Tab 3 Exploring Power Flow Solution

2013 Siemens Industry, Inc. All rights reserved

Power Flow Solution Methods


Newton-Raphson

Gauss-Seidel
Normal Gauss-Seidel (SOLV)
Modified Gauss-Seidel (MSLV)

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Fixed Slope Decoupled Newton-Raphson (FDNS)


Full Newton-Raphson (FNSL)
Decoupled Newton-Raphson (NSOL)

3-2

Power Flow Solution


Power Flow>Solution>Solve
or Toolbar

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Convergence Monitor

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

3-3

Comparison of Solution Methods


Advantages
Rapid convergence on well
conditioned cases.

Disadvantages
Intolerant of data errors
and voltages. No indication for
cause of convergence failure.
Difficulty converging when
reactive limits are restrictive.

Fixed Slope Newton (FDNS) is faster than Full Newton (FNSL).


Possible to reach a tighter tolerance with Full Newton.

Solution Methods
Gauss-Seidel
(SOLV,MSLV)

Advantages
Tolerant of data errors and
poor starting voltages. Fails
gently, indicates area of network with problems.

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

Disadvantages
Slow to converge, number of
iterations increases as system
size increases. Sensitive to
acceleration factors. SOLV
cannot handle negative
reactances.

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Solution Methods
Newton-Raphson
(FNSL,FDNS)

3-4

Solution Options

Transformer Tap
Switched Shunts
Area Interchange
Control
Phase Shifter
DC Taps

Other Options
Generator Var Limits
Flat Start
Non-divergent Solution

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Automatic Adjustments:

3-5

Solution Parameters - 1

Eliminating small, non-zero


impedance lines
(particularly if represented
with only an inductive
component) by raising
THRSHZ may allow
solution to reach a lower
tolerance.
For cases with tight
reactive limits, the user
may find it helpful to
reduce acceleration factor,
ACCN (i.e. slow down
voltage change in each
iteration).
Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Power Flow > Solution >


Parameters

3-6

Solution Parameters - 2

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Solution parameters for


Gauss and TYSL solution
methods

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

3-7

Reviewing Power Flow Results


Graphics

Report

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

List

3-8

Subsystem Selector

Access from pull-down


menu:
Subsystem > Bus / Simple
Bus / Area / Owner / Zone

Memorize and Recall


previous subsystem
selections

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Access from toolbar:

3-9

Filter: To create filtered spreadsheet by the Filter Grid Dialog.


First, select a column (left click on heading).
Right click at the heading.
Select Filter Grid (Boolean operation of AND / OR).
Any number of columns may be filtered. But, only one at a time.
A new filtered spreadsheet
will be created.
Cells in filtered spreadsheet
are linked directly to cells in
original spreadsheet.
Cell values displayed may be
rounded-off.
Can change precision, font,
style, color for any column.
Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Filtering in Spreadsheet View

3-10

Display Power Flow Solution Results at a Bus or Branch


(GOUT)
From POUT to GOUT
Display / Change Data at a Bus or Branch (GEXM)
Display Power Flow Solution Results in Slider Diagram
User Graphical Report (GRPG)

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Power Flow Graphics Overview

3-11

Double-click to
go to next bus

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Graphically Display Power Flow Solution


Results (GOUT)

3-12

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

From POUT to GOUT

Double
click on
bus
number

Siemens Power Academy TD NA - PSSC 525 PSS E Fast Track for Power Flow and Dynamics
Siemens
Power Academy TD-NA PSSC 550
Dynamic Simulation

Page 1-13

Toggle between GOUT &


GEXM

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Graphically Display/Change Data (GEXM)

3-14

Generate Graphical Report (GRPG)

Select GRPG
File

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Select
Plotting
Device

3-15

Data Listing Activities


Power Flow > List data
Bus names (ALPH)
Examine (EXAM)
Sequence data (SQLI)
OPF
Outaged equipment (OUTS)
Bus shunts (SHNT)

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Powerflow (LIST)

