MODBUS & BACNET Communication with ELNET PowerMeters

Last Update 20.4.2016


The ElNet Energy Powermeters and Analyzers are suporting communication over
MODBUS (RS485 and TCP/IP) and BACNET (IP and MSTP). The supported modes for each
model are described in the following table:

MODEL

MODBUS

BACNET

RS485

TCP/IP

MSTP

TCP/IP

GR\PQ

LT

LT TCP

MC

PIC

LTE

LTC

Table 1-1 Supported protocols

MODBUS Protocol
The ElNet Energy & Powermeters has a serial and TPC/IP interface ports allowing direct
interface with an external communication network supporting the MODBUS Protocol.
MODBUS is an Industry Standard, widely known and commonly used communications
protocol. Using MODBUS provides communication between a PC and up to 247 Powermeter
slaves on a common line- the PC being the master and the powermeters the slaves. The PC
initiates the transaction (either a query or broadcast) and the Powermeter/s responds.
Powermeters respond to the master PCs request, but will not iniate any transmission on its
own. The PC sends a single Query transaction and the Powermeter responds in a single response
frame and is capable of only one query and one response at a time

1.1 MODBUS Framing


1.1.1 RTU Transmission Mode
MODBUS uses the standard Remote Terminal Unit (RTU) transmission mode. RTU mode
sends data in 8-bit binary EVEN parity or 8-bit binary NO parity data format. For the ElNet
Energy & Powermeterto successfully communicate, choose one in the communication Set
Up.
Field

No. of bits

Start bit
Data bits
Parity
Stop it

1
8
1
1

Table 1-2 RTU Data Format

1.1.2 The RTU Frame Format


Query and response information is sent in frames. Each frame contains:
Address
Function (See Section 1.1.4 for descriptions of functions),
Data
Check.
Address Function
8 bits

Data

8 bits

Check

N * 8 bits 16 bits

Table 1-3 R T U Message Frame Format


If the receiving device (Powermeter) detects a time laps of five characters, then it will assume
the message is incomplete and will flush the frame. The device then assumes that the next byte
received will be an address. The maximum query and response message length is 256 bytes
includuing check characters.

1.1.3 Address Field


Each Powermeter is designated in a network system by a user assigned address. The Address
can be any number between 1 and 255. The Powermeter will only respond to its own
specifacally assigned address.

1.1.4 Function Field


2

The function field contains the code that tells the Powermeter what action to perform.
The ElNet Energy & Powermeteruses and responds to four standard Message Format
Functions.
Function 03
Function 04
Function 06
Function 16
Function
Function 03
Function 04
Function 06
Function 16

Meaning in MODBUS

Action

Read holding register

Obtain data from Powermeter


(Read register)
Read input register
Obtain data from Powermeter
(Read register)
Preset single register
Transmit data to Powermeter
(Write single register)
Preset multiple register Transmit data to Powermeter
(Write multiple register)
Table 1-4 Function Codes

1.1.5 Data Field


The Data field contains the body of the message and contains instructions from the PC master
to the Powermeter slave to perform a particuler action or respond to a query. The reply message
from the Powermeter will be information contained in one or more of its registers.

1.1.6 Check Field


The error check field contains the result of Cyclical Redundancy Check (CRC). The start of the
message is ignored in calculating the CRC.
For more detailed information on CRC, refer to the MODBUS Protocol Reference Guide.

1.2 Registers for ElNet Multimeter


The ElNet Energy & Powermeter is capable of supporting either Function 03 or Function
04 Message Format(See Table 1-3). In a reply to a query from the PC master for a reading from
a particular field, the response from the Powermeter can be either in Format 03 or Format 04 but
will depend on which Format the qeuery was originally sent.
The difference is significant because by using Function 03 the ElNet will only send the
INTEGER part of the field value requested and the PC master will only display the INTEGER
part of the field value.
Function 04 on the other hand, is capable of sending two separate halves of the full FLOAT
requested information (each half contained in a separate register). Then it is the task of the PC
master to merge the two halves into a full FLOAT reply. (For more detailed information See
IEEE Standard 754 Floating-Point).
3

E.G. 1 If the users PC master supports Function 03, then the reply will contain the INTEGER
part of the field only.
The PC master requests the Voltage from Line1, and the actual Voltage in that field is
230.5 Volts.
Function 03 will respond with the INTEGER only i.e.

230V.

E.G. 2 If the user PC master supports Function 04, then the reply will contain the information
stored in the two registers asssigned to that field and will contain the full, accurate reply.
The PC master requests the Voltage from Line1, and the actual Voltage in that field is
230.5 Volts.
Function 04 will respond with a composite reply of both register 1 and 2 giving the full
FLOAT value (in IEEE Format) from that field i.e.
230.5V.

When Writing The Clock Registers (151-157)


User must write special value (123) in register 99.

Bacnet Protocol
The ElNet powermeters supports Bacnet IP and MSTP communication modes (please check
page 1, table 1-1).
The information that can be read\write from the ElNets is:

Time and Date


Analog values

The BACNET "analog value" address numbers appear under the right column of the address
table.
The RS485 port can not support simultaneously MODBUS and BACNET MSTP, the default
mode of the RS485 communication port of the ElNet powermeters is set to be MODBUS, in
order to activate the BACNET MSTP mode the password 2244 must be used.

When using ElNet TXT (System B) User must add 2000 to item (4000 to Register)
(e.g Current Line 1 - System B = ModBus Register # 4013-14)
MODBUS

Field Description

Type

GR

Register

1-2
3-4
5-6
7-8
9-10
11-12
13-14
15-16
17-18
19-20
21-22
23-24
25-26
27-28
29-30
31-32
33-34
35-36
37-38
39-40
41-42

Voltage Line 1
Voltage Line 2
Voltage Line 3
Voltage between line 1 and Line 2
Voltage between line 2 and Line 3
Voltage between line 3 and Line 1
Current in Line 1
Current in Line 2
Current in Line 3
Active Power Line 1 (Watt)
Active Power Line 2 (Watt)
Active Power Line 3 (watt)
Combined Active Power Line 1+2 +3 (watt)
Apparent Power Line 1 (VA)
Apparent Power Line 2 (VA)
Apparent Power Line 3 (VA)
Combined Apparent Power Line 1+2+3
Reactive Power Line 1 (VAR)
Reactive Power Line 2 (VAR)
Reactive Power Line 3 (VAR)
Combined Reactive Power Line 1+2+3

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
6

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21

MODBUS

Field Description

Type

GR

67-68

Power Factor Line 1 (PF)


Power Factor Line 2 (PF)
Power Factor Line 3 (PF)
Combined Power Factor for Line 1+2+3
Frequency Line 1 (Hrz)
Frequency Line 2 (Hrz)
Frequency Line 3 (Hrz)
Current Neutral Line
Power Factor Line 1 (L & C)
Power Factor Line 2 (L & C)
Power Factor Line 3 (L & C)
Combined Power Factor for Line 1+2+3 (L &
C)
Total Current in Line 1+2+3

77-78
79-80
81-82
83-84
85-86
87-88
89-90
91-92
93-94

TOU (Taoz) rate


Active Total Energy (Wh)
Reactive Total Energy (VARh)
Apparent Total Energy (Vah)
Date Time (Win Format)
Time from 01 01 2000 in seconds
ADDRESS
BAUD RATE
PARITY

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R
R
R
R
R
R
R
R
R
R
R

UniArt \
BACnet
AV
22
23
24
25
26
27
28
29
30
31
32
33

34

R/W
R
R
R
R
R
R
R
R

39
40
41
42
43
44
45
46
47

Register

43-44
45-46
47-48
49-50
51-52
53-54
55-56
57-58
59-60
61-62
63-64
65-66

PQ

MODBUS

Field Description

Type

GR

Register

95-96
97-98
99-100
101-102
103-104
105-106
107-108
109-110
111-112
113-114
115-116
117-118
119-120
121-122
123-124
125-126
127-128
129-130
131-132
133-134
135-136
137-138
139-140
141-142

Current Transformer Ratio


Timed average Voltage
Timed average Current
Timed average Power
Timed avaerge Frequqncy
THD for Volts Line 1
THD for Volts Line 2
THD for Volts Line 3
THD for Current Line 1
THD for Current Line 2
THD for Current Line 3
Active Rate (1,2,3)
Active Energy Line 1 (W-Import)
Active Energy Line 2 (W-Import)
Active Energy Line 3 (W-Import)
Reactive Energy Line 1 (VAR-Import)
Reactive Energy Line 2 (VAR-Import)
Reactive Energy Line 3 (VAR-Import)
Apparant Energy Line 1 (VA-Import)
Apparant Energy Line 2 (VA-Import)
Apparant Energy Line 3 (VA-Import)
Active Energy Line 1 Rate 1 (Imp)
Active Energy Line 2 Rate 1 (Imp)
Active Energy Line 3 Rate 1 (Imp)

R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R/W
R/W
R/W
8

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71

MODBUS

Field Description

Type

GR

Register

143-144
145-146
147-148
149-150
151-152
153-154
155-156
157-158
159-160
161-162
163-164
165-166
167-168
169-170
171-172
173-174
175-176
177-178
179-180
181-182
183-184
185-186
187-188
189-190

Active Energy Line 1 Rate 2 (Imp)


Active Energy Line 2 Rate 2 (Imp)
Active Energy Line 3 Rate 2 (Imp)
Active Energy Line 1 Rate 3 (Imp)
Active Energy Line 2 Rate 3 (Imp)
Active Energy Line 3 Rate 3 (Imp)
Active Energy Line 1+2+3 Rate 1 (I)
Active Energy Line 1+2+3 Rate 2 (I)
Active Energy Line 1+2+3 Rate 3 (I)
Apparant Energy Line 1 Rate 1 (I)
Apparant Energy Line 2 Rate 1 (I)
Apparant Energy Line 3 Rate 1 (I)
Apparant Energy Line 1 Rate 2 (I)
Apparant Energy Line 2 Rate 2 (I)
Apparant Energy Line 3 Rate 2 (I)
Apparant Energy Line 1 Rate 3 (I)
Apparant Energy Line 2 Rate 3 (I)
Apparant Energy Line 3 Rate 3 (I)
Apparant Energy 1+2+3 Rate 1 (I)
Apparant Energy 1+2+3 Rate 2 (I)
Apparant Energy 1+2+3 Rate 3 (I)
Voltage Transformer Ratio
Epeom Revision
Demo Mode

R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R/W
R
R/W*
9

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

191-192
193-194
195-196
197-198
199-200

Configuration PassWord
Min. Current To Accumulate Energy
MuliMeter ID
User Function Mode (Technical)
Test Value 12.34

R/W
R/W
R
R/W
R

UniArt \
BACnet
AV
96
97
98
99
100

201-202
203-204
205-206
207-208
209-210
211-212
213-214
215-216
217-218
219-220
221-222
223-224
225-226
227-228
229-230
231-232
233-234
235-236

Demand KW Max (Watt)


Demand PF (KW)
Demand Date (KW)
Demand KVA (Watt)
Demand PF (KVA)
Demand Date (KVA)
Demand Current (A) L1
Demand Current (A) L2
Demand Current (A) L3
Demand Current (A) L1+L2+L3
Demand Current (A) L1 Date
Demand Current (A) L2 Date
Demand Current (A) L3 Date
Demand Current (A) L1+2+3 Date
Demand KVA (Last)
Demand KVAR (Last)
Clear All Current Demand
Demand KW (Last)

R
R
R
R
R
R
R/W*
R/W*
R/W*
R/W*
R
R
R
R
R
R
R/W
R

101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118

Register

10

Field Description

MODBUS

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

237-238

Min. Current For Display (0.1A)

R/W

UniArt \
BACnet
AV
119

241-242
243-244
245-246
247-248
249-250
251-252
253-254
255-256
257-258
259-260
261-262
263-264
265-266
267-268
269-270
271-272
273-274
275-276
277-278
279-280
281-282
283-284

PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R
R

121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142

Register

Power Factor
On Time
Off Time
Avarege Time (Minute)
Stages
Mode Of Operation
THD (Volt)
Capacitor #1 (KVAR)
Capacitor #2 (KVAR)
Capacitor #3 (KVAR)
Capacitor #4 (KVAR)
Capacitor #5 (KVAR)
Capacitor #6 (KVAR)
THD (Current)
Min. Voltage
PF Avarrage Time
Comb. Stayble Time
Hysteresis
% Voltage (VT) For OK
% Current (CT) To Stop
Capacitor #1 Status
Capacitor #2 Status

