Beruflich Dokumente
Kultur Dokumente
PAG E
GS 400
REV. 3
REV.
NO.
BY
DATE
TR
10/16/00
1 OF 18
CHK
APP.
GENERAL SPECIFICATION
ELECTRICAL STANDARD PRACTICES
GS - 400
DATE
REMARKS
REWRITE ON MS WORD
SPECS NO.
GS 400
REV. 3
GENERAL SPECIFICATION
ELECTRICAL STANDARD PRACTICES
GS - 400
INDEX
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
SCOPE
CODES, STANDARDS AND COMPANY SPECIFICATIONS
INTENT
ENVIRONMENT
ELECTRICAL SYSTEM
EQUIPMENT
WIRING SYSTEM
GROUNDING
CONTROL
PROTECTION
METERING
PAG E
2 OF 18
SPECS NO.
GS 400
REV. 3
1.0
PAG E
3 OF 18
SCOPE
This specification covers the standard practices to be used when designing the
electrical system on offshore platforms
2.0
2.2
NFPA
2.1.2
NEMA
2.1.3
ANSI
2.1.4
IEEE
2.1.5
API
2.1.6
NEC(NFPA70)
2.1.7
UL
Underwriter's Laboratories
2.1.8
FM
Factory Mutual
General Specifications
GS-401
GS-410
GS-411
GS-412
GS-413
Motors - Submersible
GS-415
GS-421
GS-425
GS-426
SPECS NO.
GS 400
REV. 3
3.0
GS-430
Generators
GS-431
Navigational Aid
GS-432
GS-435
Electric Heaters
GS-470
D.C. Systems
GS-471
Electrical Building
GS-472
GS-473
Trace Heating
PAG E
4 OF 18
INTENT
The purpose of this specification and its referenced codes, standards, and general
specifications is to establish a minimum level of design. Alternate designs of equal or
superior quality may be proposed, provided all exceptions are listed and written
approval for all exceptions is obtained from COMPANY.
4.0
ENVIRONMENT
4.1
Area Classification
Area classification shall be determined in accordance with API 500B.
For the purpose of classification it shall be assumed that a drill rig or wire line
unit are in operation.
To obtain uniformity of material and obviate classification problems if future
process equipment is installed, all equipment shall be suitable for installation
in a Class 1 Division 2 Group D area as a minimum. (Exceptionstandby/emergency generators and associated switchgear require enclosures for
an unclassified area only, provided they are installed in an unclassified area
determined in accordance with API 500B).
SPECS NO.
GS 400
REV. 3
4.2
PAG E
5 OF 18
Temperature
The ambient temperature shall be 95F (35C).
4.3
Humidity
Relative humidity shall be 100%.
4.4
5.0
Atmosphere
4.4.1
Open Deck Area's - Salt laden with winds up to 80 mph (ANSI A58.1).
4.4.2
ELECTRICAL SYSTEM
The characteristics of the power, lighting and control electrical system shall be in
accordance with the following :
Generation
Transmission/Distribution
Utilization
208 V, 1 phase, 60 Hz
SPECS NO.
GS 400
REV. 3
Motor Control
6.0
48 VDC
Switchgear Control
48 VDc (preferred)
Instrumentation
120 V, 1 phase, 60 Hz
24 VDC (preferred)
Communication
24 VDC
Navigational Aid
24 VDC
PAG E
6 OF 18
EQUIPMENT
6.1
Generators
6.1.1
General
Generators shall be in accordance with the following general
specification :
GS-430
6.1.2
Generators
Emergency Generators
If required by the detailed design drawings, platforms shall be provided
with an 85KW emergency, standby, diesel driven generator as
manufactured by caterpillar model 3304T or equal.
6.1.3
Transportable Generators
Each platform shall be provided with switchgear and a junction box to
allow the connection of a transportable, skid mounted, diesel driven
generator.
The transportable generator will be 2400 V, 3 phase, 60 Hertz and will
be provided with a circuit breaker and synchronization controls.
SPECS NO.
GS 400
REV. 3
6.2
PAG E
7 OF 18
Transformers
6.2.1
General
Transformers shall be in accordance with the following general
specification :
GS-415
6.2.2
Rating
Transformers shall have a self cooled (OA) rating of 120 % of the
maximum running load.
