Section 1
1. Scope of works :
a)
The general character and the scope of work to be carried out under this
contract is illustrated in the Data Point Summary, specifications and the
schedule of the quantities. The contractor shall carry out and complete the said
work under this contract in every respect in conformity with the contract
documents and with the direction of and to the satisfaction of the owners site
representative/consultants. The contractor shall furnish all labor, materials and
equipment as listed under the schedule of quantities and specified otherwise,
transportation and incidentals necessary for supply, installation, testing and
commissioning of the complete BAS system as described in the specifications.
This also includes any material, equipment, appliances and incidental work not
specifically mentioned herein or noted on the documents as being furnished or
installed. But which are necessary and customary to be performed under this
contract and which are required under the Bill of Quantities and the
specifications for the central Integrated Building Automation System.
2.
i.
All civil works associated with IBMS installations like making openings to run
the conduits and making them good and any other as required shall be covered
under the scope of this contract.
3.
The contractor shall ensure that senior planning and execution personnel from his
organization are assigned exclusively for this project. They shall have minimum 10
years experience in this type of installations.
For quality control & monitoring of workmanship, contractor shall assign at least one
full time engineer who would be exclusively responsible for ensuring strict quality
control, adherence to the specifications and ensuring top class workmanship for the
air-conditioning installation.
The contractor shall arrange to have mechanized and modern facilities for
transportation of materials to the place of installation for speedy execution of work.
4.
Performance Guarantee:
The Contractor shall carry out the works in accordance with the specifications,
schedule of the quantities and other documents forming part of the contract. The
contractor shall be fully responsible for the performance of selected items/equipment
(installed by him) at the specified parameters and for the efficiency of the installations
to deliver the required end results. The contractor shall guarantee that the IBMS
system as installed shall maintain the parameters required under the BOQ and
-
70
specifications. The guarantee shall be submitted in the Performa sheet. Complete set
of architectural drawings are available in the office of architect/consultants and
reference may be made to same for any detail or information. The contractor shall also
guarantee that the performance of various equipment individually, shall not be less
than the quoted capacity.
5.
The installations shall be in conformity with the by-laws and regulations and standards
of the local authorities concerned, in so far as these become applicable to the
installations. But if these specifications and drawings call for a higher standard of
material and /or workmanship than those required by any of the above regulations and
standards then these drawings and specifications shall take precedence over the said
regulations and standards. However if the specifications require something which
violates the bye-laws and regulations, then the bye-laws and regulations shall govern
the requirement of the installations.
6.
The contractor shall obtain all permits/licenses and pay for any or all fees required for
inspection, approvals and commissioning of their installations if required.
7.
Technical Datas:
Each tenderer shall submit along with his tender, the technical data for all items.
Failure to submit complete data with the tenders may result in summary rejection of
the tender.
8.
Shop Drawings:
8.1
All the shop drawings shall be prepared on computer through Autocad system
based on the architectural drawings, site measurements and interior designers
drawings. These shop drawings shall contain all information required to
complete terminations. These shop drawings shall contain all the information
required to complete the project as per specifications and as required by the
Architect/Consultant/Owners site representative. These drawings shall contain
details of constructions, size arrangement, operating clearances, performance
characteristics and capacity of all items of equipment. Each shop drawing shall
contain tabulation of all measurable items of equipment/material/works and
progressive cumulative totals from other related drawings to arrive at a
variation in quantity statement at the completion of all shop drawings. Minimum
7 sets of drawings shall be submitted after final approval along with their
floppies.
Each item of equipment/material proposed shall be a standard catalogue product
of an established manufacturer strictly from the manufactures listed in under the
approved list of makes and quoted by tenderer in technical data part of tender.
When the Architect/Consultant makes any amendment in the above drawings,
the contractor shall supply two fresh sets of drawings with the amendments duly
71
incorporated along with check prints for approval. The contractor shall submit
further 7 sets of the shop drawings
When the Architect/Consultant makes any amendments in the above drawings,
the contractor shall supply two fresh sets of drawings with amendments duly
incorporated along with check prints for approval. The contractor shall submit
further seven copies of shop drawings to the owners site representative for the
exclusive use of the owners site representative and all other agencies. No
material or equipment may be delivered or installed at the job site until the
contractor has in his possession the approved shop drawing for the particular
material/equipment/installations.
8.2 Shop drawings shall be submitted for approval four weeks in advance of planned
delivery and installation of any material to allow Architect/Consultant ample time
for scrutiny. No claims for extension of time shall be entertained because of any
delay in works due to his failure to produce shop drawings at the right time in
accordance with the approved program.
8.3 Manufacturers drawings, catalogues, pamphlets and other documents submitted
for approval shall be in four sets. Each item in each set shall be properly labeled,
indicating the specific services for which the material /equipment is to be used,
giving reference to the governing section and clause number and clearly
identifying in ink the items and the operating characteristics. Data for general
nature shall not be accepted.
8.4 Samples of all materials like sensors, field devices, controls, control wires etc.
shall be submitted to the owners site representative prior to procurement. These
will be submitted in 2 sets of approval and retention by owners site
representative and shall be kept in their site office for reference and verification
till the completion of the project. Wherever directed a mockup or sample
installation shall be carried out for approval before proceeding for further
installations.
8.5 Approval of shop drawings shall not be considered as a guarantee of
measurement or that of a building dimension. Where drawings are approved said
approval doesnt mean that the drawings supercede the contract requirements,
nor does it in any way relieve the contractor of the responsibility or requirements
to furnish material and perform as required by the contract.
8.6 Where contractor propose to use an item or equipment other than that specified
or detailed on the drawing which requires any redesign of the structure, partitions
, foundations, piping or any other apart of the electrical and architectural
layouts ,all such redesign and all new drawings and detailing required therefore
shall be prepared by the contractor at his own expenses and gotten approved by
the architect/consultant/owners site representative. Any delay on such account
shall be at the cost and consequences to the contractor.
8.7 IBMS contractor shall prepare coordinated service shop drawings based on the
drawings prepared by HVAC, electrical, plumbing & low voltage contractors to
ensure adequate clearances are available for installation of service for each
trade. Where the work of the contractor has to be installed in close proximity to or
will interfere with the work of other trade he shall assist in working out space
-
72
10.
Accessibility:
The contractor shall verify the sufficiency of the size of the shaft openings,
clearances in cavity walls and suspended ceiling for proper installation of his
work. His failure to communicate is insufficiency of the same. The contractor shall
locate all equipment which must be serviced, operated or maintained in fully
accessible positions.
11. Materials and equipment :
All materials and equipment shall conform to the relevant Indian standards and
shall be of the approved make and design. Makes shall be strictly in conformity
with the list of approved manufactures.
12. Manufactures Instructions :
Where manufacturer has furnished specific instructions relating to the
material/equipment used in this project, covering points especially not mentioned
in these documents, such instructions shall be followed in all cases.
73
supervision the installation was carried out .This certificate shall be in the
prescribed form as required by the local authority if applicable.
14.
15.
COMPLETION DRAWINGS
Contractor shall periodically submit completion drawings as and when work in
all respects is completed in a particular area. These drawings shall be
submitted in the form of two sets of floppies/CDs and four portfolios (300 x 450
mm ) each containing complete set of drawings on approved scale indicating
the work as installed .These drawings shall clearly indicate complete plant
room layouts ,location of wiring and sequencing of automatic controls ,locations
of all concealed piping ,valves, controls, dampers, wiring and other services
.Each portfolio shall also contain consolidated control diagrams and technical
literature on all controls. The contractor shall frame under glass, in the IBMS
room, one set of these consolidated control diagrams.
16.
17.
On Site Training:
Upon completion of all works and all tests, the contractor shall furnish
necessary operators labor and helpers for operating the entire installation for a
period not less than two weeks of ten hours each to enable the owners staff
get acquainted with the operation of the system. During this period the
contractor shall train the owners personnel in the operation, adjustment and
maintenance of all equipment installed.
74
18.
18.1
Complains:
The contractor shall receive calls for any or all problems experienced in the
operation of the system under this contract, attend to these within four hours of
receiving the complaints and shall take steps to immediately correct any
deficiencies that may exist.
18.2
Repairs:
All equipment that requires repairing shall be immediately serviced and
repaired. Since the period of mechanical maintenance runs for two years
concurrently with the defects liability period, all replacement parts and labor
shall be supplied promptly free of charge to the owner.
19.
Uptime Guarantee:
The contractor shall guarantee for the installed system an uptime of 98%. In case of
shortfall in any month during the defects liability period, the defects liability period gets
extended by a month for every month having shortfall. In case of shortfall beyond the
defects liability period the contract shall get extended by a month for every month
having the shortfall and no reimbursement shall be done for the extended period.
The contractor shall provide log in the form of diskettes and bound printed
comprehensive log book containing tables for daily record of all temperature,
pressure, humidity, power consumption starting and stopping times for various
equipment, daily service rendered for the system alarms, maintenance records of
unusual observations etc.
Contractor shall also submit preventive maintenance schedule.
Each tenderer shall submit along with the tender, a detailed operation assistance
proposal for the owners site representative / consultants review. This should include
the type of service planned to be offered during the defects liability period and beyond.
The operation assistance proposal shall give the details of the proposed monthly
reports to the management.
The tenderer shall include a list of such project where such operation assistance has
been provided.
20.
Manpower:
i)
ii)
iii)
iv)
75
End of Section
SPECIFICATIONS
76
Section 2
INTEGRATED BUILDING MANAGEMENT SYSTEM
1.0
-
The system will consist of a flat, open architecture that utilizes the LonTalk
protocol as the common communication protocol between all controlled and
controlling devices, and LNS architecture for the definition of the device
database. No other device database structure will be permitted. When
necessary or desired, LonTalk packets shall be encapsulated into TCP/IP
messages to take advantage of existing infrastructure or to increase network
bandwidth. Any such encapsulation of the LonTalk protocol into IP datagrams
shall conform to existing LonMark guidelines for such encapsulation. Systems
that utilize non standard routing methods or hierarchal systems consisting of
master or global controllers that poll and/or control less intelligent unitary
controllers on a secondary bus will not be considered.
Microprocessor based Direct Digital Distributed Controllers (DDC) shall
interface with sensors, actuators and environmental control systems (i.e.
HVAC , electrical, Fire & plumbing and electrical system etc.) and carry out
followings functions:
a.
b.
c.
d.
e.
f.
g.
h.
78
Overall, the system shall be provided with 15% spare capacity, with spare of
at least 15% points on each controller. Also, in case of HVAC system, each
controller shall control maximum one chiller and associated chilled water pump.
There shall be one control station located in Building Automation Room. The
computer shall be sized to cover the graphic display memory and planning
information. The display shall be in the form of dynamic colour graphics and
text format with menu driven pop-up windows and help facility.
Reference Standards
1. Control system components shall be new and in conformance with
the following applicable standards for products specified:
i. ANSI\EIA 709.1 (LonTalk Protocol)
ii. LonMark Certified (Version 3.1 Guidelines)
iii. UL 916 (Energy Management Equipment)
Products
1. Utilize standard components for all assemblies. Custom hardware,
operating system, and utility software are not acceptable.
2. All products (PCU's, TDCU's and ID's) shall contain LonWorks
networking elements to allow ease of integration of devices from
multiple vendors.
3. All materials, equipment and software shall be standard components,
regularly manufactured for this and other systems and custom
designed for this project. All systems and components shall be
thoroughly tested.
79
2.0
a.
DESCRIPTION
Processor
Memory
Cache (External)
ROM
Expansion Bus
Graphic Accelerator
Hard Disk
80 GB E-IDE/100 ATA
Power Supply
350 W switchable/50 Hz
Keyboard
Operating System
Software
Office XP/Vista
Antivirus Software
CD Writer
b)
Key board : The central station shall be complete with detached 101-keys
keyboard which includes
full upper/lower case ASCII keyset, a numeric
pad, dedicated cursor control pad, and a minimum of 10 programmable
functional keys.
c)
80
horizontal, 768 lines vertical and minimum 16 base colors. The monitor shall
be with tilt and swivel facilities.
d)
e)
Printers: The contractor shall provide printers as specified for printing alarms,
operator transactions and reports.
There shall be two printers with each Control Station. One printer shall be
dedicated for alarm printing and the second printer for printing reports, trend
log, summary, tantalizer logging, recording alarms and providing system
reports etc. Each of these shall be identical and inter-changeable, and shall
have the following characteristics:
i)
ii)
132 column/300 character per second print speed with minimum 24 pin head.
iii)
Adjustable line spacing of six or eight lines per inch with compressed mode
option and bidirectional printing and logic seeking.
f)
The available PCI slots on the PC shall be used only for communication cards
and shall not be utilized for mounting protocol converter cards. If protocol
0converter cards are used, they shall be external to PC and separately
powered and backed-up by the UPS supply.
3.0
81
82
83
84
85
Calendar.
Scheduling.
Trending.
Alarm monitoring and routing.
Time synchronization.
Time zone handling
Integration of LONWORKS controller data
Object linking and embedding for process control (OPC) for
connectivity to third party OPC compliant software/devices
ix. Color graphic display
x. On-line plots
xi. Use Microsoft NT security
xii. System documentation generation
xiii. Dynamic data exchange (DDE)
xiv. Dispatch of a single time schedule to all programmable nodes
4. System Configuration. At a minimum, the HMI shall permit the
operator to perform the following tasks, with proper password
access:
i. Create, delete, upload, or modify control strategies.
ii. Add/delete objects to the system.
iii. Tune control loops through the adjustment of control loop
parameters.
iv. Enable or disable systems
v. Generate text file reports to a networked printer.
vi. Select points to be alarmable and define the alarm state.
vii. Configure alarms to be sent to Microsoft windows mail client
viii. Select points to be trended over a period of time and initiate the
recording of values automatically.
ix. Provide different levels of security to every object in the HMI
database
-
86
x. Modify and create users with passwords and access levels and
also be able to use currently logged on users and passwords
5. Event Alarm Notification and Actions
i. The HMI software shall provide alarm recognition, storage,
routing, management, and analysis.
ii. The HMI software shall be able to route any alarm condition to
any defined user location whether connected to a local network or
remote via dial-up, telephone connection, or wide-area network.
iii. Alarm generation shall be selectable for annunciation type and
acknowledgement requirements including, but not limited to:
a. To alarm.
b. Return to normal.
c. To fault.
iv. Provide for the creation of alarm classes for the purpose of
routing types and or classes of alarms, i.e.: security, HVAC, Fire,
etc.
v. Provide timed (schedule) routing of alarms by class, object,
group, or node.
vi. Provide alarm generation from runtime and /or event counts for
equipment maintenance. The user shall be able to reset runtime
or event count values with appropriate password control.
vii. Control equipment and network failures shall be treated as alarms
and annunciated.
viii. Alarms shall be annunciated in any of the following manners as
defined by the user:
a. Screen message text.
b. Email of the complete alarm message to multiple
recipients. Provide the ability to route and email
alarms based on:
i. Day of week.
ii. Time of day.
iii. Recipient.
c. Pagers via paging services that initiate a page on
receipt of email message.
ix. Auto answer (at OWS) and auto dial (from node)
x. Graphic with flashing alarm object(s).
xi. Printed message, routed directly to a dedicated alarm printer.
xii. Audio messages.
xiii. The following shall be recorded by the OWS HMI software for
each alarm (at a minimum):
a. Time and date.
b. Location (building, floor, zone, office number, etc.).
c. Equipment (air handler #, accessway, etc.).
d. Acknowledge time, date, and user who issued
acknowledgement.
e. Number of occurrences
87
88
89
90
vii. Alarm Blink Objects and text data shall blink based on alarm
state and acknowledged state.
viii. Text and Numeric Animation - The software shall display the
numeric value of an analog point, text of a text point, and the
descriptors of a binary point. Display Linking - The software shall
provide a display linking function. Clicking the object associated
with the link changes the display to a new user-defined display.
ix. Pickable/Non-Pickable - The software shall enable active points to
be selected with the mouse and accessed. It shall be possible to
make a point non-pickable: the dynamic information shall be
displayed, but the operator will not be able to access a detail
display, change the value, etc. based on security settings of the
software.
x. Ability to open external executable files from button click
xi. Ability to open HTML web pages from button click
xii. Ability to view Microsoft Excel files from button click
11. On-Line Help. Provide a context sensitive help system to assist the
operator in operation and editing of the system. Help screens shall
be available for all applications and shall provide the relevant data for
that particular screen.