11

MODBUS

Field Description

Type

GR

PFC Capacitor #3 Status


PFC Capacitor #4 Status
PFC Capacitor #5 Status
PFC Capacitor #6 Status
Pulse Value (KW-IMP) Relay 1
Pulse Value (KW-EXP) Relay 2
Pulse Value (KQ-IMP) Relay 3
Pulse Duration (Seconds)
Clock : Seconds
Clock : Minutes
Clock : Hours
Clock : Week Day (1-7)
Clock : Day
Clock : Month
Clock : Year (20xx)
Run Time (Seconds With Current)
Day Time (Win Format)
Force Cpu To response in MC
Type Of Din 1
Type Of Din 2
Type Of Din 3
Type Of Din 4

333-334

K.Factor Current Line 1

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R
R
R
R/W
R/W
R/W
R/W
R/W*
R/W*
R/W*
R/W*
R/W*
R/W*
R/W*
R/W*
R
R/W
R/W*
R/W*
R/W*
R/W*

UniArt \
BACnet
AV
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164

167

Register

285-286
287-288
289-290
291-292
293-294
295-296
297-298
299-300
301-302
303-304
305-306
307-308
309-310
311-312
313-314
315-316
317-318
319-320
321-322
323-324
325-326
327-328

PQ

12

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

335-336

K.Factor Current Line 2

UniArt \
BACnet
AV
168

337-338

K.Factor Current Line 3

169

339-340
341-342
343-344
345-346
347-348
349-350
351-352
353-354
355-356
357-358
359-360
361-362
363-364
365-366
367-368
369-370
371-372

K.Factor Current Line 1+2+3


Din 1 Energy Total Rate 1
Din 2 Energy Total Rate 1
Din 3 Energy Total Rate 1
Din 4 Energy Total Rate 1
Din 1 Energy Total Rate 2
Din 2 Energy Total Rate 2
Din 3 Energy Total Rate 2
Din 4 Energy Total Rate 2
Din 1 Energy Total Rate 3
Din 2 Energy Total Rate 3
Din 3 Energy Total Rate 3
Din 4 Energy Total Rate 3
Din 1 Energy Total Rate 1+2+3
Din 2 Energy Total Rate 1+2+3
Din 3 Energy Total Rate 1+2+3
Din 4 Energy Total Rate 1+2+3

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186

379-380
381-382
383-384

Temprature Sensor
Digital In 1 - Status
Digital In 2 - Status

R/W*
R
R

190
191
192

Register

13

MODBUS

Field Description

Type

GR

Digital In 3 - Status
Digital In 4 - Status

395-396
397-398
399-400
401-402
403-404
405-406
407-408
409-410
411-412
413-414
415-416
417-418
419-420
421-422
423-424
425-426
427-428
429-430
431-432
433-434
435-436

Web Authentication (User=admin)


Fast Trend Cycle Time (Seconds)
History - Date
History Day
History Month
History - Year
History-Active Energy Line 1 Rate 1
History-Active Energy Line 2 Rate 1
History-Active Energy Line 3 Rate 1
History-Active Energy Line 1 Rate 2
History-Active Energy Line 2 Rate 2
History-Active Energy Line 3 Rate 2
History-Active Energy Line 1 Rate 3
History-Active Energy Line 2 Rate 3
History-Active Energy Line 3 Rate 3
History-ReActive Energy Ln 1Rate 1
History-ReActive Energy Ln 2Rate 1
History-ReActive Energy Ln 3Rate 1
History-ReActive Energy Ln 1Rate 2
History-ReActive Energy Ln 2Rate 2
History-ReActive Energy Ln 3Rate 2

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R

UniArt \
BACnet
AV
193
194

R/W
R/W
R/W
R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218

Register

385-386
387-388

PQ

14

MODBUS

Field Description

Type

GR

History-ReActive Energy Ln 1Rate 3


History-ReActive Energy Ln 2Rate 3
History-ReActive Energy Ln 3Rate 3
History-Din 1 Energy Rate 1
History-Din 2 Energy Rate 1
History-Din 3 Energy Rate 1
History-Din 4 Energy Rate 1
History-Din 1 Energy Rate 2
History-Din 2 Energy Rate 2
History-Din 3 Energy Rate 2
History-Din 4 Energy Rate 2
History-Din 1 Energy Rate 3
History-Din 2 Energy Rate 3
History-Din 3 Energy Rate 3
History-Din 4 Energy Rate 3

491-492
493-494
495-496
497-498
499-500
501-502
503-504
505-506

History Reading Date


Debug Counter 1
Debug Counter 2
Debug Counter 3
Debug Counter 4
Technical Calibration Value 1
Technical Calibration Value 2
Technical Calibration Value 3

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UniArt \
BACnet
AV
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233

R
R/W
R/W
R/W
R/W
R
R
R

246
247
248
249
250
251
252
253

Register

437-438
439-440
441-442
443-444
445-446
447-448
449-450
451-452
453-454
455-456
457-458
459-460
461-462
463-464
465-466

PQ

15

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

507-508
509-510
511-512
513-514

Technical Calibration Value 4


Float Format (0,1,2)
Compatibility Mode (0,130,170)
Technical Current Calibration

R
R/W
R/W
R/W

UniArt \
BACnet
AV
254
255
256
257

519-520
521-522
523-524
525-526
527-528
529-530
531-532
533-534

Start Time1 For Period Alarm


Stop Time1 For Period Alarm
High Power (KW) (Period)
Low Power (KW) (Period)
Time Table For Period Alarm High
Time Table For Period Alarm Low
Start2 Time For Period Alarm
Stop2 Time For Period Alarm

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

260
261
262
263
264
265
266
267

537-538
539-540
541-542
543-544
545-546
547-548
549-550
551-552
553-554
555-556

ReActive Energy Line 1 Rate 1 (Imp)


ReActive Energy Line 2 Rate 1 (Imp)
ReActive Energy Line 3 Rate 1 (Imp)
ReActive Energy Line 1 Rate 2 (Imp)
ReActive Energy Line 2 Rate 2 (Imp)
ReActive Energy Line 3 Rate 2 (Imp)
ReActive Energy Line 1 Rate 3 (Imp)
ReActive Energy Line 2 Rate 3 (Imp)
ReActive Energy Line 3 Rate 3 (Imp)
ReActive E. Line 1+2+3 Rate 1 (I)

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R

269
270
271
272
273
274
275
276
277
278

Register

16

MODBUS

Field Description

Type

GR

591-592
593-594
595-596

ReActive E. Line 1+2+3 Rate 2 (I)


ReActive E. Line 1+2+3 Rate 3 (I)
Virtual Pulse Value (KW) P-Total
Virtual Pulse Counter
Fix Value (Debug) 123.4
Float Order (0=LM),(1=ML)
ReActive E.Total In Capacitor Mode
ReActive E.Total In Non Capacitor Mode
Demand KVAR (Var)
Demand PF (KVAR)
Demand Date (KVAR)
Delay (MS) for response time (RS485)
Current Line 1 Opposite Error
Current Line 2 Opposite Error
Current Line 3 Opposite Error
Voltage Seq. Error
Reactive Energy Quadrant # 1 (kvarh)
W:Imp, Q:Imp
Reactive Energy Quadrant # 2 (kvarh)
W:Imp, Q:Exp
Reactive Energy Quadrant # 3 (kvarh)
W:Exp, Q:Imp
Reactive Energy Quadrant # 4 (kvarh)
W:Exp, Q:Exp

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R
R/W
R/W
R
R/W
R
R
R
R
R
R/W
R
R
R
R
R

UniArt \
BACnet
AV
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295

296

297

298

Register

557-558
559-560
561-562
563-564
565-566
567-568
569-570
571-572
573-574
575-576
577-578
579-580
581-582
583-584
585-586
587-588
589-590

PQ

17

Field Description

MODBUS

Type

GR

Register

601-602
603-604

1st Harmonics for Volts Line 1


2nd Harmonics for Volts Line 1

661-662
663-664
665-666
667-668

31st Harmonics for Volts Line 1


32nd Harmonics for Volts Line 1
1st Harmonics for Volts Line 2
2nd Harmonics for Volts Line 2

725-726
727-728
729-730
731-732

31st Harmonics for Volts Line 2


32nd Harmonics for Volts Line 2
1st Harmonic for Volts Line 3
2nd Harmonics for Volts Line 3

789-790
791-792
793-794
795-796

853-854
855-856

st

31 Harmonics for Vots Line 3


32nd Harmonics for Volts Line 3
1st Harmonics for Current Line 1
2nd Harmonics for Current Line 1

31st Harmonics for Current Line 1


32nd Harmonics for Current Line 1

R
R

R
R
R
R

R
R
R
R

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV

301
302

331
332
333
334

363
364
365
366

R
R
R
R

R
R
18

395
396
397
398

427
428

Field Description

MODBUS

Type

GR

Register

857-858
859-860

1st Harmonics for Current Line 2


2nd Harmonics for Current Line 2

917-918
919-920
921-922
923-924

31st Harmonics for Current line 2


32nd Harmonicsfor Current Line 2
1st Harmonics for Current Line 3
2nd Harmonics for Current Line 3

R
R

R
R
R
R

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
429
430

459
460
461
462

981-982
983-984

31st Harmonics for Current Line 3


32nd Harmonics for Current Line 3

R
R

993-994
995-996
997-998

Current Transformer Ratio (Line 1)


Current Transformer Ratio (Line 2)
Current Transformer Ratio (Line 3)

R/W
R/W
R/W

497
498
499

1001-2
1003-4
1005-6

User Alarm #1
User Alarm #2
User Alarm #3

R
R
R

501
502
503

R
R

627
628
629

1253-4
1255-6
1257-8

User Alarm #127


User Alarm #128

19

491
492

MODBUS

Field Description

Type

GR

Demand Synchronize Pulse


Demand Watt L1
Demand Watt L2
Demand Watt L3
Demand VAR L1
Demand VAR L2
Demand VAR L3
Demand VA L1
Demand VA L2
Demand VA L3
Demand Watt L1+L2+L3
Demand VAR L1+L2+L3
Demand VA L1+L2+L3
Demand Current (A) L1
Demand Current (A) L2
Demand Current (A) L3
Demand Current (A) L1+L2+L3

1293-94
1295-96
1297-98
1299-00
1301-02
1303-04

Displacement Power Factor Line 1 (CosF)


Displacement Power Factor Line 2 (CosF)
Displacement Power Factor Line 3 (CosF)
Long Wave Write Now !!
Long Wave Event (Before) - Seconds
Long Wave Event (Total) - Seconds

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UniArt \
BACnet
AV
630
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646

R
R
R
W
R/W
R/W

647
648
649
650
651
652

Register

1259-60
1261-62
1263-64
1265-66
1267-68
1269-70
1271-72
1273-74
1275-76
1277-78
1279-80
1281-82
1283-84
1285-86
1287-88
1289-90
1291-92

PQ

20

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

1305-06
1307-08

Current L1 High - Write Long Wave Event


Current L1 Hysteresis (Long Wave Event)

R/W
R/W

UniArt \
BACnet
AV
653
654

1313-14
1315-16
1317-18
1319-20
1321-22
1323-24
1325-26
1327-28
1329-30
1331-32
1333-34
1335-36
1337-38
1339-40
1341-42
1343-44
1345-46
1347-48
1349-50
1351-52
1353-54

Conn Type (0=STAR,1=DELTA)


PQ V.Nominal
PQ Enable (Active)
Active Energy Line 1 (Export)
Active Energy Line 2 (Export)
Active Energy Line 3 (Export)
Reactive Energy Line 1 (Export)
Reactive Energy Line 2 (Export)
Reactive Energy Line 3 (Export)
Apparant Energy Line 1 (Export)
Apparant Energy Line 2 (Export)
Apparant Energy Line 3 (Export)
Active Energy Line 1 Rate 1 (Exp)
Active Energy Line 2 Rate 1 (Exp)
Active Energy Line 3 Rate 1 (Exp)
Active Energy Line 1 Rate 2 (Exp)
Active Energy Line 2 Rate 2 (Exp)
Active Energy Line 3 Rate 2 (Exp)
Active Energy Line 1 Rate 3 (Exp)
Active Energy Line 2 Rate 3 (Exp)
Active Energy Line 3 Rate 3 (Exp)

