
27.420 17.702
28.150 16.825
26.529 23.302
27.420 22.988
28.150 22.111
28.773 20.859
29.396 19.608
30.018 18.356
30.641 17.105
28.150 24.753
28.773 23.502
29.396 22.250
30.018 20.999
30.641 19.747
46
TC(kW) SC(kW)
21.835 11.892
22.767 11.835
22.767 17.120
23.700 17.062
24.632 17.004
25.565 16.946
26.290 16.163
24.632 22.290
25.565 22.232
26.290 21.448
26.876 20.181
27.462 18.914
28.048 17.646
28.634 16.379
26.290 24.091
26.876 22.824
27.462 21.556
28.048 20.289
28.634 19.022
20
24
28
30
15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24
20
TC(kW) SC(kW)
30.592 19.623
31.345 18.451
31.345 23.736
32.098 22.565
32.851 21.393
33.603 20.222
34.351 19.034
32.851 26.679
33.603 25.507
34.351 24.319
35.096 23.120
35.841 21.922
36.586 20.723
37.331 19.524
34.351 26.962
35.096 25.763
35.841 24.564
36.586 23.365
37.331 22.166
29
R22 MODELS
(HEATPUMP)
MODEL : ACC 75DR / AMC 75ER
COOLING MODE
ID DBC ID WBC
20
24
28
30
15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24
20
TC(kW) SC(kW)
24.294 15.345
24.586 14.284
24.586 18.738
24.877 17.677
25.169 16.616
25.461 15.555
25.750 14.484
25.169 21.069
25.461 20.008
25.750 18.938
26.038 17.860
26.325 16.783
26.612 15.706
26.899 14.629
25.750 21.164
26.038 20.087
26.325 19.010
26.612 17.933
26.899 16.855
25
TC(kW) SC(kW)
22.767 13.934
23.133 13.052
23.133 17.505
23.500 16.623
23.866 15.742
24.233 14.860
24.572 13.887
23.866 20.195
24.233 19.313
24.572 18.341
24.893 17.308
25.214 16.274
25.535 15.241
25.856 14.208
24.572 20.567
24.893 19.534
25.214 18.501
25.535 17.468
25.856 16.435
Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
21.240 12.522 19.713 11.110
21.681 11.819 20.229 10.587
21.681 16.273 20.229 15.040
22.122 15.570 20.744 14.517
22.563 14.867 21.260 13.993
23.004 14.164 21.775 13.469
23.393 13.290 22.215 12.693
22.563 19.321 21.260 18.447
23.004 18.618 21.775 17.923
23.393 17.744 22.215 17.147
23.748 16.755 22.603 16.202
24.103 15.766 22.992 15.257
24.458 14.777 23.381 14.313
24.813 13.788 23.770 13.368
23.393 19.971 22.215 19.374
23.748 18.982 22.603 18.429
24.103 17.993 22.992 17.484
24.458 17.004 23.381 16.539
24.813 16.015 23.770 15.595
HEATING MODE
ID DBC
15
17
19
21
23
25
27
-9
TC(kW) SC(kW)
15.812 15.812
15.621 15.621
15.431 15.431
15.240 15.240
15.149 15.149
15.058 15.058
14.967 14.967
-6
TC(kW) SC(kW)
17.812 17.812
17.640 17.640
17.468 17.468
17.296 17.296
17.149 17.149
17.002 17.002
16.855 16.855
FROST REGION
-5
TC(kW)
18.478
18.313
18.147
17.981
17.816
17.650
17.485
SC(kW)
18.478
18.313
18.147
17.981
17.816
17.650
17.485
Outdoor WBC
6
TC(kW) SC(kW)
25.812 25.812
25.414 25.414
25.017 25.017
24.619 24.619
24.564 24.564
24.510 24.510
24.455 24.455
30
12
TC(kW)
29.812
29.546
29.280
29.014
28.748
28.482
28.217
40
TC(kW) SC(kW)
18.186 9.698
18.776 9.354
18.776 13.808
19.366 13.463
19.956 13.119
20.546 12.774
21.036 12.096
19.956 17.572
20.546 17.228
21.036 16.550
21.459 15.649
21.882 14.749
22.304 13.848
22.727 12.948
21.036 18.777
21.459 17.876
21.882 16.976
22.304 16.075
22.727 15.174
SC(kW)
29.812
29.546
29.280
29.014
28.748
28.482
28.217
15
TC(kW)
31.812
31.529
31.245
30.961
30.678
30.394
30.110
46
TC(kW) SC(kW)
16.354 8.004
17.033 7.875
17.033 12.329
17.713 12.199
18.392 12.070
19.072 11.940
19.622 11.380
18.392 16.523
19.072 16.394
19.622 15.833
20.085 14.986
20.549 14.138
21.012 13.291
21.476 12.443
19.622 18.060
20.085 17.213
20.549 16.365
21.012 15.518
21.476 14.670
SC(kW)
31.812
31.529
31.245
30.961
30.678
30.394
30.110
18
TC(kW)
33.812
33.511
33.210
32.908
32.607
32.306
32.004
SC(kW)
33.812
33.511
33.210
32.908
32.607
32.306
32.004
R22 MODELS
(HEATPUMP)
MODEL : ACC 100D / AMC 100ER
COOLING MODE
ID DBC ID WBC
20
24
28
30
15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24
20
TC(kW) SC(kW)
30.592 19.623
31.345 18.451
31.345 23.736
32.098 22.565
32.851 21.393
33.603 20.222
34.351 19.034
32.851 26.679
33.603 25.507
34.351 24.319
35.096 23.120