12. Security. Each operator shall be required to log on to that system
with a user name and password in order to view, edit, add, or delete
data.
i. System security shall be selectable for each operator.
ii. The system administrator shall have the ability to set passwords
and security levels for all other operators.
iii. Each operator password shall be able to restrict the operators
access for viewing and/or changing each system application, full
screen editor, and object.
iv. Each operator shall automatically be logged off of the system if no
keyboard or mouse activity is detected.
v. All system security data shall be stored in an encrypted format.
vi. Each object in the HMI database must be able to have a security
policy applied to it.
13. System Diagnostics. The system shall automatically monitor the
operation of network connections and controllers. The failure of any
device shall be annunciated to the operator.
14. DDE Server - The HMI software shall be able to communicate and
exchange data with any Third Party DDE compliant application.
15. The same software will act as programming software.
4.0
4.1
91
1)
DDC controllers shall be capable of fully stand- alone operation i.e. in the
event of loss of communication with other DDCs or Control Station, they
shall be able to function on their own. The controllers shall be LonWorks
based products.
2)
3)
The memory available to the controller board as working space for storage of
the Operating system software and data files shall be decided on the basis of
number of points being controlled by them.
4)
5)
6)
7)
The controllers shall have a resident real time for providing time of day, day of
week, date, month and year. These shall be capable of being synchronized with
other clocks in the network.
Back-up power shall support the clock. Upon power restoration all clocks shall
be automatically synchronized.
8)
9)
iii)
ii)
The cards shall provide for analog or digital, input or output, hardwired
connections to the installed plant.
The quantity and combination of these cards shall be determined by the
requirements of the plant in that location with the concurrence of the Owner/
Consultant.
10)
11)
4-20 mA.
0-1 volts.
0-10 volts.
0-5 volts, and
2-10 volts.
Resistance Signals (either PTC or NTC)
(PT 100, PT 1000, PT 3000, Balco 500, NI 1000)
Digital input/output types to be supported shall be, but not limited to the
following:
i)
ii)
Normally-open contacts.
Normally-closed contacts.
Modulating outputs shall be true proportional outputs and not floating control
type.
12)
Controllers packaging shall be such that, complete installation and check out of
field wiring can be done prior to the installation of electronic boards.
13)
14)
15)
93
17)
18)
19)
The controllers shall be housed in vandal proof boxes to protect them from
tampering by any unauthorized personnel. All DDC controllers used in plant
room spaces and external application shall be housed IP66/IP54 rating
enclosures.
20)
It shall be possible to add new controllers to the system without taking any
part of the system off-line.
4.2
1)
The Controllers shall have a self analysis feature and shall transmit any
malfunction messages to the Control Station. For any failed chip the
diagnostic tests, printout shall include identification of each and
every
chip on the board with the chip number/location
and whether the chip
Passed or Failed the diagnostic
test. This is a desired requirement as
it would facilitate trouble-shooting and ensure the shortest possible down
time of any failed controller. Controllers without such safety feature shall
be provided with custom software diagnostic resident in the EEPROM. The
tenderer shall confirm in writing that all controllers are provided with this
diagnostic requirement.
2)
3)
4)
94
6)
The DDC Controllers shall have Adaptive Control capability whereby the
control software measures response time and adjusts control parameters
accordingly to provide optimum control. The software shall allow self-tuning of
the variable control loops (all or any of P, P+I, P+I+D) of the AHUs and chiller
system so as to provide the most efficient and optimized controls at different
load conditions. The energy management programs shall update their
parameters based on past experience and current operating conditions.
8)
9)
Run time shall be accumulated based on the status of a digital input point. It
shall be possible to total either ON time or OFF time. Run time counts shall be
resident in non-volatile memory.
10)
95
11)
4.3
General
1. Equip each router with a network transceiver on each network port
(inbound and outbound) as dictated by the network type (Type 1 FTT, Type 2 - TP).
2. The network router shall be designed to route messages from a
segment, sub-net, or domain in full duplex communication mode.
3. Routers shall utilize LonTalk protocol transport, network, and
session layers to transparently route messages bound for a node
address in another sub-net or domain.
4. Routers and repeaters shall be fully programmable and permit a
systems integrator to define message traffic, destination, and other
network management functions utilizing LONWORKS software tool.
5. The routers and repeaters shall be capable of DIN rail or panel
mounting and be equipped with status LED lights for Network traffic
and power.
6. Provide a minimum of two Neuron 3120 or 3150 processors for use
as the network router communication controller.
B. Ethernet IP Router
1. Equip each router with an Ethernet IP communication on one side
and a LonTalk transceiver Type 1 FTT or Type 2 - TP on the other
side.
2. The network router shall be designed to route messages from a
segment, sub-net, or domain in full duplex communication mode.
3. On Ethernet IP side, the router shall utilize Ethernet IP protocol
transport to route messages.
4. On the LonTalk side, the routers shall utilize LonTalk protocol
transport, network, and session layers to transparently route
messages bound for a node address in another sub-net or domain.
5. Routers shall be fully programmable and permit a systems integrator
to define message traffic, destination, and other network
management functions utilizing LonWorks software tool.
-
96
General Requirements.
1. The DDUs shall permit the project operating staff to:
i. Display point values
ii. Display parameters
iii. Change time schedule elements
iv. List and acknowledge alarms
v. Monitor points in the system
vi. Command points (manual overrides) of points
vii. Override input points (put inputs in test)
viii. Read and check LonWorks variables on the network
ix. Password protected
x. Node configuration for Fan Coil and Rooftop Unit TCUs
2. DDU with the following components:
i. Liquid Crystal Display
ii. Minimum 4x20 character
iii. Pushbuttons for scrolling display and enter
iv. Permanent mount or portable connection.
97
6.0
DATA COMMUNICATION
2)
7.0
FIELD DEVICES
7.1
Weather Protection
Pipework Immersion
Corrosion resisting pockets of a length suitable for the complete active length
of the device, screwed (13 mm) or (20 mm) NPT suitable for the
temperature, pressure and medium.
-
98
(iii)
7.2
(i)
(ii)
TEMPERATURE SENSOR
Temperature sensors for space, pipes and ducts, shall be of the Resistance
Temperature detector (RTD) type or thermistor. These shall be two wire type
and shall conform to the following specifications :
1)
2)
3)
4)
The sensor housing shall plug into the base so that the same can be
easily removed without disturbing the wiring connections.
5)
6)
7)
The sensors shall not be mounted near any heat source such as
windows, electrical appliances etc.
The temperature sensors may be of any of the following types :
1)
2)
3)
4)
-
5)
7.3
NTC1800
HUMIDITY SENSOR
Space and duct humidity sensors shall be of capacitance type with an
effective sensing range of 10% to 90% RH. Accuracy shall be + 3% or better.
Duct mounted humidity sensors shall be provided with a sampling chamber.
Wall mounted sensors shall be provided with a housing. The sensor housing
shall plug into the base so that the same can be easily removed without
disturbing the wiring connections. The sensors shall not be mounted near
any heat source such as windows, electrical appliances etc.
7.4
FLOW METER
Water flow meters shall be either ultrasonic type or electromagnetic type. For
electromagnetic flow meter, teflon lining with 316 SS electrodes must be
provided. The housing shall have IP 55 protection. Vendors shall have to get
their design/ selection approved by the Consultant, prior to the supply.
The exact ranges to be set shall be determined by the contractor at the
time of commissioning. It should be possible to zero the flowmeter
without any external instruments, with the overall accuracy of atleast 1%
full scale.
7.5
7.6
7.7
100
7.9
7.10
7.11
101
LEVEL SWITCH
The level switches shall have to meet the following requirement :
7.13
Type
Mounting
Connection
Float material
Stem Material
Output
Switch Enclosure
:
:
:
:
:
Float Type/Capacitance
type/Conductivity type
To suit application.
Flanged ANSI 150 lbs RF Carbon steel
316 SS
316 SS
2 NO, 2 NC potential free
IP 55
Type
Stem / Trim
Plug and seat
Plug characteristics
Service
Stroke Length
Compliance
Packing
:
:
:
:
:
:
:
:
Actuator
a.
b.
Actuator
Actuator type
:
:
Electrical/Electronic/Magnetic.
Proportionating(Modulating)
c.
d.
e.
f.
g.
h.
i.
:
:
:
:
:
:
:
j.
Noise Level
Yes
2 Nos. for open and close.
Required
0 10 V dc, 4 20 mA
240 V ac
To be selected by the vendor
Screwed upto 2 Beyond that
ANSI 150
Lb RF
Not exceeding 70 DB
102
k.
Weather Proof
NEMAI
Note :
Actuator should be directly coupled to
acceptable.
Leakage not to exceed 0.1% of flow.
7.14
the
trim.
7.15.1 Valve
a.
b.
Type of valve
Body Material
c.
Body
seat ring
applicable)
Vane
Packing
Mounting Stool
Shaft
Seat
Fasteners
d.
e.
f.
g.
h.
J
: Butterfly Valve.
: Carbon steel ASTM A 216
(if : Gr WCB
:
:
:
:
:
:
SS-316
Teflon
Required.
SS-316
Nitrile rubber
SS-316
7.15.2 Actuators
Type
-
: Electric
103
Duty.
Motor power supply
Travel limit switches
Torque limit switches.
Hand wheel
Speed
NOTE
a.
b.
c.
8.0
Actuator must open/ close with one changeover contact. Control panel, if
required, must be supplied integral with the Actuator.
No gear box is envisaged, however if gear box is provided, the travel limit
switches must be connected directly to the valve stem.
Cover tube for the valve stem must be provided
ELECTRONIC METERING
Electronic metering shall be provided on the main LT panel at incoming and
outgoing feeders. These meters shall be free supply by the BAS contractor to
the Electrical contractor whereby these shall be installed in the LT panel by the
Electrical contractor. The electrical contractor shall also provide necessary CT,
PT and 220 V power input for the meters. All further control wiring and
networking of the meters shall be in scope of BAS contractor.
The specifications for the electronic meters to be supplied by BAS contractor is
as follows:
Type
Instantaneous
Measurements
a.
b.
c.
d.
e.
f.
a.
Event Triggered
b.
Sequence of event
Features
:
104
energy
(active,
c.
d.
e.
f.
Display
:
Panel mountable
Internal battery backup
Transducerless
connection
standard CT / PT
Y2K compliance
via
10.0
105
and sizes of conduits, sizes and location of conduits and other relevant details.
Any discrepancy found in the drawings shall be brought to the notice of
Architect/Engineers Any modifications suggested by the Contractor shall be got
approved by the Architect /Engineers before the actual laying of conduits is
commenced.
10.1
CONDUITS / TRUNKER
Conduits and accessories shall conform to relevant Indian Standards. PVC
conduits of required dia shall be used as called for in the schedule of quantities.
Joints between conduits and accessories shall be securely made, with help of
adhesive.
The conduits shall be delivered to the site of construction in original bundles
and each length of conduit shall bear the label of the manufacturer.
10.2
CONNECTIONS
All jointing methods shall be subject to the approval of the Architect/Engineer.
Separate conduits shall run for all power wiring.
The threads and sockets shall be free from grease and oil. Connections
between conduit and controller metal boxes shall be by means of brass
hexagon smooth bore bush, fixed inside the box and connected through a
coupler to the conduit. The joints in conduits shall be smooth to avoid damage
to insulation of conductors while pulling them through the conduits.
10.3
BENDS IN CONDUIT
Where necessary, bends or diversions may be achieved by means of bends
and/or circular inspection boxes with adequate and suitable inlet and outlet
screwed joints. In case of recessed system each junction box shall be provided
with a cover properly secured and flush with a finished wall surface. No bends
shall have radius less than 2-1/2 times the outside diameter of the conduit.
11.0
a.
Wire
b.
Size
c.
No. of conductors
d.
Shielding
e.
Jacket
Chrome PVC
106
11.1
f.
Nominal DCR
g.
Nominal OD
8.5 mm
h.
Nominal capacitance:
i.
Colour
COMMUNICATION CABLE
The communication cable shall be of the following specifications:
a.
Wire
b.
Size
c.
No. of conductors
d.
Shielding
e.
Jacket
Chrome PVC
f.
Nominal DCR
g.
Nominal OD
5.64 mm
h.
Nominal capacitance:
i.
Colour
107
End of section
Section 3
VARIABLE FREQUENCY DRIVES
1) The VFD shall be of the type suitable for operation on a 3 phase, 415 V, 50 Hz
input power supply at the following conditions:
Input supply voltage variations
:
+ 10 %
Input supply frequency variations :
48 62 Hz + 1%
Ambient temperature
:
0 - 45 oC, without derating.
Maximum relative humidity
:
95% non condensing
Vibration :
0.7 g RMS in 3 directions
Minimum efficiency at full load
:
96%
2) The VFDs will be mounted in the open near the AHUs Cooling towers in the
AHU room / Plant room. Hence the VFDs shall have integrated, factory built
metallic enclosures of IP 54 rating, without any de-rating. VFDs of IP00 / IP 20 /
IP 21/ IP 42 rating enclosures with additional sheet metal enclosures to achieve
IP 54 ratings are not permitted.
3) VFDs shall conform to the recognized international standards like IEC and
manufactured according to ISO 9001, BS 5750 part 1 & 2 and shall be UL
listed. It shall carry the CE mark on EMC compliance.
4) The VFD shall be capable of providing a starting torque of 160% for 0.5 sec
and an overload torque of 110% torque for 1 minute.
108
5) The VFD shall maintain full output voltage during mains variations of + 10% to
prevent loss of torque and speed variations occurring during motor operation.
6) The VFD shall comply with Electro Magnetic Compatibility (EMC) product
standard EN61800-3, First Environment, Unrestricted distribution with
minimum 50 meters of output cabling. The supplier of drives shall include
additional filters needed, if any, to meet this compliance.
7) The VFDs shall allow connecting shielded / screened 3 core plus earth motor
cable for all power sizes, without any restriction.
8) The VFDs shall have internal harmonic filters on both limbs of the DC bus to
reduce current harmonics. AC line chokes on the input side are not allowed for
harmonic current control as it will cause voltage drop to the VFD and motor.
9) For easier maintenance and to reduce inventory, the VFD shall allow
connection of motors one frame size larger and 4 sizes smaller than its nominal
rating.
10) The VFD shall have the following protective functions: Electronic motor
overload, Protection to motor and VFD against input transients, phase loss,
short circuit, under voltage, over voltage, phase imbalance, motor over temp.,
phase to phase short circuit or earth fault at motor terminals.
11) The Upeak of the VFD shall be below 1000 Volts (when measured with a cable
length of 50 meters) to prevent damage to motor insulation. Manufacturer of the
VFD shall submit data sheet to verify this requirement in order to permit the
usage of standard motors for the applications specified.
12) The VFD shall be capable of having an output motor cable length of at least
150 meters (armoured cabling) with out any need of additional equipment like
output chokes. This is essential for applications like chilled water pumps and
cooling towers where the motors are located far away from the control center.
13) The VFDs shall incorporate a surge protection circuit as standard to protect the
VFD from transients and spikes in the incoming power supply.
14) The VFD shall be fully protected from switching a contactor / isolator at the
output with out causing tripping e.g.: for switching on/off the isolators of the
AHU / ventilation fans / pumps near the motor and switching back ON with VFD
in on mode.
15) The VFD shall monitor the belt (AHU etc.) or coupling etc.), and it shall display
a warning signal if it detects a broken coupling / belt. There shall be provision to
export this warning signal to the BMS system through RS 485, without any
need of I/Os.