R/W
R/W
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

657
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677

Register

21

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

1355-56
1357-58
1359-60
1361-62
1363-64
1365-66
1367-68
1369-70
1371-72
1373-74
1375-76
1377-78
1379-80
1381-82
1383-84
1385-86
1387-88
1389-90

Active Energy Line 1+2+3 Rate 1 (E)


Active Energy Line 1+2+3 Rate 2 (E)
Active Energy Line 1+2+3 Rate 3 (E)
Apparant Energy Line 1 Rate 1 (E)
Apparant Energy Line 2 Rate 1 (E)
Apparant Energy Line 3 Rate 1 (E)
Apparant Energy Line 1 Rate 2 (E)
Apparant Energy Line 2 Rate 2 (E)
Apparant Energy Line 3 Rate 2 (E)
Apparant Energy Line 1 Rate 3 (E)
Apparant Energy Line 2 Rate 3 (E)
Apparant Energy Line 3 Rate 3 (E)
Apparant Energy 1+2+3 Rate 1 (E)
Apparant Energy 1+2+3 Rate 2 (E)
Apparant Energy 1+2+3 Rate 3 (E)
Active Energy (Export)
Reactive Energy (Export)
Apparant Energy (Export)

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UniArt \
BACnet
AV
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695

1393-94
1395-96
1397-98

Energy Flow Line #1 (1=Export)


Energy Flow Line #2 (1=Export)
Energy Flow Line #3 (1=Export)

R
R
R

697
698
699

1401-02

BacNet MSTP Max Master

R/W

701

Register

22

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

1403-04
1405-06
1407-08

BacNet MSTP Instance


BacNet MSTP MAC
BacNet MSTP Slave Mode

R/W
R/W
R/W

UniArt \
BACnet
AV
702
703
704

1419-20
1421-22
1423-24

PQ Level 0.95
PQ Level 1.05
PQ Level 1.10

R/W
R/W
R/W

710
711
712

1429-30
1431-32
1433-34
1435-36
1437-38
1439-40

Crest Factor Voltage L1


Crest Factor Voltage L2
Crest Factor Voltage L3
Crest Factor Current L1
Crest Factor Current L2
Crest Factor Current L3

R
R
R
R
R
R

715
716
717
718
719
720

3841-42
3843-44

Summer Clock DTE #1 (Sec)


Summer Clock DTE #2 (Sec)

R/W
R/W

1921
1922

R/W
R/W
R/W

1940
1941
1942

Register

3879-80
3881-82
3883-84

Summer Clock DTE #20 (Sec)


Summer Clock #1 Minute To Add
Summer Clock #2 Minute To Add

23

Field Description

MODBUS

Type

GR

Summer Clock #20 Minute To Add


Summer Clock DTE #1 (Hour)
Summer Clock DTE #2 (Hour)

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R/W
R/W
R/W

UniArt \
BACnet
AV
1960
1961
1962

Register

3919-20
3921-22
3923-24

PQ

3959-60

Summer Clock DTE #20 (Hour)

R/W

1980

3961-62
3963-64
3965-66
3967-68
3969-70
3971-72
3973-74
3975-76
3977-78
3979-80

PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC
PFC

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

1981
1982
1983
1984
1985
1986
1987
1988
1989
1990

3981-82
3983-84
3985-86
3985-86
3987-88

ModBus/IP Port
HTTP Port
UDP Extended Port
High PF Limit
High PF Limit Delay (sec)

R/W
R/W
R/W
R/W
R/W

1991
1992
1993
1993
1994

Capacitor #7 (KVAR)
Capacitor #8 (KVAR)
Capacitor #9 (KVAR)
Capacitor #10 (KVAR)
Capacitor #11 (KVAR)
Capacitor #12 (KVAR)
Capacitor #13 (KVAR)
Capacitor #14 (KVAR)
Capacitor #15 (KVAR)
Capacitor #16 (KVAR)

24

MODBUS

Field Description

Type

GR

4071-72
4073-74
4075-76

4143-44
4145-46
4147-48

Active Energy (L123)- Month 1 -KWh


Active Energy (L123)- Month 2-KWh

Active Energy(L123)- Month 36-KWh


Month # 1 (1-12) (For Item 2001)
Month # 2 (1-12) (For Item 2002)

Month #36 (1-12) (For Item 2036)


Year # 1 (2001-99) (Item 2001)
Year # 2 (2001-99) (Item 2002)

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R

UniArt \
BACnet
AV
2001
2002

R
R
R

2036
2037
2038

R
R
R

2072
2073
2074

2108

Register

4001-2
4003-4

PQ

4215-16

Year #36 (2001-99) (Item 2036)

4239-40
4241-42
4243-44
4245-46
4247-48
4249-50
4251-52

Keyboard Lock Status


Comm.Alarm High Current Value
Comm.Alarm High Voltage Value
Comm.Alarm Low Voltage Value
Comm.Alarm Low PF Value
Comm.Alarm High V.THD Value
Comm.Alarm High I.THD Value

R/W
R/W
R/W
R/W
R/W
R/W
R/W

2120
2121
2122
2123
2124
2125
2126

4261-62

Comm.Alarm High Current DelayOn

R/W

2131
25

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

4263-64
4265-66
4267-68
4269-70
4271-72

Comm.Alarm High Voltage DelayOn


Comm.Alarm Low Voltage DelayOn
Comm.Alarm Low PF DelayOn
Comm.Alarm High V.THD DelayOn
Comm.Alarm High I.THD DelayOn

R/W
R/W
R/W
R/W
R/W

UniArt \
BACnet
AV
2132
2133
2134
2135
2136

4281-82
4283-84
4285-86
4287-88
4289-90
4291-92
4293-94
4295-96
4297-98
4299-300
4301-02
4303-04
4305-06
4307-08
4309-10
4311-12
4313-14

Demand THD Current (A) L1


Demand THD Current (A) L2
Demand THD Current (A) L3
Demand THD Current (A) L1 | L2 | l3
Demand THD Current (A) L1 - Date
Demand THD Current (A) L2 - Date
Demand THD Current (A) L3 - Date
Demand THD Current (A) L123 - Date
Demand THD Voltage (A) L1
Demand THD Voltage (A) L2
Demand THD Voltage (A) L3
Demand THD Voltage (A) L1 | L2 | l3
Demand THD Voltage (A) L1 - Date
Demand THD Voltage (A) L2 - Date
Demand THD Voltage (A) L3 - Date
Demand THD Voltage (A) L123 - Date
Clear All THD Demand

R/W*
R/W*
R/W*
R/W*
R
R
R
R
R/W*
R/W*
R/W*
R/W*
R
R
R
R
R/W

2141
2142
2143
2144
2145
2146
2147
2148
2149
2150
2151
2152
2153
2154
2155
2156
2157

Register

26

MODBUS

Field Description

Type

GR

Register

4399-00
4401-02
4403-04
4405-06
4407-08
4409-10
4411-12
4413-14
4415-16
4417-18
4419-20
4421-22
4423-24
4425-26
4427-28
4429-30
4431-32
4433-34
4435-36
4437-38
4439-40
4441-42
4443-44

Alarm- High Voltage L1


Alarm- High Voltage L2
Alarm- High Voltage L3
Alarm- High Voltage L1-2
Alarm- High Voltage L2-3
Alarm- High Voltage L3-1
Alarm- High Current L1
Alarm- High Current L2
Alarm- High Current L3
Alarm- High Current L0
Alarm- High PF L1
Alarm- High PF L2
Alarm- High PF L3
Alarm- High PF Total
Alarm- High Voltage THD L1
Alarm- High Voltage THD L2
Alarm- High Voltage THD L3
Alarm- High Current THD L1
Alarm- High Current THD L2
Alarm- High Current THD L3
Alarm- High Current THD L0
Alarm- High Current TDD L1
Alarm- High Current TDD L2

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
2200
2201
2202
2203
2204
2205
2206
2207
2208
2209
2210
2211
2212
2213
2214
2215
2216
2217
2218
2219
2220
2221
2222

27

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

4445-46
4447-48
4449-50
4451-52
4453-54
4455-56
4457-58
4459-60
4461-62
4463-64
4465-66
4467-68
4469-70
4471-72
4473-74
4475-76
4477-78
4479-80
4481-82

Alarm- High Current TDD L3


Alarm- High Current TDD L0
Alarm High KW L1
Alarm High KW L2
Alarm High KW L3
Alarm High KW Total 1
Alarm High KW Total 2
Alarm High UnBalanced Current
Alarm High UnBalanced Voltage
Alarm High Freq - L1
Alarm High Freq L2
Alarm High Freq L3
Alarm - High KVA Total
Alarm - High KVAR Total
Alarm- High CosF L1
Alarm- High CosF L2
Alarm- High CosF L3
Alarm- High Demand Total KW
Alarm High Demad Total Current

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

UniArt \
BACnet
AV
2223
2224
2225
2226
2227
2228
2229
2230
2231
2232
2233
2234
2235
2236
2237
2238
2239
2240
2241

4599-00
4601-02
4603-04
4605-06

Alarm- Low Voltage L1


Alarm- Low Voltage L2
Alarm- Low Voltage L3
Alarm- Low Voltage L1-2

R/W
R/W
R/W
R/W

2300
2301
2302
2303

Register

28

MODBUS

Field Description

Type

GR

Register

4607-08
4609-10
4611-12
4613-14
4615-16
4617-18
4619-20
4621-22
4623-24
4625-26
4627-28
4629-30
4631-32
4633-34
4635-36
4637-38
4639-40
4641-42
4643-44
4645-46
4647-48
4649-50
4651-52
4653-54

Alarm- Low Voltage L2-3


Alarm- Low Voltage L3-1
Alarm- Low Current L1
Alarm- Low Current L2
Alarm- Low Current L3
Alarm- Low Current L0
Alarm- Low PF L1
Alarm- Low PF L2
Alarm- Low PF L3
Alarm- Low PF Total
Alarm- Low Voltage THD L1
Alarm- Low Voltage THD L2
Alarm- Low Voltage THD L3
Alarm- Low Current THD L1
Alarm- Low Current THD L2
Alarm- Low Current THD L3
Alarm- Low Current THD L0
Alarm- Low Current TDD L1
Alarm- Low Current TDD L2
Alarm- Low Current TDD L3
Alarm- Low Current TDD L0
Alarm- Low KW L1
Alarm Low KW L2
Alarm Low KW L3

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
29

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
2304
2305
2306
2307
2308
2309
2310
2311
2312
2313
2314
2315
2316
2317
2318
2319
2320
2321
2322
2323
2324
2325
2326
2327

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

4655-56
4657-58
4859-60
4861-62
4863-64
4865-66
4867-68
4869-70
4871-72
4873-74
4875-76
4877-78
4879-80
4881-82

Alarm Low KW Total 1


Alarm Low KW Total 2
Alarm Low UnBalanced Current
Alarm Low UnBalanced Voltage
Alarm Low Freq - L1
Alarm Low Freq L2
Alarm Low Freq L3
Alarm - Low KVA Total
Alarm - Low KVAR Total
Alarm - Low CosF L1
Alarm - Low CosF L2
Alarm - Low CosF L3
Alarm - Low Demand Total KW
Alarm Low Demad Total Current

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

UniArt \
BACnet
AV
2328
2329
2330
2331
2332
2333
2334
2335
2336
2337
2338
2339
2340
2341

4799-00
4801-02
4803-04
4805-06
4807-08
4809-10
4811-12
4813-14
4815-16

Alarm- Relay High Voltage L1


Alarm- Relay High Voltage L2
Alarm- Relay High Voltage L3
Alarm- Relay High Voltage L1-2
Alarm- Relay High Voltage L2-3
Alarm- Relay High Voltage L3-1
Alarm- Relay High Current L1
Alarm- Relay High Current L2
Alarm- Relay High Current L3

