CHAPTER-1
INTRODUCTION TO POWER SYSTEM
PER UNIT SYSTEM
The equipment such as transformers, transmission lines, machines, generators, condenser,
etc. used in the power systems are represented by its electrical equivalent circuit consisting of
impedances, admittances. The value of these variables are given in terms of its actual value based
on the ratings of the equipment. The system uses many equipment with different ratings. This
needs the calculation of other variables on the actual basis. Thus to avoid heterogeneity of
calculations, a common mode of representing the variables is used. This is known as per unit
system.
In per unit system, the power system variables such as voltage, current and impedances etc.
are represented on a common base. For this purpose we need to define base quantity of the system.
Generally two base quantities Base KVA or Base MVA and Base KV are defined and others can
be calculated.
Let
Base Current = I Base
Base Impednace = Z Base
I Base
Z Base
Base KVA1
Base KVLN
2
Base KVLN
X 10 3
Base KVA1
(1.1)
(1.2)
Z Base
2
Base KVLN
Base MVA1
(1.3)
Base KVA3
I Base
(1.4)
3 X Base KVLL
2
Z Base
Base KV LL
X 10 3
3
Base KVA3
Z Base
Z Base
(1.5)
Base KVLL 2
(1.6)
Base KVLL 2
(1.7)
X 10 3
Base KVA3
Base MVA3
(1.8)
V p.u.
V Actual
VBase
(1.9)
I p.u.
I Actual
I Base
(1.10)
Z p.u.
Z Actual
Z Base
(1.11)
MVA p.u.
MVAActual
MVABase
(1.12)
Many a times the per unit quantities need to be calculated to a new base. It can be done by
calculating the actual value at first and then converted to per unit on a new base.
Let the old base is given by BaseKVOld , BaseMVAOld and new base is given by
BaseKV New , BaseMVANew .
The old and new per unit value of impedance is given by Z p.u..(Old ) & Z p.u..(New) respectively.
From (1.11) we get at the old base:
Base KV
LL(Old)
(1.13)
Base KV
LL(New)
(1.14)
Z p.u..(New) Z p.u..(old) X
Z p.u..(New) Z p.u..(old) X
Base KV
LL(Old)
Base KV
Base KV
X
Base KV
X
(1.15)
LL(New)
LL(Old)
LL(New)
(1.16)
Base KVLL(Old)
X
Base KV
LL(New)
(1.17)
By (1.17) the per unit impedance can be calculated on the new base.
POWER FLOW IN A TRANSMISSION LINE
The power flow in a transmission line can be calculated by considering the system shown
in Fig.-1.1. It consists of a single transmission line connected between two buses. These buses are
known as Sending end bus and Receiving end bus.
A A , B B
So that the power received at the receiving end is given by
S R PR jQR VR I R*
(1.18)
(1.19)
I S CVR DI R
(1.20)
From (1.19)
IR
VS AV R
B
(1.21)
V AV R
I S
*
R
I R*
(1.22)
A VR 0
(1.23)
PR jQ R VR 0
A VR 0
(1.24)
V R VS
B
VR
(1.25)
V R VS
B
Cos
VR
Cos
2
V R VS
VR A
QR
Sin
Sin
B
B
(1.26)
(1.27)
For the transmission line series resistance is very less as compared to series reactance and
A 1.0, 0.0, B Z X , 90
Hence (1.26) can be fairly approximated as (1.28)
PR
V R VS
X
Sin
(1.28)
From (1.28) we conclude that the power transmitted over a transmission line is determined
by the voltage at both the ends, the reactance of the line and phase difference between the voltages
of both ends. Similarly the power flow between two buses can be given by (1.29)
10
V1 V2
X 12
Sin 1 2
(1.29)
LINE COMPENSATION
As stated above the power flow in a transmission line depends upon the voltage at both the
ends, the reactance of the line and phase difference between the voltages. If the power flow has to
be increased or decreased then e have to control these variables. It can be controlled by
Once the installation of the transmission line is over its A, B, C, D parameters are constant
because these depend upon the size and material of conductors and the configurations of the
conductors. And hence the value of reactance and resistance are also fixed. The value of reactance
Series compensation
Shunt compensation
11
12
If the magnitude of voltage at the bus is less than the required magnitude then the shunt
capacitor is connected. If the magnitude of voltage at the bus is more than the required magnitude
then the shunt reactor is connected. Other way we can say, the shunt capacitor is used to improve
the voltage and the shunt reactor is used to avoid the overvoltage.
With the insertion of compensation the circuit parameters changes and thus the operation
of the power system. The line compensation provides:
Voltage control
Improved stability
Improved security
Modern power system uses flexible AC transmission system (FACTS) devices to achieve
required degree of compensation and thus control over the system operation.
CHAPTER-2
B US I MPEDANCE M ATRIX
The bus impedance matrix Z BUS can be determined for a ' N bus' power system by using
the algorithm described as below. By using this algorithm Z BUS can also be modified. The existing
Z BUS can be modified either by addition of a new bus or a new link. A new bus can be added to
the system by connecting it to either reference bus through a link or an existing bus through a link.
A new link can be added to the system by connecting it between reference bus and existing bus or
between two existing bus. Thus Z BUS can be modified in four ways.
The block diagram of ' N bus' power system is shown in Fig.-2.1.
Where,
'Vi ' - Voltages at the ' i th ' bus
' I i ' - Currents injected at the ' i th ' bus
N-Bus Power
System
13
14
Z BUS
Z 11
Z
21
Z N1
Z 12
Z 22
ZN2
Z 1N
Z 2 N
Z NN
(2.1)
(2.2)
Where
V BUS
V1
V
2
V N
(2.3)
I BUS
I1
I
2
I N
(2.4)
V1 Z 11
V Z
2 21
V N Z N 1
Z12
Z 22
ZN2
Z 1N I 1
Z 2 N I 2
Z NN I N
(2.5)
It means
Vi I1 Z i1 I 2 Z i 2 I i Z ii I j Z ij I N Z iN
(2.6)
CASE-1 ADDITION OF A NEW BUS ' p' TO REFERENCE BUS THROUGH LINK Z b
The system is modified by addition of a new bus ' p' to a reference bus through link Z b as
shown in Fig.-2.2.