35.841 21.922
36.586 20.723
37.331 19.524
34.351 26.962
35.096 25.763
35.841 24.564
36.586 23.365
37.331 22.166
25
TC(kW) SC(kW)
28.908 18.136
29.695 17.179
29.695 22.464
30.483 21.507
31.270 20.549
32.057 19.592
32.801 18.482
31.270 25.835
32.057 24.877
32.801 23.767
33.515 22.555
34.230 21.343
34.944 20.131
35.659 18.919
32.801 26.410
33.515 25.198
34.230 23.986
34.944 22.774
35.659 21.562
Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
27.224 16.650 25.540 15.163
28.046 15.906 26.396 14.634
28.046 21.192 26.396 19.919
28.868 20.448 27.253 19.390
29.690 19.705 28.109 18.861
30.512 18.962 28.966 18.332
31.251 17.930 29.700 17.378
29.690 24.991 28.109 24.146
30.512 24.247 28.966 23.617
31.251 23.215 29.700 22.663
31.935 21.990 30.354 21.425
32.618 20.765 31.007 20.186
33.302 19.539 31.660 18.948
33.986 18.314 32.314 17.709
31.251 25.858 29.700 25.306
31.935 24.632 30.354 24.067
32.618 23.407 31.007 22.829
33.302 22.182 31.660 21.590
33.986 20.957 32.314 20.352
HEATING MODE
ID DBC
15
17
19
21
23
25
27
-9
TC(kW) SC(kW)
23.133 23.133
23.140 23.140
23.147 23.147
23.154 23.154
22.720 22.720
22.285 22.285
21.851 21.851
-6
TC(kW) SC(kW)
24.838 24.838
24.669 24.669
24.500 24.500
24.330 24.330
24.051 24.051
23.772 23.772
23.492 23.492
FROST REGION
-5
TC(kW)
25.406
25.178
24.951
24.723
24.495
24.267
24.039
SC(kW)
25.406
25.178
24.951
24.723
24.495
24.267
24.039
Outdoor WBC
6
TC(kW) SC(kW)
31.659 31.659
31.852 31.852
32.046 32.046
32.239 32.239
31.455 31.455
30.670 30.670
29.886 29.886
31
12
TC(kW)
35.069
34.756
34.444
34.131
33.818
33.505
33.192
40
TC(kW) SC(kW)
23.856 13.676
24.747 13.362
24.747 18.647
25.638 18.332
26.529 18.017
27.420 17.702
28.150 16.825
26.529 23.302
27.420 22.988
28.150 22.111
28.773 20.859
29.396 19.608
30.018 18.356
30.641 17.105
28.150 24.753
28.773 23.502
29.396 22.250
30.018 20.999
30.641 19.747
SC(kW)
35.069
34.756
34.444
34.131
33.818
33.505
33.192
15
TC(kW)
36.775
36.447
36.119
35.791
35.463
35.135
34.807
46
TC(kW) SC(kW)
21.835 11.892
22.767 11.835
22.767 17.120
23.700 17.062
24.632 17.004
25.565 16.946
26.290 16.163
24.632 22.290
25.565 22.232
26.290 21.448
26.876 20.181
27.462 18.914
28.048 17.646
28.634 16.379
26.290 24.091
26.876 22.824
27.462 21.556
28.048 20.289
28.634 19.022
SC(kW)
36.775
36.447
36.119
35.791
35.463
35.135
34.807
18
TC(kW)
38.480
38.137
37.794
37.451
37.108
36.765
36.422
SC(kW)
38.480
38.137
37.794
37.451
37.108
36.765
36.422
R407C MODELS
(COOLING ONLY)
MODEL : ACC 75D / A4MC 75D
ID DBC ID WBC
20
24
28
30
15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24
20
TC(kW) SC(kW)
24.294 15.345
24.586 14.284
24.586 18.738
24.877 17.677
25.169 16.616
25.461 15.555
25.750 14.484
25.169 21.069
25.461 20.008
25.750 18.938
26.038 17.860
26.325 16.783
26.612 15.706
26.899 14.629
25.750 21.164
26.038 20.087
26.325 19.010
26.612 17.933
26.899 16.855
25
TC(kW) SC(kW)
22.767 13.934
23.133 13.052
23.133 17.505
23.500 16.623
23.866 15.742
24.233 14.860
24.572 13.887
23.866 20.195
24.233 19.313
24.572 18.341
24.893 17.308
25.214 16.274
25.535 15.241
25.856 14.208
24.572 20.567
24.893 19.534
25.214 18.501
25.535 17.468
25.856 16.435
Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
21.240 12.522 19.713 11.110
21.681 11.819 20.229 10.587
21.681 16.273 20.229 15.040
22.122 15.570 20.744 14.517
22.563 14.867 21.260 13.993
23.004 14.164 21.775 13.469
23.393 13.290 22.215 12.693
22.563 19.321 21.260 18.447
23.004 18.618 21.775 17.923
23.393 17.744 22.215 17.147
23.748 16.755 22.603 16.202
24.103 15.766 22.992 15.257
24.458 14.777 23.381 14.313
24.813 13.788 23.770 13.368
23.393 19.971 22.215 19.374
23.748 18.982 22.603 18.429
24.103 17.993 22.992 17.484
24.458 17.004 23.381 16.539
24.813 16.015 23.770 15.595
40
TC(kW) SC(kW)
18.186 9.698
18.776 9.354
18.776 13.808
19.366 13.463
19.956 13.119
20.546 12.774
21.036 12.096
19.956 17.572
20.546 17.228
21.036 16.550
21.459 15.649
21.882 14.749