3-16

Reporting Power Flow Results


Power Flow > Reports
Bus based reports

Limit checking reports


Area / owner / zone totals reports

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Area / zone based reports

3-17

Tie Line and Inter-Area Flows

Inter-area/zone reports: Reports power


flow on inter-area or zone
Tie lines: Reports power flow on ties
between areas or zones

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Power Flow > Reports > Area / zone


based reports

3-18

Area / Owner / Zone Reporting

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Power Flow > Reports > Area / owner / zone totals


AREA
- Control Area Totals including desired versus
scheduled interchange.
OWNER - Owner Totals
ZONE
- Zone Totals

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

3-19

Bus Based Power Flow Output

Displays solved case information for a


bus, such as voltage and power flow.
Regular format: Displays branch flows
Wide format output: Displays actual
bus voltage, generator / load / shunt
attached to the bus, and branch flows
Output with amps: Only available when
wide format output is in effect.
Displays flows and ratings in amperes
(if bus base kV > 0)

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Power Flow > Reports > Bus


based reports > Powerflow
output

3-20

Examining Power Flow Output


Example: Bus based report for bus 205:

TO
TO
TO
TO
TO
TO
TO

LOAD-PQ
SHUNT
154 DOWNTN
201 HYDRO
203 EAST230
203 EAST230
206 URBGEN

230.00 CKT

230.00
500.00
230.00
230.00
18.000

1
&1
1
2
1

MW

MVAR

MVA

% 0.9490PU -9.18 X-- LOSSES --X X--- AREA --X X-- ZONE 218.27KV
MW
MVAR
2 LIGHTCO
2 SECOND

1200.0 700.0 1389.2


0.0 -270.2 270.2
354.9 250.5 434.4 76
-590.7 -148.2 609.0 76 1.0000UN
-83.3 -29.7
88.5 47
-83.3 -29.7
88.5 47
-797.5 -472.8 927.1 103 1.0000LK

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

0.70
12.46
0.42
0.42
2.48

7.05
174.07
3.81
3.81
127.22

1
2
2
2
2

FLAPCO
LIGHTCO
LIGHTCO
LIGHTCO
LIGHTCO

1
2
2
2
2

FIRST
SECOND
SECOND
SECOND
SECOND

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

BUS 205 SUB230

3-21

Subsystem Totals
Power Flow > Reports > Bus based reports > Subsystem summary / totals

6 BUSES
3 LOADS

2 PLANTS
8 BRANCHES

2 MACHINES
3 TRANSFORMERS

2 FIXED SHUNTS
0 DC LINES

X------ ACTUAL ------X X----- NOMINAL ------X


MW
MVAR
MW
MVAR
FROM GENERATION
1500.0
162.4
1500.0
162.4
TO CONSTANT POWER LOAD
1200.0
900.0
1200.0
900.0
TO CONSTANT CURRENT
0.0
0.0
0.0
0.0
TO CONSTANT ADMITTANCE
0.0
0.0
0.0
0.0
TO BUS SHUNT
0.0
349.9
0.0
300.0
TO FACTS DEVICE SHUNT
0.0
0.0
0.0
0.0
TO GNE BUS DEVICES
0.0
0.0
0.0
0.0
TO LINE SHUNT
0.0
0.0
0.0
0.0
FROM LINE CHARGING
0.0
841.2
0.0
820.0
VOLTAGE
X----- LOSSES -----X
LEVEL BRANCHES
MW
MVAR
500.0
3
11.10
195.99
230.0
3
6.92
93.57
21.6
2
3.28
148.78

X-- LINE SHUNTS --X


MW
MVAR
0.0
0.0
0.0
0.0
0.0
0.0

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

CHARGING
MVAR
817.9
23.3
0.0

MVABASE
900.0

0 SWITCHED SHUNTS
0 FACTS DEVICES
0 GNE DEVICES

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

****************** SUMMARY FOR THE SUBSYSTEM SPECIFIED BY ******************


BUSES:
101 [NUC-A
21.600]
TO
154 [DOWNTN
230.00]
******************************************************************************
AREA SWING BUS SUMMARY
X---- AREA -----X X------ SWING BUS ------X X---- ZONE -----X
# X-- NAME --X
BUS# X-- NAME --X BASKV
# X-- NAME --X
MW
MVAR
1 FLAPCO
101 NUC-A
21.600
77 PLANT
750.0
81.2