N-Bus Power
System
The system voltage equation of (2.5) is modified as a new bus ' p' is added because the
current injected at bus ' p' introduces the voltage drop I p Z b and the voltage of bus ' p' , V p equals
this voltage drop. It implies the system is modified by the addition of a new row in (2.5) as follows.
Z 12 Z 1N
0 I1
V1 Z 11
V
0 I 2
2 Z 21 Z 22 Z 2 N
0 I N
V N Z N 1 Z N 2 Z NN
0
0
Z b I p
V p 0
Z BUS , New
Z 12 Z 1N
0
Z 11
Z
0
21 Z 22 Z 2 N
0
Z N 1 Z N 2 Z NN
Z b
0
(2.7)
(2.8)
15
16
Z BUS , New
Z BUS ,Original
Z b
0
(2.9)
CASE-2 ADDITION OF A NEW BUS ' p' TO AN EXISTING BUS ' k ' THROUGH Z b
The bus impedance matrix can be modified with the addition of a new bus to an existing
bus through a link as shown in Fig.-2.3.
N-Bus Power
System
FIG. 2.3 ADDITION OF NEW BUS ' p ' TO AN EXISTING BUS ' k '
With the addition of a link, the voltage at the k th bus is updated by the voltage drop of
I p Z pp due to current injection of ' i p ' at the p th bus and given by
Vk ,new Vk ,original I p Z kk
(2.10)
Where
Vk ,original I1 Z k1 I 2 Z k 2 I k Z kk I N Z kN
(2.11)
V p Vk I p Z b Vk ,original I p Z kk I p Z b
(2.12)
V p I 1 Z k1 I 2 Z k 2 I N Z kN I p Z kk Z b
(2.13)
Vk , original
Thus the system voltage as mentioned in (2.5) can be modified as per (2.14) and so is the
bus impedance matrix (2.15).
Z 12 Z 1N
Z 1k I 1
V1 Z 11
V
Z 2 k I 2
2 Z 21 Z 22 Z 2 N
Z Nk I N
V N Z N 1 Z N 2 Z NN
Z kk Z b I p
V p Z k1 Z k 2 Z kN
(2.14)
Z BUS , New
Z 12 Z 1N
Z 1k
Z 11
Z
Z 2 k
21 Z 22 Z 2 N
Z Nk
Z N 1 Z N 2 Z NN
Z kk Z b
Z k1 Z k 2 Z kN
(2.15)
Z BUS , New
Z 1k
Z 2 k
Z BUS ,Original
Z Nk
Z kN
Z kk Z b
Z k1 Z k 2
(2.16)
17
18
N-Bus Power
System
FIG.-2.4 ADDITION OF NEW LINK BETWEEN THE EXISTING BUS ' k ' AND REFERENCE BUS
The addition of new link having impedance Z b between the existing bus ' k ' and reference
bus can be regarded as the addition of a new bus ' p' to an existing bus ' k ' through Z b . Then new
bus ' p' is shorted with the reference bus. That means the voltage equations shall be updated by as
per (2.14) then V p equals to zero as follows.
Z 12 Z 1N
Z 1k I 1
V1 Z 11
V Z
Z 2 k I 2
2 21 Z 22 Z 2 N
Z Nk I N
V N Z N 1 Z N 2 Z NN
Z kk Z b I p
0 Z k1 Z k 2 Z kN
(2.17)
Z 1k I 1
V1
V
Z 2 k I 2
2
Z Bus,Original
Z Nk I N
V N
Z kN
Z kk Z b I p
0 Z k1 Z k 2
(2.18)
The new bus impedance matrix can be calculated after reducing the Z BUS in (2.18) by
eliminating the last row and last column using Krons reduction.
Z hi,new Z hi,old
Z h ( n1) Z ( n1)i
Z kk Z b
(2.19)
The resulting Z hi,new shall be new bus impedance matrix Z BUS ,new .
ADDITION OF NEW LINK HAVING IMPEDANCE Z b BETWEEN TWO EXISTING
BUSES ' j ' AND ' k '
A new link having impedance Z b can be added between two existing buses ' j ' and ' k ' as
shown in Fig.-2.5
N-Bus Power
System
By adding a link between j th bus and k th bus the current injected at the j th bus and
k th bus are modified to I j I b and I k I b where I b is current flowing through the link Z b .
(2.20)
(2.21)
19
20
(2.22)
V1
V10
V1 V10 V1
(2.23)
Similarly
V j V j0 V j
Vk Vk0 Vk
V j I1 Z j1 I 2 Z j 2 I j Z j j I k Z jk I N Z jN I b Z j j Z jk
(2.24)
Vk I1 Z k1 I 2 Z k 2 I j Zk j I k Z kk I N Z kN I b Zk j Z kk
(2.25)
V j Vk Z j1 Z k1 I 1 Z j 2 Z k 2 I 2 Z jj Z kj I j Z kj Z kk I k
Z jN Z kN I N Z jj 2Z jk Z kk I b
(2.26)
But the addition of link Z b has resulted in the network equation (2.26)
Vk V j I b Z b
(2.27)
I b Z b V j Vk 0
(2.28)
I b Z b Z j1 Z k1 I 1 Z j 2 Z k 2 I 2 Z jj Z kj I j Z kj Z kk I k
Z jN Z kN I N Z jj 2Z jk Z kk I b 0
Z Z I Z Z I Z Z I Z
Z Z I Z 2Z Z Z I 0
j1
k1
jN
kN
j2
k2
jj
jj
jk
kk
kj
kj
Z kk I k
(2.29)
(2.30)
(2.30) suggests addition of new row and new column in (2.5) as follows.