22.304 13.848
22.727 12.948
21.036 18.777
21.459 17.876
21.882 16.976
22.304 16.075
22.727 15.174
46
TC(kW) SC(kW)
16.354 8.004
17.033 7.875
17.033 12.329
17.713 12.199
18.392 12.070
19.072 11.940
19.622 11.380
18.392 16.523
19.072 16.394
19.622 15.833
20.085 14.986
20.549 14.138
21.012 13.291
21.476 12.443
19.622 18.060
20.085 17.213
20.549 16.365
21.012 15.518
21.476 14.670
25
TC(kW) SC(kW)
28.908 18.136
29.695 17.179
29.695 22.464
30.483 21.507
31.270 20.549
32.057 19.592
32.801 18.482
31.270 25.835
32.057 24.877
32.801 23.767
33.515 22.555
34.230 21.343
34.944 20.131
35.659 18.919
32.801 26.410
33.515 25.198
34.230 23.986
34.944 22.774
35.659 21.562
Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
27.224 16.650 25.540 15.163
28.046 15.906 26.396 14.634
28.046 21.192 26.396 19.919
28.868 20.448 27.253 19.390
29.690 19.705 28.109 18.861
30.512 18.962 28.966 18.332
31.251 17.930 29.700 17.378
29.690 24.991 28.109 24.146
30.512 24.247 28.966 23.617
31.251 23.215 29.700 22.663
31.935 21.990 30.354 21.425
32.618 20.765 31.007 20.186
33.302 19.539 31.660 18.948
33.986 18.314 32.314 17.709
31.251 25.858 29.700 25.306
31.935 24.632 30.354 24.067
32.618 23.407 31.007 22.829
33.302 22.182 31.660 21.590
33.986 20.957 32.314 20.352
40
TC(kW) SC(kW)
23.856 13.676
24.747 13.362
24.747 18.647
25.638 18.332
26.529 18.017
27.420 17.702
28.150 16.825
26.529 23.302
27.420 22.988
28.150 22.111
28.773 20.859
29.396 19.608
30.018 18.356
30.641 17.105
28.150 24.753
28.773 23.502
29.396 22.250
30.018 20.999
30.641 19.747
46
TC(kW) SC(kW)
21.835 11.892
22.767 11.835
22.767 17.120
23.700 17.062
24.632 17.004
25.565 16.946
26.290 16.163
24.632 22.290
25.565 22.232
26.290 21.448
26.876 20.181
27.462 18.914
28.048 17.646
28.634 16.379
26.290 24.091
26.876 22.824
27.462 21.556
28.048 20.289
28.634 19.022
20
24
28
30
15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24
20
TC(kW) SC(kW)
30.592 19.623
31.345 18.451
31.345 23.736
32.098 22.565
32.851 21.393
33.603 20.222
34.351 19.034
32.851 26.679
33.603 25.507
34.351 24.319
35.096 23.120
35.841 21.922
36.586 20.723
37.331 19.524
34.351 26.962
35.096 25.763
35.841 24.564
36.586 23.365
37.331 22.166
32
R407C MODELS
(HEATPUMP)
MODEL : ACC 75DR / A4MC 75ER
COOLING MODE
ID DBC ID WBC
20
24
28
30
15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24
20
TC(kW) SC(kW)
24.294 15.345
24.586 14.284
24.586 18.738
24.877 17.677
25.169 16.616
25.461 15.555
25.750 14.484
25.169 21.069
25.461 20.008
25.750 18.938
26.038 17.860
26.325 16.783
26.612 15.706
26.899 14.629
25.750 21.164
26.038 20.087
26.325 19.010
26.612 17.933
26.899 16.855
25
TC(kW) SC(kW)
22.767 13.934
23.133 13.052
23.133 17.505
23.500 16.623
23.866 15.742
24.233 14.860
24.572 13.887
23.866 20.195
24.233 19.313
24.572 18.341
24.893 17.308
25.214 16.274
25.535 15.241
25.856 14.208
24.572 20.567
24.893 19.534
25.214 18.501
25.535 17.468
25.856 16.435
Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
21.240 12.522 19.713 11.110
21.681 11.819 20.229 10.587
21.681 16.273 20.229 15.040
22.122 15.570 20.744 14.517
22.563 14.867 21.260 13.993
23.004 14.164 21.775 13.469
23.393 13.290 22.215 12.693
22.563 19.321 21.260 18.447
23.004 18.618 21.775 17.923
23.393 17.744 22.215 17.147
23.748 16.755 22.603 16.202
24.103 15.766 22.992 15.257
24.458 14.777 23.381 14.313
24.813 13.788 23.770 13.368
23.393 19.971 22.215 19.374
23.748 18.982 22.603 18.429
24.103 17.993 22.992 17.484
24.458 17.004 23.381 16.539
24.813 16.015 23.770 15.595
HEATING MODE
ID DBC
15
17
19
21
23
25
27
-9
TC(kW) SC(kW)
15.812 15.812
15.621 15.621
15.431 15.431
15.240 15.240
15.149 15.149
15.058 15.058
14.967 14.967
-6
TC(kW) SC(kW)
17.812 17.812
17.640 17.640
17.468 17.468
17.296 17.296
17.149 17.149
17.002 17.002
16.855 16.855
FROST REGION
-5
TC(kW)
18.478
18.313
18.147
17.981
17.816
17.650
17.485
SC(kW)
18.478
18.313
18.147
17.981
17.816
17.650
17.485
Outdoor WBC
6
TC(kW) SC(kW)