3-22

Problem 3-1: Check power flow cases


Pick up EXER2-2.SAV
What is the size of the case? (File > File Information > List the number of system components)

Get a power flow solution report at all buses in the case. (Power Flow > Reports > Bus based reports)

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Find out the generation, load, and loss in each area (Power Flow > Reports > Area/Owner/Zone Total)

3-23

Power Flow>Reports>Limit Checking


Reactive capability
Generator bus
Machine terminal
Branches
Regulated buses
Controlling transformers
Out-of-limit bus voltage

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Limit Checking Reports

3-24

Include transformer, non-transformer


branches and/or breakers & switches.
Choice of Rating Set A, B, C or All.
Percent loading computed either on MVA
basis or current basis, as defined in raw
data file or Program Settings.

SUBSYSTEM LOADING CHECK (INCLUDED: LINES; BREAKERS AND SWITCHES; TRANSFORMERS) (EXCLUDED: NONE)
LOADINGS ABOVE 90.0 % OF RATING SET A (MVA FOR TRANSFORMERS, CURRENT FOR NON-TRANSFORMER BRANCHES):
X--------- FROM BUS ----------X X---------- TO BUS -----------X
BUS# X-- NAME --X BASKV AREA
BUS# X-- NAME --X BASKV AREA CKT LOADING
153 MID230
230.00
1
154 DOWNTN
230.00*
1 1
276.0
205 SUB230
230.00
2
206 URBGEN
18.000*
2 1
1000.0
Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

RATING PERCENT
300.0
92.0
900.0
111.1

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Branch Overload Checking

3-25

Branch Loading Calculation


Irating (amps) =

Branch Rating:

Iflow (amp) =

Branch Flow:

x 1000

3x kVbase
MVAflow

x 1000

3 x kVactual

% Line Loading =

Current Loading (in units of MVA):

Iflow
Irating

x 100 =

MVAflow
MVArating x Vpu

3 x I flow (amps) x kVbase


1000

Transformer MVA Loading based on:


% Transformer Loading =
Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

x 100

MVAflow

MVAflow
MVArating

Vpu

x 100

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Percent Loading:

MVArating

3-26

Power
Flow>Reports>Limit
Checking>Out-of-limit bus
voltage
Scans working case for bus
voltages outside of a userdefined range.
BUSES WITH VOLTAGE GREATER THAN 1.0300:
BUS# X- NAME -X BASKV AREA V(PU) V(KV)
201 HYDRO
500.00
2 1.0400 520.00
3011 MINE_G
13.800
5 1.0400 14.352

BUS# X- NAME -X BASKV AREA V(PU) V(KV)


211 HYDRO_G
20.000
2 1.0404 20.808

BUSES WITH VOLTAGE LESS THAN 0.9700:


BUS#
154
205
3008

X- NAME -X BASKV AREA V(PU) V(KV)


DOWNTN
230.00
1 0.9389 215.95
SUB230
230.00
2 0.9490 218.27
CATDOG
230.00
5 0.9586 220.48

BUS#
203
3007
204

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

X- NAME -X BASKV AREA V(PU) V(KV)


EAST230
230.00
2 0.9665 222.30
RURAL
230.00
5 0.9637 221.65
SUB500
500.00
2 0.9476 473.81

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Bus Voltage Limit Checking

3-27

Generator Limit Checking

Machine terminal (GEOL) - Reports individual


generator terminal conditions. Multiple machines at a
bus are listed individually.
When implicit step-up transformer modeling is used, GEOL
works backwards through the transformer to obtain the
terminal conditions.
Checks loading against an assumed reactive capability curve.