V1 Z 11
V Z
21
2
V N Z N 1
0 Z j1 Z k1
Z12
Z 22
ZN2
Z j 2 Z k 2
Z 1N
Z 2N
Z NN
Z jN Z kN
Z
Z
Z1k
I1
2 j Z 2k
I2
Z Nj Z Nk I N
Z jj 2Z jk Z kk Z b I b
1j
(2.31)
V1
V
2
Z BUS ,Original
V N
0 Z j1 Z k1 Z j 2 Z k 2
Z jN Z kN
Z
Z
Z1k
I1
2 j Z 2k
I2
Z Nj Z Nk I N
Z jj 2Z jk Z kk Z b I b
1j
(2.32)
The new bus impedance matrix can be calculated after reducing the Z BUS in (2.32) by
eliminating the last row and last column using Krons reduction.
Z hi,new Z hi,old
Z h ( n 1) Z ( n 1)i
jj
2Z jk Z kk Z b
(2.33)
The resulting Z hi,new shall be new bus impedance matrix Z BUS ,new .
As described above the bus impedance matrix for a power system can be formed by using
above algorithm by consideration of adding either one bus or one link at a time.
Advantages
For any single modification in case of any single outage of a link or a node, new
bus impedance matrix can be obtained with less computation time.
21
22
B US A DMITTANCE M ATRIX
The system voltage for a ' N bus' power system shown in Fig.-2.1 is given in (2.2)
VBUS Z BUS I BUS
(2.34)
It can be rewritten as
I BUS YBUS VBUS
(2.35)
YBUS
YN 1 YN 2 YNN
(2.36)
The bus admittance matrix YBUS for a ' N bus' power system shown in Fig.-2.1 can be
determined by inverting bus impedance matrix Z BUS or the vice versa as in (2.37)
YBUS Z BUS
(2.37)
Z BUS YBUS
(2.38)
(2.39)
I i YiiVi
(2.40)
i 1
The diagonal element of the YBUS such as Yii is the self-admittance of i th bus . It can be
determined by adding all the admittances connected at i th bus .
The off-diagonal element of the YBUS such as Yij is the transfer admittance between the
i th bus and j th bus . It can be determined by adding all the admittances connected between the
CHAPTER-3
LOAD FLOW ANALYSIS
POWER FLOW
A ' N bus' power system is shown in Fig.-3.1. The power flow at the i th bus can be
given by
Si Vi I i* Pi jQi
(3.1)
For all i 1,2,3,, N
(3.2)
N-Bus Power
System
In a power system having ' N ' number of buses the current at the i th -bus can be determined
as
23
24
I i YijV j
(3.3)
j 1
(3.4)
j 1
Since the voltage at the i th bus can be given by its magnitude and phase angle Vi Vi i
the above equation can be modified as
N
Y
j 1
ij
V j ( ij j i )
(3.5)
Therefore the real and reactive power at the i th bus can be given by
N
Pi Vi Y ij V j cos( ij j i )
(3.6)
j 1
Qi Vi Y ij V j sin( ij j i )
(3.7)
j 1
The real and reactive power at the i th bus can be given by (3.8) and (3.9) respectively.
Pi PGi PDi
(3.8)
Qi QGi QDi
(3.9)
Where
PGi , PDi - Real power generation and demand at the i th bus (Fig.-3.2)
QGi , QDi - Reactive power generation and demand at the i th bus (Fig.-3.3)
i th bus
i th bus
TYPES OF BUSES
In power system the buses can be classified as
Slack bus: At this bus V and are defined.
Load bus: At this bus P and Q are defined. ( PQbus)
Voltage controlled bus: At this bus P and V are defined ( PV bus)
GAUSS SIEDEL METHOD FOR POWER FLOW
For all ( PQbus) from (3.5) we can calculate the voltage at the i th bus as follows
Vi
Yii
Vi*
j 1
Y V
j i 1
ij
(3.10)
k th iteration .
Vi ( k )
( k 1)*
Yii
Vi
j 1
Y V
j i 1
ij
( k 1)
j
Vi ( k ) Vi ( k ) Vi ( k 1)
(3.11)
(3.12)
(3.13)
k)
(k )
( k 1)
Vi (( acc
) Vi ( acc) Vi ( acc)
(3.14)
25
26
The value of acceleration factor is usually between 1.1 to 1.4. The value of 1.2 is found to
be the most perfect.
For all ( PV bus) the voltage magnitude is already specified. Hence at this bus the value
of reactive power injected is calculated by(3.16) and checked for limit violence by (3.17).
Qi im Vi* Yij V j
j 1
(3.15)
For k th iteration
N
i 1
Qi( k ) im Vi ( k 1)* YijV j( k ) YijV j( k 1)
j i
j 1
(3.16)
(3.17)
If the limit is violated then the value of Qi at this bus is set to its lower limit or upper limit
as the case may be and the bus is treated as the load bus i.e. ( PQbus) . If the limit is not violated
then the revised value of i is calculated using (3.18)
ik Vi k
(3.18)
(3.19)
After calculation of the voltages of all the buses both ( PQbus) and ( PV bus) , then
the difference in the magnitude of voltages (calculated in this iteration) and the magnitude of
voltages (calculated in the previous iteration) is calculated using (3.20).
Vi ( k ) Vi ( k ) Vi ( k 1)
(3.20)
(3.21)
j 1
j 1
S1 V1 I 1* P1 jQ1 V1 Y1 jV j* V1 Y 1 j V j (1 j j 1 )
(3.22)
PV Bus
Yes
PQ Bus
No
If Q(i) Q(i)min then
Set Q(i)= Q(i)min
If Q(i) Q(i)max then
Set Q(i)= Q(i)max
Calculate (i) as
per (3.18) and
update V(i)
angle
No
Yes
No
Yes
FIG.-3.4 FLOW CHART FOR LOAD FLOW USING GAUSS SEIDEL METHOD
27
28
The line power flow between i th bus and j th bus can be given by (3.23)
(3.23)
The complete algorithm for load flow calculation has been given in flow chart shown in
Fig.-3.4.
