Once the valve type is selected, the next task is to choose the valve characteristics, and size the

valve. Three of the most common valve characteristics are described in Figure 1 below, and the
tabulation below lists the recommended selections of valve characteristics for some of the most
common process applications.

The characteristic curves were drawn, assuming that the pressure


drop through the valves remain constant while the valves throttle.
The three valve characteristics differ from each other in their gain
characteristics.

>> How to select control


valves, Part 1

Download our beginner's guide to differential pressure level transmitters


The gain of a control valve is the ratio between the change (=%) in the control signal, which the
valve receives and the resulting change (=%) in the flow through the valve. Therefore, the valve
gain (Gv) can be expressed as GPM/% stroke. The gain (Gv = GPM/%) of a linear valve is
constant, the gain of an equal percentage (=%) valve is increasing at a constant slope, and the
gain of a quick opening (QO) valve is dropping as the valve opens.
The valve characteristics are called linear (straight line in Figure 1), if the gain is constant
(Gv=1), and a 1% change in the valve lift (control signal) results in the same amount (GPM) of
change in the flow through the valve, no matter how open the valve is. This change is the slope
of the straight line in Figure 1, and it can be expressed as a percentage of maximum flow per a
1% change in lift, or as a flow quantity of say 5 GPM per % lift, no matter how open the valve is.
FIGURE 1: VALVE CHARACTERISTICS

The most common control valve characteristics for common applications.


If a 1% change in the valve stroke results in the same percentage change (not quantity, but % of
the flow that is occurring!), then the valve characteristic is called equal percentage (=%). If the

valve characteristics is =%, the amount of change in flow is a small quantity, when the valve is
nearly closed, and it becomes larger and larger as the valve opens.
As shown in Figure 1, in case of quick opening (QO) valves, the opposite is the case; at the
beginning of the stroke, the valve gain is high (the flow increases at a fast slope) and towards full
opening, the slope is small.
Get the latest trends and improvements in level and flow technologies
The recommended choice of the valve characteristic is a function of the application. For common
applications, the recommendations are tabulated at the bottom of Figure 1. It should be noted
that Figure 1s valve characteristics assume that the valve pressure drop is constant.
Unfortunately, in most applications, it isnt constant, but drops off as the load (flow) increases.
This is why the valve characteristics recommended in Figure 1 are different if the ratio of
maximum to minimum pressure differential across the valve is above or below 2:1.
One approach to characterizing an analog control signal is to insert either a divider or a multiplier
into the signal line. By adjusting the zero and span, a complete family of curves can be obtained.
A divider is used to convert an air-to-open, equal-percentage valve into a linear one, or an air-toclose linear valve into an equal-percentage one. A multiplier is used to convert an air-to-open
linear valve into an equal-percentage, or an air-to-close equal-percentage valve into linear one.
Distortion of Valve Characteristics
Figure 2 below shows the effect of the distortion coefficient (Dc, defined in Figure 2) on the
characteristics of an =% valve. As the ratio of the minimum to maximum pressure drop increases,
the Dc coefficient drops and the =% characteristics of the valve shifts towards linear.
FIGURE 2: DISTORTION COEFFICIENT

The characteristic curve of an equal percentage valve shifts towards linear as the Distortion
Coefficient (Dc) drops. This drop also reduces the rangeabillity of the valve.
Similarly, under these same conditions, the characteristics of a linear valve would shift towards
quick opening (QO, not shown in Figure 2). In addition, as the Dc coefficient drops, the
controllable minimum flow increases, and therefore the rangeability of the valve also drops.
Rangeability
The conventional definition of rangeability is the ratio between the maximum and minimum
controllable flows through the valve. Minimum controllable flow (Fmin) is not the leakage flow
(which occurs when the valve is closed), but the minimum flow that is still controllable, and can
be changed up or down as the valve is throttled.
Using this definition, manufacturers usually claim a 50:1 rangeability for equal-percentage
valves, 33:1 for linear valves, and about 20:1 for quick-opening valves. These claims suggest
that the flow through these valves can be controlled down to 2%, 3%, and 5% of maximum.
However, these figures are often exaggerated. In addition, as can be seen in Figure 2, the
minimum controllable flow (Fmin) rises as the distortion coefficient (Dc) drops. Therefore, at a Dc
of 0.1, the 50:1 rangeability of an equal-percentage valve drops to about 10:1.
Consequently, the rangeability should be defined as the flow range over which the actual
installed valve gain stays within 25% of the theoretical (inherent) valve gain (in the units of GPM
per % stroke). To illustrate the importance of this limitation, Figure 3 shows the actual gain of an
equal percentage valve starts to deviate from its theoretical gain by more than 25%, when the
flow reaches about 65%.
Therefore, in determining the rangeability of such a valve, the maximum allowable flow should be
65%. Actually, if one uses this definition, the rangeability of an =% valve is seldom more than
10:1. In such cases, the rangeability of a linear valve can be greater than that of an =% valve.
Also, the rangeability of some rotary valves can be higher because their clearance flow tends to
be lower, and their body losses near the wide open position also tend to be lower than those of
other valve designs.
To stay within 25% of the theoretical valves gain, the maximum flow should not exceed 60% of
maximum in a linear valve or 70% in an =% valve. In terms of valve lift, these flow limits
correspond to 85% of maximum lift for =% and 70% for linear valves.
How to select control valves, Part 1

PICKING THE RIGHT CONTROL VALVE

Click image to view an enlarged pdf of this chart.


When it comes to selecting and sizing control valves, this unique and completely non-commercial
valve selection chart not only helps you pick the right control valve for the job, but also serves as
a fantastic reference tool you can download!
>> CLICK HERE to open an enlarged pdf version for easy viewing chart, or click the Download
Now button at the end of this article to save the chart for future reference.
[Editor's Note: How to Select Control Valves, Part 3, will appear in the November 2006 issue
of Control magazine, and here on ControlGlobal.com.]

Selection criteria for


control valve.
1. Maximum operating pressure
2. Maximum flow rate
3. Operating temp range
4. Rate of cycling
5. Response time
6. Air/Fluid quality
7. Mounting method
8. Leakages
9. Maintenance.