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Generator bus (GENS) - Summarizes generating plant


conditions. Shows total plant output at the bus if more
than one machine on a bus.

3-28

GENS VS GEOL
Implicit Generator Step-Up Transformer

XTRAN

GEOL Reports Here

GENS Reports Here

Explicit Generator Step-Up Transformer

GEOL Reports Here

XTRAN

GENS Reports Here

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

3-29

Generator Limit Checking Output


# MACH
BUS# X--NAME--X BASKV ON/OFF TYP
MW
MVAR
QMAX
QMIN
101 NUC-A
21.600 1 0
2 750.0 126.3 400.0 -100.0
102 NUC-B
21.600 1 0
2 650.0 113.1 410.0 -110.0
206 URBGEN
18.000 1 0
2 800.0 283.9 500.0 -400.0
211 HYDRO_G
20.000 1 0
2 600.0
88.1 510.0 -100.0
301 NORTH
765.00 3 0
3 2990.7 898.6 2130.0 -1850.0
401 COGEN-1
500.00 1 0
3 321.0 142.3 600.0 -100.0
402 COGEN-2
500.00 1 0
3 321.0 142.3 610.0 -110.0
3011 MINE_G
19.400 1 0
3 1322.7 155.2 620.0 -120.0
3018 CATDOG_G 13.800 2 0
2 500.0
-0.8 375.0 -225.0
SUBSYSTEM TOTALS
8255.3 1949.1 6155.0 -3115.0

X---- REMOTE BUS -----X


VSCHED VACTUAL BUS# X--NAME--X BASKV MVABAS
1.0100 1.0100
900.0
1.0100 1.0100
950.0
1.0000 1.0000
1000.0
1.0000 1.0000
725.0
1.0000 1.0000
3212.0
1.0000 1.0000
600.0
1.0000 1.0000
610.0
1.0000 1.0000
1050.0
0.9900 0.9900
650.0
9697.0

MACHINE SUMMARY (GEOL):


BUS# X--NAME--X BASKV
101 NUC-A
21.600
102 NUC-B
21.600
206 URBGEN
18.000
211 HYDRO_G
20.000
301 NORTH
765.00
301 NORTH
765.00
301 NORTH
765.00
401 COGEN-1
500.00
402 COGEN-2
500.00
3011 MINE_G
19.400
3018 CATDOG_G 13.800
3018 CATDOG_G 13.800
SUBSYSTEM TOTALS

ID
1
1
1
1
1
2
3
1
1
1
1
2

MW
MVAR
QMAX
QMIN
750.0 126.3 400.0 -100.0
650.0 113.1 410.0 -110.0
800.0 283.9 500.0 -400.0
600.0
88.1 510.0 -100.0
1011.8 434.0 760.8 -597.6
1008.6 434.9 773.0 -555.0
1009.6 435.6 785.1 -554.8
321.0 142.3 600.0 -100.0
321.0 142.3 610.0 -110.0
1322.7 155.2 620.0 -120.0
400.0
-0.6 300.0 -150.0
100.0
-0.2
75.0
-75.0
8294.8 2354.9 6343.9 -2972.4

ETERM CURRENT
1.0100
753.0
1.0100
653.2
1.0000
848.9
1.0000
606.4
1.0319 1066.9
1.0285 1068.0
1.0286 1069.0
1.0000
351.1
1.0000
351.1
1.0000 1331.8*
0.9900
404.0
0.9900
101.0

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

PF
MVABASE
X T R A N
GENTAP
0.9861
900.0
0.9852
950.0
0.9424 1000.0
0.9894
725.0
0.9190 1067.0 0.0140 0.1260 1.0250
0.9183 1070.0 0.0110 0.1270 1.0260
0.9182 1075.0 0.0120 0.1280 1.0270
0.9142
600.0
0.9142
610.0
0.9932 1050.0
1.0000
530.0
1.0000
120.0
9697.0

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

GENERATOR SUMMARY(GENS):