NEWTON RAPHSON METHOD
The set of equations (3.6) and (3.7) for real and reactive power at the i th bus can be given
rewritten as
N
Pi Vi Gii Vi Y ij V j Cos ( ij j i )
2
(3.24)
j 1
j i
Qi Vi Bii Vi Y ij V j Sin ( ij j i )
2
(3.25)
j 1
j i
(3.26)
Qi f V ,
(3.27)
Pi
N
Qi
Qi
j
V j
j 1 j
j 1 V j
(3.28)
Qi
(3.29)
N
Pi
P
Pi
j i V j
j 1 j
j 1 V j
N
(3.30)
N
Qi
Qi
j
V j
j 1 j
j 1 V j
N
Qi
(3.31)
j 1 j
j 1 V j
Pi
P
i V
j
V
j
N V
Qi
j Qi
j
V j
j 1 j
j 1 V j V j
Vj
Vj
(3.32)
Qi
(3.33)
Pi
N
Qi
Pi V j
j V j
Vj Vj
j 1 j
j 1
(3.34)
Qi
(3.35)
However for a given value of real and reactive power at the i th bus we can calculate the
deviation from the schedule value to calculated value
Pi Pi ( sch) Pi (calc)
(3.36)
Qi Qi ( sch) Qi (calc)
(3.37)
(for all i 2,3,, N ) since the value of P, Q are not known at the slack bus. Where
(3.38)
(3.39)
29
30
(3.40)
j 1
j i
(3.41)
j 1
j i
P2
2
P
N
2
Q2
Q N
2
P2
N
PN
N
Q2
Q N
P2
V2
P
V2 N
V2
Q2
V2
V2
Q N
V2
V2
V2
P2
V N
PN
V N
V N
Q2
V N
V N
Q N
V N
V N
V N
P2
V2 PN
Q2
V
2
2 Q N
V2
(3.42)
The first matrix of the above equation is known as Jacobian matrix J of the power
system. It has 2 N 2X 2 N 2 dimension if all the buses except slack bus are load buses. The
Jacobian matrix J of the power system shall have four sub-matrices as shown below (3.43)
J 11
J 21
J 12
J 22
(3.43)
J 11
Pi
Vi Y ij V j Sin ( ij j i )
j
(3.44)
J 11
N
Pi
2
Vi Y ij V j Sin ( ij j i ) Qi Vi Bii
i
j 1
(3.45)
j i
J 12
Qi
Vi Y ij V j Cos ( ij j i )
j
(3.46)
N
Qi
2
Vi Y ij V j Cos ( ij j i ) Pi Vi Gii
i
j 1
(3.47)
j i
J 21 V j
Pi
Vj
Vi Y ij V j Cos( ij j i )
Qi
j
(3.48)
N
Pi
2
Vi
Vi 2 Vi Gii Y ij V j Cos ( ij j i ) Pi Vi Gii
Vi
j 1
j i
(3.49)
J 22 V j
Qi
Vj
Vi Y ij V j Sin ( ij j i )
Pi
j
(3.50)
N
Qi
2
Vi
Vi 2 Vi Bii Y ij V j Sin ( ij j i ) Qi Vi Bii
Vi
j 1
j i
(3.51)
J 12 i Pi
Vi
Q
J 22
Vi i
(3.52)
31
32
i
Vi J 11
J
Vi 21
J 12 Pi
(for all i 2,3,, N )
J 22 Qi
(3.53)
(3.53) gives the amount by which the voltage magnitude and phase angle has to be updated.
Hence the updated value of the voltage magnitude and phase angle becomes
i i i
(3.54)
Vi Vi Vi
(3.55)
Vi
(3.56)
j 1
j 1
S1 V1 I 1* P1 jQ1 V1 Y1 jV j* V1 Y 1 j V j (1 j j 1 )
(3.57)
The line power flow between i th bus and j th bus can be given by (3.23)
(3.58)
The complete algorithm for load flow calculation has been given in flow chart shown in
Fig.-3.5 only for load buses. This flow chart does not incorporate the voltage controlled bus.
Calculate mismatch
P(i), Q(i) as per
(3.36) and (3.37)
Calculate Jacobian
by (3.44) and (3.51)
Calculate
Corrections (i),
V(i) by (3.53)
Increment Iteration
Count k=k+1
No
Yes
FIG.-3.4 FLOW CHART FOR LOAD FLOW USING NEWTO MN RAPHSON METHOD
(ONLY LOAD BUSES)
33
34
J to 2 N 2 1X 2 N 2 1 .
CHAPTER-4
POWER SYSTEM STABILITY
The following definitions provide the foundation for transient stability and small-signal
stability analysis.
1) Disturbance in a Power System. A disturbance in a power system is a sudden change or
a sequence of changes in one or more of the operating parameters of the system, or in one or more
of the operating quantities.
2) Small Disturbance in a Power System. A small disturbance is disturbance for which the
equations that describe the dynamics of the power system may be linearized for the purpose of
analysis.
3) Large Disturbance in a Power System. A large disturbance is a disturbance for which
the equations that describe the dynamics of the power system cannot be linearized for the purpose
of analysis.
4) Steady-State Stability of a Power System. A power system is steady-state stable for a
particular steady-state operating condition if, following any small disturbance, it reaches a steadystate operating condition which is identical or close to the pre-disturbance operating condition.
This is also known as small disturbance stability of a power system.
5) Transient Stability of a Power System. A power system is transiently stable for a
particular steady-state operating condition and for a particular disturbance if, following that
disturbance, it reaches an acceptable steady-state operating condition.
The transient stability analysis involves more detailed nonlinear models, solution
techniques, and includes steady-state stability analysis of the operating condition that will be
reached following the transient. Traditionally, the stability problem has been associated with
maintaining synchronous operation. In the evaluation of stability, the concern is the behavior of
the power system when subjected to a disturbance. The disturbance may be small or large. This
aspect of stability is influenced by the dynamics of the generator rotor angles and the power-angle
relationships and is referred to as rotor angle stability.
35
36
A NGLE STABILITY
INTRODUCTION
In general, the components of the power system that influence the electrical and mechanical
torques of the synchronous machines are listed below.
1) The transmission network before, during, and after the disturbance.
2) The loads and their characteristics.
3) The parameters of the synchronous machines.
4) The control components of the synchronous machines (excitation systems, power system
stabilizers).
5) The mechanical turbine and the speed governor.
6) Other power plant components that influence the mechanical torque.