16) The display of the VFD shall be Alpha numeric type. Display of all messages
and faults shall be in English text format. Codes are not acceptable The display
shall show the following operating parameters:
-
109
17) It shall be possible to see at least 4 of the above operating parameters in the
VFD display, simultaneously.
18) A parameter lock shall be available in the VFD local display panel to prevent
unauthorized resetting of parameters.
19) The VFDs shall have internal galvanic isolation (PELV) to avoid damage to
BMS / PLC / DDC system when interconnected. If PELV is not available, the
VFD vendor should offer opto-isolators for all the inputs and outputs in the VFD.
20) The VFD shall automatically adjust the switching frequency based on motor
current demand rather than motor speed so that the best possible switching
frequency is provided, to match both performance and to maintain silent
operation all speeds. The switching frequency range shall be from 4-14 kHz for
VFDs to be installed on AHUs.
21) The VFD shall monitor the relationship between voltage and current in the
motor and adjust the output voltage to minimize current and maximize motor
and drive efficiency. VFDs offering fixed settings of V/f ratios are not permitted.
22) The VFD shall have Auto / OFF / Manual switch on the key pad itself. It shall be
possible to manually change the speed of the AHUs from the key pad of the
VFD, if required, without the need of an external potentiometer. In manual
mode the speed reference signal shall be from keypad of VFD and in auto
mode, the reference shall be from the remote either BMS or transmitter.
23) The VFD shall have self adjustable ramp times to prevent tripping / VFD
damage in case inappropriate ramp times are set with respect to application
requirement.
24) The VFDs shall have the provision to program a minimum and maximum speed
of operations, through the VFD programming itself.
25) In case of a power failure, the VFD shall be capable of automatically restarting
after a programmable time delay, without the need of an operator having
switch on the unit.
26) To prevent damage to the VFDs due to pre-rotating fans, the VFD shall have
the capability to detect such spinning fans and adjust its frequency to its
spinning speed before it starts controlling the fan. If the fan is running in the
opposite direction, the VFD should brake the fan by sending a DC current,
before starting the fan in the right direction.
110
27) If a temperature / pressure / flow feedback signal is given to the VFD, it shall
use its PID controller to modulate the speed in such a way that the set point of
temperature or pressure is accurately maintained.
28) The VFD shall be capable of accepting two such feedback signals
simultaneously and be able to do a speed control based on average / sum /
difference / minimum / maximum / 2 zone control of the above 2 signals.
29) The feedback signal shall be monitored by the VFD and should provide a
warning signal if the feedback goes above or below the programmed high and
low limits. It shall be possible to transfer this signal to the BMS system as well.
30) If the VFD loses the feedback signal or reference signal in auto mode, the VFD
shall be capable of maintaining the speed at which it is running or to go to
maximum speed or to trip.
31) The VFD shall have the provision to automatically stop the motor when the
feedback signal remains at the low level for a predetermined time.
32) The PID controller shall be capable of programming the set points and
incoming signals in any of the flowing units : RPM, l/s, l/m, l/h, m 3/h, m3/s, bar,
Pa, kPa, GPM, lb/s, lb/h, CFM, in3/h, inwg, ft wg, PSI, kW, HP, oC, oF, as
required by the application, and be able to display the same while in operation.
33) The VFD shall enable the motor to step over speeds that cause mechanical
vibration / resonance in duct work / pipe lines which can potentially damage the
mechanical components in the system.
34) The VFD shall have an auto de-rating facility by operating at a lower capacity in
case of a phase loss or higher ambient temperature so that minimum air
conditioning can be maintained. VFDs that trip on a phase loss or high ambient
temperature are not suitable for this application and hence not permitted.
35) The VFDs shall have the provision of 4 parameter set ups, which can be
activated by the IBMS or by digital inputs.
36) The VFD shall have the provision to generate a warning signal, if the operating
frequency is above or below programmed the high and low limits, to stage
on /off other devices.
37) The variable frequency drives (VFD) shall have the provision to integrate into a
BMS system, utilizing a serial communication through Modbus RTU protocol
that enables a full read & write seamless interface between the VFD & IBMS.
The VFD manufacturer shall be responsible for technical support to the IBMS
Vendor in the implementation of a serial interface to the BMS System. The BMS
Vendor shall be responsible for the complete integration and interoperability of
the VFD through the IBMS via the serial interface.
38) The VFD shall provide to IBMS, via serial communication (by RS-485, 2 wire),
access to the following VFD parameters as a minimum:
-
111
Motor current
Motor kW
AHU KWh
AHU Running hours
Auto / Off / Manual status feedback
PID controller programming
112
39) The VFD shall also be able to provide the following selectable &
programmable physical I/Os to the BMS system
40) It shall be possible to read the digital / analog inputs and control the
analog and relay outputs of the VFD from the BMS system through the
serial communications, thereby enabling the drives inputs / outputs to
be used as extended I/Os for the IBMS system, to achieve maximum
operational and cost efficiency.
41) To extent the life of a motor in a damp environment (like cooling
towers), the VFD should trickle a small amount of current to the motor,
while stopped, to protect it from condensation and the effects of a cold
start.
42) Upon receiving a start command, the VFD should be able to export
another signal, which can be used to start a damper / valve motor
actuator. On receiving the signal from damper / valve that it is open, the
VFD should start its operation. If the valve / damper is closed, the VFD
should not start.
43) The VFD should have a start delay feature, where in it gives time to
prepare for the operation, open dampers or VAV boxes before starting
to accelerate the motor.
44) The VFD should have a firemans override feature, where in the drive
can override its standard settings to provide for a life safety application
such as building pressurization or smoke purge operation.
45) The VFDs shall have a Real Time Clock (RTC) by which the start / stop
of the system can be programmed on a real time basis along with
scheduling. The RTC should also allow the speed of the VFD to be
changed on the basis of actual time and also log the faults with a date
and time stamp.
End of section
113
Section 4
VARIABLE AIR VOLUME BOXES (VAV)
1.0
SCOPE
This specification covers the general design, materials, construction
features, manufacture, shop inspection and testing at manufacturers
works, delivery at site, installation, testing, commissioning and carrying
out performance test at site of Variable Air Volume System.
2.0
3.0
CONTRUCTION FEATURES
Construction details shall be generally in accordance with the details
given here under.
VARIABLE AIR VOLUME (VAV) BOXES
a.
These shall of the low velocity variable air volume boxes without reheat coils, and shall be a proprietary line as marketed by a firm
specializing in this field. The contractor shall supply and install units to
the quantity and locations as specified.
b.
The unit shall be complete with damper, airflow ring, and solid-state
electronic controls to provide accurate room temperature control. The
damper shall be aerofoil type construction with bearings.
c.
d.
114
e.
The unit shall be complete with transformer, access panel and other
accessories as per the standard. The noise level shall be less than
35Dba.
f.
g.
Boxes shall be able to reset any air flow between 15% and the
maximum air quantity that the boxes can handle without changing
orifices or other parts. Air quantity limiters will not be accepted.
h.
i.
The VAVs shall be used in standalone mode complete with its own
temperature sensor and controller and shall perform the function of
maintaining the temperature and airflow. However, the VAVs shall be
BMS compatible to enable to network the VAVs to a Network Control
Unit and onto BMS. In this mode all VAV data shall be available at the
BMS workstation and it shall be possible to change set points and flow
settings from the BMS workstation. VAVs shall able to release open
protocol Lonworks and to integrate with any third party Building
Management System.
j.
115
End of section
Section 5 :
List of Approved Makes
Sr.
Manufacturers name
3. Immersion Temperature
Sensors
Schneider Electric/Siemens/Honeywell
5. D/ P Switches
Schneider Electric/Siemens/Honeywell
6. Flow transmitters
7. Level switches
Kele / Veksler
9. VFDs
BEC / AKG
14. Thermostats
116
End of section
117
Section 1
Scope of works :
The general character and the scope of work to be carried out under this contract is illustrated
in drawings, specifications and the schedule of the quantities. The contractor shall carry out
and complete the said work under this contract in every respect in conformity with the contract
documents and with the direction of and to the satisfaction of the owners site representative.
The contractor shall furnish all labor, materials and equipment as listed under the schedule of
quantities and specified otherwise, transportation and incidentals necessary for supply,
installation, testing and commissioning of the complete air conditioning system as described
in the specifications and as shown on the drawings. This also includes any material,
equipment, appliances and incidental work not specifically mentioned herein or noted on the
drawings/documents as being furnished or installed. But which are necessary and customary
to be performed under this contract. The central heating, ventilating and air conditioning shall
comprise of the following :
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)
m)
n)
o)
p)
q)
r)
Supply and installation of the screw compressor type air cooled chilling
Machines, VRV system with ODs and Indoor cassette units & F/A units.
Pumping Systems.
Air Handling Units (AHUs).
Fan Coil Units (FCUs)
Hot water Generator.
Centrifugal and propeller fans for mechanical ventilation.
Motor Control Centers.
Expansion tank along with the accessories.
Chilled water, hot water, condensate drain and ref piping inclusive of all
valves, fittings and pipes insulations.
Sheet metal ducts inclusive of external insulation, acoustic lining,
canvas connection, volume Control Dampers and smoke & fire
dampers as specified.
Supply of return air registers and diffusers.
Insulation of pipes, pumps and tanks.
Vibration isolation for HVAC equipments
Automatic Controls and instruments.
Wiring and earthing from MCC panels to various refrigeration, airconditioning and mechanical ventilation equipment control wiring and
interlocking.
Cutting holes, chases and the likes through all types of non structural
walls and finishing for all type of wall crossings, including sealing,
framework, fire proofing, providing sleeves, cover plates, making good
structure and finishing to an approved standard.
Balancing, testing and commissioning of the entire HVAC and
mechanical ventilation installations.
118
s)
t)
u)
3.
4.1.
All associated electrical works listed below are excluded from the
scope of this contract. These shall be installed by other agencies in
accordance with the shop drawings and under supervision of the air
conditioning contractor.
Providing power supply with earthing at the incoming of the control
panel in A/C plant room.
Providing 15 amps power outlet within 3 meters reach of fan coil units
at locations called for on air-conditioning contractors shop drawings.
Providing 15 amps power outlet within 3 meters reach of single phase
fans at locations called for on air-conditioning contractors shop
drawings.
Providing wiring and earthing for the sump pumps in the airconditioning plant room.
All associated plumbing works listed below are excluded from the
scope of this contract. These shall be installed by other agencies, in
accordance with the approved shop drawing of and under the direct
supervision of the air-conditioning contractor.
Providing soft make up water at cooling towers, air-washers,
humidifiers and at chilled water /hot water expansion tanks.
i.
ii.
iii.
iv.
4.2
ii.
119
iii.
v.
Providing sump pump and necessary piping for drainage of airconditioning plant room and other machine rooms at ground level.
Providing for drains/traps in cooling tower area and air handling unit
rooms.
Make up water for the chilled water and the hot water circuit.
5.
iv.
The contractor shall ensure that senior planning and execution personnel from his
organization are assigned exclusively for this project. They shall have minimum 10
years experience in this type of installations.
For quality control & monitoring of workmanship, contractor shall assign at least one
full time engineer who would be exclusively responsible for ensuring strict quality
control ,adherence to the specifications and ensuring top class workmanship for the
air-conditioning installation.
The contractor shall arrange to have mechanized and modern facilities for
transportation of materials to the place of installation for speedy execution of work.
6.
Performance Guarantee :
The Contractor shall carry out the works in accordance with the drawings,
specifications, schedule of the quantities and other documents forming part of
the contract. The contractor shall be fully responsible for the performance of
selected equipment (installed by him) at the specified parameters and for the
efficiency of the installations to deliver the required end results. The contractor
shall guarantee that the HVAC system as installed shall maintain the inside
conditions in the air-conditioning spaces as described under the Basis of
Design in the specifications. The guarantee shall be submitted in the performa
sheet. Complete set of architectural drawings are available in the
architect/Consultants office and reference may be made to same for any detail
or information. The contractor shall also guarantee that the performance of
various equipment individually, shall not be less than the quoted capacity
,actual power consumption shall not exceed the quoted rating, during testing
and commissioning ,handling over and guarantee period.
7.
The installations shall be in conformity with the by-laws and regulations and standards of the
local authorities concerned, in so far as these become applicable to the installations. But if
these specifications and drawings call for a higher standard of material and /or workmanship
than those required by any of the above regulations and standards then these drawings and
specifications shall take precedence over the said regulations and standards. However if the
drawings and specifications require something which violates the bye-laws and regulations,
then the bye-laws and regulations shall govern the requirement of the installations.
8.
9.
Drawings :
The HVAC drawings listed herewith , which may be issued with tenders are
diagrammatic only and indicate arrangement of various systems and the
120
extent of works covered in the contract. These drawings indicate the points of
supply and termination of services and broadly follows the routes to be
followed. Under no circumstances shall dimension be scaled from the
drawings. The architectural/interior drawings and details shall be examined for
exact location of the equipment, controls, grilles and diffusers.
The contractor shall follow the tender drawings in preparation of his shop
drawings and for subsequent installation work. He shall check the drawings of
other trades/services to verify spaces in which his works shall be installed.
Maximum headroom and space conditions shall be maintained at all points. Where head
room appears inadequate the contractor shall notify architect/consultant/owners site
representative before proceeding with the installations. In case installation is carried out
without notifying the works shall be rejected and the contractor shall rectify the same at his
own cost. The contractor shall examine all the architectural, structural, plumbing , electrical
and other services drawings and check the as built works before starting the work , report to
the owners site representative of any discrepancies and obtain clarification. Any changes
found essential to coordinate his work with other services and trades, shall be made with prior
approval of architect/consultant/owners site representative without additional cost to the
owner. The data given in the drawings and specifications as exact as could be procured , but
its accuracy is not guaranteed.
10.
Technical Datas :
Each tenderer shall submit along with his tender, the technical data for all items listed in the
indicated fromat. Failure to submit complete data with the tenders may result in summary
rejection of the tender.
11.
Shop Drawings :
11.1
11.2
11.3
11.4
11.5
11.6
13.
Accessibility :
The contractor shall verify the sufficiency of the size of the shaft
openings, clearances in cavity walls and suspended ceiling for proper
installation of his ducting and piping. His failure to communicate
insufficiency of the same. The contractor shall locate all equipment which
must be serviced ,operated or maintained in fully accessible positions.
The exact location and size of all access panels required for each
concealed damper ,valves or other devices requiring attendance shall
be finalized and communicated in sufficient time to be provided in the
normal course of work. Failing this the contractor shall make all
necessary changes and repairs at his own expenses. Access panel shall
123
Electrical Installations :
The electrical work related to air-conditioning services , shall be carried out in full
knowledge of ,and with complete coordination of contractor . The electrical installation
shall be in total conformity with the control wiring drawings prepared by the contractor
and approved by the architect /consultant .All air-conditioning equipments shall be
connected and tested in the presence of an authorized representative of the contractor.
COMPLETION CERTIFICATE :
On completion of the electrical installation for air-conditioning, a
certificate shall be furnished by the contractor , counter signed by the
licensed supervisor ,under whose direct supervision the installation was
carried out .This certificate shall be in the prescribed form as required by
the local authority .
The contractor shall be responsible for getting the entire electrical
installation for air-conditioning system duly approved by the local
authorities concerned and shall bear expenses, if any in connection with
the same.
18.
COMPLETION DRAWINGS
Contractor shall periodically submit completion drawings as and when
work in all respects is completed in a particular area . These drawings
shall be submitted in the form of two sets of floppies/CDs and four
portfolios (300 x 450mm ) each containing complete set of drawings on
approved scale indicating the work as installed .These drawings shall
clearly indicate complete plant room layouts ,location of wiring and
sequencing of automatic controls ,locations of all concealed piping
,valves, controls, dampers, wiring and other services .Each portfolio
shall also contain consolidated control
diagrams and technical
literature on all controls. The contractor shall frame under glass , in the
air-conditioning plant room , one set of these consolidated control
diagrams.