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

2400
2401
2402
2403
2404
2405
2406
2407
2408

Register

30

MODBUS

Field Description

Type

GR

Register

4817-18
4819-20
4821-22
4823-24
4825-26
4827-28
4829-30
4831-32
4833-34
4835-36
4837-38
4839-40
4841-42
4843-44
4845-46
4847-48
4849-50
4851-52
4853-54
4855-56
4857-58
4859-60
4861-62
4863-64

Alarm- Relay High Current L0


Alarm- Relay High PF L1
Alarm- Relay High PF L2
Alarm- Relay High PF L3
Alarm- Relay High PF Total
Alarm- Relay High Voltage THD L1
Alarm- Relay High Voltage THD L2
Alarm- Relay High Voltage THD L3
Alarm- Relay High Current THD L1
Alarm- Relay High Current THD L2
Alarm- Relay High Current THD L3
Alarm- Relay High Current THD L0
Alarm- Relay High Current TDD L1
Alarm- Relay High Current TDD L2
Alarm- Relay High Current TDD L3
Alarm- Relay High Current TDD L0
Alarm- Relay High KW L1
Alarm Relay High KW L2
Alarm Relay High KW L3
Alarm Relay High KW Total 1
Alarm Relay High KW Total 2
Alarm Relay High UnBalanced Current
Alarm Relay High UnBalanced Voltage
Alarm Relay High Freq - L1

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
31

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
2409
2410
2411
2412
2413
2414
2415
2416
2417
2418
2419
2420
2421
2422
2423
2424
2425
2426
2427
2428
2429
2430
2431
2432

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

4865-66
4867-68
4869-70
4871-72
4873-74
4875-76
4877-78
4879-80
4881-82

Alarm Relay High Freq L2


Alarm Relay High Freq L3
Alarm - Relay High KVA Total
Alarm - Relay High KVAR Total
Alarm - Relay High CosF L1
Alarm - Relay High CosF L2
Alarm - Relay High CosF L3
Alarm - Relay High Demand Total KW
Alarm Relay High Demad Total Current

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

UniArt \
BACnet
AV
2433
2434
2435
2436
2437
2438
2439
2440
2441

4999-00
5001-02
5003-04
5005-06
5007-08
5009-10
5011-12
5013-14
5015-16
5017-18
5019-20
5021-22
5023-24
5025-26

Alarm- Relay Low Voltage L1


Alarm- Relay Low Voltage L2
Alarm- Relay Low Voltage L3
Alarm- Relay Low Voltage L1-2
Alarm- Relay Low Voltage L2-3
Alarm- Relay Low Voltage L3-1
Alarm- Relay Low Current L1
Alarm- Relay Low Current L2
Alarm- Relay Low Current L3
Alarm- Relay Low Current L0
Alarm- Relay Low PF L1
Alarm- Relay Low PF L2
Alarm- Relay Low PF L3
Alarm- Relay Low PF Total

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

2500
2501
2502
2503
2504
2505
2506
2507
2508
2509
2510
2511
2512
2513

Register

32

MODBUS

Field Description

Type

GR

Register

5027-28
5029-30
5031-32
5033-34
5035-36
5037-38
5039-40
5041-42
5043-44
5045-46
5047-48
5049-50
5051-52
5053-54
5055-56
5057-58
5059-60
5061-62
5063-64
5065-66
5067-68
5069-70
5071-72
5073-74

Alarm- Relay Low Voltage THD L1


Alarm- Relay Low Voltage THD L2
Alarm- Relay Low Voltage THD L3
Alarm- Relay Low Current THD L1
Alarm- Relay Low Current THD L2
Alarm- Relay Low Current THD L3
Alarm- Relay Low Current THD L0
Alarm- Relay Low Current TDD L1
Alarm- Relay Low Current TDD L2
Alarm- Relay Low Current TDD L3
Alarm- Relay Low Current TDD L0
Alarm- Relay Low KW L1
Alarm Relay Low KW L2
Alarm Relay Low KW L3
Alarm Relay Low KW Total 1
Alarm Relay Low KW Total 2
Alarm Relay Low UnBalanced Current
Alarm Relay Low UnBalanced Voltage
Alarm Relay Low Freq - L1
Alarm Relay Low Freq L2
Alarm Relay Low Freq L3
Alarm - Relay Low KVA Total
Alarm - Relay Low KVAR Total
Alarm - Relay Low CosF L1

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
33

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
2514
2515
2516
2517
2518
2519
2520
2521
2522
2523
2524
2525
2526
2527
2528
2529
2530
2531
2532
2533
2534
2535
2536
2537

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

5075-76
5077-78
5079-80
5081-82

Alarm - Relay Low CosF L2


Alarm - Relay Low CosF L3
Alarm - Relay Low Demand Total KW
Alarm Relay Low Demad Total Current

R/W
R/W
R/W
R/W

UniArt \
BACnet
AV
2538
2539
2540
2541

5199-00
5201-02
5203-04
5205-06
5207-08
5209-10
5211-12
5213-14
5215-16
5217-18
5219-20
5221-22
5223-24
5225-26
5227-28
5229-30
5231-32
5233-34
5235-36

Alarm- T.Tbl Voltage L1


Alarm- T.Tbl Voltage L2
Alarm- T.Tbl Voltage L3
Alarm- T.Tbl Voltage L1-2
Alarm- T.Tbl Voltage L2-3
Alarm- T.Tbl Voltage L3-1
Alarm- T.Tbl Current L1
Alarm- T.Tbl Current L2
Alarm- T.Tbl Current L3
Alarm- T.Tbl Current L0
Alarm- T.Tbl PF L1
Alarm- T.Tbl PF L2
Alarm- T.Tbl PF L3
Alarm- T.Tbl PF Total
Alarm- T.Tbl Voltage THD L1
Alarm- T.Tbl Voltage THD L2
Alarm- T.Tbl Voltage THD L3
Alarm- T.Tbl Current THD L1
Alarm- T.Tbl Current THD L2

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

2600
2601
2602
2603
2604
2605
2606
2607
2608
2609
2610
2611
2612
2613
2614
2615
2616
2617
2618

Register

34

MODBUS

Field Description

Type

GR

Register

5237-38
5239-40
5241-42
5243-44
5245-46
5247-48
5249-50
5251-52
5253-54
5255-56
5257-58
5259-60
5261-62
5263-64
5265-66
5267-68
5269-70
5271-72
5273-74
5275-76
5277-78
5279-80
5281-82

Alarm- T.Tbl Current THD L3


Alarm- T.Tbl Current THD L0
Alarm- T.Tbl Current TDD L1
Alarm- T.Tbl Current TDD L2
Alarm- T.Tbl Current TDD L3
Alarm- T.Tbl Current TDD L0
Alarm- T.Tbl KW L1
Alarm T.Tbl KW L2
Alarm T.Tbl KW L3
Alarm T.Tbl KW Total 1
Alarm T.Tbl KW Total 2
Alarm T.Tbl UnBalanced Current
Alarm T.Tbl UnBalanced Voltage
Alarm T.Tbl Freq - L1
Alarm T.Tbl Freq L2
Alarm T.Tbl Freq L3
Alarm - T.Tbl KVA Total
Alarm - T.Tbl KVAR Total
Alarm - T.Tbl CosF L1
Alarm - T.Tbl CosF L2
Alarm - T.Tbl CosF L3
Alarm - T.Tbl Demand Total KW
Alarm T.Tbl Demad Total Current

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
35

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
2619
2620
2621
2622
2623
2624
2625
2626
2627
2628
2629
2630
2631
2632
2633
2634
2635
2636
2637
2638
2639
2640
2641

MODBUS

Field Description

Type

GR

Alarm- T.Tbl #1

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R/W

UniArt \
BACnet
AV
2701

Register

5401-2

PQ

5431-32

Alarm- T.Tbl #16

R/W

2716

5601-2
5603-4
5605-6
5607-8
5609-10
5611-12
5613-14
5615-16
5617-18
5619-20
5621-22
5623-24
5625-26
5627-28
5629-30
5631-32
5633-34
5635-36
5637-38

TOU- custom (Dbl) Low - From


TOU- custom (Dbl) Low - To
TOU- custom (Dbl) Low - From
TOU- custom (Dbl) Low - To
TOU- custom (Dbl) Med - From
TOU- custom (Dbl) Med - To
TOU- custom (Dbl) Med - From
TOU- custom (Dbl) Med - To
TOU- custom (Dbl) High - From
TOU- custom (Dbl) High - To
TOU- custom (Dbl) High - From
TOU- custom (Dbl) High - To
TOU- Uruguay (Trpl) Low - From
TOU- Uruguay (Trpl) Low - To
TOU- Uruguay (Trpl) Low - From
TOU- Uruguay (Trpl) Low - To
TOU- Uruguay (Trpl) Med - From
TOU- Uruguay (Trpl) Med - To
TOU- Uruguay (Trpl) Med - From

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

2801
2802
2803
2804
2805
2806
2807
2808
2809
2810
2811
2812
2813
2814
2815
2816
2817
2818
2819
36

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

5639-40
5641-42
5643-44
5645-46
5647-48

TOU- Uruguay (Trpl) Med - To


TOU- Uruguay (Trpl) High - From
TOU- Uruguay (Trpl) High - To
TOU- Uruguay (Trpl) High - From
TOU- Uruguay (Trpl) High - To

R/W
R/W
R/W
R/W
R/W

UniArt \
BACnet
AV
2820
2821
2822
2823
2824

6001-2
6003-4
6005-6
6007-8
6009-10
6011-12

Relay # 1 Force Start Time


Relay # 1 Force Stop Time
Relay # 1 Force Start Time
Relay # 1 Force Stop Time
Relay # 1 Force Start Time
Relay # 1 Force Stop Time

R/W
R/W
R/W
R/W
R/W
R/W

3001
3002
3003
3004
3005
3006

6017-18
6019-20
6021-22
6023-24
6025-26
6027-28

Relay # 2 Force Start Time


Relay # 2 Force Stop Time
Relay # 2 Force Start Time
Relay # 2 Force Stop Time
Relay # 2 Force Start Time
Relay # 2 Force Stop Time

R/W
R/W
R/W
R/W
R/W
R/W

3009
3010
3011
3012
3013
3014

6033-34
6035-36
6037-38
6039-40

Relay # 3 Force Start Time


Relay # 3 Force Stop Time
Relay # 3 Force Start Time
Relay # 3 Force Stop Time

R/W
R/W
R/W
R/W

3017
3018
3019
3020

Register

37

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

6041-42
6043-44

Relay # 3 Force Start Time


Relay # 3 Force Stop Time

R/W
R/W

UniArt \
BACnet
AV
3021
3022

6049-50

Flg To Clear SST At MidNight

R/W

3025

6061-62
6063-64
6065-66
6067-68
6069-70
6071-72

Digital Out #1 (Status)


Digital Out #2 (Status)
Digital Out #3 (Status)
Digital Out #4 (Status)
Digital Out #5 (Status)
Digital Out #6 (Status)

R
R
R
R
R
R

3031
3032
3033
3034
3035
3036

6201-2
6203-4

TOU January Type


TOU February Type

R/W*
R/W*

3101
3102

R/W*
R/W*

3112
3113

R/W*

3328

R
R

3400
3401

Register

6223-24
6225-26

TOU December Type


TOU Hour Details

6655-56

TOU Hour Details

6799-0
6801-2

Active Total Energy (KWh)


Reactive Total Energy (KVARh)

38

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

Apparent Total Energy (KVah)


Active Energy Line 1 (KWh-Import)
Active Energy Line 2 (KWh-Import)
Active Energy Line 3 (KWh-Import)
Reactive Energy Line 1 (KVARh-Import)
Reactive Energy Line 2 (KVARh-Import)
Reactive Energy Line 3 (KVARh-Import)
Apparant Energy Line 1 (KVAh-Import)
Apparant Energy Line 2 (KVAh-Import)
Apparant Energy Line 3 (KVAh-Import)
Active Energy Line 1 Rate 1 KWh (Imp)
Active Energy Line 2 Rate 1 KWh (Imp)
Active Energy Line 3 Rate 1 KWh (Imp)
Active Energy Line 1 Rate 2 KWh (Imp)
Active Energy Line 2 Rate 2 KWh (Imp)
Active Energy Line 3 Rate 2 KWh (Imp)
Active Energy Line 1 Rate 3 KWh (Imp)
Active Energy Line 2 Rate 3 KWh (Imp)
Active Energy Line 3 Rate 3 KWh (Imp)
Active Energy Line 1+2+3 Rate 1 KWh (I)