7) Other control devices, such as supplementary controls, special protection schemes, and
FACTS (Flexible AC Transmission System) devices that are deemed necessary in the
mathematical description of the system.
The power system stability is defined as the property of the system which enables the
synchronous machines of the system to respond to a disturbance from a normal operating
conditions so as to return to conditions where their operation is again normal.
Transient stability: It is defined as the property of the system which enables the
synchronous machines of the system to respond to a major disturbances such as transmission line
faults, sudden load changes, loss of generation or line switching, from a normal operating
conditions so as to return to conditions where their operation is again normal. Or we can say,
Transient stability is the ability of the power system to maintain synchronism when subjected to
large disturbances. The system equations for a transient stability study are usually nonlinear.
Dynamic Stability: It is defined as the property of the system which enables the
synchronous machines of the system to respond to a disturbance from a normal operating
conditions so as to return to conditions where their operation is again normal. Or we can say,
Small-signal (small-disturbance) stability is the ability of the power system to maintain
synchronism under small disturbances. Instability can result in the form of 1) steady increase in
rotor angle due to lack of sufficient synchronizing forces, or 2) rotor oscillations due to lack of
sufficient damping forces. In today's power systems, small-signal stability is largely a problem of
insufficient damping of oscillations.
FUNDAMENTAL ASSUMPTIONS
Only system frequency currents and voltages are considered in the stator winding
and the power system. Consequently dc offset currents are neglected.
d 2 m
Ta Tm Te
dt 2
(4.1)
m smt m
(4.2)
d m
d
sm m
dt
dt
(4.3)
37
38
d 2 m d 2 m
dt 2
dt 2
(4.4)
d m
d m
0
is constant if
dt
dt
d m
Represents the deviation of rotor speed from synchronism
dt
(4.4) and (4.1) yields
d 2 m
J
Ta
dt 2
To introduce
(4.5)
d m
for angular velocity of rotor
dt
d 2 m
J m
Pa Pm Pe
dt 2
(4.6)
d 2 m
Pa Pm Pe
dt 2
(4.7)
In machines
2
1
J sm
M sm
H
2
S mach
S mach
1
2
2H
sm
(4.8)
S mach MJ / mech.rad.
P
P Pe
2 H d 2 m
a m
2
sm dt
S mach
S mach
(4.9)
2 H d 2
Pa Pm Pe p.u.
s dt 2
(4.10)
H d 2
Pa Pm Pe ( - electrical radian)
f dt 2
(4.11)
2 H d 2
Pa Pm Pe p.u.
s dt 2
(4.12)
(4.13)
d
s p.u.
dt
(4.14)
H system H mach
S mach
S system
(4.15)
2 H 1 d 2 1
Pm1 Pe1
s dt 2
(4.16)
For Machine-2
2 H 2 d 2 2
Pm 2 Pe 2
s dt 2
(4.17)
d 2 1 d 2 2 s Pm1 Pe1 Pm 2 Pe 2
2 H 1
H 2
dt 2
dt 2
(4.18)
39
40
H1H 2
H1 H 2
2 H 12 d 2 12
Pm12 Pe12
s dt 2
(4.19)
Where
H 12
H1 H 2
H1 H 2
Pm12
Pm1 H 2 Pm 2 H 1
H1 H 2
Pe12
Pe1 H 2 Pe 2 H 1
H1 H 2
(4.20)
(4.21)
(4.22)
2 H d 2 0
Pm Pe 0 Pe
s
dt 2
(4.23)
2 H d 2
Pmax cos 0 0
s dt 2
(4.24)
0 is constant value
Pmax cos 0 - slope of power angle curve at angle 0
Sp
dPe
d
d 2 s
S P 0
2H
dt 2
(4.25)
It is the linear second order equations and solutions of which depends on algebraic sign of
S p . If S p is positive then solution shall be simple harmonic motion. If S p is negative then solution
n
fn
s S p
2H
1
2
s S p
2H
Hz
(4.26)
(4.27)
The electrical power output is suddenly reduces to Zero whereas the mechanical
power input remains the same i.e. unchanged.
Due to which the difference in power input and power output must be accounted
for by a rate of change of Kinetic Energy of the rotor mass.
41
42
f
e
d 2 s
Pm
2H
dt 2
(4.28)
d
s Pm dt s Pm t
dt 0 2 H
2H
t
So that
s
4H
Pm t 2 0
(4.29)
(4.30)
At the instance of fault clearing 0 advances to c due to increase in rotor speed and angle
is given by
d
dt
t t c
t t t
c
s
2H
s
4H
Pm t c
(4.31)
Pm t c2 0
(4.32)
f
e
At f the rotor speed is again synchronous although rotor angle has advanced to x
Angle x is determined with the fact that area ' A1 ' and ' A2 ' must be equal.
Rotor angle moves back from at f along the power angle curve to point a.
From a to i exceeds and the rotor increases speed again until it reaches at
i as shown in Fig.-4.3. Point i is located so that area 3 and 4 are equal.
43
44
In the absence of damping, rotor would continue to oscillate in the sequence f-a-i,
i-a-f with synchronous speed occurring at i and f.
When one m/c is swinging with respect to infinite bus we may use this principle of equity
of areas called equal area criterion, to determine the stability of system under transient condition,
without solving the swing equation.
The swing equation is:
2 H d 2
Pm Pe
s dt 2
(4.33)
(4.34)
d r d 2
2
dt
dt
(4.35)
2 H d r
Pm Pe
s dt
(4.36)
d
dt
2 H d r
d
( r ) Pm Pe
s dt
dt
(4.37)
H d r2
d
Pm Pe
s dt
dt
(4.38)
d
2
r
Pe d
(4.39)
Pe d
(4.40)
This equation applies to any two points 1 and 2 on power angle curve provided they are
points at which the rotor speed is synchronous.