20.
21.
On Site Training :
Upon completion of all works and all tests, the contractor shall furnish
necessary operators labor and helpers for operating the entire
125
installation for a period not less than two weeks of ten hours each to
enable the owners staff get aquainted with the operation of the system.
During this period the contractor shall train the owners personnel in the
operation, adjustment and maintenance of all equipment installed.
22.
22.1
Complaints :
The contractor shall receive calls for any or all problems experienced in
the operation of the system under this contract, attend to these within
four hours of receiving the complaints and shall take steps to
immediately correct any deficiencies that may exist.
22.2
Repairs :
Uptime Guarantee :
The contractor shall guarantee for the installed system an uptime of 98%. In case of shortfall
in any month during the defects liability period, the defects liability period gets extended by a
month for every month having shortfall. In case of shortfall beyond the defects liability period
the contract shall get extended by a month for every month having the shortfall and no
reimbursement shall be done for the extended period.
The contractor shall provide log in the form of diskettes and bound printed
comprehensive log book containing tables for daily record of all temperature.
pressure, humidity, power consumption starting and stopping times for various
equipment, daily service rendered for the system alarms, maintenance
records of unusual observations etc.
Contractor shall also submit preventive maintenance schedule.
Each tenderer shall submit along with the tender, a detailed operation
assistance proposal for the owners site representative / consultants review.
This should include the type of service planned to be offered during the
defects liability period and beyond. The operation assistance proposal shall
give the details of the proposed monthly reports to the management.
The tenderer shall include a list of such project where such an operation assistance has been
provided.
24.
Contractor may be required to carry out the HVAC installation for a period of
two years from the date of commissioning and handing over of the entire
system, i.e. during the defects liability period . Further he may also be
required to carry out operation and all inclusive maintenance of the entire
system for a period of three years beyond the defects liability period. Cost of
such proposal shall be quoted separately as per the BOQ.
126
25.
Operation Contract :
i)
ii)
iii)
iv)
v)
vi)
26.
Terms of Payment :
i)
27.
a)
i)
ii)
iii)
iv)
b)
i)
ii)
iii)
iv)
v)
c)
Manpower :
v)
vii)
viii)
d)
Shutdowns :
i)
ii)
vi)
127
28.
The contractor shall submit with their tender ,the requirement of soft make up
water and power at each of their equipment/system wise/floor wise/section
wise.
End of Section
128
SPECIFICATIONS
Section 2
SYSTEM DESIGN DATA
A. DESIGN PHLOSOPHY;
129
HVAC system in the Hospital/healthcare stands out for its complexities and stringent demands
on indoor air quality, airflow patterns, cross contamination control, odour control and noise
control etc. The hospital air conditioning system further demands more care in energy aspects
due to its longer hours of operations.
The following factors have been considered for the design of hospital HVAC services:
1
2
3
4
5
6
7
To effectively design an HVAC system for this hospital building, the design is
made as per the building layout and the departmental areas or zones. These
zones are broadly classified as follows.
1. Inpatient Wards/ ICUs
3. Administration/Faculty
/academic areas
ZONING :
From the isolation point of view, the building area will be segregated into the
following zones.
Sensitive areas like operation theatres and intensive care units, labs,
X-Ray, MRI etc.
Treatment and recovery areas, wards and administrative areas
The individual requirements of the above will be considered for designing the
system
B. General :
The system design , basis of design, requirements and other relevant data are
outlined in this section. The detailed specifications and specific requirements
are outlined in the subsequent sections.
C.
Location:
The proposed
Bengal).
130
D.
Scope of works :
The work proposed under this tender includes providing and fixing air-conditioning ,
heating and ventilation systems for the above work.
Providing and fixing at site all main equipment associated with airconditioning and ventilation for the above.
To execute all incidental work at site including material supply at site
associated with the system asked in the specifications.
Nature of such works will be sheet metal ductwork, air distribution
devices viz. grilles and diffusers , copper refrigerant piping and its
insulation , drain piping etc., incidental civil works, incidental electrical
works ,cable , control panel etc. at site for all manufactured items at
works and also items fabricated at site.
Routine Testing, pressure testing of
commissioning of complete plant at site.
fabricated
components,
Basis of Design :
Station Name
Latitude
22.32North
Altitude
Daily Range
20F
32.2C/90F
Dry
bulb
temperature
131
Winter
13.3C/58F
X-ray/MRI/CAT Scan
23.3A1.1
3.
Labs
4.
Administration/
Conferences/academics
23.3A1.1
50A5%
50A5%
23.3A1.1
(-)
(-)
50A5%
(-)
5.
Pre/Post IPD
22.2A1.1
50A5%
(+)
6.
22.2A1.1
50A5%
(+)
7.
Operation Theatres
21.0A1.0
50A5%
(+)
8.
23.3A1.1
50A5%
(A)
9.
Clean Utilities
23.3A1.1
50A5%
(-)
10.
Patient Room
23.3A1.1
50A5%
(A)
===========================================================
==
Ventilation
Lighting Load
Roof Insulation
OTs
132
roof to be
50 thick
polystyrene
equivallant
Toilets/Labs
Kitchen
Dirty utility Room
Based on the area wise detailed heat loads of the above design data and the
details the estimated loads are summarized as below :
===========================================================
==============
Sr.No.
Area Description
Area (ft2)
Load TR
=======================================================================
==
Fifth Floor
Sixth Floor
Seventh Floor
39000
39000
200
200
39000
200
9.
Eighth Floor
39000
200
10
Ninth Floor
39000
220
===========================================================
==============
Total
195000 ft2
1020 TR
133
water primary pumps (one stand by) , 5nos chilled water secondary pumps(one standby), 4
nos. hot water pumps(One standby), Air Handling Units, TFA units, HRV units and Fan coil
units as per the requirements at various floors/areas.
The plant shall be installed at the Plant space allocated at site (as existing) and chilled water
from this plant shall be supplied to various AHUs at the ground floor, first floor, second floor,
third floor, fourth floor, fifth floor areas as per requirements and as shown in the drawings. The
system shall be complete with electrical panel boards, power cabling, control cabling, earthing
and controls.
End of section
Section 3
AIR COOLED SCREW PACKAGE CHILLING MACHINE
3.1
SCOPE
The scope of this section comprises supply, erection, testing and
commissioning of Air cooled
screw package chilling Machines
134
TYPE
The chilling machine shall be with hermetic/semi hermetic type (and not
open type) compressor, consisting of mono/ twin screw compressor,
squirrel cage induction motor, closed transition star-delta starter, air
cooled condenser, shell and tube chiller, refrigerant piping, micro
processor control, all mounted on a steel frame and control power
wiring/cabling.
3.3
ACTUAL CAPACITY
Actual refrigeration capacity of chilling machine shall be as shown on
drawings and in schedule of Quantities.
3.4
3.5
SCREW COMPRESSOR
The compressor will be mono/ twin screw (helical Rotary) type design
for positive displacement for use with ozone friendly refrigerant
conforming to prevailing international standard.
During function, it will be pure rotary motion providing uniform gas flow,
even torque and positive displacement to ensure vibration-free
operation over a wide range of operating conditions.
The rotor tip clearance will be optimized to reduce leakage between
high and low pressure cavities during compression and also to achieve
high energy-efficiency.
The capacity controlling device shall be arranged for unloaded start
power consumption shall proportionately reduce with the stepping
down of compressor capacity to as low as 25% of full load in direct
response to refrigeration load changes.
3.6
135
The screw compressor will have, accessible hermetic direct drive motor
with 2950 rpm (or as per manufacturers design speed), working on
415V+ 10%,3 phase, 50 HZ power supply, as normally available in
India. The motor will be squirrel cage two pole induction type will be
section gas-cooled. Due consideration will be given while deciding the
protection devices to take care of probable voltage fluctuations
prevailing at site.
The system will be provided with oil separator and filtration devices.
3.7 CONDENSER
Condenser coil shall be air cooled with integral sub-cooler constructed
of aluminum fins mechanically bonded to seamless copper tubes which
shall be then cleaned, dehydrated and sealed.
Condenser fans shall be direct driven propeller/axial type, with totally
enclosed air over motor, having class F insulation and IP 54
protection, discharging air vertically upwards and shall be equipped
with the following features.
a.
b.
c.
Air cooled condenser coil shall be leak tested at 150 Psig (1034 KPa)
and pressure tested at 450 Psig (3103 KPa).
3.8 CHILLER (COOLER)
Chillers shall be direct- expansion/flooded type comprising mild steel
shell, integrally finned copper tube Rolled into tube sheets, cast iron
water headers, liquid line connection, suction header, drain plug and
purge valves.
Shell and tube type chillers shall have the following components:
a.
b.
TUBE SHEETS
A thick steel tube sheet shall be welded to each end of the shell
and shall be drilled and reamed to accommodate tubes. Annular
grooves in the tube sheets shall prevent leakage at the tube
136
TUBES
12.5 to 19 mm dia. Seamless copper tubing, not less than 24G
wall thickness, shall be used for evaporator surface. Tube shall
be rolled into the tube sheets and shall pass through
intermediate supports so that the refrigerant side of the
evaporator shall be leak free and there shall be no relative
motion between tubes and tube supports. Each tube shall be
individually replaceable.
d.
INSULATION
The chiller shell be covered with closed cell insulation material.
b.
c.
d.
e.
f.
b.
c.
d.
3.11
a.
COTROLS
b.
c.
d.
e.
3.12 QUALITY
CHILLERS)
ASSURANCE
(AIR
COOLED
SCREW
PACKAGE
ARI
550-90 Air Conditioning and Refrigeration Institute :
Standard for Air Cooled Screw water Chilling Packages
(General Specifications, Testing and Rating)
ARI
575 - Air
Conditioning and Refrigeration Institute:
Standard
Method of Measuring Machinery soundWithEquipment Rooms
(Basis of all data
presented or field testing of equipment, with relation to sound
requirements).
ASME CODE- American Society of Mechanical Engineers
Code :For Unfired Pressure Vessels Section VIII (Design,
Construction, testing and Certification of Pressure vessels).
ANSI-B9.1American National Standards Institute Safety,
Code
For Mechanical Refrigeration (Overall general
safety
Requirements, relief device sizing etc.)
ANSI-B31.5 TEMA
ISO R 281 -
End of Section
Section 4 :
Electric Hot Water Generator
The hot water generator shall be vertical/horizontal shell type designed, constructed and
tested for the specified water flow and temperatures.
The shell of the generator shall be made of steel with electric fusion welded
seams. The shell shall be designed for 50 Deg C of water circulation unless
specified otherwise.
140
The shell with insulation shall be mounted inside a cabinet of angle iron frame
with 16 SWG mild steel covers held with lock/bolts and hinges. The cabinet
shall be provided with sufficient louvers and rat proofing to ensure ventilation
of heater terminals of boilers shall be installed above the finished surface of
insulation and angle iron frame. The angle iron frame shall be provided with
fittings lugs and pedestals.
Electric heaters shall be provided in banks of equal capacity distributed on
three power phases. Heaters shall be mounted within seamless
incoloysheathed electrically resistant U tubes. The heaters shall be easily
removable externally without opening the terminal plate or disturbing other
components. The heater mounting socket shall be made leak proof. Heaters
shall be suitable for 415V+_10%/50hz/3phase power supply.
Flow switch, float switch, automatic alarm for low water level and high
temperature / pressure switch with respective indication lights.
Descaling Valves
The Electrical control cabinet shall be made as detailed above and mounted
directly on the main frame. All controls and terminals shall be factory wired
and tested. The control cabinet shall consist of following major controls and
rated capacities unless specified otherwise.
Incoming MCCB
Thermostats
The panel shall be openable only after switchingoff the incoming supply.
The external surface of the shell shall be cleaned ,derusted and applied
with three coats of primer and panted.
End of section
Section 5
AIR HANDLING UNITS
SCOPE
The Scope of this section comprises the supply, erection, testing and commissioning
of double skin Air Handling Units conforming to these Specifications and in
accordance with requirements of drawings and schedule of quantities.
TYPE
142
The Air Handling Units shall be of floor mounted draw through type
having sections such as filter section with pre-filters, microvee filters
and HEPA filters as required under BOQ ,cooling coil section with
suitable chilled water cooling coil, fan section with DIDW fan, mixing
section where required under BOQ, humidification section with
centrifugal fan as per schedule of quantities and arrangement shown
on the drawings.
3
CAPACITY
The air moving and coil capacities (Air Conditioning Load) shall be as
shown in Schedule of equipment and quantities and on drawings.
CASING
The housing/ casing of the air handling unit shall be of double skin
construction. The housing shall be so made that it can be delivered at
site in total/ semi knock down conditions depending upon the
conditions. The frame work shall be of extruded aluminium hollow
sections with thermal break profile fitted with pre-formed insulated
sections. All the members shall be assembled thru mechanical joints to
make a sturdy and strong frame work for various sections. Casings
should be as per EN 1886.
Double skin panels (each not exceeding 750mm wide) shall be made
of 22G pre-coated Galvanised sheet steel and 22G galvanised sheet
inside with pressure injected PU foam insulation of 25mm thick X 38
Kg/Cu.M in in between, these panels shall be with thermal break
barrier also. The panels shall be bolted from inside on to the frame
work with soft rubber gasket in between to make the joints air tight.
Frame work for each section shall be bolted together with soft rubber
gasket in between to make the joints air tight. Suitable doors with
powder coated hinges and latches shall be provided for access to
various panels for maintenance.
The fan and the motor arrangement shall be mounted on to the
extruded aluminium frame work. The entire housing i.e. The Air
Handling Unit shall be mounted on extruded aluminium base channel
framework.
Drain pan shall be constructed of 16 SS sheet having 12 mm thick 32
Kq/Cu. XPE insulation.The pan shall have necessary slope to facilitate
for fast removal of condensate.
FAN
The fan shall be forward, curved double inlet double width type
complete with motor and drive package. The wheel and housing shall
be fabricated from heavy gauge galvanized steel. The fan impeller shall
be mounted on a solid shaft supported to housing with angle iron frame
and pillow block heavy duty ball bearings. The fan shall be selected for
a speed not exceeding 1000 RPM. The fan outlet velocity shall not be
more than 1800 rpm. Fan housing with motor shall be mounted on a
common steel base mounted inside the AHU on anti vibration springs
or cushy foot mount. The fan shall be direct driven type. Another fire
retardant canvass connection shall be provide at unit outlet to connect
the ducts.
7.
Cooling Coils :
The cooling coil shall be seamless copper tubes not less than 0.437 mm thick and
12.5 mm O.D. The coil shall have continuous aluminium fins. The tube shall be
staggered in the direction of air flow. The fins shall be uniformaly bonded to the tubes
by mechanical expansion of the tube. The coil shall be tested against leaks
At a hydraulic pressure of 21kg/m3 for a period of two hours.The water
headers shall be of copper pipes to connect all the tubes. The header shall be
complete with water In/Out connections, vent plug and drain at the bottom and
designed to provide a water velocity between 0.6 to 1.8 m/s ( 2 to 6 FPS)
8.
Filters :
As asked for under Bill of quantities.
9.
Electrical Panel :
Each unit shall have its own electric panel consisting of MCCB / fuse
switch unit, starter, indicating lamps ,incoming/outgoing internal and
external wiring and earthing as per the details in BOQ.
10
144
An adjustable damper of GI sheet along with bird screen ,air inlet louvers and air
filters shall be provided for fresh air entry. The damper shall be sized for 50%
of designed air quantity.
11
Limitations :
The air velocity across the cooling coils shall not exceed 500 fpm.
The fan outlet velocity shall not exceed 1800 fps (9m/s) in any case.
The velocity across the filters shall not exceed 500 fpm in any case.
End of Section
Section 6
General
The fan coil units shall be ceiling mounting box type complete with
finned coil, fan section with motor, insulated drain pans, cleanable air
filters and fan speed regulator and other controls as described.