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UniArt \
BACnet
AV
3402
3403
3404
3405
3406
3407
3408
3409
3410
3411
3412
3413
3414
3415
3416
3417
3418
3419
3420
3421

6843-44

Active Energy Line 1+2+3 Rate 2 KWh (I)

3422

6845-46

Active Energy Line 1+2+3 Rate 3 KWh (I)

3423

Register

6803-4
6805-6
6807-8
6809-10
6811-12
6813-14
6815-16
6817-18
6819-20
6821-22
6823-24
6825-26
6827-28
6829-30
6831-32
6833-34
6835-36
6837-38
6839-40
6841-42

39

MODBUS

Field Description

Type

GR

6849-50
6851-52
6853-54
6855-56
6857-58
6859-60
6861-62
6863-64
6865-66
6867-68
6869-70
6871-72
6873-74
6875-76
6875-76

ReActive Energy Line 1 Rate 1 KVARh


(Imp)
ReActive Energy Line 2 Rate 1 KVARh
(Imp)
ReActive Energy Line 3 Rate 1 KVARh
(Imp)
ReActive Energy Line 1 Rate 2 KVARh
(Imp)
ReActive Energy Line 2 Rate 2 KVARh
(Imp)
ReActive Energy Line 3 Rate 2 KVARh
(Imp)
ReActive Energy Line 1 Rate 3 KVARh
(Imp)
ReActive Energy Line 2 Rate 3 KVARh
(Imp)
ReActive Energy Line 3 Rate 3 KVARh
(Imp)
ReActive E. Line 1+2+3 Rate 1 KVARh (I)
ReActive E. Line 1+2+3 Rate 2 KVARh (I)
ReActive E. Line 1+2+3 Rate 3 KVARh (I)
Combined Active Power Line 1+2 +3 (KW)
Combined Active Power 1+2 +3 (MW)
Combined ReActive Power 1+2 +3 (MVAR)
Combined ReActive Power 1+2 +3 (KVAR)

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
3424

3425

3426

3427

3428

3429

3430

3431

3432

R
R
R
R
R
R
R

3433
3434
3435

Register

6847-48

PQ

3436
3437
3438
3439
40

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

6879-80
6881-82
6883-84

Active Total Energy (Wh) -Meter B


Reactive Total Energy (VARh) -Meter B
Apparent Total Energy (Vah) -Meter B

R
R
R

UniArt \
BACnet
AV
3440
3441
3442

6885-86
6887-88

Combined Apparant Power 1+2 +3 (KVA)


Combined Apparant Power 1+2 +3 (MVA)

R
R

3443
3444

6891-92
6893-94
6895-96

Active Total Energy (Wh) Alternate Meter


Reactive Total Energy (VARh) -Alternate Meter
Apparent Total Energy (Vah) - Alternate Meter

R
R
R

3446
3447
3448

6899-00
6901-02
6903-04
6905-06
6907-08
6909-10
6911-12
6913-14
6915-16

Active Energy L1 Rate 1 (Im)- Alternate Meter


Active Energy L2 Rate 1 (Im)- Alternate Meter
Active Energy L3 Rate 1 (Im)- Alternate Meter
Active Energy L1 Rate 2 (Im)- Alternate Meter
Active Energy L2 Rate 2 (Im)- Alternate Meter
Active Energy L3 Rate 2 (Im)- Alternate Meter
Active Energy L1 Rate 3 (Im)- Alternate Meter
Active Energy L2 Rate 3 (Im)- Alternate Meter
Active Energy L3 Rate 3 (Im)- Alternate Meter

R
R
R
R
R
R
R
R
R

3450
3451
3452
3453
3454
3455
3456
3457
3458

6919-20
6921-22
6923-24

Active Energy Line 1 (W-Import) -Meter B


Active Energy Line 2 (W-Import) -Meter B
Active Energy Line 3 (W-Import) -Meter B

R
R
R

3460
3461
3462

Register

41

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

6925-26
6927-28

Reactive Energy Line 1 (VAR-Import) -Meter B


Reactive Energy Line 2 (VAR-Import) -Meter B

R
R

UniArt \
BACnet
AV
3463
3464

6929-30
6931-32
6933-34
6935-36
6937-38
6939-40
6941-42
6943-44
6945-46
6947-48
6949-50
6951-52
6953-54
6955-56
6957-58
6959-60
6961-62
6963-64
6965-66
6967-68
6969-70

Reactive Energy Line 3 (VAR-Import) -Meter B


Apparant Energy Line 1 (VA-Import) -Meter B
Apparant Energy Line 2 (VA-Import) -Meter B
Apparant Energy Line 3 (VA-Import) -Meter B
Active Energy Line 1 Rate 1 (Imp) -Meter B
Active Energy Line 2 Rate 1 (Imp) -Meter B
Active Energy Line 3 Rate 1 (Imp) -Meter B
Active Energy Line 1 Rate 2 (Imp) -Meter B
Active Energy Line 2 Rate 2 (Imp) -Meter B
Active Energy Line 3 Rate 2 (Imp) -Meter B
Active Energy Line 1 Rate 3 (Imp) -Meter B
Active Energy Line 2 Rate 3 (Imp) -Meter B
Active Energy Line 3 Rate 3 (Imp) -Meter B
Active Power Line 1 (KW)
Active Power Line 2 (KW)
Active Power Line 3 (KW)
ReActive Power Line 1 (KVAR)
ReActive Power Line 2 (KVAR)
ReActive Power Line 3 (KVAR)
Apparent Power Line 1 (KVA)
Apparent Power Line 2 (KVA)

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

3465
3466
3467
3468
3469
3470
3471
3472
3473
3474
3475
3476
3477
3478
3479
3480
3481
3482
3483
3484
3485

Register

42

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

6971-72

Apparent Power Line 3 (KVA)

UniArt \
BACnet
AV
3486

6979-80
6981-82
6983-84
6985-86
6987-88
6989-90
6991-92
6993-94
6995-96

ReActive En. L1 Rate 1 (Im)- Alternate Meter


ReActive En. L2 Rate 1 (Im)- Alternate Meter
ReActive En. L3 Rate 1 (Im)- Alternate Meter
ReActive En. L1 Rate 2 (Im)- Alternate Meter
ReActive En. L2 Rate 2 (Im)- Alternate Meter
ReActive En. L3 Rate 2 (Im)- Alternate Meter
ReActive En. L1 Rate 3 (Im)- Alternate Meter
ReActive En. L2 Rate 3 (Im)- Alternate Meter
ReActive En. L3 Rate 3 (Im)- Alternate Meter

R
R
R
R
R
R
R
R
R

3490
3491
3492
3493
3494
3495
3496
3497
3498

7001-2
7003-4

33 Harmonics for Volts Line 1


34 Harmonics for Volts Line 1

R
R

3501
3502

R
R
R
R

3531
3532
3533
3534

R
R

3563
3564

Register

7061-62
7063-64
7065-66
7067-68

7125-26
7127-28

63 Harmonics for Volts Line 1


64 Harmonics for Volts Line 1
33 Harmonics for Volts Line 2
34 Harmonics for Volts Line 2

63 Harmonics for Volts Line 2


64 Harmonics for Volts Line 2

43

MODBUS

Field Description

Type

GR

7189-90
7191-92
7193-94
7195-96

7253-54
7255-56
7257-58
7259-60

7317-18
7319-20
7321-22
7323-24

7381-82
7383-84

33 Harmonic for Volts Line 3


34 Harmonics for Volts Line 3

63 Harmonics for Vots Line 3


64 Harmonics for Volts Line 3
33 Harmonics for Current Line 1
34 Harmonics for Current Line 1

63 Harmonics for Current Line 1


64 Harmonics for Current Line 1
33 Harmonics for Current Line 2
34 Harmonics for Current Line 2

63 Harmonics for Current line 2


64 Harmonicsfor Current Line 2
33 Harmonics for Current Line 3
34 Harmonics for Current Line 3

63 Harmonics for Current Line 3


64 Harmonics for Current Line 3

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R

UniArt \
BACnet
AV
3565
3566

R
R
R
R

3595
3596
3597
3598

R
R
R
R

3627
3628
3629
3630

R
R
R
R

3659
3660
3661
3662

R
R

3691
3692

Register

7129-30
7131-32

PQ

44

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R
R
R
R

UniArt \
BACnet
AV
3695
3696
3697
3698
3699

XAOut 1 Item #
XAOut 2 Item #
XAOut 3 Item #
XAOut 4 Item #

R/W
R/W
R/W
R/W

3701
3702
3703
3704

7433-34
7435-36
7437-38
7439-40

XAOut 1 Mode
XAOut 2 Mode
XAOut 3 Mode
XAOut 4 Mode

R/W
R/W
R/W
R/W

3717
3718
3719
3720

7465-66
7467-68
7469-70
7471-72

XAOut 1 Measured value 1


XAOut 2 Measured value 1
XAOut 3 Measured value 1
XAOut 4 Measured value 1

R/W
R/W
R/W
R/W

3733
3734
3735
3736

7497-98
7499-00
7501-02

XAOut 1 Measured value 2


XAOut 2 Measured value 2
XAOut 3 Measured value 2

R/W
R/W
R/W

3749
3750
3751

Register

7389-90
7391-92
7393-94
7395-96
7397-98

UnBalance % (Now)
UnBalance % (Last 10 Minutes)
PST (Last 10 Minutes) For Line 1
PST (Last 10 Minutes) For Line 2
PST (Last 10 Minutes) For Line 3

7401-02
7403-04
7405-06
7407-08

45

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

7503-04

XAOut 4 Measured value 2

R/W

UniArt \
BACnet
AV
3752

7529-30
7531-32
7533-34
7535-36

XAOut 1 Output value 1


XAOut 2 Output value 1
XAOut 3 Output value 1
XAOut 4 Output value 1

R/W
R/W
R/W
R/W

3765
3766
3767
3768

7561-62
7563-64
7565-66
7567-68

XAOut 1 Output value 2


XAOut 2 Output value 2
XAOut 3 Output value 2
XAOut 4 Output value 2

R/W
R/W
R/W
R/W

3781
3782
3783
3784

R/W

3796

R/W
R/W

3800
3801

R/W
R/W
R/W

3899
3900
3901

R/W

3999

Register

7591-92
7599-00
7601-02

7797-98
7799-00
7801-02

7997-98

Map Item 3900 (Reg 7799-7800)


Map Item 3901 (Reg 7801-7802)

Map Item 3999 (Reg 7997-7998)


Maped Item 3800 (Reg 7599-7600)
Maped Item 3801 (Reg 7601-7602)

Maped Item 3899 (Reg 7797-7798)

46

MODBUS

Field Description

Type

GR

Register

8799-00
8801-02
8803-04
8805-06
8806-08
8809-10
8811-12
8813-14
8815-16
8817-18
8819-20
8821-22
8823-24
8825-26
8827-28
8829-30
8831-32
8833-34
8835-36
8837-38
8839-40
8841-42
8843-44

Alarm- High -Voltage L1


Alarm- High -Voltage L2
Alarm- High -Voltage L3
Alarm- High -Current L1
Alarm- High -Current L2
Alarm- High -Current L3
Alarm- High -Demand Total KW
Alarm- High -Import Total KW
Alarm- High -Export Total KW
Alarm- High -Temprature
Alarm- High -kVarhC/kWh
Alarm- High -kVarhL/kWh
Alarm- High -No Volt L1
Alarm- High -No Volt L2
Alarm- High -No Volt L3
Alarm- High -No Current L1
Alarm- High -No Current L2
Alarm- High -No Current L3
Alarm- High -Leakage Current
Alarm- High -PF
Alarm- Low -Voltage L1
Alarm- Low -Voltage L2
Alarm- Low -Voltage L3

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
4400
4401
4402
4403
4404
4405
4406
4407
4408
4409
4410
4411
4412
4413
4414
4415
4416
4417
4418
4419
4420
4421
4422

47

MODBUS

Field Description

Type

GR

Register

8845-46
8846-48
8849-50
8851-52
8853-54
8855-56
8857-58
8859-60
8861-62
8863-64
8865-66
8867-68
8869-70
8871-72
8873-74
8875-76
8877-78
8879-80
8881-82
8883-84
8885-86
8886-88
8889-90
8891-92