Performing integration in two steps for points 0 and x for Fig.-4.2.
c
Pm Pe d Pm Pe d
Pe d
(4.41)
Pe d
(4.42)
The corresponding time for clearing the fault is called critical clearing time t cr
A5
cr
Pe d
(4.43)
(4.44)
45
46
A6
max
max
Sin Pm d
(4.45)
cr
(4.46)
Pm
max cr Cos max
Pmax
(4.47)
Cos cr
Cos cr
Pmax Sin 0
2 0 Cos 0
Pmax
(4.48)
(4.49)
s
4H
Pm t 2 0
cr
s
4H
Pm t cr2 0
(4.50)
t cr
4 H cr 0
s Pm
(4.51)
f
a
c
O
FIG.-4.5 POWER ANGLE CURVE FOR THE GENERATOR (POWER TRANSMITTED DURING FAULT)
In many cases, the power is still transmitted under fault, if the fault is other than short
circuit or 3 fault as show in Fig.-4.5.
Hence under such case the electric power transmitted during the fault, is given by
Pe1 r1 Pmax Sin
(4.52)
And the electric power transmitted after the fault is cleared, is given by
Pe 2 r2 Pmax Sin
(4.53)
As per equal area criteria area A7 and A8 are equal. Thus we can write from (4.
The corresponding time for clearing the fault is called critical clearing time t cr
A7
cr
Pe1 d
(4.54)
A8
max
e2
Pm d
(4.55)
(4.56)
cr
(4.57)
Cos cr
Pm
max 0 r2 Cos max r1Cos 0
Pmax
r2 r1
(4.58)
Hence critical clearing angle can be calculated by using (4.58) for the case when the power
is still being transmitted under fault condition.
MULTI-MACHINE STABILITY (CLASSICAL REPRESENTATION)
The equal area criterion can not be used directly in system where three or more machines
are represented. When many machines are simultaneously undergoing transient oscillation the
swing curve will reflect the combined presence of many such oscillations.
The following additional assumptions are made
The mechanical power to each machine constant during the entire period of swing
curve computation
47
48
The mechanical rotor angle of each machine coincides with , the electrical phase
angle of the transient internal voltage.
All loads may be considered as shunt impedance to ground with values determined
by conditions prevailing immediately prior to the transient conditions.
The system stability model based on these assumptions is classical stability model and
classical stability studies.
In multi-machine case two preliminary steps are required
Pre-fault network representation is determined and modified to account for the fault
and the post-fault conditions.
The angular velocity is constant throughout any interval at the value computed for
the middle of the interval Fig.-4.7.
However, neither of the assumptions are true because is changing and both Pa and
are function of Fig.-4.8.
The change in speed is the product of the acceleration and time interval and so
49
50
r n1 / 2 r n3 / 2
d 2
180 f
t
Pa ,n1t
2
H
dt
(4.59)
(4.60)
n n n1 tr n1 / 2
(4.61)
Where, K
(4.62)
180 f
t 2
H
The accelerating power is calculated at the beginning of each new interval. Greater
accuracy is obtained when the duration of interval is small.
An interval of 0.05s is usually satisfactory.
Excitation system
Excitation effect is to reduce the initial rotor angle swing following the fault
Initial fault
Voltage reduced
1
cycle gain in critical
2
51
52
V OLTAGE S TABILITY
INTRODUCTION
Instability may also be encountered without loss of synchronism. A system could become
unstable because of the collapse of voltages at certain buses in the system. In this instance, the
concern is stability and control of voltage. The analysis in this case deals with the ability of the
power system to maintain steady acceptable voltages at all buses in the system under normal
operating conditions and after being subjected to disturbances. The main factor causing instability
is the inability of the power system to meet the demand. Voltage instability takes on the form of a
dramatic drop of transmission system voltages, which may lead to system disruption. During the
past two decades it has become a major threat for the operation of many systems and, in the
prevailing open access environment, it is a factor leading to limit power transfers.
The transfer of power through a transmission network is accompanied by voltage drops
between the generation and consumption points. In normal operating conditions, these drops are
in the order of a few percents of the nominal voltage. One of the tasks of power system planners
and operators is to check that under heavy stress conditions and/or following credible events, all
bus voltages remain within acceptable bounds. In some circumstances, however, in the seconds or
minutes following a disturbance, voltages may experience large, progressive falls, which are so
pronounced that the system integrity is endangered and power cannot be delivered correctly to
customers. This phenomenon is referred to as voltage instability and its result as voltage collapse.
This instability stems from the attempt of load dynamics to restore power consumption beyond the
amount that can be provided by the combined transmission and generation system.
BASIC THEORY
The following changes in power system contribute to voltage collapse.
Increase in loading
x f x, y,
.
0 g x, y,
x -state variable,
y -Algebraic variables
Pu,
Qu, F u, 0
V
Where u
53
54
SENSITIVITY FACTORS
dV
VSFi max i
dQi
SF
dZ
d
SINGULAR VALUES
J Dz F z 0 , 0
At equilibrium
n
J R S T i i siT
i 1
where
-Diagonal Matrix can be given by
1
2
n
i , siT - ith column of the unitary matrices R and S and known as singular values
Singular value decomposition is used to determine the rank of matrix and equal to the
number of no-zero singular values of J.
It monitors smallest singular value
J WU T wi i viT
i 1
Maximum entries in ' w' indicates the most sensitive voltage magnitudes (critical buses)
Maximum entries in 'v' indicates the most sensitive direction for changes of power
injections.
Second order proximity index
Voltage instability proximity index
Only a ppair of solution remains near the collapse point and then coalesces on it
VIPI uses this pair on rectangular coordinates
LOADING MARGIN
Most basic and widely accepted index of voltage collapse
Not based on particular power system model only requires static power system model
Takes full account of power system non-linearity and limits
Account for the patterns of load increase
Energy Function
Reacitve power margin
Tangent vectors
55
56
CHAPTER-5
ECONOMIC OPERATION OF POWER
SYSTEM
The proper distribution of the output of a plant between the generator or units within the
plant is very much necessary to determine for economic operation of the power system. We can
also study a method of expressing transmission loss as a function of the outputs of the various
plants. The power system consists of many equipment. The cost involved for installation of these
equipment can be regarded as the capital cost. The cost involved for the operation of these
equipment is known as variable cost. Further the interest incurred on capital cost can form a part
of the variable cost. The variable cost also depend on the power output. Hence the variable
operating cost of the units must be expressed in in terms of power output. In general the power
output is directly proportional to the fuel input. Hence fuel cost can also be function of output.