6.3
Motors
6.3.1
General
Motors shall be in accordance with the following specifications:
6.3.2
GS-410
Electric Motors
GS-411
Electric Motors
GS-412
Electric Motors
GS-413
Electric Motors
Submersible
Voltage
Motor terminal voltage shall generally be as follows :
Less than 1/2 H.P.
1/2 H.P. to 200 H.P.
Above 200 H.P.
Starting
Motors shall generally be direct-on-line started. Other methods of
starting may be used only after written approval is obtained from
COMPANY.
SPECS NO.
GS 400
REV. 3
6.4
PAG E
8 OF 18
Switchgear
6.4.1
General
Switchgear shall be in accordance with the following general
specification
GS-421
6.4.2
Type
Switchgear shall be metalclad, withdrawable, vacuum circuit breaker or
SF6, type. Oil circuit breakers shall not be used.
6.5
Controllers
6.5.1
General
Controllers shall be in accordance with the following general
specifications :
GS-425
GS-426
6.6
7.0
WIRING SYSTEMS
7.1
General
7.1.1
Bridge-Connected Platform
Cables between bridge connected platforms shall generally be PVC
jacketed type MC (metal clad) cable.
Subsea cable may also be used, if it is being installed elsewhere in the
system, and spare lengths are available.
SPECS NO.
GS 400
REV. 3
7.1.2
PAG E
9 OF 18
7.1.3
Deck Areas
7.1.3.1
7.1.3.2
7.1.4
Inside Buildings
Wiring shall be XHHW insulated cable enclosed in rigid, copper free
aluminum conduit, or PVC jacketed type MC multicore cable.
7.1.5
Segregation
Cables shall be grouped as follows :
Group A
Group B
Group C
Group D
SPECS NO.
GS 400
REV. 3
7.2
PAG E
10 OF 18
SUBSEA CABLE
Subsea cable shall be in accordance with the following general specification :
GS-472 Subsea Power Cables.
7.3
7.4
CONDUIT
Conduit shall be rigid, copper free aluminum in accordance with Article 346 of
NEC or liquid tight flexible metal conduit in accordance with Article 351 A of
N.E.C.
The minimum conduit size shall be 3/4 inch except at instrument connections
where 1/2 inch conduit may be used.
The size of conduit required shall be determined in accordance with NEC
(NFPA70) requirements.
7.5
CABLE TRAY
Cable tray shall be of copper free (less than 0.4%) aluminum or fiberglass
reinforced polymer in accordance with Article 318 of NEC.
SPECS NO.
GS 400
REV. 3
7.6
PAG E
11 OF 18
CONDUCTORS
7.6.1
Voltage Rating
Conductors shall be rated for the following minimum voltage relative
to the operating voltage.
Operating Voltage
34500Y/19,900V AC
13800Y/7967V AC
4160Y/2400V AC
2400Y/1385V AC
480Y/277V AC
208Y/120V AC
120V AC
120DC and Below
Instrumentation 4-20mA
7.6.2
Size
Conductor shall be sized as follows :
-
#10 AWG
#12 AWG
#14 AWG
#16 AWG
SPECS NO.
GS 400
REV. 3
7.6.3
PAG E
12 OF 18
Color Coding
Power Conductors shall be color coded as follows :
3 phase : Phase A
Phase B
Phase C
- Black
- Red
- Blue
1 phase : Phase
Neutral
- Black
- White
DC
- Red
- Black
: Positive
Negative
GROUNDING
8.1
General
All non-current carrying metal shall be grounded in accordance with the NEC
(NFPA 70).
8.2
8.3
SPECS NO.
GS 400
REV. 3
8.4
PAG E
13 OF 18
Bonding Jumper
Bonding Jumpers sized in accordance with NEC (NFPA 70) article 250 shall
be installed between equipment metallic enclosures and the structural deck or
jacket (grounding electrode conductors).
Two (2) bonding jumpers shall be installed for the following equipment:
-
Switchgear
Motor Control Centers
Transformers rated over 225 KVA
Generator frames
Outdoor Switchracks
Skids containing electrical equipment
Buildings containing electrical equipment
One (1) bonding jumper shall be installed for the following equipment:
8.5
Static Grounding
Process equipment and pipes shall be effectively grounded to the deck or
jacket structure.