Alarm- Low -Current L1


Alarm- Low -Current L2
Alarm- Low -Current L3
Alarm- Low -Demand Total KW
Alarm- Low -Import Total KW
Alarm- Low -Export Total KW
Alarm- Low -Temprature
Alarm- Low -kVarhC/kWh
Alarm- Low -kVarhL/kWh
Alarm- Low -No Volt L1
Alarm- Low -No Volt L2
Alarm- Low -No Volt L3
Alarm- Low -No Current L1
Alarm- Low -No Current L2
Alarm- Low -No Current L3
Alarm- Low -Leakage Current
Alarm- Low -PF
Alarm- Hysteresis -Voltage L1
Alarm- Hysteresis -Voltage L2
Alarm- Hysteresis -Voltage L3
Alarm- Hysteresis -Current L1
Alarm- Hysteresis -Current L2
Alarm- Hysteresis -Current L3
Alarm- Hysteresis -Demand Total KW

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
48

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
4423
4424
4425
4426
4427
4428
4429
4430
4431
4432
4433
4434
4435
4436
4437
4438
4439
4440
4441
4442
4443
4444
4445
4446

MODBUS

Field Description

Type

GR

Register

8893-94
8895-96
8897-98
8899-00
8901-02
8903-04
8905-06
8907-08
8909-10
8911-12
8913-14
8915-16
8917-18
8919-20
8921-22
8923-24
8925-26
8926-28
8929-30
8931-32
8933-34
8935-36
8937-38
8939-40

Alarm- Hysteresis -Import Total KW


Alarm- Hysteresis -Export Total KW
Alarm- Hysteresis -Temprature
Alarm- Hysteresis -kVarhC/kWh
Alarm- Hysteresis -kVarhL/kWh
Alarm- Hysteresis -No Volt L1
Alarm- Hysteresis -No Volt L2
Alarm- Hysteresis -No Volt L3
Alarm- Hysteresis -No Current L1
Alarm- Hysteresis -No Current L2
Alarm- Hysteresis -No Current L3
Alarm- Hysteresis -Leakage Current
Alarm- Hysteresis -PF
Alarm- Delay On -Voltage L1
Alarm- Delay On -Voltage L2
Alarm- Delay On -Voltage L3
Alarm- Delay On -Current L1
Alarm- Delay On -Current L2
Alarm- Delay On -Current L3
Alarm- Delay On -Demand Total KW
Alarm- Delay On -Import Total KW
Alarm- Delay On -Export Total KW
Alarm- Delay On -Temprature
Alarm- Delay On -kVarhC/kWh

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
49

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
4447
4448
4449
4450
4451
4452
4453
4454
4455
4456
4457
4458
4459
4460
4461
4462
4463
4464
4465
4466
4467
4468
4469
4470

MODBUS

Field Description

Type

GR

Register

8941-42
8943-44
8945-46
8947-48
8949-50
8951-52
8953-54
8955-56
8957-58
8959-60
8961-62
8963-64
8965-66
8966-68
8969-70
8971-72
8973-74
8975-76
8977-78
8979-80
8981-82
8983-84
8985-86
8987-88

Alarm- Delay On -kVarhL/kWh


Alarm- Delay On -No Volt L1
Alarm- Delay On -No Volt L2
Alarm- Delay On -No Volt L3
Alarm- Delay On -No Current L1
Alarm- Delay On -No Current L2
Alarm- Delay On -No Current L3
Alarm- Delay On -Leakage Current
Alarm- Delay On -PF
Alarm- Delay Off -Voltage L1
Alarm- Delay Off -Voltage L2
Alarm- Delay Off -Voltage L3
Alarm- Delay Off -Current L1
Alarm- Delay Off -Current L2
Alarm- Delay Off -Current L3
Alarm- Delay Off -Demand Total KW
Alarm- Delay Off -Import Total KW
Alarm- Delay Off -Export Total KW
Alarm- Delay Off -Temprature
Alarm- Delay Off -kVarhC/kWh
Alarm- Delay Off -kVarhL/kWh
Alarm- Delay Off -No Volt L1
Alarm- Delay Off -No Volt L2
Alarm- Delay Off -No Volt L3

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
50

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
4471
4472
4473
4474
4475
4476
4477
4478
4479
4480
4481
4482
4483
4484
4485
4486
4487
4488
4489
4490
4491
4492
4493
4494

MODBUS

Field Description

Type

GR

Register

8989-90
8991-92
8993-94
8995-96
8997-98
8999-00
9001-02
9003-04
9005-06
9006-08
9009-10
9011-12
9013-14
9015-16
9017-18
9019-20
9021-22
9023-24
9025-26
9027-28
9029-30
9031-32
9033-34
9035-36

Alarm- Delay Off -No Current L1


Alarm- Delay Off -No Current L2
Alarm- Delay Off -No Current L3
Alarm- Delay Off -Leakage Current
Alarm- Delay Off -PF
Alarm- Relay -Voltage L1
Alarm- Relay -Voltage L2
Alarm- Relay -Voltage L3
Alarm- Relay -Current L1
Alarm- Relay -Current L2
Alarm- Relay -Current L3
Alarm- Relay -Demand Total KW
Alarm- Relay -Import Total KW
Alarm- Relay -Export Total KW
Alarm- Relay -Temprature
Alarm- Relay -kVarhC/kWh
Alarm- Relay -kVarhL/kWh
Alarm- Relay -No Volt L1
Alarm- Relay -No Volt L2
Alarm- Relay -No Volt L3
Alarm- Relay -No Current L1
Alarm- Relay -No Current L2
Alarm- Relay -No Current L3
Alarm- Relay -Leakage Current

R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
51

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
4495
4496
4497
4498
4499
4500
4501
4502
4503
4504
4505
4506
4507
4508
4509
4500
4511
4512
4513
4514
4515
4516
4517
4518

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

9037-38

Alarm- Relay -PF

R/W

UniArt \
BACnet
AV
4519

9039-40
9041-42

Alarm- High -Digital In 1


Alarm- High -Digital In 2

R/W
R/W

4520
4521

9079-80
9081-82

Alarm- Low -Digital In 1


Alarm- Low -Digital In 2

R/W
R/W

4540
4541

9119-20
9121-22

Alarm- Hysteresis -Digital In 1


Alarm- Hysteresis -Digital In 2

R/W
R/W

4560
4561

9159-60
9161-62

Alarm- Delay On -Digital In 1


Alarm- Delay On -Digital In 2

R/W
R/W

4580
4581

9199-00
9201-02

Alarm- Delay Off -Digital In 1


Alarm- Delay Off -Digital In 2

R/W
R/W

4600
4601

9239-40
9241-42

Alarm- Relay -Digital In 1


Alarm- Relay -Digital In 2

R/W
R/W

4620
4621

10001-02
10003-04

Trip Current Amper (Point 1)


Trip Current Amper (Point 2)

R/W
R/W

5001
5002

Register

52

MODBUS

Field Description

Type

GR

Trip Current Amper (Point 20)


Trip Current Time (Point 1)
Trip Current Time (Point 2)

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R/W
R/W
R/W

UniArt \
BACnet
AV
5020
5021
5022

Register

10039-40
10041-42
10043-44

PQ

10079-80

Trip Current Time (Point 20)

R/W

5040

10081-82
10083-84
10085-86
10087-88
10089-90
10091-92
10093-94
10095-96
10097-98

Trip Current Phase 1 DTE (Write To Clear)


Trip Current Phase 2 DTE (Write To Clear)
Trip Current Phase 3 DTE (Write To Clear)
Trip Current Phase 1 Amper
Trip Current Phase 1 Time (Seconds)
Trip Current Phase 2 Amper
Trip Current Phase 2 Time (Seconds)
Trip Current Phase 3 Amper
Trip Current Phase 3 Time (Seconds)

R/W
R/W
R/W
R
R
R
R
R
R

5041
5042
5043
5044
5045
5046
5047
5048
5049

10101-02
10103-04
10105-06
10107-08
10109-10
10111-12
10113-14

Simple Trip Current #1 SetPoint (Amper)


Simple Trip Current #1 Time (Seconds)
Simple Trip Current #1 Relay (1-4)
Simple Trip Current #1 Status
Simple Trip Current #2 SetPoint (Amper)
Simple Trip Current #2 Time (Seconds)
Simple Trip Current #2 Relay (1-4)

R/W
R/W
R/W
R/W
R/W
R/W
R/W

5051
5052
5053
5054
5055
5056
5057
53

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

10115-16

Simple Trip Current #2 Status

R/W

UniArt \
BACnet
AV
5058

10121-22
10123-24
10125-26
10127-28

Dout Mode # 1
Dout Mode # 2
Dout Mode # 3
Dout Mode # 4

R/W
R/W
R/W
R/W

5061
5062
5063
5064

10139-40
10141-42
10143-44
10145-46

Demand Current (A) AVR(L1+L2+L3)


Demand Current (A) L0
Demand Current (A) AVR(L1+L2+L3) Date
Demand Current (A) L0 Date

R/W
R/W
R
R

5070
5071
5072
5073

10159-60
10161-62
10163-64
10165-66
10167-68
10169-70

Demand Current (A) L1 (Last)


Demand Current (A) L2 (Last)
Demand Current (A) L3 (Last)
Demand Current (A) L1+L2+L3 (Last)
Demand Current (A) AVR(L1+L2+L3) (Last)
Demand Current (A) L0 (Last)

R
R
R
R
R
R

5080
5081
5082
5083
5084
5085

10179-80
10181-82

THD for Volts Lines 1+2+3


THD forCurrent Lines 1+2+3

R
R

5090
5091

10199-00
10201-02

Minimum Volt L1
Minimum Volt L2

R
R

5100
5101

Register

54

MODBUS

Field Description

Type

GR

Register

10203-04
10205-06
10207-08
10209-10
10211-12
10213-14
10215-16
10217-18
10219-20
10221-22
10223-24
10225-26
10227-28
10229-30
10231-32
10233-34
10235-36
10237-38
10239-40
10241-42
10243-44
10245-46
10247-48
10249-50

Minimum Volt L3
Maximum Volt L1
Maximum Volt L2
Maximum Volt L3
Maximum Current L1
Maximum Current L2
Maximum Current L3
Maximum Current L0
Minimum Volt L1-3
Minimum Volt L2-3
Minimum Volt L3-1
Maximum Volt L1-3
Maximum Volt L2-3
Maximum Volt L3-1
Maximum Active Power Total
Maximum Apparent Power Total
Maximum ReActive Power Total
Minimum PF. L1
Minimum PF. L2
Minimum PF. L3
Minimum PF. Total
Maximum PF. L1
Maximum PF. L2
Maximum PF. L3

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
55

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
5102
5103
5104
5105
5106
5107
5108
5109
5110
5111
5112
5113
5114
5115
5116
5117
5118
5119
5120
5121
5122
5123
5124
5125

MODBUS

Field Description

Type

GR

Register

10251-52
10253-54
10255-56
10257-58
10259-60
10261-62
10263-64
10265-66
10267-68
10269-70
10271-72
10273-74
10275-76
10277-78
10279-80
10281-82
10283-84
10285-86
10287-88
10289-90
10291-92
10293-94
10295-96
10297-98

Maximum PF. Total


Minimum Freq.
Maximum Freq.
Minimum Current L1
Minimum Current L2
Minimum Current L3
Minimum Current L0
Maximum Active Power (W) L1
Maximum Active Power (W) L2
Maximum Active Power (W) L3
Minimum Active Power (W) L1
Minimum Active Power (W) L2
Minimum Active Power (W) L3
Maximum ReActive Power (VAR ) L1
Maximum ReActive Power (VAR) L2
Maximum ReActive Power (VAR) L3
Minimum ReActive Power (VAR) L1
Minimum ReActive Power (VAR) L2
Minimum ReActive Power (VAR) L3
Maximum Apparent Power (VA ) L1
Maximum Apparent Power (VA) L2
Maximum Apparent Power (VA) L3
Minimum Apparent Power (VA) L1
Minimum Apparent Power (VA) L2

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
56

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
5126
5127
5128
5129
5130
5131
5132
5133
5134
5135
5136
5137
5138
5139
5140
5141
5142
5143
5144
5145
5146
5147
5148
5149