Cooling Coil
145
The coil shall be of seamless copper tubes not less than 5/8" O.D, 0.56
mm thick. The coil shall have aluminium fins. The fins shall be spaced by
collars forming integral part of the fins. The tubes shall be staggered in
the direction of air flow. The coil circuit should be sized for adequate
water velocity but not exceeding 1.8 M/S (6 FPS) the fins shall be
uniformly bonded to the tubes by mechanical expansion of the tubes.
The coils shall be tested against leaks at a hydraulic pressure of 10
kg/sq.cm. This pressure shall be maintained for a period of 24 hours. No
drop should be observed indicating any leaks.
3
Fan
This shall consist of (2) two light weight aluminium impellers of forward
curved type, both statically and dynamically balanced, along with
properly designed G.I. sheet casings.
The two impellers shall be directly mounted on to a double shaft, single
phase multiple winding motor capable of running at (3) three speeds.
A G.I. plenum shall connect the fan outlets to the coil.
Drain Pans
The drain pan shall be sandwich type fabricated out of deep drawn
single piece stainless steel sheet, covering the whole of coil section and
extended on one side for accommodating coil connection valve, etc. and
complete with a 25mm drain connection. The drain pan shall be
insulated with 12mm XPE insulation .
Air Filter
The filter shall be cleanable type 15mm thick with 90% efficiency down
to 20 micron of rubberised coir to be mounted behind the return air grille
in the unit casing.
Speed Control
A sturdy switch shall be provided with the unit complete with wiring, for
off and with minimum (3) three speed control, of the fan.
Automatic Controls
Each unit shall have a room type thermostat and a 3 way motorised
modulating water valve. The valve shall be fixed at a convenient
146
location. The thermostat shall be mounted along with the speed control
switch on a common plate. The plate shall clearly indicate the fan
positions.
The water valves on inlet line shall be of gun metal ball type with internal
water strainers, having BSP (FPT) inlet and flare type MPT outlet
connection. The valves on return line shall be as above, but without the
water strainer.
8
Water Connections
The water lines shall be finally connected to the coil of the fan coil unit,
by at least 300 mm long, type L seamless solid drawn copper tubing,
with flare fittings and connections.
End of Section
Section 7
PUMPS
1.
General
The various items of pump shall be complete in all respect and comply
with the specification given below:
2.
Pump Sets
The pump sets shall be vertical split casing type with end suction and
top discharge flanged connections, mounted on drip proof squirrel cage
induction motor with suitable starter as specified.
147
Casing
2.
Impeller
Bronze
3.
Shaft
4.
Shaft sleeve
Bronze
5.
Bearings
6.
Base Plate
7.
Flanges
BIS 1536/1960
8.
Packing
Graphited Asbestos
9.
Max. Speed
10.
Drive
11.
Starter
a)
Drive ratings shown are only tentative and Tenderers shall select their
drivers at least 5% in excess of the maximum BHP of the pump plus
transmission losses, if any. Drivers shall be supplied with starters unless
otherwise stated.
3.
i)
ii)
iii)
iv)
v)
4.
Installation
Pumps shall be installed as per manufacturer's recommendations. Pump
set shall be mounted on concrete block which in turn is mounted on
machinery isolation cork or any other equivalent vibration isolation fitting.
Concrete foundation will be made by the Contractor as per approved
drawings and specifications and the isolation pad foundation bolts, etc.,
shall also be supplied by the Contractor. Contractor shall ensure that the
foundation bolts are correctly embedded.
Pump sets shall preferably be factory aligned whenever necessary, site
alignment shall be done by competent persons. Before the foundation
bolts are grouted and the coupling bolted, the bed plate levels and
alignment results shall be submitted to the Engineer.
5.
Insulation
Pumps used for chilled water service shall be insulated so that the dismantling of
pumps not affected. Insulation shall be provided in a manner so as to minimize the
damage to the insulation in case of maintenance of pumps or other components.
6.
Testing
Tenderers shall submit the performance curves of the pumps. They
shall also be responsible for the selection of capacity and total head
requirements of each pump to match his own piping and equipment
layout.
On completion of the entire installation, pumps shall be tested for their
discharge head, flow and B.H.P. Test results shall correspond to the
performance curves.
Tenderers shall furnish the required testing instruments and arrange for
their connection as required.
7.
Painting
After complete installation and testing, pumps accessories and fittings
shall be given two coats of approved finishing paint.
149
End of section
Section 8
AIRCOOLED VARIABLE REFRIGERANT VOLUME SYSTEM
1.1
Scope
The scope of this section comprise the supply, erection testing and commissioning of
Variable Refrigerant Volume system conforming to these specifications and in
accordance with the requirements of drawing and schedule of quantities.
1.2
Type
Units shall be air cooled variable refrigerant volume air-conditioner
consisting of one outdoor units and multiple indoor units each indoor
units having capability to cool or heat independently for the
requirements of the various areas as shown in the drawings.
150
The refrigerant piping between indoor units and outdoor unit shall be
possible to extend up to 150m with maximum 50m level difference
without any oil traps.
Both indoor units and outdoor units shall be factory assembled ,tested and filled with first charge
of refrigerant before delivering at site.
1.3
The outdoor units shall be factory assembled. weather proof casting and constructed
from heavy gauge mild steel panels and coated with baked enamel finish.
The unit shall be completely factory wired tested with all necessary controls:
All outdoor units shall have minimum two scroll compressor and be
able to
operate even in case one of compressor is out of order.
In case of outdoor units above 18 hp, the outdoor units shall have
compulsorily at least 2 separate inverter compressors so that the
operation is not disrupted with failure of any inverter compressor and if
one inverter compressor malfunctions, other continues to provide
emergency operation smoothly till repair is effected.
The outdoor units shall be modular in design and should be allowed for side by side
installation
The unit shall be provided with its own microprocessor control panel.
151
The outdoor units should have anti-corrosion paint free galbarium base
plate for easy mounting of unit.
The machine must have a sub cool feature to use coil surface more
effectively thru proper circuit/bridge so that it prevents flushing of
refrigerant from long piping due to this effect thereby achieving energy
savings.
The outdoor units should be fitted with low noise. Aero spiral design fan
with aero fitting grill for spiral discharge airflow to reduce pressure loss
and should be fitted with DC fan motor for better efficiency. The unit
should be capable to deliver 55 pa external static pressure to meet
long exhaust duct connection requirement.
The condensing unit shall be designed to operate safely when
connected
to multiple fan Coil units.
COMPRESSOR
The compressor shall be highly efficient scroll/rotary type and capable
of inverter control. The inverter compressor shall change the speed in
accordance to the variation in cooling or heating load requirement:
1.5
All outdoor units shall have multiple steps of capacity control to meet
load Fluctuation and
indoor unit individual control. All parts of compressor shall be
sufficiently lubricated stock. Forced lubrication may also be employed.
Oil heater shall be proved in the compressor casing.
The Inverter compressor shall preferably be Reluctance DC inverter
Compressor for higher efficiency and improved reliability
Heat exchanger
The heat exchanger shall be constructed with copper tubes
mechanically bonded to aluminum fins to form a cross fin coil.
152
1.6
REFRIGERANT CIRCUIT
The refrigerant circuit shall include liquid & gas shut off valve and a
solenoid valve at condenser end.The equipment must have in built
refrigerant stabilization control for proper refrigerant distribution.The
refrigerant shall be R 410a or R 407c.
All necessary safety devices shall be proved to ensure the safety
operation of the system.
1.7
SAFETY DEVICES
INDOOR UNT
153
operation of the system. The fan shall be direct driven type mounted directly
on motor shaft having supported from housing.
The cooling coil shall be made out of seamless copper tubes and have
continuous aluminum fins the fins shall be spaced by collars forming an
integral part.
The tubes shall be staggered in the direction of air flow. the tubes shall
be hydraulically/mechanically expanded for minimum thermal contact
resistance with fins each coils shall be factory tested at 21 kg /sqm air
pressure under water .
Unit shall have cleanable type filter fixed to an integrally moulded
plastic frame. The Filter shall be slide away type and neatly inserted.
Each indoor unit shall have computerized PID control for maintaining
design room temperature each unit shall be provided with
microprocessor thermostat for cooling or cooling and heating.
Each unit shall be with wired LCD type remote controller. the remote
controller shall memorize the latest mall code for easy maintenance.
The controller shall have self - diagnostic feature for easy and quick
maintenance and service. The controller shall be able to change fan
speed and angle of swing flap individually as per requirement.
1.9.1 CEILING MOIUNTED CASSETTE TYPE UNIT(MULTY FLOW TYPE)
The unit shall be ceiling mounted type the unit shall include pre - filter .fan section and
DX coil section the housing of the unit shall be powder coated galvanized
steel. The Body shall be light in weight and shall be able to suspend from four
corners. The fan shall be aerodynamically designed diffuser turbo fan type.
Unit shall have an external attractive panel for supply and return air
.unit shall four way supply air grilles on sides and return air grille in
center.
Each unit shall have high left drain pump, fresh air intake provision (if specified) low
gas detection system and very low operating sound .
154
The units shall be wall -mounted type .The unit includes pre-filter, fan
section & DX coil Section the housing of unit shall be light weight
powder coated galvanized steel.
Unit shall have an attractive external casting for supply and return air .
1.9.5 FLOOR STANDING TYPE
Unit shall be suitable for floor standing arrangement. the unit include
pre filter .
fan section & DX coil section the housing of unit shall be
light weight powder coated galvanized steel.
1.10
155
End of section
Section 9
Ventilation System
1.
General :
2.
2.1
The ventilation fan shall be complete in all respects and shall generally
comply with the following specifications given below :
Inline Fans :
General :
The inline fan shall be complete in all respects and shall comply with
the following specifications :
156
2.2
Fans :
The fan shall be complete with centrifugal impeller, casing, direct driven
motor, vibration isolators etc.
2.2.1 Housing :
The housing shall be constructed of hot rolled GSS sheet metal
construction. Housing metal shall be either spot welded or screwed or
mounted together with the rivets. The housing shall indicate arrow
showing rotation, make, model and duty condition.
2.2.2 Fan Wheel :
Fan wheel shall be forward/backward curved type and it shall be statically and
dynamically balanced.
2.2.4
Ball Bearing :
The ball bearing shall be completely maintenance free and can be used in any
mounting position at maximum indicted temperature. The bearing lubricant
shall be suitable for min. ambient temperature of 15C. For applications at
max. indicated ambient temperature life expectancy LIO is 40,000 hours
minimum.
End of section
Section 10
Refrigerant and Drain Pipework of VRV system
1.
General :
All piping work shall conform to quality standards and shall be carried out as per
specifications and details given hereunder.
2.
Piping :
2.1
Drain Piping :
157
2.13
2.14
2.15
2.16
2.17
2.2
2.2.1 Seamless soft copper tubing type L shall be used to make connection
to the equipment wherever required or specified.
2.2.2 Flare fittings e.g. flare nuts, tees, elbows, reducers etc. shall be of
brass.
2.3
Refrigerant Piping :
All refrigerant piping for the air conditioning system shall be constructed
from soft seamless upto 19.1 mm and hard drawn copper refrigerant pipes
for above 19.1 mm with copper fittings and silver-soldered joints. The
refrigerant piping arrangements shall be in accordance with good practice
within the air conditioning industry and are to include charging
connections. Suction line insulation and all other items normally forming
part of proper refrigerant circuits.
All joints in copper piping shall be sweat joints using low temperature
brazing and or silver solder. Before jointing any copper pipe or fittings
its interiors shall be thoroughly cleaned by passing a clean cloth via wire
or cable through its entire length. The piping shall be continuously kept
clean of dirt etc. while constructing the joints. Subsequently it shall be thoroughly
blown out using nitrogen.
After the refrigerant piping installation has been completed, the refrigerant
piping system shall be pressure tested using nitrogen at pressure of 20Kg
per sq.cm and 10 Kg per sq.cm (lowside). Pressure shall be maintained in
the system for 24 hours. The system shall then be evacuted to minimum
vaccum of 700 mm Hg and held for 24 hours.
The air-conditioning system supplier shall be design sizes and erect proper
interconnections of the complete refrigerant circuit.
The thickness of copper piping shall not be less than mentioned below:
Pipe Size in mm (OD)
Wall Thickness in mm
a) 54.1
1.5
b) 41.3
1.3
c) 34.9
1.3
158
d) 28.6
1.2
e) 25.4
1.2
f)
22.2
1.0
g) 19.1
1.0
h) 15.9
1.0
i)
12.7
0.8
j)
9.5
0.8
k) 6.4
0.8
The suction line pipe size and the liquid line pipe size shall be selected according to
the manufacturers specified outside diameter. All refrigerant pipes shall be properly
supported and anchored to the building structure using steel hangers. anchors,
brackets and supports which shall be fixed to the building structure by means of
inserts or expansion shields of adequate size and number to support the load
imposed thereon.
Pipe Insulation :
a.
End of section
Section 11 :
Pipes & Valves :
1.
General
The scope shall comprise the supply, installation of pipe, fittings, valves,
etc. and testing/balancing of complete system. Pipe sizes shown on
drawing are for the guidance of Contractor and shall not relieve
Contractor of responsibility of providing smooth, noiseless circulation of
fluid.
2.
Pipes
159
All piping work shall conform to quality standards and shall be carried
out as per specifications and details given hereunder:
All pipes shall be of schedule 40 thick as per ANSI-B-36.1.
All pipes in sizes upto 150mm dia shall be M.S. ERW pipe heavy class
as per IS:1239-Part-I (as per latest amendment).
All pipes in sizes 200mm and above shall be M.S. ERW pipe heavy
class as per IS:3589 (as per latest amendment).
3.
Fittings
The dimensions of the fittings shall conform to I.S. 1239-Part-II (as per
latest amendment) unless otherwise indicated in the specifications.
All bends in sizes upto and including 150mm dia. shall be ready made of
heavy duty, wrought steel of appropriate class.
All bends in sizes 200mm and larger dia. shall be fabricated from pipes
of the same dia. and thickness with a minimum of 4 sections, and having
a minimum centre line radius of 1.5 diameter of pipes.
All fittings such as branches, reducers, etc. in all sizes shall be
fabricated from pipes of the same dia. and thickness and its length
should be at least twice the dia. of the pipe.
The branches may be welded straight to the main line, without making a
separate fitting, where specified on drawings or required by
Engineer-in-Charge.
Blank ends are to be formed with flanged joints and 6mm thick blank
between flange pair for 150mm and over in case where, a future
extension is to be made, otherwise blank end discs of 6mm thickness
are to be welded on, with additional cross stiffners from 50mm x 50mm x
5mm heavy angles.
4.
Flanges
All flanges shall be of mild steel as per IS:6392/71 and shall be steel
slip-on-type, welded to the pipes flanges thickness shall be to suit
class-II pressures.Flanges may be tack welded into position, but all final
welding shall be done with joints dismounted. 3mm thick gaskets shall
be used with all flanged joints. The gaskets shall be fibre reinforced
160
Valves
a)
Valves :
All gate valves, globe and check valves upto and including 40mm dia.
Shall be of gun metal screwed type, conforming to class 1 of IS:778.
All butterfly valves of 50mm dia. and above shall be flanged type, have
cast iron body with black nitrile rubber seat and conforming to class
PN-10 of IS:780 (for sizes upto 300mm) and of IS:2906 (for sizes
350mm and above).
All globe and check valve of 50mm dia. and above shall be flanged type in cast iron
construction and conforming to class PN-10.
Air valves shall be provided at all higher points in the piping system for
venting as per the sizes shown in the BOQ.
All air needle valves shall be of gun metal and tested upto a pressure of
class 1 pressure rating. All globe valves of size 50mm and above shall
be of rising spindle type.
b)
Balancing Valves
All balancing valves of upto and including 50 mm dia. shall be in gun
metal screwed type construction. The valves of 65 mm dia. and above
shall be in cast iron flanged end construction.
