TECHNICAL ANNEXURE OF LT INDUCTION MOTORS

Document ID

Annexure (ES0122-75650500-MOT-0001)

Revision: 00

Item Code

MOT001

Qty: As below

Description

General Electrical Spec for motor

Sheet : 1 of 4

Item code

Item Description

Element

Total Qty.

1.

Make

SIEMENS (only accepted)

2.

Altitude referring

569 m above mean sea level.

3.

Location

4.

Environment

5.

Application

To be mentioned by Vendor

6.

Rating in KW at starting
method as per clause no.18

To be mentioned by vendor

7.

Speed in RPM

To be mentioned by vendor

8.

Frame size

To be mentioned by vendor

9.

Voltage % / frequency % /
Combined variation %

460 V 10% / 60 Hz 5%
/10 % (Solidly earthed)

10.

System fault level

50 KA at 460 V for 1 sec

11.

Insulation class

12.

Design Ambient Temperature &


permissible temp. rise

13.

Duty

14.

Type

15.

Type of mounting

16.

Degree of Protection

17.

Type of enclosure

TEFC

18.

Starting Method

DOL starter for rating upto 90KW & SOFT


STARTER for rating 110KW and above.

19.

Starting Current

700 %

20.

Method of coupling

To be mentioned by vendor

21.

Direction of rotation

Bi directional

Required for motor rating 75KW and above


ratings

3 wire type RTDs (Platinum, 100 ohm

22.
23.

Anti-condensation heater
Supply Voltage : 230 V, 1
Phase, 60Hz
PTC/RTDs (2 Nos. per phase)

Outdoor / Indoor (Based on location /


application)
Relative humidity (60%), Seismic Zone IV, Max.
wind velocity 45 m/s. Dusty , Tropical

45 C & Class B
70C by resistance & 80C by RTD method
Continuous (S1) / Based on equipment
application
3 Phase, Induction Motor SQ Cage
Horizontal foot mounting (B3) / Based on
equipment application
IP 55 (GI sheet fabricated Canopy to be
supplied for all outdoor duty motors)

Project: M/s. ENERGIA INMEDIATA, S.A


Prepared by: SMR
Reviewed By: NK

APPROVED By : EAM

TECHNICAL ANNEXURE OF LT INDUCTION MOTORS


Document ID

Annexure (ES0122-75650500-MOT-0001)

Revision: 00

Item Code

MOT001

Qty: As below

Description

General Electrical Spec for motor

Sheet : 2 of 4

resistance at 0 C calibrated to DIN


43760 standards) are required in
motor windings.
3 wire Duplex type BTDs are also required in
the bearings of the motor. RTD / BTD
required only for VFD application motors.

24.

Terminal Box
i)
Location
ii)
Angle of rotation
iii)
No. of terminals
iv)
External power cable
size(XLPE insulation)
v)
Cable gland type/size
vi)
Fault level

:
:
:
:
:
:

25.

Applicable codes and standards

26.

Torque v/s Speed curves of


load

27.

28.

29.

Will be specified during GA drawing approval.


50KA for 0.25 Second
The 4th core of the power cable will be
terminated inside the motor terminal box for
earthing connection. Hence the earthing stud
shall be made available both inside and outside
the TB box.
IEC-60034(Latest), IEC-61936, IEC-60071-2
IEC-60064-1,IEC-60721/2/3
To be provided by vendor
GA Drg. Of Motor, Detail of Main Terminal Box
& auxiliary Terminal Boxes, Motor Data Sheet.
Torque & Current Vs Speed, Load Current &

Speed Vs Time, Power factor & Efficiency &


:
Slip Vs Load, Thermal With stand Curve.
Quality Assurance Plan, Motor name plate
detail.

The characteristics curves and


information to be furnished

Motor shall be capable to


starting and accelerating the
load with the applicable
method of starting without
exceeding acceptable winding
temperature when supply
voltage is 80% of the rated
voltage for LV Motor.
Starting duty (No. of Start-ups)
Under full load condition, per
hour
i)
HOT ( Consecutive)
ii)
COLD ( Consecutive)

Shall be decided during drawing approval.


90 o in steps (4x90 deg)
6
Will be specified during GA drawing approval.