25.812 25.812
25.414 25.414
25.017 25.017
24.619 24.619
24.564 24.564
24.510 24.510
24.455 24.455
33
12
TC(kW)
29.812
29.546
29.280
29.014
28.748
28.482
28.217
40
TC(kW) SC(kW)
18.186 9.698
18.776 9.354
18.776 13.808
19.366 13.463
19.956 13.119
20.546 12.774
21.036 12.096
19.956 17.572
20.546 17.228
21.036 16.550
21.459 15.649
21.882 14.749
22.304 13.848
22.727 12.948
21.036 18.777
21.459 17.876
21.882 16.976
22.304 16.075
22.727 15.174
SC(kW)
29.812
29.546
29.280
29.014
28.748
28.482
28.217
15
TC(kW)
31.812
31.529
31.245
30.961
30.678
30.394
30.110
46
TC(kW) SC(kW)
16.354 8.004
17.033 7.875
17.033 12.329
17.713 12.199
18.392 12.070
19.072 11.940
19.622 11.380
18.392 16.523
19.072 16.394
19.622 15.833
20.085 14.986
20.549 14.138
21.012 13.291
21.476 12.443
19.622 18.060
20.085 17.213
20.549 16.365
21.012 15.518
21.476 14.670
SC(kW)
31.812
31.529
31.245
30.961
30.678
30.394
30.110
18
TC(kW)
33.812
33.511
33.210
32.908
32.607
32.306
32.004
SC(kW)
33.812
33.511
33.210
32.908
32.607
32.306
32.004
R407C MODELS
(HEATPUMP)
MODEL : ACC 100D / A4MC 100ER
COOLING MODE
ID DBC ID WBC
20
24
28
30
15
16
16
17
18
19
20
18
19
20
21
22
23
24
20
21
22
23
24
20
TC(kW) SC(kW)
30.592 19.623
31.345 18.451
31.345 23.736
32.098 22.565
32.851 21.393
33.603 20.222
34.351 19.034
32.851 26.679
33.603 25.507
34.351 24.319
35.096 23.120
35.841 21.922
36.586 20.723
37.331 19.524
34.351 26.962
35.096 25.763
35.841 24.564
36.586 23.365
37.331 22.166
25
TC(kW) SC(kW)
28.908 18.136
29.695 17.179
29.695 22.464
30.483 21.507
31.270 20.549
32.057 19.592
32.801 18.482
31.270 25.835
32.057 24.877
32.801 23.767
33.515 22.555
34.230 21.343
34.944 20.131
35.659 18.919
32.801 26.410
33.515 25.198
34.230 23.986
34.944 22.774
35.659 21.562
Outdoor DBC
30
35
TC(kW) SC(kW) TC(kW) SC(kW)
27.224 16.650 25.540 15.163
28.046 15.906 26.396 14.634
28.046 21.192 26.396 19.919
28.868 20.448 27.253 19.390
29.690 19.705 28.109 18.861
30.512 18.962 28.966 18.332
31.251 17.930 29.700 17.378
29.690 24.991 28.109 24.146
30.512 24.247 28.966 23.617
31.251 23.215 29.700 22.663
31.935 21.990 30.354 21.425
32.618 20.765 31.007 20.186
33.302 19.539 31.660 18.948
33.986 18.314 32.314 17.709
31.251 25.858 29.700 25.306
31.935 24.632 30.354 24.067
32.618 23.407 31.007 22.829
33.302 22.182 31.660 21.590
33.986 20.957 32.314 20.352
HEATING MODE
ID DBC
15
17
19
21
23
25
27
-9
TC(kW) SC(kW)
23.133 23.133
23.140 23.140
23.147 23.147
23.154 23.154
22.720 22.720
22.285 22.285
21.851 21.851
-6
TC(kW) SC(kW)
24.838 24.838
24.669 24.669
24.500 24.500
24.330 24.330
24.051 24.051
23.772 23.772
23.492 23.492
FROST REGION
-5
TC(kW)
25.406
25.178
24.951
24.723
24.495
24.267
24.039
SC(kW)
25.406
25.178
24.951
24.723
24.495
24.267
24.039
Outdoor WBC
6
TC(kW) SC(kW)
31.659 31.659
31.852 31.852
32.046 32.046
32.239 32.239
31.455 31.455
30.670 30.670
29.886 29.886
34
12
TC(kW)
35.069
34.756
34.444
34.131
33.818
33.505
33.192
40
TC(kW) SC(kW)
23.856 13.676
24.747 13.362
24.747 18.647
25.638 18.332
26.529 18.017
27.420 17.702
28.150 16.825
26.529 23.302
27.420 22.988
28.150 22.111
28.773 20.859
29.396 19.608
30.018 18.356
30.641 17.105
28.150 24.753
28.773 23.502
29.396 22.250
30.018 20.999
30.641 19.747
SC(kW)
35.069
34.756
34.444
34.131
33.818
33.505
33.192
15
TC(kW)
36.775
36.447
36.119
35.791
35.463
35.135
34.807
46
TC(kW) SC(kW)
21.835 11.892
22.767 11.835
22.767 17.120
23.700 17.062
24.632 17.004
25.565 16.946
26.290 16.163
24.632 22.290
25.565 22.232
26.290 21.448
26.876 20.181
27.462 18.914
28.048 17.646
28.634 16.379
26.290 24.091
26.876 22.824
27.462 21.556
28.048 20.289
28.634 19.022
SC(kW)
36.775
36.447
36.119
35.791
35.463
35.135
34.807
18
TC(kW)
38.480
38.137
37.794
37.451
37.108
36.765
36.422
SC(kW)
38.480
38.137
37.794
37.451
37.108
36.765
36.422
Note: Dimension in mm
MODEL : ACC 100D/DR
Note: Dimension in mm
35
OUTDOOR UNIT
MODEL : AMC / A4MC 75 / 100 D/ER
Note: Dimension in mm
36
. REFRIGERANT
9.