161
The valve shall have PTFE/SS disc with special erosion/ corrosion proof
sealing.
The valves shall be capable of delivering metered quantity of water and
subsequently should function as isolating valve. All the valves shall have
built in pressure drop measuring facility to ascertain water flow rate. The
valves shall have temper proof adjustable and lockable arrangement for
required water quantity after commissioning. The valve shall be to the
minimum requirement of IS:778 Class-1.
The valves shall be complete with drain cock, pressure test cocks, etc.
c)
Miscellaneous Valves
All gauge cocks shall be of gunmetal plug type, complete with siphon
(brass chrome plated).
All drain valves shall be of gunmetal with a hose union connection on
one end or extended upto the drain pit as the case may be.
All valves on the supply line of fan coil units shall be of gunmetal ball
type with integral water strainers, having (BSP) FPT inlet and flare type
MPT outlet connection.
d)
All valves on the return line of fan coil units shall be as above but without
integral water strainer.
Strainers
The strainers shall either be 'pot' type or 'Y' type with cast iron or
fabricated steel body, tested to a pressure of 10 kg/sq.cm. applicable for
the butterfly valves as shown on the drawings.
The strainers shall have a perforated bronze sheet screen with 3mm
perforation, 0.63mm thick.
Pot strainers and Y strainers shall be provided with flanged connections.
The strainers shall be designed to facilitate in easy removal of filter
screen for cleaning, without disconnection of pipe line
Pot strainer shall be fabricated out of M.S. sheet and the sizes shall be
as under:
============================================================
==
Pipe size
Pot Dia
Pot HT
Basket dia
Basket HT
162
ESIC Medical College at Joka(WB)
(mm)
(mm)
(mm)
(mm)
(mm)
============================================================
===============
50
300
400
200
240
80
350
450
250
250
100
450
500
300
280
125
500
600
330
340
150
540
700
360
390
200
610
815
400
470
250
800
955
550
510
300
1000
1105
750
580
350
1190
1300
895
678
400
1350
1500
1020
785
450
1518
1700
1060
890
500
1690
1800
1100
900
============================================================
==
Jointing
All pipelines shall be welded type except G.I. piping which shall have
screwed connections.
Square cut plain ends will be welded to pipe upto and including 100mm
dia.
All pipes 125mm dia. or larger will be bevelled by 35o for welding.
7.
Miscellaneous
a)
b)
Provide valves and capped connections for all low points in piping
system, necessary or required for draining systems. Provide for all risers
isolating valves and drain valves to permit repairs without interfering with
the rest of the system
d)
e)
f)
g)
h)
i)
j)
Cut the pipes accurately according to measurements, established at building and work
into place without springing or forcing.
k)
Pipe supports shall be adjustable for height and prime coated with rust
preventive paint and finish coated with grey paint, both as approved by
Engineer-in-Charge. Spacing of pipe supports shall not be more than
that as specified below :
============================================================
==
Nominal pipe size
Spacing
164
(MM)
(Metres)
============================================================
==
15
1.25
20 & 25
1.25
32, 40, 50 & 65
2.0
80, 100 & 125
2.5
150 & above
2.5
============================================================
=
l)
Extra supports shall be provided at the bends, and at heavy fittings like
valves to avoid undue stresses on the pipes. Pipe hangers shall be fixed
on walls and ceilings by means of `Hilti' metallic dash fasteners.
m)
Insulated piping shall be supported in such a manner so as not to put
undue pressure on the insulation.
Hangers and supports shall be provided and installed for all piping and
tubing wherever indicated, required or otherwise specified. Wherever
necessary, additional hangers and supports shall be provided to prevent
vibration or excessive deflection of piping and tubing.
All hangers and supports shall be made of steel or other durable and
non-combustible materials, galvanised or plated. Wood, wire or
perforated strap iron shall not be used as permanent hangers or
supports.
Hangers shall be supported from structural steel, concrete inserts and
pipe racks, specifically approved.
No hanger/equipment shall be suspended midway, between steel joists
and panel points.
Drilling or punching of holes in steel joist members will not be permitted.
All pipes in AC plant room shall be supported from pipes and channels
from floor.
9
Sleeves
Where pipes pass through walls, provide galvanised steel pipe sleeves
50mm larger than outside diameter of pipe without any extra cost.
Where pipes are insulated, sleeves shall be large enough to have ample
clearance for insulation.
Where pipes pass through outside walls or floor slab the space between
pipe and sleeve shall be packed with lead wool and oakum.
165
The centre of pipes shall be in the centre of sleeves and sleeves shall be
flush with the finished surface. Floor sleeves shall project 50mm above
finished floor level.
10
Expansion or Contraction
The Contractor shall provide for expansion and contraction of all piping
installed by the use of swing connections and expansion loops.
11
Testing
In general, tests shall be applied to piping before connection of
equipment and appliances. In no case shall piping equipment or
appliances be subjected to pressures exceeding their test rating.
The tests shall be completed and approved before any insulation is
applied. Testing of segments of pipe work will be permitted, provided all
open ends are first closed, by blank-offs or flanges.
After tests have been completed, the system shall be drained and
flushed 3 to 4 times and cleaned of all dust and foreign matter. All
strainers, valves and fittings shall be cleaned of all dirt, fillings and
debris.
All piping shall be tested to hydraulic test pressure of at least two times
the maximum operating pressure but less than 10 kg/sq. cm. for a period
of not less than 24 hours. All leaks and defects in the joints revealed
during the testing shall be rectified to the satisfaction of the
Engineer-in-Charge, without any extra cost.
All the piping systems shall be tested in the presence of the
Engineer-in-Charge or their authorised representative. Advance notice of
test dates shall be given and all equipments, labour, material required for
inspection, and repairs during the test shall be provided by the
contractor. A test shall be repeated till the entire system is found
satisfactory to the above authority. The tests shall be carried out for a
part of work if required by the Engineer-in-Charge in order to avoid
hinderance in the work of the insulation contractor.
All water and condensate pipes shall be tested and proven tight under
hydrostatic pressure of 10 kg/sq.cm., unless otherwise stated, for a
minimum period of 24 hours without drop in pressure.
The Contractor shall make sure that proper noiseless circulation is
achieved through all piping systems. If due to poor air bond, proper
circulation is not achieved, the contractor shall bear all expenses for
carrying out the rectification work including finishing of floors, walls and
ceiling damaged in the process of rectification.
The Contractor shall provide all labours and materials to make provision
for removing water and throwing it at the proper place during the testing
or/and after the testing to avoid damages to employer or other
167
Copper Piping
Heavy gauge soft copper tubing, type M, shall be used to make
connections to equipment, wherever required or specified by
Engineer-in-Charge.
Flare fittings e.g. flare nuts, tees, elbows, reducers, etc. shall all be of
brass.
14.
Refrigerant Piping
The refrigerant circuit piping shall be of carbon steel seemless, as per
ASTMA-106, grade B or BS-3602 grade 23 and dimensioned as per
ANSI B-36.1, schedule 40. The fittings shall be heavy class. The pipes
and fittings shall be connected by means of welded joints. The
connections to gauges, controls, etc. shall be with flare fittings.The
refrigerant valves, required in the circuit shall be as follows:
Valve Size
Connections
Valve Material
Type of
fittings
======================================================
============
Upto 12mm
Brass packless type
Flare
16mm and above
Brass/Steel packed
Brazed/Welded
type
Note :-All valves shall be tested against leaks upto 28 kg/sq.cm.
The strainers for the refrigerant liquid line shall be 'Y' type with gun metal
body and bronze filter screen of fine mesh. The filter screen shall be
easily removable type without dismantling the strainer from the circuit.
The moisture indication sight glass in the liquid line shall have leak proof
glass on opposite sides to permit easy inspection of the liquid refrigerant.
Silencers and moisture drier etc. shall be provided as part of the
refrigerant piping.
Bolts wherever used shall be electro-galvanised steel. Brazed joints, in
the refrigerant piping, which has leak, shall be opened and re-done.
These shall in, no case be repaired by addition of brazing alloy to the
joint.
168
15.
Drain Piping
The drain piping shall be medium class galvanizeed steel as per IS:1239
(as per latest amendment).
The fittings shall be of as per IS:1239 Part-II with screwed connections.
The gate valves shall be of gun metal as described earlier.
Pipe crosses shall be provided at bends, to permit easy cleaning of drain
line. The drain line shall be provided upto the nearest drain trap and
pitched towards the trap.
Drain lines shall be provided at all the lowest points in the system, as
well as at equipments where leakage of water is likely to occur, or to
remove condensate and water from pump glands. The drain pipe work
shall be carried out with threaded joints only. No welded joint shall be
permissible.
16 .
Painting
All pipes supports, hangers, etc., shall be given two coats of red oxide
primer.
All pipes (insulated and non insulated) shall then be given two coats
finish paint, of a type and colour as approved by the Engineer-in-Charge.
End of section
Section 12
Sheet Metal Work & Air Distribution
1.
Scope :
The scope of work shall include supply, fabrication and installation of site fabricated
G.I. sheet metal duct as shown in the relevant duct drawing, testing at site, loading &
unloading of G.I. sheets at site, and shifting the G.I. sheets and other hardware from
site stores to exact location inside the office complex. The packing shall be suitable
for marine transportation purpose and all other natural disasters and the same shall
be transported to respective office warehouses to achieve a guaranteed commercial
operation of the same to the entire satisfaction of client.
2.
Materials
169
Thickness (mm)
Galvanized Steel Sheet
Aluminum Sheet
Up to 750 mm
0.63
0.80
751-1500
0.80
1.00
1501-2250
1.00
1.50
2250-2500
1.20
1.60
The bracing shall be as per ISS 655-1964. Supports for ducts at 2.4m
distance apart up to 2250/1.2m distance apart for larger ducts.
Ducts shall be rectangular in cross section and fabricated in accordance
with the following table :
170
Maximum
Side of
Duct
(mm)
Minimum
Thickness of
Sheet
(mm/SWG)
Transverse
Joints
Reinforcement
Hang
er
Rod
Dia
(mm)
Up to 400
25mm pocket/s
slip
Cross Break
401 to 750
25mm pocket/s
slip
25 X 25 X 4.2
Girth angle @ 1000
mm c/c
751 to 900
0.80(22SWG)
38x38x4.2
Companion
Flanges
25 X 25 X 4.2
Girth angle @ 1000
mm c/c
901 to 1500
0.80(22SWG)
38x38x4.2
Companion
Flanges
38x38x4.2
Girth angle @ 760
mm c/c
10
1501 to
2250
1.00(20SWG)
38x38x4.2
Companion
Flanges
38x38x4.2
Girth angle @ 760
mm c/c
10
2250 and
above
1.25(18 SWG)
50x50x4.2
Companion
Flanges
50x50x4.2
Girth angle @ 610
mm c/c
12
Plenums
1.25(18 SWG)
50x50x6.4
Companion
Flanges
50x50x6.4
Girth angle @ 610
mm c/c
12
Rounds Ducts :
Aluminium
Round Ducts 150 mm dia to 500 mm dia.
Round Ducts 501mm dia to 750 mm dia
Round Ducts 751 mm dia to1000 mm dia.
GSS
24 Guage
22 Guage
22 Guage
22 guage
22 guage
20 guage
Girth angles and companion flanges shall be mitered and welded at corners and riveted to
duct sheets at 75mm centers. Flanged joints shall be made with 9.5-mm GI bolts spaced at
1.5cm centers and provided with 4.2mm rubber or 6.0mm. All joints and seams shall be
rendered airtight. All duct seams and joints to be sealed with silicon sealant to stop supply air
leakage. Duct panels are not to be cross-broken if insulated. Longitudinal seams shall be
inside groove of Pittsburgh type. All ducting supports, bracing and framework shall be painted
with 2 coats of epoxy primer and 2 coats of epoxy paint min. (50 microns).
3.
Accessories:
All dampers, except where shown, shall be louver dampers having multiple
opposed blades type or with parallel blades of airfoil construction. The
construction of the dampers shall be robust and tight fitting. They should
171
ESIC Medical College at Joka(WB)
Motors shall be rated for fire damper (spring to close power to open)
operation and shall be suitable for outdoor installation (IP55). Fire
dampers are closed on a signal from the fire control module. Module
supply and wiring by fire control contractor.
300mm X 300mm access panels with gasket neoprene and stud bolt type
shall be provided near lower dampers/ splitters dampers and fire damper.
All main ducting work shall be accessible throughout using tight fitted
hinged access doors. Doors shall be cemented sponge rubber gaskets of
6mm thickness. Felt is not acceptable. In the case of insulated ducts with
access doors, the same shall be properly insulated, such that it can be
operated without damaging the duct insulation and there should be no
condensation either on the access doors or on the ducts when he plant is
running.
4.
Installation Guidelines
172
The duct fabrication and installation shall generally confirm to IS 6551963.
All ducts shall be supported from the concrete slab or beams. Duct
supports shall be fixed through the use of two anchor fasteners for each
leg. The anchor fasteners shall be of approved make. If ducting is
supported from steel structure, Beam Clamps shall be provided. In no
case shall the duct be supported from the false ceiling hangers or be
permitted to rest on a hung ceiling.
Wherever the ducts are acoustically lined, the duct size shall be increased
by the thickness of the duct lining.
The contractor shall provide and neatly erect all sheet metal work as per
the specifications and drawings. This work ,in all its parts and details, shall
meet with the approval of the Engineer
The contractor shall make all necessary allowances and provisions for
beams, pipes or other obstructions in the ducting, whether or not the same
has been shown in the drawings. Wherever necessary to avoid beams or
other structural works, plumbing or other pipes / conduits, the ducts shall
be transformed, divided or curved to one side as approved or directed by
the Engineer. However the required cross-sectional area shall be
maintained.
All metal work shall be done in dead or furred down spaces so as not to
cause any delay to other contractors on the building.
All ducts shall be rigid and shall be adequately supported with standing
seams, tees or angles of ample size wherever required to keep the ducts
true to shape, prevent buckling, vibration and breathing.
All duct joints shall be tightly fitted using rubber gasket of nonflammable
type and all interior surfaces shall be smooth. Bends shall be made with
radius not less than one-half of the width of the duct or with properly
designed interior curved vanes. Two vanes shall be spaced such that the
aspect ratio of each of the individual elbows formed by the vane will be
about five to one.
All sheet metal connections, partitions and plenums required to confine the
flow of air to and through the filters and fans, shall be constructed from
16G galvanised iron thoroughly stiffened with 25mm X 25mm angle iron
braces and fitted with all necessary doors as required to give access to all
parts of the apparatus. Doors shall not be less than 46 cm X 71cm. Sheet
Metal connections to indoor units shall be flexible, double thickness
fiberglass cloth or equivalent nonflammable material of 100mm long.
6.
End of Section
175
Section 13 :
Duct and Pipe Insulation
Angle iron Flanges, Stiffeners, hangers and supports shall be painted with 2
coats of anti-rust primer and remaining uncovered duct shall be further
painted with 2 coats of synthetic enamel paints of black color.
Testing and Balancing
After completion of ducting work, system shall be tested for air leakage.
Leakage if any shall be plugged and all the adjustments and balancing are
completed. The air quantity readings shall be recorded. All dampers shall be
set and locked in position after the final adjustments. All readings made shall
be submitted to the consultants for approval.
Insulation
All tests like pressure testing should be completed and recorded. All systems
shall be approved by the Consultants before insulation is applied to the
equipment, duct and piping. Insulation material shall be supplied by approved
manufacturers and shall be of the type specifically intended for the services
required.
Ductwork & Piping Insulation Application Guidelines :
Pipes shall be thoroughly cleaned with wire brush and rendered free
from all rust and grease.
Ductwork Insulation :
176
25 mm
50 mm
75 mm
Acoustic Insulation
Interior of duct shall be coated with primer. 25mm thick resin bonded
fiberglass Twiga finished with RP tissue shall be fixed to duct using spot
hot bitumen. All joints shall be sealed with bitumen. The acoustic lining to
be covered with RP tissue and perforated aluminum sheets of 30G
thickness. The lining of aluminum sheet facing to be mechanically
fastened to the duct with GI bolts/nuts and washers Contractor to ensure a
smooth internal finish.