3-30

Power Flow > Reports > Limit Checking >


Reactive capability (GCAP)
Check machine loading against userdefined capability curve.
Q limits from capability curve for actual P
loading in in working case.
Option to update VAR limits in working
case. File extension name: gcp.
Note: Check update VAR limits in working
case for new power flow solutions!
CAPABILITY CURVE CHECK:
BUS#
101
102
206
211
3011
3018

X- NAME -X BASKV
NUC-A
21.600
NUC-B
21.600
URBGEN
18.000
HYDRO_G
20.000
MINE_G
13.800
CATDOG_G 13.800

ID
1
1
1
1
1
1

PGEN
750.0
750.0
800.0
600.0
258.7
100.0

QGEN
81.2
81.2
600.0*
17.7
104.0
80.0

X-- CAPABILITY
QMAX
QMIN
243.8
-37.5
243.8
-37.5
160.0
0.0
583.3
-77.8
270.5 -100.0
80.0
0.0

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

CURVE --X X------- WORKING CASE -------X


PLIMIT
QMAX
QMIN
PMAX
PMIN
900.0
600.0 -100.0
810.0
0.0
900.0
600.0 -100.0
810.0
0.0
1000.0
600.0
0.0
900.0
0.0
950.0
400.0 -100.0
616.2
0.0
1000.0
600.0 -100.0
900.0
0.0
130.0
80.0
0.0
117.0
0.0

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Reactive Capability

3-31

Checking Equipment Controls

Controlling transformers (TLST)


Provides a summary
of controlling transformers.

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Regulated buses (REGB) - Lists regulated buses in the Working


Case, including voltage controlling equipment (generators,
switched shunts, transformer taps)and violations of scheduled
voltage setpoints.

3-32

Direct Report Output (OPEN)


Direct Progress Output (PDEV)
Direct Alert Output (errors and warning messages)
Direct Prompt Output (ODEV)
Set path for use with & filenames (PATH),
e.g. CASE > &filename.sav
PRINTER1

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Input/Output Control

3-33

A.

Pick up case EXER2-2.SAV and find all branches which are loaded above their normal rating (RATEA).

B.

Identify only transformers which are loaded above their normal current rating. (Misc > Change program settings > Transformer
percent units > Current expressed as MVA)

C.

Is there any machine loaded beyond its capability (based on the PSSE-assumed reactive capability curve)? What is the reactive
loss through the step-up transformers for the machines at Bus 100?

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

Problem 3-2 Examining & Checking Power Flow


Results

3-34

Problem 3-2 Examining & Checking Power Flow


Results (continued)

MW
0
2
5
8
10

Max. MVAR Min. MVAR


4
3
2
1
0

-4
-3
-2
-1
0

Solve the case with the new reactive limits using Full Newton-Raphson Solution, using the same solution options as in Problem 22. How does the voltage at bus 201 change? Do not save the case.

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

D. Apply a capability curve to the machine at bus 201 using the following data. You must build a file containing this data with the
text editor then apply this data to case EXER2-2.SAV with Reactive Capability function in Limit Checking Reports. Refer to
Program Operation Manual for the data format. Name this file EXER3-2.GCP

3-35

Problem 3-2 Examining & Checking Power Flow


Results (continued)
Hint:
The format of the reactive capability curve data file is as following:

where:
I:
Bus number. Bus I must has a generator.
ID:
Two character machine identifier
Pi:
Generator active power output along the "MW" axis of the machines capability
curve, entered in MW
QTi: Maximum (i.e., overexcited) reactive power limit at Pi MW, entered in Mvar
QBi: Minimum (i.e., underexcited) reactive power limit at Pi MW, entered in Mvar
* File must end with a 0 bus number

Siemens Power Academy TD NA - PSSC 525 PSSE Fast Track for Power Flow and Dynamics

2013 Siemens Industry, Inc., Siemens Power Technologies International (Siemens PTI)

I, ID, P1, QT1, QB1, P2, QT2, QB2, ... P10, QT10, QB10/

3-36