REFRIGERANTCIRCUIT
CIRCUIT
MODEL : AC C 75/100D - AMC / A4MC 75/100D
37
38
39
11. INSTALLATION
PRELIMINARY SITE SURVEY
Electrical supply and installation is to conform to local authority's codes and regulations. (e.g. National Electricity Board).
Voltage supply fluctuation must not exceed +/- 10% of rated voltage. Electricity supply lines must be independent of
welding transformers which can cause high supply fluctuation. Ensure that the location is convenient for wiring and
piping.
The indoor unit must be installed such that there is no short circuit of the cool discharge. Comply to the installation
clearance recommended. Do not put the indoor unit where there is direct sunlight on unit. Make sure the location is
suitable for piping and drainage. Precautions steps :
800.0
800.0
800.0
PIPINGS
Do not use contaminated or damaged copper tubings. If pipings, evaporator or condenser are exposed or
had been opened for 15 seconds or more, vacuum and purge with field supplied refrigerant. Generally, do
not remove plastic/rubber plugs/caps from fittings, tubings and coils until ready to connect suction or liquid
line into fittings.
OPERATIONAL CHECK
After all electrical wiring is completed and the system is charged with refrigerant, make sure unit is operating
properly. Check that:
a)
b)
c)
d)
Condenser fans are running, with warm air blowing off the condenser coil.
Evaporator blowers are running and discharging cool air.
Suction line inside condensing unit feels cool.
Liquid line inside condensing unit feels warm.
ELECTRICAL CONNECTION
As wiring regulations differ from country to country, please refer to your LOCAL ELECTRICAL CODES for
field wiring regulations and ensure that these are complied with. Besides, observe the following general
precautions:
a) Ensure that the rated voltage of the unit corresponds to that of the name plate before commencing wiring
work.
b) Provide a power outlet to be used exclusively for each unit. A power supply disconnect and a circuit
breaker for over-current protection should be provided in the exclusive line.
c) The unit must be GROUNDED to prevent possible hazard due to insulation failure.
d) All wiring must be firmly connected.
e) Electrical wiring must not touch the refrigerant piping, compressor and any moving parts of the fan
motors.
40
R407C is a zeotropic refrigerant mixture which has Zero Ozone Depletion Potential (ODP = 0) and thus
conformed to the Montreal Protocol regulation. It requires Polyol-ester oil (POE) oil for its compressor's
lubricant. Its refrigerant capacity and performance are about the same as the refrigerant R22.
2) COMPONENTS
3) CHARACT ERISTIC
R407C liquid and vapor components have different compositions when the fluid evaporates or
condenses. Hence, when leak occurs and only vapor leaks out, the composition of the refrigerant
mixture left in the system will change and subsequently affect the system performance. DO NOT add
new refrigerant to leaked system. It is recommended that the system should be evacuated thoroughly
before recharging with R407C.
When refrigerant R407C is used, the composition will differ depending on whether it is in gaseous or
liquid phase. Hence when charging R407C, ensure that only liquid is being withdrawn from the cylinder
or can. This is to make certain that only original composition of R407C is being charged into the
system.
POE oil is used as lubricant for R407C compressor, which is different from the mineral oil used for R22
compressor. Extra precaution must be taken not to expose the R407C system too long to moist air.
Tubing
Refrigerant R407C is more easily affected by dust of moisture compared with R22, make sure to
temporarily cover the ends of the tubing prior to installation
Compressor oil
No additional charge of compressor oil is permitted.
Refrigerant
No other refrigerant other that R407C
Tools
Tools specifically for R407C only (must not be used for R22 or other refrigerant)
i)
Manifold gauge and charging hose
ii)
Gas leak detector
iii) Refrigerant cylinder/charging cylinder
iv) Vacuum pump c/w adapter
v)
Flare tools
vi) Refrigerant recovery machine
Like R22 system, the handling and installation of R407C system are closely similar. All precautionary
measures; such as ensuring no moisture, no dirt or chips in the system, clean brazing using nitrogen, and
thorough leak check and vacuuming are equally important requirements. However, due to zeotropic nature
of R407C and its hydroscopic POE oil, additional precautions must be taken to ensure optimum and
trouble-free system operation.
a) Filter-dryer must be installed along the liquid line for all R407C air conditioners. This is to minimise the
contamination of moisture and dirt in the refrigerant system. Filter-dryer must be of molecular sieve
type. For a heat-pump system, install a two-way flow filter dryer along the liquid line.
b) During installation or servicing, avoid prolong exposure of the internal part of the refrigerant system to
moist air. Residual POE oil in the piping and components can absorb moisture from the air.
41
c) Ensure that the compressor is not expose to open air for more than the recommended time specified by
its manufacturer (typically less than 10 minutes). Removed the seal plugs only when the compressor is
about to be brazed.
d) The system should be thoroughly vacuumed to 1.0 Pa ( 700mmHg) or lower. This vacuuming level is
more stringent than R22 system so as to ensure no incompressible gas and moisture in the system.
e) When charging R407C, ensure that only liquid is being withdrawn from the cylinder or can. This is to
ensure that only the original composition of R407C is being delivered into the system. The liquid
composition can be different from the vapor composition.
R32/R125/R134
23% / 25% / 52%
33% / 33% / 34%
Normally, the R407C cylinder or can is being equipped with a dip pipe for liquid withdrawal. However, if
the dip pipe is not available, invert the cylinder or can so as to withdraw liquid from the valve at the
bottom.