=
()
dFi
. Where
dPi
For economic division of load between units within a plant is that all units must operate at
the same incremental fuel cost
For a plant with N units, the total cost of fuel can be given (5.1), whereas the total load is
given by (5.2).
N
FT F1 F2 F N Fi
(5.1)
i 1
PR P1 P2 P N Pi
(5.2)
i 1
dFT
FT
F
F
dP1 T dP2 T dPN 0
P1
P2
PN
(5.3)
(5.4)
FT
P2
PN
(5.5)
F
F1 F2
N
P1 P2
PN
(5.6)
(5.7)
Where
a, b, c are the coefficients representing the variable and fixed part of the cost components.
In this method only the fuel cost of only one unit will vary if only the power output of that
unit is varied. The procedure is known as Lagrangian multiplier.
CRITERION FOR DISTRIBUTION OF THE LOAD CONSIDERING THE LOSSES
If the load has to be distributed between the power stations then the losses incurred in
transmission of power has to be taken into account. These losses are also function of plant
57
58
generation. Let us take an example system shown in Fig.-5.1. In this system two generating stations
'a' and 'b' are connected by a transmission line having sections as shown. The load is connected
at bus 'c' .
a
c
FIG.-5.1 POWER SYSTEM HAVING TWO GENERATING STATION AND A LOAD
(5.8)
PL 3I a2 Ra Rc 3I b2 Rb Rc 6I a I b Rc
(5.9)
Pa
Since I a
PL Pa2
3Va pf a
Ra Rc
2
a
V pf
2
a
, Ib
2 Pa Pb
Pb
3Vb pf b
R R
Rc
Pb2 b2 2c
VaVb pf a pf b
Vb pf b
(5.10)
(5.11)
The general form of the loss equation (5.11) for the power loss is given by
PL Pm Bmn Pn
m
(5.12)
FT F1 F2 F N Fi
(5.13)
i 1
PR P1 P2 P N Pi
i 1
(5.14)
P P
i
i 1
PR 0
(5.15)
dP dP
i
i 1
(5.16)
dFT
i 1
N
dPL
i 1
FT
i 1
FT
dPi 0
Pi
(5.17)
PL
dPi 0
Pi
(5.18)
PL
dPi 0
Pi
(5.19)
FT
P
L 0 for every value of 'i '
Pi
Pi
(5.20)
dFi 1
PL
dPi
1
Pi
(5.21)
dFn
Ln
dPn
Where Li
(5.22)
1
is regarded as the penalty factor of plant 'i '
PL
1
Pi
(5.23)
The above method explains how to calculate the economic distribution of load between the
plants considering the transmission losses. As we notice, we have to consider the penalty factor to
take into account the losses.
59
60
CHAPTER-6
FAULT ANALYSIS
SYMMETRICAL COMPONENTS
The power systems are subjected to faults. Most of the faults in power system are
unsymmetrical in nature. However symmetrical faults such as short circuits or 3 faults may also
occur. The unsymmetrical faults are (i) Line to Ground faults, (ii) Line to Line faults or Double
Line faults, (iii) Double Line to Ground faults. C. L. Fortescue has introduced method of
symmetrical components to deal with the unbalanced polyphase circuits. This method describes
that an unbalanced system of 'n' related phasors can be resolved into 'n' system of balanced
phasors known as symmetrical components of the original systems. Hence a three phase
unbalanced systems can be resolved into three balanced systems as shown in Fig.-6.1.
Va1 ,Vb1 ,Vc1 -Positive sequence voltages of three phases a, b, c equal in magnitudes and
displaced from each other by 120 in phase. Subscript '1' represents positive sequence i.e. having
the same phase sequence as the original system.
Va 2 ,Vb 2 ,Vc 2 -Negative sequence voltages of three phases a, b, c equal in magnitudes and
displaced from each other by 120 in phase. Subscript '2' represents negative sequence i.e. having
the opposite phase sequence as the original system.
Va 0 ,Vb0 ,Vc 0 -Zero sequence voltages of three phases a, b, c equal in magnitudes and
displaced from each other by 0 in phase. Subscript '0' represents zero sequence.
Hence the three phasors of original system can be written as (6.1a)-(6.1c)
Va Va1 Va 2 Va 0
(6.1a)
Vb Vb1 Vb 2 Vb0
(6.1b)
Vc Vc1 Vc 2 Vc 0
(6.1c)
( a 1120 )
Hence the set of (6.1) can be written as (6.2a)-(6.2c)
Va Va1 Va 2 Va 0
(6.2a)
Vb a 2Va1 aVa 2 Va 0
(6.2b)
Vc aVa1 a 2Va 2 Va 0
(6.2c)
The set of (6.2) in matrix form is given by (6.3) or taking inverse by (6.4)
Va 1 1
V 1 a 2
b
Vc 1 a
Va 0
1 1
V 1 1 a
a1 3
Va 2
1 a 2
1 Va 0
a Va1
a 2 Va 2
1 Va
a 2 Vb
a Vc
(6.3)
(6.4)
Hence
Va 0
1
Va Vb Vc
3
Va1
1
Va aVb a 2Vc
3
Va 2
1
Va a 2Vb aVc
3
(6.5a)
(6.5b)
(6.5c)
61
62
Similarly the set of equations (6.1), (6.2), (6.3), (6.4) and (6.5) can be written for the
currents of three phases i.e. for I a , I b , I c with the subscripts having the same description as given
for the voltages.
SYMMETRICAL COMPONENTS OF UNLOADED GENERATOR
Let us consider an unloaded generator, the terminal voltages of which can be given by
Va ,Vb ,Vc .