All plenums, connecting pieces connected to air handling units and return
air pieces shall also be acoustically insulated.
End of section
177
Section 14
Controls
1.
General :
1.1
1.2
2.
3.
1.3
1.4
3.2
The thermostat for Fan coil unit shall be space type for cooling. It shall
be snap acting type , line voltage, murcury bulb type with differential of
1.1 C. It shall have minimum three speed control complete with wiring
etc.
1.5
1.6
End of section
178
Section 15
Control Panel, Motors and switchgears
1.
General
Error: Reference source not found Equipment shall conform to the latest
applicable standards as mentioned. In case of conflict between the
standards and this specification, this specification shall govern.
All components shall be of reputed make and subject to Purchaser's
approval and as per recommended manufacture.
3
+ 10%
+ 5%
variation
4
+ 10%
Site Conditions
The following site conditions shall be considered for the design of the
MCCs
Reference Temperature
Relative Humidity
Climatic Conditions
}
}
}
Ref :Basis of Design
Painting
All sheet steel work shall be phosphated in accordance with the
following procedure and in accordance with applicable standards.
Oil, grease, dirt and swarf shall be thoroughly removed by emulsion
cleaning.
Rust and scale shall be removed by pickling with dilute acid followed by
washing with running water, rinsing with slightly alkaline hot water and
drying.
180
After phosphating, thorough rinsing shall be carried out with clean water,
followed by final rinsing with dilute dichromate solution and oven drying.
Panels shall be dry electrostatic painted (powder coated).
Finished painted appearance of equipment shall present an aesthetically
pleasing appearance, free from dents and uneven surfaces.
7
Constructional Features
Switchgear panel shall be :
a)
b)
c)
d)
e)
f)
g)
h)
i)
j)
k)
l)
b)
c)
d)
A vertical cable alley covering the entire height. The cable alley shall be
minimum 200mm wide for motor control modules and 500mm wide for
circuit breaker controlled modules.
e)
A horizontal separate enclosure for all auxiliary power and control buses,
as required, shall be located so as to enable easy identification,
maintenance and segrgation from the main power buses. Tap-off
connections from these buses shall be arranged separately for each
vertical section.
Each vertical section shall be equipped with space heaters which may
be located in the cable alley as specified in schedule of quantities.
One metal sheet to be provided between two adjacent vertical sections
running to the full height of the switchgear except for the horizontal
busbar compartment. However, each shipping section shall have metal
sheets at both ends.
All equipment associated with a single circuit shall be housed in a
separate module compartment of the vertical section. The compartment
shall be sheet steel enclosed on all sides and the rear, with the
withdrawable units in position or removed, except on the cable alley
side. A plate cover with a slot to permit wiring connections shall be
provided on the side corresponding to the cable alley. The front of the
compartment shall be provided with a hinged door.
For dial out type, modules, only the handles of control and selector
switches, push buttons, knobs and cut-outs for lamps and meters shall
be arranged on the front doors of the respective compartments to permit
operation without opening the door. On circuit breaker controlled
circuits, protective relays shall be mounted on the front door of the
compartment. All other equipment pertaining to a circuit shall be
mounted on the withdrawable chassis. All cut-outs shall be provided
with gaskets for the purpose of dust-proofing.
182
b)
Fixed Type
In this type of construction all power connections to the equipment
mounted on the base plate shall be of the bolted type. All control circuit
183
Interchangeability
All identical equipment and corresponding parts including chassis of
drawout modules of the same size shall be fully interchangeable, without
having to carry out modifications. For trouble free interchangeability, the
drawout arrangements shall be designed such that normal dimensional
variations are taken care of by self-aligning feature of the modules.
Components and equipment that are not fully interchangeable will be
rejected.
VENDOR shall replace all such equipment by fully
interchangeable equipment at his cost.
Switchgear shall be designed in such a way that all component
equipment and bus bars operate satisfactorily without exceeding their
respective maximum permissible rise in temperature under ambient
temperature conditions prevailing with the switchgear cubicle, with
reference ambient temperature outside the switchgear cubicles.
All dummy cubicles necessary to meet the requirements of this
specification shall be included in the VENDOR's scope.
No equipment/devices associated with a particular circuit shall be
mounted in any other circuit module.
a)
grade.
Busbars shall be provided with at least the minimum clearances in air as
per applicable standards for a 500V, 3 phase system.
184
All bus-bars, bus-taps shall be insulated with close fitting sleeve of hard,
smooth, dust and dirt free plastic insulation of high dielectric strength
(450 V/mil) to provide a permanent high dielectric non-ageing and
non-tracking protection; imprevious to water, tropical conditions and
fungi. The insulation shall be non-inflammable and self-extinguishing
and in fast colours to indicate phase. The joints shall be insulated in uch
a way as to provide for accessibility of contact bolts for maintenance.
The dielectric strength and properties shall hold good for the
temperature range of 0 deg.C to 90 deg.C.
Busbars shall be adequately supported and braced to withstand the
stresses due to the specified short circuit currents for the associated
switchgear. Busbars supports shall be made of Hylam sheets, glass
reinforced moulded plastic material, permali wood or cast resin.
Separate supports shall be provided for each phase of the busbars. If a
common support is provided for all three phases, antitracking barriers
shall be incorporated.
Busbar joints shall be complete with high tensile steel bolts and lock
washers and nuts. Busbars shall be thoroughly cleaned at the joint
locations and a suitable contact grease shall be applied just before
making a joint.
b)
Auxiliary Buses
Auxiliary buses for control power supply, space heater power supply or
any other specified service shall be provided. These buses shall be
insulated, adequately supported and sized to suit specific requirements.
The material of control power supply buses shall be electrolytic copper.
The material for space heater power supply buses shall be same as that
for the main power buses. Supply transformer(s), auxiliary busbars and
necessary connections to the supply transformers and associated
circuits shall be in the VENDOR's scope.
Circuit Breakers
a)
Circuit breakers shall be of the airbreak drawout type, mounted
along with its operating mechanism on a wheeled carriage moving on
guides, designed to align correctly and allow easy movements.
-
185
b)
c)
Circuit breaker closing and trip coils shall be rated for satisfactory
operation on a control supply system indicated in Data Sheet-A.
d)
Closing and trip coil shall operate satisfactorily under the following
conditions of supply voltage variation :
Closing coils-85% to 110% of rated voltage.
Trip coils-50% to 110% of rated voltage.
The breakers controlling motors shall operate satisfactory under
following conditions :-
i)
ii)
e)
Operating Mechanism
The circuit breaker shall not close unless the spring is fully charged.
ii)
i)
Provided with a universal motor suitable for operation on A.C. and D.C.
control supplies specified in Annexure-A with voltage variation from 85%
to 110% rated voltage.
ii)
iii)
10.
11
a)
MCBs shall be hand operated, air break, quick make, quick break type
conforming to applicable standards.
b)
c)
12
a)
Air break switches shall be of heavy duty, group operated load break,
fault make type, complying with the requirements of applicable
standards.
b)
188
c)
d)
Whenever solid links are used for the connections between switches and
fuses, such links shall be fitted with insulated sleeves.
e)
f)
g)
13
Fuses
Fuses generally shall be of the HRC cartridge fuse-link type having a
certified repturing capacity of not less than 80 kv at 440 V. Fuses upto
63A for distribution systems of medium short circuit levels may be of
HRC cartridge screw-cap type, having a certified rupturing capacity of
not less than 46ka at 440 V and 16 KA at 250V DC.
Fuses shall be provided with visible indication to show that they have
operated.
Fuses shall preferably be mounted on moulded plastic carriers and shall
be complete with fuse bases.
Wherever it is not possible to mount fuses on carriers, fuses shall be
directly mounted on plug in type of bases. In such cases an insulated
fuse pulling handle shall be provided for each size of fuse for each
switch board.
14
Motor Starters
189
a)
Contactor
Direct-On-Line Starters
Direct-on-line starters shall be suitable for Class AC 3 utilisation
category.
c)
Reversing Starters
Reversing starters shall comprise forward and reverse contactors,
electrically interlocked with each other.
Reversing starters shall be suitable for Class AC 4 duty.
d)
`Stop' push button of the starter and hand reset device shall be separate
from each other.
Overload relay hand reset push button shall be brought out on the front
of the compartment door.
Overload relay shall be provided with atleast one 'NO' and one 'NC' or
one change-over contact.
15
Current Transformers
Current transformers shall be of the dry type.
Current transformer shall have a short time withstand rating equal to the
short time withstand rating of the associated switchgear for one second.
Unless otherwise specified, the minimum performance requirement of
current transformers are as follows :-
a)
b)
Protective CTs - 7.5 VA, accuracy class 5P and an accuracy limit factor
of 10.
Notwithstanding the above it shall be the VENDOR'S responsibility to
coordinate the current transformer burden with the requirements of
relays, instruments and leads associated with that particular current
transformer.
Test links shall be provided in both secondary leads of the CTs to easily
carry out current and phase angle measurement tests.
All current transformers shall be earthed through a separate earth link on
the terminal block to permit easy measurement of the current
transformer insulation resistance. (CTs built-in with the thermal relays of
the contactors are excluded).
16
Voltage Transformer
Voltage transformers shall be of dry type.
191
b)
c)
Dual purpose VTs - 100 VA and dual accuracy class 1.0/3.0 for metering
and protection respectively. VA is per phase.
All secondary windings of voltage transformers including open delta
windings shall be rated for 110/ 3 V per phase.
Voltage transformers shall have a continuous overvoltage factor of 1.2
and short time overvoltage factor as follows :
1.5 for 30 seconds in case of effectively earthed. 1.9 for 8 hours in case of
non-effectively earthed system.
Relays
The following clauses shall apply to the protective relays.
Relay shall be -
a)
b)
c)
Provided with positive acting hand-reset flag indicators visible from the
front.
Access to setting devices shall be possible only after the front covers are
removed. Access to resetting devices shall be external to the case.
Auxiliary relays shall be rated to operate satisfactorily between 70% and 110% rated
voltage.
Each relay shall be provided with at least two separate voltage from
contacts.
Make and type of relays shall be subject to the EIC approval.
18
dial.
193
19
Indicating Lamps
Indicating lamps shall be :
a)
b)
c)
provided with translucent lamp covers of colours 'Red', 'Green' and
'Amber'
as required in the control wiring diagrams.
Bulbs and lenses shall be easily replaceable from the front.
20
a)
b)
c)
a)
194
a)
of the maintained contact stayput type. Switches in ammeter circuits
shall have make-before-break type contact.
b)
Push Buttons
c)
22
a)
b)
provided with single pole MCD with overload and short circuit release
c)
23
Cable Terminations
195
Suitable compression type heavy duty brass cable glands with nuts,
rubber sealing ring and brass washers mounted on a removable and
control cables entering the switchgear shall incorporate built in facilities
for earthing the wire armour of cables. Cable glands shall be plated to
avoid corrosion.
Power cable glands and crimping type lugs shall be supplied to suit the
cable sizes given in clause 3. If during course of detailed engineering of
the switchgear it is found necessary to provide more glands or glands of
higher size than those envisaged the vendor shall provide and
accommodate the same.
Wire Sizes :
The vendor shall select the power cable glands and lugs based on the
following cable sizes.
Type of cable : 1100 V grade stranded aluminium conductor PVC
insulated PVC sheathed armoured and outer sheathed FRSL ceated
cable conforming to IS:1554 Part-I.
------------------------------------------------------------------------------------------------------------KW Rating
No. of cores x
Approximate overall
Service
conductor size(mm2)
diameter/mm
------------------------------------------------------------------------------------------------------------Upto 3
3x4
18
3.1 - 7.5
3x6
19.5
7.6 - 1.5
3 x 16
24
16 - 25
3 x 35
30
26 - 40
3 x 70
34
41 - 55
3 x 120
40
56 - 70
3 x 185
49
71 - 85
3 x 240
55.5
86 - 110
3 x 400
60
111- 175
3 x 1C x 500
Space Heating
2x6
19
For supporting & clamping cable cores at regular intervals inside the
cable alleys, suitable shutted angles, upto the respective terminal blocks
shall be provided.
196
Necessary crimping type of tinned copper cable lugs for connecting the
individual cores to the respective terminals, shall be provided.
24
Internal Wiring
Control wiring shall be of the rating of 650V and power wiring shall be of
the rating of 1100V.
Wiring inside the switchgear shall be carried out with 1100/650 V grade,
PVC insulated, stranded conductor wires. Minimum size of conductor
for power circuits is 4 sq.mm copper or equivalent size aluminium
conductor. Control circuits shall be wired with copper conductor of at
least 2.5 sq.mm for CT circuits and 1.5 sq.mm for other circuits, the
number and size of strands shall be 7 of 0.67 mm and 0.5mm diameter
respectively.
Engraved identification ferrules, marked to correspond with the wiring
diagrams shall be fitted to each wire. Ferrules shall be of yellow colour
with black lettering.
Wires forming part of a tripping circuit of circuit breaker shall be provided
with an additional red ferrule marked 'T'.
Spare auxiliary contacts of all equipment forming part of the switchgear
shall be wired up to the terminal blocks.
Spare and unassigned modules shall be complete with internal wiring.
Wiring shall be terminated on preferably stud type terminal blocks such
that the wires are connected by cable lugs with nuts and
washers/lock-nuts.
Not more than two connections shall be made on any one terminal.
25
Terminal Blocks
Terminal blocks (both for power and control circuit) shall be of reputed
make specially for CT and VT circuit. It shall comprise of finely threaded
pairs of brass studs of at least 6mm diameter, links between each pair of
studs, washers, nuts and locknuts. The studs, shall be securely locked
within the mounting base to prevent their turning. Insulated barriers shall
be provided between adjacent terminals.
197
Labels
All labels shall comprise white letters one a black background.
Labels shall be made of non-rusting metal or 3-ply lamicoid, or engraved
PVC.
Labels shall be properly fixed, with provision to prevent distortion due to
expansion.
Size of lettering shall be 6mm.
27
Earthing
Each MCC and LCC shall be provided with an earth busbar running
along the entire length of the board. Material and size of the earth
busbar shall be as specified in data sheets. At either end of the earth
bus, one (1) clamp type terminal with nuts, bolts and washers shall be
provided for bolting the main earthing conductor of size and material
indicated in data sheets. In case the earth bus is provided near top of
the switchgear, one down comer at either end shall be provided for
connection to the main earthing conductor.
198
a)
b)
c)
d)
e)
Provided with inscription plates of rear engraved perspex with white
letters on black background. The letter size shall be 6mm.
f)
Provided with two earthing terminals suitable for 8 SWG G.I. wire.
g)
be
h)
All local push button stations shall have locking facility. The lock switch
shall have two positions "locked" and "unlocked". When in unlocked
position the switch shall allow individual starting of the equipment.
Start/stop push
buttons
provided for local operation of the
199
ESIC Medical College at Joka(WB)
The stop push buttons shall be stay put type with mushroom knob.
c)
i)
Fitted with two (2) normally open and two (2) normally closed contacts
rated to carry and break 6 Amps at 415 Volts. (10A at 240 AC).
ii)
d)
e)
200
a)
Compressor
b)
Chiller thermostat
c)
Oil pressure
d)
Main motor
c)
Condenser and chilled water pumps and cooling tower fans shall be
interlocked with chilling units to prevent operation without pump and
cooling
tower fan running.
30
Tests
Switchgear shall be subjected to following tests :
a)
b)
c)
d)
e)
f)
Certified copies of all type and routine test certificates shall be submitted
for the Engineers approval before despatch of the switchgear.
31
data :
a)
For each switchgear, overall dimension drawing showing front view,
plan, elevation and cross-section.
All drawings and data sheets shall be annotated in English.