Invert cylinder
without dip-pipe
Dip-pipe
Liquid
withdrawal
g) When servicing leak, the top up method, commonly practiced for R22 system, is not recommended for
R407C system. Unlike R22 where the refrigerant is of a single component, the composition of R407C,
which made up of three different components, may have changed during the leak. Consequently, a top
up may not ensure that the R407C in the system is of original composition. This composition shift may
adversely affect the system performance. It is recommended that the system should be evacuated
thoroughly before recharging with R407C.
42
Warning
Disconnect from Main Supply before Servicing the air conditioner
The unit is designed to give a long life operation with minimum maintenance required. However, it should be
regularly checked and the following items should be given due attention.
Components
Air Filters
Maintenance Procedure
1. Clean with a vacuum cleaner, or by tapping lightly
and then washing in lukewarm water (below 40C)
With neutral soap.
Recommended Schedule
Every 2 weeks.
More frequently if required.
Every 2 weeks.
More frequently if required.
Every 3 months.
Indoor Fan
As necessary.
Indoor/Outdoor Coil
Every month.
1.
Every month.
Every 2 months.
Every 2 months.
Compressor
Every 6 months.
Compressor
Lubrication
No maintenance required.
Fan Motors
Lubrication
No maintenance required.
43
The design concept of the Condensing Unit is such that all servicing can be done from the front and side of the unit.
Upon removal of front and side panel, all the electrical "terminal box", fan and motor assembly and compressor are easily
accessible.
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surfaces once
quarterly. However, if a unit is installed in area subjected to much oil, mist and dust, the coil must be regularly cleaned by
qualified Air Conditioner Service Technicians to ensure sufficient heat exchange and proper operation. Otherwise, the
systems life span might be shortened.
CAUTION
When the compressor is to be stopped for a long time, the crankcase heater should be energized for at least
6 hours before start of operation.
Do not charge OXYGEN, ACETYLENE or other flammable and poisonous gases into the refrigeration cycle
when performing a leakage test or an airtight-test. These types of gases are extremely dangerous, because
explosion can occur.
It is recommended that nitrogen or refrigerant be charged for these types of tests.
Bear the following points in mind to safeguard against malfunction and breakdown.
Do not stick rods or other objects through the air outlet during operation since this may result to damage or injury
The air conditioner must not re-start within 3 minutes after shutdown. (These models are equipped with a crankcase
heater with the compressor).
Make sure the air conditioner is properly grounded by checking the ground terminal.
MAINTENANCE
For superb performance and lasting durability, please do not forget to conduct proper and regular maintenance.
Cleaning The Outdoor Unit Heat Exchanger
If you use your air conditioner for prolonged period of time, the outdoor unit heat exchanger will become dirty
impairing its function and reducing the performance of the air conditioned. Consult your local dealer about the cleaning of
the heat exchanger.
44
13. TROUBLESHOOTING
When any air-conditioner malfunction is noted, immediately switch off the power supply to the unit, and
contact the local dealer, if necessary. Some simple troubleshooting tips are given below :
FAULT
CAUSE
The unit has a lower temperature point, increase the point and
operate at high speed.
45
No Cooling
: Check
: Faulty
: Cause
Remedy
Stop
Unit Power
Supply
Running
Faulty
Fuse For
Operation
Circuit
Blown
Overcurrent
Relay For
Evaporator Fan
Tripped
Evaporator Fan
Contactor
Single-Phase
Components Shorted
Connections Loose
High Volage or Low Voltage
Single-Phase
Faulty
Coil Burned
Contact Faulty
Faulty Fan Motor
Defective Operation Switch
Condenser
Fan Motor
Stop
Overcurrent
Relay For
Condenser Fan
Tripped
Running
Condenser Fan
Contactor
Faulty
Coil Burnt
Contact Faulty
Fan Motor Faulty
Other Electrical Component Faulty
Compressor
Contactor
Faulty
Coil Burnt
Contact Faulty
Open Compressor Windings
Incorrect Wiring
46
INSUFFICIENT COOLING
Insufficient Cooling
Compressor
Cycling
Cycling On
Dual Pressure
Switch
Tripping
Running
Overcurrent
Relay For
Compressor
Tripping
Discharge Gas
Thermostat or
Internal
Thermostat
Tripping
Condenser
Air Inlet
Temperature
High
Condenser
Air Flow
Excessive
47
Evaporator
Air Inlet
Temperature
Evaporator
Air Flow
Restricted
Evaporator
Air Inlet
Temperature
Low
Restricted Duct
Short Cycling
Faulty Thermostat
Restricted Liquid LIne And
Suction Line
Low Refrigerant Charge
Low Discharge Pressure
NOISY OPERATION
Noisy Operation
Compressor
Noisy
Shipping
Bolt(s)
Noisy
Liquid
Refrigerant
Backing Up
Evaporator
Fan
Liquid Line
Noisy
Knocking Runner
Noisy
Strainer
Whistling
Worn Bearing
Partially Clogged
Add Refrigerant
48
Too
High
PROBABLE CAUSE
A Little
High
Circuit
Normal
Too
Low
Data
A Little
Low
PRESSURE
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
High Side
Low Side
No Cooling / Heating
Unit fail to start
Loose Connections,
Contactors
Reset
Irregular
49
Insufficient Cooling
Unit Starts
Check air circulation
Leakage
Excessive heat
source e.g. electric
kettle
Restriction e.g. at
strainer, capillary,
filter dryer, etc.
Room overcrowded
with people
Compressor
Windows / doors
wide open
Less or no compression
(Low running current)
Insufficient Heating
Unit Starts
Check air circulation
Leakage
Air filters dirty
Restriction e.g. at
strainer, capillary,
filter dryer, etc.