80%
:

:
:

1
2
3

Project: M/s. ENERGIA INMEDIATA, S.A


Prepared by: SMR
Reviewed By: NK

APPROVED By : EAM

TECHNICAL ANNEXURE OF LT INDUCTION MOTORS


Document ID

Annexure (ES0122-75650500-MOT-0001)

Revision: 00

Item Code

MOT001

Qty: As below

Description

General Electrical Spec for motor

Sheet : 3 of 4

iii)
30.
31.
32.
33.
34.

35.

36.
37.
38.

Equally spread

Paint shade

:
:

RAL 7032

Starting torque shall be not less than 200 % of rated torque unless otherwise
specified.
Motor shall be capable of withstanding locked rotor current for at least 5 seconds
longer than the starting time under rated load conditions.
Motors shall be suitable to withstand at 150% of rated voltage even at phase
opposition.
Motors shall work satisfactorily at Full Load for 5 minute under 75% voltage
condition.
Hot withstand time of the motor shall be at least 10 seconds longer than the starting
time under rated load conditions, for the motors where the starting time is more
than 30 second. For motors with lesser starting time, a margin of 5 seconds shall be
ensured.
Motor shall be designed to withstand hundred twenty (120) percent of rated speed
without any mechanical damage for two minutes,
The maximum double amplitude vibrations for motors shall be as per IEC IEC-34
(Latest)
Maximum noise level measured at a distance of 1 meter from the outer surface of
the motor shall not exceed 85 db (A).

39.

All Motors shall be energy efficient type (IE2) as per IEC: 60034-30.

40.

All bearing to be of lubricated anti-friction type. No forced lubrication acceptable. Life


of bearings shall be suitable for greater than 20000 working hours for lubricated
bearings and 40000 hours for re-grasable type bearings with 8000 hours without
changing the grease.

41.

Each Motor shall have two earthing terminals.

42.

43.

44.
45.

Break away torque, pull up torque and pull out torque shall be properly coordinated
with the speed torque characteristics of the driven equipment.
Supplier shall be fully responsible for determining motor duty cycle, rating
performance, tests and mechanical arrangement entirely adequate for the duty and
comply with the relevant standards for the applications in the factory, environment
and site conditions.
All VFD driven Motors winding should be VPI TREATED with two coats enameled.
The motor shall be designed to operate both DOL/VFD continuously.
VFD driven Motors rating shall have Insulated Bearing at NDE.

Project: M/s. ENERGIA INMEDIATA, S.A


Prepared by: SMR
Reviewed By: NK

APPROVED By : EAM

TECHNICAL ANNEXURE OF LT INDUCTION MOTORS


Document ID

Annexure (ES0122-75650500-MOT-0001)

Revision: 00

Item Code

MOT001

Qty: As below

Description

General Electrical Spec for motor

Sheet : 4 of 4

46.

47.

VFD driven motors shall be suitable to run on IGBT Based Drives and hence to
be sized to operate satisfactorily under Lowest Speed condition with out
effecting the cooling of motors. Motor speed variation range shall be 30 % to
100 %.
Manufacturer shall submit detailed calculations for adequacy of the motor design
under extreme conditions furnishing motor selection chart for VFD application.
Motor shall be routine tested as per applicable standard by supplier and results to be
furnished to ISGEC. On review of the same motor may be inspected at
manufacturers works by ISGEC.
For TYPE/ROUTINE test by us or our ultimate client. Dispatch clearance shall be
given by us after reviewing the test certificates OR inspection.

All the motors shall be manufactured and tested as per IEC standard only.
Test certificates shall be based on IEC only will be acceptable.
48.

The consumables / often replaced / changed items used in the motors like
lubricants, bearings, coolants, etc., shall be of universally available make
and model. Supplier to confirm this and specify in the motor data sheet.

49.

One set of Motor bearings at drive end and non-drive end per type / rating
of motor shall be supplied along with motor as operational spare.

50.

GI sheet fabricated canopy (Hood) for each motor located in outdoor and
exposed to direct atmosphere application shall be included in the vendor
scope. This is not required for indoor duty type motors.

51.
52.

Motor will have sea worthy packing.


Provision to fix the Vibration monitoring probes for Boiler Feed pump motors, Main
cooling water pump motors, and all fan motors.

Project: M/s. ENERGIA INMEDIATA, S.A


Prepared by: SMR
Reviewed By: NK

APPROVED By : EAM