pgnul gSoll Saudi Aramco EQUIPMENT INSPECTION RECORD-GENERAL, SUADI ARABAIN OIL COMPANY Sui Aramco 2093 (1190) Plant o unit Equipment H.P.BOILER 30-1-D-725 (CONDENSATE DRIP RECEIVER ) DATE REMARKS 9/772010 | Initial inspection was conducted and found with moderate sludge T&I | accumulated at the bottom section. Water wash was recommended and after cleaning inspection was revealed. The shell and the heads were in good condition with general pitting lake type was noted at the bottom section to 0.100” deep. All accessible welds were found in good working condition with pitting lake type was noted on the circumferential weld at the bottom section as the shell. The top 6” nozzle weld overlaid was found with pitting lake type to 0.050" deep. The nozzles ID's were free of corrosion. The vortex breaker was in serviceable condition. The man way, man way cover and the gasket surfaces were found in serviceable condition .The shell bottom quarter was coated with APCS-2C to mitigate the corrosion. UT reading was performed and found acceptable. AMK Khoraim, Ali M “yom: Muailu, Jamal H Lent: Wednesday, September 15, 2010 10:43 AM To: Khoraim, Ali M Ce: Mubarky, Hassan Y; Fageeh, Abdulrahman S Subject: Drip Receiver 30-D-725 Importance: High All Under-deposit corrosion up to about 0.100” depth was observed at the bottom of Drip Receiver 30-D-725. The long downtime allowed scale and deposits to precipitate and cause this type of corrosion. Recommendation: To mitigate under-deposit corrosion, coat the bottom quarter of the drum using APCS- 2C. APCS-2C is suitable for service temperatures up to 250°F which is higher than the operating temperature of the drum (200 to 230°F). Note that the drum must not be steamed, during start-ups and shutdowns, without artially filling it with condensate in order to prevent exceeding the maximum allowable service temperature of the coating Regards, Jamal Al-Muailu, Corr, Engr, RED/Insp. Unit Tel 673-2542, Fax 673-2812 EQUIPMENT INSPECTION RECORD-GENERAL SUADI ARABAIN OIL COMPANY Saud Aramco 2093 (150) Plant o unit Equipment 30-1 30-D-725, Condensate Drum. DATE REMARKS 12/27/2005 _| The drum (30-D-725) was taken out of service on December 20, 2005 for scheduled T&L. Initial internal visual inspection revealed that the drum internal surfaces are dirty with about 5 buckets of sludge and water deposits accumulated at the bottom surface. Hydrojet cleaning was recommended and performed, After cleaning, the drum was thoroughly inspected and found free of corrosion and in good condition. ‘All scem welds and nozzles were ie sound and in good mechanical condition. UT was performed and found all readings are above the drum Tm. The drum was accepted to ‘be closed and_was put back on service on 12/26/2005. MAZ EQUIPMENT INSPECTION RECORD-GENERAL ‘Saud Aramco 2093-ENG (11/90) ‘Saudi Arabian OIL COMPANY Plant or unit 30-1 2am Plant 30-D-725, Condensate Drum DATE, REMARKS 8/15/00 __| The subject drum 30-D-725 was completely taken out of service for maintenance ‘and inspection on July 20,1999 and returned back to service on August 12,2000 The Initial internal visual inspection was conducted and found the drum shell internal Surfaces are dirty which required to be hydrojet clean with condensate ‘The internal shell surfaces and heads were internally inspected after hydrojet cleaning ‘and found In good condition with no pitting or corrosion was detected. “The piping and valves were inspected and found in good condition MHQ 8/15/00

Das könnte Ihnen auch gefallen