Fan Malfunction
Compressor
Less or no compression
(Low running current)
50
Windows / doors
wide open
No.
Description
1
Assy, Panel Front Base
2
Panel, Back Base
3
Assy, Drain Pan
4
Assy, Coil Tubing CC 75D
5
Cover, Coil Right
6
Cover, Coil Left
7
Flange, Filter Right
8
Flange, Filter Left
9
Rail, Filter (CC75D/DR)
10
Drain Pan Seperator
11
Assy, Panel Top
12
Flange, Filter T/B
13
Assy, Fan Deck
14
Panel, Side Ledt
15
Panel, Header Small Right
16
Panel, Side Big Right
17
Assy, Bracket Drain Pump Cover
18
Switch, Level
19
Assy. Terminal Box
20
Cover, Filter L/R
21
Hanger
Parts Not Shown in Diagram
Control Module
Valve, TXV
51
Part Number
A50014076024
A01014074050
A50019023584
A50024078270
A01014073369
A01014073370
A01014073811
A01014073810
A12014076976
A01014077402
A50014073371
A01014074120
A50034074053
A01014073368
A01014073366
A01014073365
A50014080406
A04069022966
A50044080388
A01014074119
A01014032372
A04089025212
A05019015343
No.
Description
1
Assy, Panel Front Base
2
Panel, Back Base
3
Assy, Drain Pan
4
Assy, Coil Tubing CC 75DR
5
Cover, Coil Right
6
Cover, Coil Left
7
Flange, Filter Right
8
Flange, Filter Left
9
Rail, Filter (CC75D/DR)
10
Drain Pan Seperator
11
Assy, Panel Top
12
Flange, Filter T/B
13
Assy, Fan Deck
14
Panel, Side Ledt
15
Panel, Header Small Right
16
Panel, Side Big Right
17
Assy, Bracket Drain Pump Cover
18
Switch, Level
19
Assy. Terminal Box
20
Cover, Filter L/R
21
Hanger
Parts Not Shown in Diagram
Control Module
Valve, TXV
52
Part Number
A50014076024
A01014074050
A50019023584
A50024074055
A01014073369
A01014073370
A01014073811
A01014073810
A12014076976
A01014077402
A50014073371
A01014074120
A50034074053
A01014073368
A01014073366
A01014073365
A50014080406
A04069022966
A50044076981
A01014074119
A01014032372
A04089023681
A05019022121
No.
Description
1
Assy, Panel Front Base
2
Panel, Back Base
3
Assy, Drain Pan
4
Assy, Coil Tubing CC 100D
5
Cover, Coil Right
6
Cover, Coil Left
7
Flange, Filter Right
8
Flange, Filter Left
9
Rail, Filter (CC100D/DR)
10
Drain Pan Seperator
11
Assy, Panel Top
12
Flange, Filter T/B
13
Assy, Fan Deck
14
Panel, Side Ledt
15
Panel, Header Small Right
16
Panel, Side Big Right
17
Assy, Bracket Drain Pump Cover
18
Switch, Level
19
Assy. Terminal Box
20
Cover, Filter L/R
21
Hanger
Parts Not Shown in Diagram
Control Module
Valve, TXV
53
Part Number
A50014076025
A01014073346
A50019023585
A50024078271
A01014073369
A01014073370
A01014073811
A01014073810
A12014076977
A01014077402
A50014074594
A01014073812
A50034073347
A01014073368
A01014073366
A01014073365
A01014077181
A04069022966
A50044080388
A01014074119
A01014032372
A04089025212
A05019015344
No.
Description
1
Assy, Panel Front Base
2
Panel, Back Base
3
Assy, Drain Pan
4
Assy, Coil Tubing CC 75D
5
Cover, Coil Right
6
Cover, Coil Left
7
Flange, Filter Right
8
Flange, Filter Left
9
Rail, Filter (CC75D/DR)
10
Drain Pan Seperator
11
Assy, Panel Top
12
Flange, Filter T/B
13
Assy, Fan Deck
14
Panel, Side Ledt
15
Panel, Header Small Right
16
Panel, Side Big Right
17
Assy, Bracket Drain Pump Cover
18
Switch, Level
19
Assy. Terminal Box
20
Cover, Filter L/R
21
Hanger
Parts Not Shown in Diagram
Control Module
Valve, TXV
54
Part Number
A50014076025
A01014073346
A50019023585
A50024073351
A01014073369
A01014073370
A01014073811
A01014073810
A12014076977
A01014077402
A50014074594
A01014073812
A50034073347
A01014073368
A01014073366
A01014073365
A50014080406
A04069001616
A50044076981
A01014074119
A01014032372
A04089023681
A5019022122
55
56
Description
Assy, Base Pan Main
Compressor
AMC 75D
A4MC 75D
3
Struc. Tube Support
4
Assy, Access Valve
AMC 75D
A4MC 75D
5
Support, Tube Liquid 1/2" Tube
6
Support, Tube Gas 1" Tube
7
Assy, Coil Left Main
8
Assy, Coil Right Main
9
Struc. Coil
10
Assy, Structure Back L
11
Assy, Structure Back R
12
Clamp, Tube Liquid 1/2" Tube
13
Clamp, Tube Gas 1" Tube
14
Structure, Front Left
15
Structure, Front Right
16
Cover, Terminal Board Back
17
Panel, Orifice
18
Motor
19
Fan Propeller, 32"
20
Fan Guard 32"
21
Panel, Service Top
22
Panel, Service Bottom
23
Assy, S. Hoisting Bracket
Parts Not Shown in Diagram
Pressure Switch
High Pressure Switch
Bracket, Fan Motor 32"
Phase Sequencer
Assy, Discharge Thermostat
Filter Drier
Part Number
A50014045044
No.