End of section
Section 16
Electrical Cabling Works
CABLES:
PVC insulated aluminium conductor Armoured cables shall be used for connecting
motors.
CABLE GLANDS:
202
Heavy duty compression type cable gland alongwith the cable lugs shall be used for
termination of cables. The cable glands shall be of cadmium plates brass. For all
power cables, crimped type copper cable lugs shall be provided.
The cable trays shall be channel type made out of M.S. sheets (slotted) having a
minimum thickness of 2mm duly painted. (Cable trays exposed to atmosphere shall be
hot dip galvanised). The Clamps used shall be Aluminium with G.I/Cadmium plated
nut-bolts. The size of these trays shall be selected considering the number of cables
and leaving minimum 20% spare area. The arrangement of cables in these trays shall
be in Single Tier Formation.
Sharp bending of the cables shall be avoided. The radius for bending PVC insulated
cable and sheath armoured cable shall not be less than 10D where "D" overall diameter
of the cable. Wherever cable rises from concrete trenches, these shall be taken in G.I.
pipes of suitable size. The Contractor shall make sure that the 40% area of pipe shall
be free after the cable is laid.
WIRE SIZES
Final connection to the equipment shall be through flexible wiring enclosed in
galvanised flexible conduit rigidly clamped at both ends. An isolator shall be provided
near each motor/equipment wherever the motor/equipment is separated from the
supply panel through a partition barrier or through ceiling construction. P.V.C. insulated
single strand hard drawn copper conductor wires shall be used inside the control panel
for connecting different components and all the wires inside the control panel shall be
neatly dressed and plastic beads shall be provided at both the ends for easy
identification. All the wires shall be suitably sized for motor duty.
EARTHING
Main power upto the Electrical panels in Plant rooms along with earthing shall be
provided by other agency. Each panel shall be earthed to building main earthing. All
the motor etc. shall be double earthed to the panel. All three phase motors/equipment
shall be earthed with two independent earth conductors as per the requirement of
Indian Electricity Rules and Regulation - 1956.
DRAWINGS
Shop drawing for control panel and wiring of equipment showing the route of
conduit/cables shall be got approved by the Consultant/Architect before starting the
fabrication of panel and starting the work.On completion four sets of completion/"As
installed" drawings incorporating all details like conduit routes, number of wires in
conduit, location of panels, switches, junction/pull boxes and cable route etc. shall be
furnished by the Contractor.
TESTING
Before commissioning of the equipment the entire Electrical Installation shall be tested
in accordance with code of Practice IS:732-1963 (Revised) and test report furnished by
a qualified and authorised person. The entire electrical installation shall be got
approved by Electrical Inspector and certificate from Electrical Inspector shall be
submitted. All tests shall be carried out in presence of Consultant/Architect.
Painting
All sheet steelwork shall undergo a process of degreasing, pickling in acid, cold rinsing,
phosphatising passivating and then sprayed with a high corrosion resistant primer. It
203
End of section
Section 17
Mode of Measurement
1
General
This specification covers measurement of various items/materials at site.
204
a)
205
The unit of measurements shall be the finished sheet metal surface area
in metre squares. No extra shall be allowed for overlaps.
All the guide vanes, deflectors access panels, splitter dampers within the
duct work shall be considered as part of the duct and nothing will be paid
extra on this account.
The unit duct price shall include all the duct hangers, supports and `Hilti'
metallic fasteners as well as any materials and labour required to
complete the duct frame.
b)
Box Dampers
Box dampers wherever shown or required in ducts shall be measured as
per finished inside cross-sections and paid as per the calculated are in
sq.m.
c)
Grilles/Diffusers
All measurements of grilles/diffusers shall be the nominal outlet size
excluding the outer flanges.
The square or rectangular grilles/diffusers shall be measured in plain
sq.m.
All round diffusers shall be measured by their diameters in centimetre.
All linear diffusers shall be measured as per actual length in meters.
4
a)
Pipe
(Including Water Piping, Oil Piping, L.P. Gas Piping, Air Piping, Vacuum
Piping, etc.)
All pipes shall be measured in linear meter (to the nearest Cm.) along
the axis of the pipes and rates shall be inclusive of all fittings e.g. tees,
bends, reducer, elbows, hanger support bracket, etc. Deduction shall be
made for valves in the line.
206
c)
d)
Painting
Painting of all pipes, supports, valves and fittings shall be included with
the cost of these items. Nothing extra shall be paid for this work.
Painting of grilles/diffusers, tanks and equipment wherever required shall be in the cost
of these items.
Insulation
Measurement of insulation for vessels, piping, equipment and ducts shall
be made over the bare uninsulated surface area of the metal.
a)
Pipes
The measurements for insulation of piping shall be made in linear
meters through all valves, flanges, and fittings. Pipes/bends shall be
measured along the centre line radius between tangent points. If the
outer radius is R1 and the inner radius is R2, the centre line radius shall
be measured as (R1+R2)/2. Measurement of all valves, flanges and
fittings shall be taken in running metre of pipe line as if they are also pipe
lengths. Nothing extra over the above shall be payable for insulation
over valves, flanges and fittings in pipe line/routings. Fittings that
connect two or more different sizes of pipe shall be measured as part of
the larger size.
b)
Ducts
The measurements for insulation of ducts shall be made in actual square
meters of bare uninsulated duct surface.
In case of bends the area shall be worked out by taking an average of
inner and outer lengths of the bends. Measure-ments for damper,
flanges, fittings shall be for the surface dimension for the connecting
208
duct. Nothing extra over the above shall be payable for insulation over
dampers, flanges and fittings in duct routing.
c)
Vessels
The area of standard dished and flat ends of vessels shall be measured
as the uninsulated body of the shell. Areas for other shapes shall be the
actual calculated area. There shall be no deduction or additions for
nozzles, handle ribs, dampers, expansion joints etc. all projections on
vessels or tanks shall be measured separately as pipe/duct.
d)
Accessories Insulation
The unit of measurement for accessories such as expansion tank, pumps,
chiller heads etc. shall be of uninsulated area in square meters. In case of curved or
irregular surfaces, measurements shall be taken along the curves. The unit insulation
price shall include all necessary adhesives, vapour proofing and finishing materials as
well as additional labour and material required for fixing the insulation.
e)
f)
g)
209
The unit price shall include all hold fasts, nuts, bolts connecting the size
of wall opening and making it good as well. Any additional materials and
labour to fabricate and fix the boxes.
End of Section
210
Section 18
Technical data
Contractor shall submit catalogues of the equipment offered by him :
Sr.No.
Equipment description
unit
Condition of service
1.
Screw Compressor :
a.
Manufacturer /Make
Country of origin
b.
Model No.
c.
Type(Hermatic/semihermatic)
d.
No.of compressors
e.
f.
g.
Refrigerant
h.
i.
Maximum (RPM)
j.
Mode of start
k.
l.
Power Consumption
a) Total power consumption at full load
Including fans/heater etc.
b) IKW/TR (actual for the chilling machines)
100% Load
90% Load
75% Load
50% Load
25% Load
m.
n.
o.
q.
r.
safety Devices/controls
s.
Monitoring Devices
t.
Type of Bearings
Compressor Motor :
a.
Motor Manufactures
b.
Type
c.
HP
d.
Electrical characteristics
211
e.
Method of starting
f.
class of insulation
g.
starter manufacturer
h.
i.
starting current
j.
no load current
k.
Manufacturer/Make
b.
Model
c.
Type
d.
e.
f.
Tube length
g.
h.
i.
j.
k.
l.
Type of fins
m.
n.
o.
No. of rows
p.
q.
r.
Type of fan
s.
t.
u.
v.
Air temperature
Entering F
Leaving F
w.
x.
Condensing temperature F
y.
z.
2.
i.
ii.
iii.
212
iv.
v.
vi.
vii.
viii.
xii.
xiii.
3.
Pumps
:
:
chilled
Hot
water
water
a.
Manufacturer
b.
Model No.
Pr.
c.
Capacity
USGPM
d.
Head
Meter
e.
Speed
RPM
f.
Motor Rating
KW
g.
Type of motor
4.
a.
Manufacturer
b.
Casing
c.
Coil
d.
Blower
e.
Type
f.
Overall Dimension
213
Sec.
g.
Unit Weight
Air Quantity
i.
j.
h.
i.
j.
k.
b.
No.of Rows
c.
No.of fins/cm
d.
Tube Material
e.
Tube dia
f.
g.
Thickness of tube
5.
a.
Manufacturer
b.
Casing
c.
Blower
d.
Type
e.
Overall Dimension
f.
Unit Weight
214
Air Quantity
h.
i.
No.of Rows
j.
No.of fins/cm
k.
Tube Material
l.
Tube dia
m.
n.
Thickness of tube
o.
p.
Impeller dia
q.
material of Impeller
r.
s.
Capcities
t.
u.
6.
a.
Make
b.
c.
Static Pressure
d.
Diameter/size
e.
Type
f.
Current characteristics
(cfm/TR)
215
g.
Motor Rating
h.
Type of Motor
i.
j.
Fan Speed
k.
l.
Operating Weight
m.
o.
Type of bearings
p.
Performance curves
q.
Motor Efficiency
r.
Class of Insulation
7.
Controls
Make and Model of the following :
a.
Flow Switch
b.
c.
Operating Voltage
d.
Air Stat
e.
Pessure Guage
f.
Thermometer
g.
AHU Thermostat
h.
FCUs Thermostat
8.
Electrical Accessories
216
a.
b.
c.
MCCB
d.
MCB
e.
Rotary Switch
f.
Soft Starter
g.
Auto-transformer starter
i.
Contactor
j.
Current transformer
k.
l.
m.
Ammeter/Voltmeter
Relays
Indicating Lamps
p.
Cables/wires
9.
Water Piping ;
a.
b.
c.
Make
i)
Butterfly Valve
ii)
Balancing Valve
iii)
Ball Valve
iv)
v)
Pot Strainer
vi)
Flexible connections
217
Material
vii)
Check Valves
viii)
Gate Valves
ix)
Globe Valves
x)
Y-Stariners
c)
pressure Guage
i)
Make
ii)
Model
iii)
Dial
d)
Thermometer
10.
a.
Make
b.
Gauge/Thickness
c.
Class of galvanizing
11.
12.
Insulation
a.
Manifacturer
b.
c.
d.
Make/Material/Guage
.S.No.
Description
Condition of Services
Unit
1.
1.1
1.1.1
1.1.2
HP of outdoor unit
1.1.3
1.1.4
Quantity
1.1.5
Type
1.1.6
Permissible length of
refrigerant piping
HP
Nos.
218
1.1.7
Type of Compressor
1.1.8
No. of compressor
1.1.9
No. of inverter
compressor
1.1.10
-No
(each unit)
Deg C
1.1.11
Dimensions of Machine
(H x W xD)
mm
1.1.12
Current characteristic
--
1.1.13
Indoor Units
1.2.1
Manufacturer
1.2.2
Type
1.2.1.2
-Capacity
Tons
1.2.1.3
1.2.2
Airflow Min/Max.
Sound level
Hi/Lo
1.2.3
Overall Dimensions
1.2.4
Unit weight
Kg
1.2.5
Is remote controller
(corded) provided
for each indoor unit
Yes/No
1.3
cfm
lxwxh
Centralized controller
(1 No For complete VRV system)
Detail of operation
1.4
2.
2.1
Nos.
2.3
Airquantity
cfm
cfm
2.4
Dia/speed
mm/rpm
2.5
Motor rating
Kw
2.6
mm wg
2.7
Silencer
2.8
Current characteristic
Included/Not included
----
End of section
220
Section 19:
LIST OF BUREAU OF INDIAN STANDARD CODES
IS:277-1992
IS:544-1985
IS:778
IS:655-1963
IS:13095-1991 -
Butterfly Valves
IS:659-1964
IS:1239-1990/92
IS:325
IS:822
IS:900
(Reaffirmed 1996)
IS:6392
IS:1822
IEC
Relevant Sections
IS:996
IS:4894-1987
IS:1554(I)
Centrifugal Fans
-
IS:8623-1993
IS:8828-1996
& IEC898-1995
IS:9537-1981 Part II
IS:10810-1989 -
IS:13947-1989 -
Circuit Breakers
IS:13947-1993 -
IS:139-1993(Part IV)-
-SMACNA
Application 1995
-
fundamentals 1997
End of section
Section 20 :
LIST OF APPROVED MAKES FOR HVAC EQUIPMENT AND MATERIALS
221
Sr.No.
Manufacturers name
1.
Chilling Machines
Carrier/York/Trane/McQuay
2.
3.
Primary Pumps
Hot water pumps
3a
Secondary pumps
4.
5.
Caryaire/Coil company/Hitech
6.
Greenheck/Systemaire/Ostberg
7.
Nicotra/comefrei / Krugar
8.
Electric Motors
ABB/Crompton/Kirloskar/
GEC/Siemens
9.
MS/GI Pipes
10.
GI Sheet
Sail/TATA/ Bhushan
11.
Butterfly Valves
12
Balancing Valves
Advance/Econosto/Sant/C&R/SKS
Oventrop/Belimo
13.
Check Valve
Advance/Kirloskar/Econosto
Audco / C & R/SKS
14.
Ball Valves
CIM /Festo/Oventrop
CIM /Festo/Oventrop
14
15.
Strainers
16.
Pot / Y-strainers
Rapidcool/Emerald/Sant
17.
Resistoflex/Kanwal
18.
Gate Valve
Leader/Kirloskar
19
Siemens/Honeywell/Schneider
/Belimo
222
20.
Siemens/Honeywell/schneider
21.
Pressure Guage
H.Guru/Feibig
22.
Thermometer
H.Guru/Taylor/Emerald
23.
Flow Switch
Rapidcool/Danfoss/Siemens
24.
Air Vents
Rapidcool/Anergy
25.
Grilles/Diffuser
Caryaire/Tristar/trox
26.
MS Dampers/Louvers
Caryaire/Tristar/Mapro/Trox
Fire Dampers
27.
MCCB
L&T/Siemens/GE/Shneider
28.
MCB
L&T/MDS/IShneider
29.
Control Cables
Grandlay/Batra Henlay/Kalinga
30.
Power Cable
ICC/Skytone/Plycab/Kalinga
31.
L&T/Siemens
32.
Aux.Relay/contactors
L&T/Siemens
33.
L&T/EnglishElectrc/Siemens
34.
Timer
L&T/EnglishElectrc/Siemens
35.
Terminal Block
Elmex
36.
Indicating Lamps
L&T/Siemens
37.
Selector Switches
L&T/Siemens
38.
Electrical Panel
Tricolite/Trident/Electrapower
39.
Duct Insulation
40.
Airflow/Pyroguard
41.
Gaskets
Neoprene rubber
42.
Adhesives
Fevicol / Superlon
Supreme/Trocellene/Armacell
223
43
VIBRATION ISOLATOR
Resistoflex/Dunlope/kanwal
44.
FILTERS
Thermadyne/Anfilco
45.
VRV Units
Mitsubishi Electric/Toshiba/Daikin
46.
47.
CPVC Pipes
ASTRAL
48.
Inline Fans
Systemaire/Ostberg/Greenheck
49.
50.
51.
Brassomatic/Totaline
52.
Trox
53.
54.
HRW wheel/units
Rajco/Totaline/parasmani
Eurabatex/Aeroflex/Totaline
Bryair/Novelair/Vikram Hitech
End of Section
Section 21 :
LIST OF HVAC DRAWINGS
224
===========================================================
==
Sr.No,
Description
Drawing No.
===========================================================
==
1.
HSPL/HVAC/01
2.
HSPL/HVAC/02
3.
HSPL/HVAC/03
4.
HSPL/HVAC/04
5.
HSPL/HVAC/05
6.
HSPL/HVAC/06
7.
HSPL/HVAC/07
8.
HSPL/HVAC/08
9.
HSPL/HVAC/09
10.
HSPL/HVAC/10
9.
HSPL/HVAC/11
===========================================================
==
End of section
225