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

10299-00
10301-02
10303-04
10305-06
10307-08
10309-10
10311-12
10313-14
10315-16
10317-18
10319-20
10321-22
10323-24
10325-26
10327-28
10329-30
10331-32
10333-34
10335-36
10337-38
10339-40
10341-42

Minimum Apparent Power (VA) L3


Minimum Active Power Total
Minimum Apparent Power Total
Minimum ReActive Power Total
Minimum Displacement PF. L1
Minimum Displacement PF. L2
Minimum Displacement PF. L3
Maximum Displacement PF. L1
Maximum Displacement PF. L2
Maximum Displacement PF. L3
Minimum THD V-L1
Minimum THD V-L2
Minimum THD V-L3
Maximum THD V-L1
Maximum THD V-L2
Maximum THD V-L3
Minimum THD I-L1
Minimum THD I-L2
Minimum THD I-L3
Maximum THD I-L1
Maximum THD I-L2
Maximum THD I-L3

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R

UniArt \
BACnet
AV
5150
5151
5152
5153
5154
5155
5156
5157
5158
5159
5160
5161
5162
5163
5164
5165
5166
5167
5168
5169
5170
5171

10399-00

Minimum Volt L1 (DTE)

5200

Register

57

MODBUS

Field Description

Type

GR

Register

10401-2
10403-4
10405-6
10407-8
10409-10
10411-12
10413-14
10415-16
10417-18
10419-20
10421-22
10423-24
10425-26
10427-28
10429-30
10431-32
10433-34
10435-36
10437-38
10439-40
10441-42
10443-44
10445-46
10447-48

Minimum Volt L2 (DTE)


Minimum Volt L3 (DTE)
Maximum Volt L1 (DTE)
Maximum Volt L2 (DTE)
Maximum Volt L3 (DTE)
Maximum Current L1 (DTE)
Maximum Current L2 (DTE)
Maximum Current L3 (DTE)
Maximum Current L0 (DTE)
Minimum Volt L1-3 (DTE)
Minimum Volt L2-3 (DTE)
Minimum Volt L3-1 (DTE)
Maximum Volt L1-3 (DTE)
Maximum Volt L2-3 (DTE)
Maximum Volt L3-1 (DTE)
Maximum Active Power Total (DTE)
Maximum Apparent Power Total (DTE)
Maximum ReActive Power Total (DTE)
Minimum PF. L1 (DTE)
Minimum PF. L2 (DTE)
Minimum PF. L3 (DTE)
Minimum PF. Total (DTE)
Maximum PF. L1 (DTE)
Maximum PF. L2 (DTE)

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
58

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
5201
5202
5203
5204
5205
5206
5207
5208
5209
5210
5211
5212
5213
5214
5215
5216
5217
5218
5219
5220
5221
5222
5223
5224

MODBUS

Field Description

Type

GR

Register

10449-50
10451-52
10453-54
10455-56
10457-58
10459-60
10461-62
10463-64
10465-66
10467-68
10469-70
10471-72
10473-74
10475-76
10477-78
10479-80
10481-82
10483-84
10485-86
10487-88
10489-90
10491-92
10493-94
10495-96

Maximum PF. L3 (DTE)


Maximum PF. Total (DTE)
Minimum Freq. (DTE)
Maximum Freq. (DTE)
Minimum Current L1 (DTE)
Minimum Current L2 (DTE)
Minimum Current L3 (DTE)
Minimum Current L0 (DTE)
Maximum Active Power (W) L1 (DTE)
Maximum Active Power (W) L2 (DTE)
Maximum Active Power (W) L3 (DTE)
Minimum Active Power (W) L1 (DTE)
Minimum Active Power (W) L2 (DTE)
Minimum Active Power (W) L3 (DTE)
Maximum ReActive Power (VAR ) L1 (DTE)
Maximum ReActive Power (VAR) L2 (DTE)
Maximum ReActive Power (VAR) L3 (DTE)
Minimum ReActive Power (VAR) L1 (DTE)
Minimum ReActive Power (VAR) L2 (DTE)
Minimum ReActive Power (VAR) L3 (DTE)
Maximum Apparent Power (VA ) L1 (DTE)
Maximum Apparent Power (VA) L2 (DTE)
Maximum Apparent Power (VA) L3 (DTE)
Minimum Apparent Power (VA) L1 (DTE)

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
59

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
5225
5226
5227
5228
5229
5230
5231
5232
5233
5234
5235
5236
5237
5238
5239
5240
5241
5242
5243
5244
5245
5246
5247
5248

MODBUS

Field Description

Type

GR

Register

10497-98
10499-00
10501-2
10503-4
10505-6
10507-8
10509-10
10511-12
10513-14
10515-16
10517-18
10519-20
10521-22
10523-24
10525-26
10527-28
10529-30
10531-32
10533-34
10535-36
10537-38
10539-40
10541-42

Minimum Apparent Power (VA) L2 (DTE)


Minimum Apparent Power (VA) L3 (DTE)
Minimum Active Power Total (DTE)
Minimum Apparent Power Total (DTE)
Minimum ReActive Power Total (DTE)
Minimum Displacement PF. L1 (DTE)
Minimum Displacement PF. L2 (DTE)
Minimum Displacement PF. L3 (DTE)
Maximum Displacement PF. L1 (DTE)
Maximum Displacement PF. L2 (DTE)
Maximum Displacement PF. L3 (DTE)
Minimum THD V-L1 (DTE)
Minimum THD V-L2 (DTE)
Minimum THD V-L3 (DTE)
Maximum THD V-L1 (DTE)
Maximum THD V-L2 (DTE)
Maximum THD V-L3 (DTE)
Minimum THD I-L1 (DTE)
Minimum THD I-L2 (DTE)
Minimum THD I-L3 (DTE)
Maximum THD I-L1 (DTE)
Maximum THD I-L2 (DTE)
Maximum THD I-L3 (DTE)

R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
60

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV
5249
5250
5251
5252
5253
5254
5255
5256
5257
5258
5259
5260
5261
5262
5263
5264
5265
5266
5267
5268
5269
5270
5271

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

10557-58

Last MinMax Table (DTE)

UniArt \
BACnet
AV
5279

10559-60
10561-62
10563-64
10565-66
10567-68
10569-70
10571-72
10573-74
10575-76
10577-78
10579-80
10581-82
10583-84
10585-86

Fundamental P L1
Fundamental P L2
Fundamental P L3
Fundamental P Tot
Fundamental Q L1
Fundamental Q L2
Fundamental Q L3
Fundamental Q Tot
Fundamental V L1
Fundamental V L2
Fundamental V L3
Fundamental I L1
Fundamental I L2
Fundamental I L3

R
R
R
R
R
R
R
R
R
R
R
R
R
R

5280
5281
5282
5283
5284
5285
5286
5287
5288
5289
5290
5291
5292
5293

R/W
R/W
R/W

5300
5301
5302

R/W

5315

Register

10599-0
10601-2
10603-4

Fast Trend Type (0,1,2) 2=User


User Trend Item # 1
User Trend Item # 2

10629-30

User Trend Item # 15

61

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

10639-40
10641-42
10643-44
10645-46
10647-48
10649-50
10651-52
10653-54
10655-56
10657-58
10659-60
10661-62
10663-64
10665-66

Demand PF L1
Demand PF L2
Demand PF L3
Demand PF L1+2+3
Demand Current (AVR) L1,L2,L3
Demand Current L0
Demand V- THD L1
Demand V- THD L2
Demand V- THD L3
Demand V- THD (Max) L1,L2,L3
Demand I- THD L1
Demand I- THD L2
Demand I- THD L3
Demand I- THD (Max) L1,L2,L3

R
R
R
R
R
R
R
R
R
R
R
R
R
R

UniArt \
BACnet
AV
5320
5321
5322
5323
5324
5325
5326
5327
5328
5329
5330
5331
5332
5333

10679-80
10681-82
10682-84
10685-86

Voltage Line 1 (15 Mint Average)


Voltage Line 2 (15 Mint Average)
Voltage Line 3 (15 Mint Average)
Voltage between line 1 and Line 3 (15 Mint
Average)
Voltage between line 2 and Line 3 (15 Mint
Average)
Voltage between line 3 and Line 1 (15 Mint
Average)

R
R
R
R

5340
5341
5342
5343

5344

5345

Register

10687-88
10689-90

62

MODBUS

Field Description

Type

GR

10705-06
10707-08
10709-10
10711-12
10713-14
10715-16
10717-18
10719-20
10721-22
10723-24
10725-26
10727-28

Current in Line 1 (15 Mint Average)


Current in Line 2 (15 Mint Average)
Current in Line 3 (15 Mint Average)
Active Power Line 1 -Watt (15 Mint Average)
Active Power Line 2 -Watt (15 Mint Average)
Active Power Line 3 -Watt (15 Mint Average)
Active Power Line 1+2+3 -Watt (15 Mint
Average)
ReActive Power Line 1 -VAR (15 Mint
Average)
ReActive Power Line 2 -VAR (15 Mint
Average)
ReActive Power Line 3 -VAR (15 Mint
Average)
ReActive Power Line 1+2+3 -VAR (15 Mint
Average)
Power Factor Line 1 (PF) (15 Mint Average)
Power Factor Line 2 (PF) (15 Mint Average)
Power Factor Line 3 (PF) (15 Mint Average)
Power Factor Line 1+2+3 (PF) (15 Mint
Average)
Current L0 (15 Mint Average)
Frequency (15 Mint Average)
Apparent Power Line 1 -VA (15 Mint Average)
Apparent Power Line 2 - VA (15 Mint Average)

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R
R
R
R
R
R

UniArt \
BACnet
AV
5346
5347
5348
5349
5350
5351
5352

5353

5354

5355

5356

R
R
R
R

5357
5358
5359
5360

R
R
R
R

5361
5362
5363
5364

Register

10691-92
10693-94
10695-96
10697-98
10699-00
10701-02
10703-04

PQ

63

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

10729-30
10731-32

Apparent Power Line 3 - VA (15 Mint Average)


Apparent Power Line 1+2+3 - VA (15 Mint
Average)

R
R

UniArt \
BACnet
AV
5365
5366

10739-40
10741-42
10743-44
10745-46

V1+V2+V3/3 (Average)
V12+V23+V31/3 (Average)
I1+I2+I3/3 (Average)
f1+f2+f3/3 (Average)

R
R
R
R

5370
5371
5372
5373

10779-80
10781-82
10783-84

Demand Cycle Time (Minutes)


Demand Type (0=Slide,1=Block,2=Therm)
Demand Sync (1=D.In,2=Comm,3=Clock)

R/W
R/W
R/W

5390
5391
5392

10799-00
10801-02
10803-04
10805-06
10807-08
10809-10
10811-12
10715-16
10817-18
10819-20
10821-22

EN50160 Event 1: Id
EN50160 Event 1: Event Num Code
EN50160 Event 1: Date (Dte)
EN50160 Event 1: MicroSecond
EN50160 Event 1: Length
EN50160 Event 1: Value
EN50160 Event 1: Phase
EN50160 Event 2: Id
EN50160 Event 2: Event Num Code
EN50160 Event 2: Date (Dte)
EN50160 Event 2: MicroSecond

R
R
R
R
R
R
R
R
R
R
R

5400
5401
5402
5403
5404
5405
5406
5408
5409
5410
5411

Register

64

Field Description

MODBUS

Type

GR

EN50160 Event 2: Length


EN50160 Event 2: Value
EN50160 Event 2: Phase

11583-84
11585-86
11587-88
11589-90
11591-92
11593-94

EN50160 Event 50: Id


EN50160 Event 50: Event Num Code
EN50160 Event 50: Date (Dte)
EN50160 Event 50: MicroSecond
EN50160 Event 50: Length
EN50160 Event 50: Value

11601-02
11603-04

Option # 1
Option # 2

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

R
R
R

UniArt \
BACnet
AV
5412
5413
5414

R
R
R
R
R
R

5792
5793
5794
5795
5796
5797

R/W
R/W

5801
5802

Register

10823-24
10825-26
10827-28

PQ

11647-48

Option # 24

R/W

5824

11699-00

Internal Use

R/W

5850

R/W

5910

R
R

5921
5922

11819-20

Internal Use

11681-82
11683-84

Pulse D.In 1 Rate 1


Pulse D.In 1 Rate 2

65

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

11685-86
11687-88
11689-90
11691-92
11693-94
11695-96
11697-98
11699-00
11701-02
11703-04
11703-04
11705-06
11707-08
11709-10
11711-12
11713-14