1
2
Description
Assy, Base Pan Main
Compressor
AMC 75ER
A4MC 75ER
3
Accumulator
AMC 75ER
A4MC 75ER
4
Struc. Tube Support
5
Support, Tube Liquid 1/2" Tube
6
Support, Tube Gas 1" Tube
7
Assy, Access Valve
8
Assy, Coil Left Main
9
Assy, Coil Right Main
10
Struc. Coil
11
Assy, Structure Back L
12
Assy, Structure Back R
13
Clamp, Tube Liquid 1/2" Tube
14
Clamp, Tube Gas 1" Tube
15
Structure, Front Left
16
Structure, Front Right
17
Cover, Terminal Board Back
18
Panel, Service Top
19
Panel, Orifice
20
Motor
21
Fan Propeller, 32"
22
Fan Guard 32"
23
Panel, Service Bottom
24
Assy, S. Hoisting Bracket
Parts Not Shown in Diagram
Pressure Switch
High Pressure Switch
Bracket, Fan Motor 32"
Phase Sequencer
Assy, Discharge Thermostat
Filter Drier
A50049004676
A50049014526
A01014044386
A50054028348
A50054077736
A01014024023
A01014024026
A50024044767
A50024044769
A01014022392
A50014022910
A50014029795
A01014024030
A01014024033
A01014069646
A01014069647
A01014044214
A01014044211
A03039012606
A03019021351
A01029048691
A01014069644
A01014069645
A50014022906
A04109015400
A04109015136
A01024048601
A04089018834
A50044052922
A02164034987
57
Part Number
A50014046841
A50049004676
A50049014526
A02119004676
A02119015245
A01014044386
A01014024023
A01014024026
A50054028348
A50024052994
A50024052995
A01014022392
A50014022910
A50014029795
A01014024030
A01014024033
A01014069646
A01014069647
A01014044214
A01014069644
A01014044211
A03039012606
A03019021351
A01029048691
A01014069645
A50014022906
A04109015400
A04109015136
A01024048601
A04089018834
A50044052922
A02164034987
58
59
AMC/A4MC 100D
No.
1
2
Description
Assy, Base Pan Main
Compressor
AMC 100D
A4MC 100D
3
Struc. Tube Support
4
Assy, Access Valve
5
Support, Tube Liquid 5/8" Tube
6
SupportT, Tube Gas 1-1/8" Tube
7
Assy, Coil Left Main
8
Assy, Coil Right Main
9
Struc. Coil
10
Assy, Structure Back L
11
Assy, Structure Back R
12
Clamp, Tube Liquid 5/8" Tube
13
Clamp, Tube Gas 1-1/8" Tube
14
Structure, Front Left
15
Structure, Front Right
16
Cover, Terminal Board Back
17
Panel, Orifice
18
Motor
19
Fan Propeller, 32"
20
Fan Guard 32"
21
Panel, Service Top
22
Panel, Service Bottom
23
Assy, S. Hoisting Bracket
Parts Not Shown in Diagram
Low Pressure Switch
High Pressure Switch
Bracket, Fan Motor 32"
Phase Sequencer
Assy, Discharge Thermostat
Part Number
A50014045044
No.
1
2
Description
Assy, Base Pan Main
Compressor
AMC 100ER
A4MC 100ER
3
Accumulator
4
Struc. Tube Support
5
Support, Tube Liquid 5/8" Tube
6
SupportT, Tube Gas 1-1/8" Tube
7
Assy, Access Valve
8
Assy, Coil Left Main
9
Assy, Coil Right Main
10
Struc. Coil
11
Assy, Structure Back L
12
Assy, Structure Back R
13
Clamp, Tube Liquid 5/8" Tube
14
Clamp, Tube Gas 1-1/8" Tube
15
Structure, Front Left
16
Structure, Front Right
17
Cover, Terminal Board Back
18
Panel, Service Top
19
Panel, Orifice
20
Motor
21
Fan Propeller, 32"
22
Fan Guard 32"
23
Panel, Service Bottom
24
Assy, S. Hoisting Bracket
Parts Not Shown in Diagram
Pressure Switch
High Pressure Switch
Bracket, Fan Motor 32"
Phase Sequencer
Assy, Discharge Thermostat
Filter Drier
A50049004677
A50049014427
A01014046135
A50054028348
A01014023152
A01014024027
A50024044774
A50024044776
A01014022392
A50014022910
A50014029795
A01014023149
A01014024034
A01014069646
A01014069647
A01014044214
A01014044211
A03039012606
A03019021351
A01029048691
A01014069644
A01014069645
A50014022906
A50134056107
A04109015136
A01024048601
A04089018834
A50044052922
60
Part Number
A50014046841
A50049004677
A50049014427
A02119015246
A01014046135
A01014023152
A01014024027
A50054028348
A50024053124
A50024053125
A01014022392
A50014022910
A50014029795
A01014023149
A01014024034
A01014069646
A01014069647
A01014044214
A01014069644
A01014044211
A03039012606
A03019021351
A01029048691
A01014069645
A50014022906
A50014022906
A04109015136
A01024048601
A04089018834
A50044052922
A02164034987
While upmost care is taken in ensuring that all details in the publication are correct at time of going to press, we are constantly striving for
improvement and therefore reserve the rights to alter model specifications and equipment without prior notice. Details of specifications and
equipment are also subject to change to suit local conditions and equipments and not all models are available in every market.