9.0
CONTROL
9.1
Manual Operation
Where manual operation of equipment is required, local stop and start
pushbuttons shall be provided and a stop pushbutton installed on the controller
unit.
Equipment normally inaccessible to personnel e.g. submersible pump, shall
have a start pushbutton installed on the controller unit.
9.2
Automatic Operation
Where automatic operation of equipment is required a local hand/off/auto
selector switch shall be installed to allow the equipment to be controlled
manually if desired.
SPECS NO.
GS 400
REV. 3
9.3
PAG E
14 OF 18
Indication
Red 'RUNNING' and green 'STOPPED' indicator lights shall be installed on
each controller unit and on each local control station.
9.4
Emergency Shutdown
Emergency shutdown circuits shall be designed to fail safe. Loss of power
shall cause the process equipment to attain the safest status.
10.0
PROTECTION
10.1
General
A system of protective relays shall be installed to detect abnormal currents and
voltages and, when detected, automatically open the appropriate circuit
breakers to remove the faulty part from the network and leave the healthy
circuits intact.
The type of protective relays to be installed in the system shall generally be as
indicated in the following paragraphs of this specification. Alternative types of
relay or systems to meet abnormal requirements may be used after written
approval by COMPANY.
10.2
Coordination
The relays shall be coordinated to allow the relay nearest the faulty part of the
circuit to operate first.
Discrimination between relays shall be obtained by using time and current
grading.
The coordinating time interval between relays shall be a minimum of 0.3
seconds.
For long radial feeders with a number of circuit breakers in series the
application of distance relays or voltage restraint relays shall be considered to
improve coordination.
SPECS NO.
GS 400
REV. 3
10.3
PAG E
15 OF 18
Application
10.3.1 General
The following sections indicate the minimum requirements for
protection.
10.3.2 Diesel engine generators
Up to 100 KVA
- Phase overcurrent
- Phase overcurrent
- Reverse power
- Under voltage
Phase overcurrent
Ground overcurrent
Reverse power
Under voltage
Phase differential
- Phase differential
- Ground differential
ground fault)
- Phase overcurrent
- Ground overcurrent
- Reverse power
- Under voltage
- Phase differential
- Ground differential (restricted
ground fault)
- Phase overcurrent
- Phase unbalance
- Rotor ground fault
- Reverse power
- Assynchroneous operation
- Stator temperature
- Bearing temperature
- Excessive vibration
(restricted
SPECS NO.
GS 400
REV. 3
PAG E
16 OF 18
10.3.4 Transformers
Up to 100 KVA
- Phase overcurrent
- Phase overcurrent
- Ground overcurrent
Phase overcurrent
Ground overcurrent
High rate of rise of pressure
High oil temperature (alarm only)
Low oil level (alarm only)
Phase overcurrent
Ground overcurrent
Phase differential
High rate of rise of pressure
High oil temperature (alarm only)
Low oil level (alarm only)
- Phase overcurrent
- Ground overcurrent
- Phase overcurrent
- Ground overcurrent
- Phase overcurrent
- Ground overcurrent
- Phase differential
34.5 KV bus
- Phase overcurrent
- Ground overcurrent
- Phase differential
SPECS NO.
GS 400
REV. 3
- Phase Overcurrent
- Ground Overcurrent
34.5 KV
- Phase Overcurrent
- Ground Overcurrent
- Overvoltage
- Overload
- Single phasing
Above 50 HP to 200 HP
- Overload
- Single phasing
- Ground fault
Overload
Phase Unbalance
Ground Fault
High stator temperature
Excessive vibration
Current Unbalance
Overcurrent
Undercurrent
Phase reversal
Reverse rotation (backspin)
Voltage unbalance
PAG E
17 OF 18
SPECS NO.
GS 400
REV. 3
11.0
METERING
Metering of the power transmission and distribution system shall be as follows :
34.5 KV Bus Incomer
34.5 KV Feeder
Up to 13.8 KV Incomer
Generator up to 100 KW
PAG E
18 OF 18