Pulse D.In 1 Rate 3


Pulse D.In 2 Rate 1
Pulse D.In 2 Rate 2
Pulse D.In 2 Rate 3
Pulse D.In 1 Rate 1 (x K)
Pulse D.In 1 Rate 2 (x K)
Pulse D.In 1 Rate 3 (x K)
Pulse D.In 2 Rate 1 (x K)
Pulse D.In 2 Rate 2 (x K)
Pulse D.In 2 Rate 3 (x K)
Pulse D.In1 (K)
Pulse D.In2 (K)
Pulse D.In 1 Rate 1+2+3
Pulse D.In 2 Rate 1+2+3
Pulse D.In 1 Rate 1+2+3 (x K)
Pulse D.In 2 Rate 1+2+3 (x K)

R
R
R
R
R
R
R
R
R
R
R/W
R/W
R
R
R
R

UniArt \
BACnet
AV
5923
5924
5925
5926
5927
5928
5929
5930
5931
5932
5933
5934
5935
5936
5937
5938

11789-90
11791-02
11793-04
11795-06
11797-08
11799-00
11801-02

Flash Trend Time


Flash Tend Day
Flash Trend Month
Flash Trend Year
Flash Trend Hour
Flash Trend Minute
Flash Trend Second

R/W
R/W
R/W
R/W
R/W
R/W
R/W

5940
5941
5942
5943
5944
5945
5945

Register

66

MODBUS

Field Description

Type

GR

Register

11901-02
11901-02
11903-04

User Flash Trend Record Data - Datete


User Flash Trend Record Data - Item # 1
User Flash Trend Record Data - Item # 2

11947-48

User Flash Trend Record Data - Item # 24

11949-50
11951-52

User Flash Trend Item # 1


User Flash Trend Item # 2

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV

R
R
R

5950
5951
5952

5974

R/W
R/W

5975
5976

11997-98

User Flash Trend Item # 24

R/W

5999

13981-82
13981-82

GMT (Gps Offset)


GMT Update Clock (Seconds)

R/W
R/W

6991
6992

13995-96
13997-98
13999-00
14001-02

Historical Alarm Current Record


Historical Alarm Total Records (200)
Historical Alarm # 1 -Dte
Historical Alarm # 2 -Dte

R
R
R
R

6998
6999
7000
7001

R
R

7199
7200

14397-98
14399-00

Historical Alarm # 200 -Dte


Historical Alarm # 1 -Date

67

MODBUS

Field Description

Type

GR

Register

14797-98
14799-00

15197-98
15199-00

15597-98
15599-00

15997-98
15999-00

16397-98
16399-00

16797-98
16799-00

Historical Alarm # 200 -Date


Historical Alarm # 1 -Time

Historical Alarm # 200 -Time


Historical Alarm # 1 Alarm Number

Historical Alarm # 200 Alarm Number


Historical Alarm # 1 Alarm Phase

Historical Alarm # 200 Alarm Phase


Historical Alarm # 1 Alarm Type

Historical Alarm # 200 Alarm Type


Historical Alarm # 1 Alarm On/Off

Historical Alarm # 200 Alarm On/Off


Historical Alarm # 1 Alarm Value

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

UniArt \
BACnet
AV

R
R

7399
7400

R
R

7599
7600

R
R

7799
7800

R
R

7999
8000

R
R

8199
8200

R
R

8399
8400

68

MODBUS

Field Description

Type

GR

PQ

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

17197-98

Historical Alarm # 200 Alarm Value

UniArt \
BACnet
AV
8599

17199-00

I0 First Wave Sample

8600

R
R

8799
8800

R
R

8999
9000

R
R

9199
9200

I3 Last Wave Sample


V1 First Wave Sample

R
R

9399
9400

V1 Last Wave Sample


V2 First Wave Sample

R
R

9599
9600

9799

Register

17597-98
17599-00

17997-98
17999-00

18397-98
18399-00

18797-98
18799-00

19197-98
19199-00

19597-98

I0 Last Wave Sample


I1 First Wave Sample

I1 Last Wave Sample


I2 First Wave Sample

I2 Last Wave Sample


I3 First Wave Sample

V2 Last Wave Sample

69

MODBUS

Field Description

Type

GR

19997-98

PICO VIPP

LT
color

LT

MC

LTE

LTC

ITEM #

V3 First Wave Sample

UniArt \
BACnet
AV
9800

9999

Register
19599-00

PQ

V3 Last Wave Sample

Table 1-4 Registers Table

70

1.3 UniArt Alarms for ElNet Multimeter


The ElNet Energy & Powermeteris capable of working with UNIART software. When working with UNIART software user can get specific
alarms from the unit as described in Table 1-5.
Alarm #
Description
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22

Low Voltage (Line To N)


High Voltage (Line To N)
Low Voltage (Line To N)
High Voltage (Line To N)
Low Voltage (Line To N)
High Voltage (Line To N)
Low Voltage (Line To Line)
High Voltage (Line To Line)
Low Voltage (Line To Line)
High Voltage (Line To Line)
Low Voltage (Line To Line)
High Voltage (Line To Line)
Low Current
High Current
Low Current
High Current
Low Current
High Current
Low Current
High Current
Low Power Factor
High Power Factor

Phase

GR

1
1
2
2
3
3
1-2
1-2
2-3
2-3
3-1
3-1
1
1
2
2
3
3
L0 (N)
L0 (N)
1
1
71

LT

MC

PICO

Alarm #

Description

Phase

23
24
25
26
27
28

Low Power Factor


High Power Factor
Low Power Factor
High Power Factor
Low Power Factor
High Power Factor

2
2
3
3
1+2+3
1+2+3

39
40
41
42
43
43
45
46
47
48
49
50
51
52
53
54
55
56
57

High Power Period (Item 262)


Low Power Period (Item 263)
Low Voltage THD
High Voltage THD
Low Voltage THD
High Voltage THD
Low Voltage THD
High Voltage THD
Low Current THD
High Current THD
Low Current THD
High Current THD
Low Current THD
High Current THD
Low Current THD
High Current THD
Low Current TDD
High Current TDD
Low Current TDD

1+2+3
1+2+3
1
1
2
2
3
3
1
1
2
2
3
3
L0 (N)
L0 (N)
1
1
2

GR

72

LT

MC

PICO

Alarm #
58
59
60
61
62
63
64
65
66
67
68
69
70
81
82
83
84
85
86
87
88
89
90
91
92

Description
High Current TDD
Low Current TDD
High Current TDD
Low Current TDD
High Current TDD
Low Current K.Factor
High Current K.Factor
Low Current K.Factor
High Current K.Factor
Low Current K.Factor
High Current K.Factor
Low Current K.Factor
High Current K.Factor
U.Alarm High Current
U.Alarm High Current
U.Alarm High Current
U.Alarm High Voltage
U.Alarm High Voltage
U.Alarm High Voltage
U.Alarm Low Voltage
U.Alarm Low Voltage
U.Alarm Low Voltage
U.Alarm Low PF
U.Alarm High V.THD
U.Alarm High I.THD

Phase

GR

2
3
3
L0 (N)
L0 (N)
1
1
2
2
3
3
L0 (N)
L0 (N)
1
2
3
1
2
3
1
2
3
1+2+3
1+2+3
1+2+3
Table 1-5 Alarm Table
73

LT

MC

PICO

Alarm #

Description

Phase

1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22

High Voltage (Line To N)


High Voltage (Line To N)
High Voltage (Line To N)
High Current
High Current
High Current
Demand KW
Import Power Total KW
Export Power Total KW
Temprature
% kVarhC/kWh
% kVarhL/kWh
No Volt
No Volt
No Volt
No Current
No Current
No Current
High Leakage Current
High General PF
Digital In #1
Digital In #2

1
2
3
1
2
3
Tot
Tot
Tot
--Tot
Tot
1
2
3
1
1
1
---------

41
42

Low Voltage (Line To N)


Low Voltage (Line To N)

1
2

LT Color

74

Alarm #
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60

Description
Low Voltage (Line To N)
Low Current
Low Current
Low Current
Low Demand KW
Low Import Power Total KW
Low Export Power Total KW
Low Temprature
Low % kVarhC/kWh
Low % kVarhL/kWh
Low No Volt
Low No Volt
Low No Volt
Low No Current
Low No Current
Low No Current
High Leakage Current
Low General PF

Phase

LT Color

3
1
2
3
Tot
Tot
Tot
--Tot
Tot
1
2
3
1
1
1
----Table 1-6 LT (Color) Alarm Table

75

Whats New?
01.03.2010 :
08.03.2010 :
31.05.2010 :
06.06.2010 :
22.07.2010 :
01.09.2010 :
06.06.2010 :
15.06.2010 :
08.09.2011 :
12.09.2011 :
10.11.2011 :
23.11.2011 :
10.12.2011 :
09.01.2012 :
16.02.2012 :
19.02.2012 :
20.02.2012 :
06.05.2012 :
10.05.2012 :
24.05.2012 :
17.06.2012 :
14.08.2012 :
14.08.2012 :
20.08.2012 :
29.08.2012 :
02.09.2012 :
02.09.2012 :
12.09.2012 :
13.09.2012 :
19.09.2012 :
05.11.2012 :
26.11.2012 :
02.12.2012 :
06.12.2012 :
12.12.2012 :
27.12.2012 :
09.01.2013 :
17.01.2013 :
16.07.2013 :
31.07.2013 :
20.08.2013 :
01.10.2013 :
03.10.2013 :
04.10.2013 :
08.10.2013 :
13.02.2014 :
16.02.2014 :
08.04.2014 :
08.04.2014 :
17.07.2014 :

Add LT Demand THD Values (2141-2157)


Add GR KFactor (167-170)
Add MC
Add Temp Sensor (190)
Add Modbus Response Delay (290)
Add TOU Registers (3101-3328)
Add Energy in KW (3400-3435)
Add Energy in KW (3400-3411) in LTE
Add Total Q For C & L Mode (285 & 286)
Add Meter B (3440 & 3477)
Add Fast Trend Cycle (GR) (199)
Add Long Wave Events (PQ) (650-654)
Update Alarm Table
Add LTC16 Capacitors 8-16 (1981-1990)
Add MC & LT ModBus Index (ReMap Items 3800-3999)
Add LT Alarms (Items 4400-4519)
Add PQ/GR ModBus Index (ReMap Items 3800-3999)
Add PQ Trip Current
Add LT (Color) Reactive Four Quadrant (Items 295-298)
Add PST to PQ
Add Simple Trip Data (Items 5051-5058)
Add User Trend (Items 5301-5315)
Add Item 657
Add Items 5340-5360
Add Items 697-699
Add Items 5400-5798
Add Items 1991-1993
Add Items 3437-8
Add Items 5390-2
Add Items 5320-5333
Add Items 5801-5824
Add LT Color Alarms
Update Alarm Table
Add 2120 Keyboard Lock
Add MSTP Parameters
Add Pulse Registers (5481)
Add MVAR Registers (3439)
Add Avr15M Registers (5360)
Add D.In Energy (LT)
Add User Flash Trend (LT TFT - Items 5900-5928)
Add Total D.In Energy
Add Combined Apparant Power (KVA) and (MVA) (Items 3443-3444)
Add Harmonics & Min/Max to Pico,
Add LT Historical Alarms
Add LTE VAR-LC
Add PQ Crest Factor
Update Flash trend registers.
Update GPS Registers.
Add K power per line (LT 2013 - Items 3478-3486)
Update Alarm Table (Items 4400-4640)
76

04.09.2014 :
22.12.2014:
5.8.2015:
29.9.2015:
29.9.2015:
20.4.2016:

Add Alternate Meter Energy (Items 3446-3448, 3450-3458, 3490-3498)


Add High PF Limit (Items 3985-86, 3987-88)
Add Current Demand To Pico
Add Items 5280-5293 (Fundamental Data)
Add Items 5975-5999 (Ftrend Items)
Add Digital In #1 & #2 to LTE

77