Va 0 0 Z 0
V E 0
a1 a
Va 2 0 0
0
Z1
0
0 I a0
0 I a1
Z 2 I a 2
(6.6)
>
>
>
FIG.-6.3 VOLTAGE OF phase'a' OF UNLOADED GENERATOR
63
64
I a0
1 1
I 1 1 a
a1 3
I a 2
1 a 2
1 I a
a 2 I b
a I c
(6.7)
I a0
1 1
I 1 1 a
a1 3
I a 2
1 a 2
1 I a
a 2 0
a 0
Solving (6.8)
I a1 I a 2 I a 0
From (6.6)
1
Ia
3
(6.8)
>
>
>
FIG.-6.5 EQUIVALENT NETWORK FOR UNLOADED GENERATOR HAVING SINGLE LINE TO GROUND
FAULT
Va 0 0 Z 0
V E 0
a1 a
Va 2 0 0
0
Z1
0
0 I a1
0 I a1
Z 2 I a1
(6.9)
(6.10)
Va I a1 Z 0 Ea I a1 Z1 I a1 Z 2
(6.11)
0 I a1 Z 0 Ea I a1 Z1 I a1 Z 2
(6.12)
65
66
I a1
Ea
Z 0 Z1 Z 2
I a1 I a 2 I a 0
(6.13)
Ea
Z 0 Z1 Z 2
(6.14)
The above equation shall be satisfied if the positive sequence, negative sequence and zero
sequence impedances are in series across a voltage of ' E a ' as shown in Fig.-6.5. This suggests that
for a single line to ground fault the positive sequence, negative sequence and zero sequence
network shall be connected in series at the point of fault in a power system.
LINE TO LINE FAULT
Let there be line to line fault involving terminal of phase'b' and phase'c' of the
unloaded generator (Fig.-6.6).
FIG.-6.6 LINE TO LINE FAULT INVOLVING TERMINALS phase'b' AND phase'c' OF THE
UNLOADED GENERATOR
Va 0
1 1
V 1 1 a
a1 3
Va 2
1 a 2
1 Va
a 2 Vb
a Vb
(6.15)
Va1 Va 2
(6.16)
I a0
1 1
I 1 1 a
a1 3
I a 2
1 a 2
1 0
a 2 I c
a I c
(6.17)
From (6.17)
I a 0 0, I a 2 I a1
(6.18)
Va 0 0 Z 0
V E 0
a1 a
Va 2 0 0
0 I a0
0 I a1
Z 2 I a 2
0
Z1
0 0 Z 0
Va1 E a 0
Va1 0 0
0
Z1
0
0 0
0 I a1
Z 2 I a1
(6.19)
(6.20)
I a1
Ea
Z1 Z 2
I a1 I a 2
(6.21)
(6.22)
Ea
Z1 Z 2
(6.23)
(6.23) shall be satisfied if the positive sequence and negative sequence impedances are in
parallel across a voltage of ' E a ' as shown in Fig.-6.7. This suggests that for a line to line fault the
positive sequence and negative sequence network shall be connected in parallel at the point of fault
in a power system.
67
68
ref bus
ref bus
Ea
Va1
Z2
Va 2
>
Z1
Ia 2
>
I a1
FIG.-6.7 EQUIVALENT NETWORK FOR UNLOADED GENERATOR HAVING LINE TO LINE FAULT
FIG.-6.8 DOUBLE LINE TO GROUND FAULT INVOLVING TERMINALS phase'b' AND phase'c' OF
THE UNLOADED GENERATOR
Va 0
1 1
V 1 1 a
a1 3
Va 2
1 a 2
1 Va
a 2 0
a 0
(6.24)
1
Va1 Va 2 Va 0 Va
3
Va 0 0 Z 0
V E 0
a1 a
Va 2 0 0
(6.25)
0
Z1
0
0 I a0
0 I a1
Z 2 I a 2
(6.26)
Z 1
Z0
0
0
1
Z1
0
Z 2
We get
Va1
0 I a0
1
Z Va1 Z E a I a1
Va1
0 I a 2
1
Z0
0
Z0
0
0
1
Z1
0
0
1
Z1
0
1
0
Va1 Z 0
0 Va1 0
Va1
0
Z 2
(6.27)
0
1
Z1
0
0
0 I a0
0 E a I a1
1 0 I a2
Z 2
1
0
E a1 I a1 Z 1 Z 0
0 E a1 I a1 Z 1 0
E a1 I a1 Z 1
0
Z 2
0
1
Z1
0
0
0 I a0
0 E a I a1
1 0 I a2
Z 2
(6.28)
(6.29)
69
70
Ea
E
E
E
Z
Z
Z
I a 1 a I a 1 a I a 1 a I a 0 I a1 I a 2
Z0
Z 0 Z1
Z1 Z 2
Z 2 Z1
Ia
(6.30)
I a1
Ea
Z1 Z 2 Z 0
(6.31)
The equation (6.31) shall be satisfied if the negative sequence and zero sequence
impedances are in parallel and the combined circuit is in series with positive sequence impedance.
The resulting circuit is across a voltage of ' E a ' as shown in Fig.-6.9. This suggests that for a double
line to ground fault the zero sequence and negative sequence network shall be connected in parallel
and the combined circuit is in series with positive sequence network, at the point of fault in a power
system.
>
>
>
FIG.-6.9 EQUIVALENT NETWORK FOR UNLOADED GENERATOR HAVING DOUBLE LINE TO GROUND
FAULT
The method described above can be used for calculation of fault current for power system.
A digital computer program can also be written for this algorithm. The students are advised to
implement this algorithm through computer program.
CHAPTER-7
CONTROL OF ACTIVE POWER
Active power control is closely related to frequency control and reactive power control is
closely related to voltage control.
In a network considerable drop in frequency could result in high magnetizing currents in
induction motor and transformer. The frequency of a system depends on active power balance.
The control of generation and frequency is commonly referred to as load frequency control (LFC).
The conventional generator with governor control is shown in Fig.-7.1.
Valve/ Gate
Gen
Turbine
Load
Governor
Ta
1
2 Hs
Te
FIG.-7.2 BLOCK DIAGRAM OF GENERATOR
71
72
P r T
(7.1)
P P0 P
(7.2)
Thus the torque and angular speed is modified as (7.3) & (7.4)
T T0 T
(7.3)
r 0 r
(7.4)
Where P0 , T0 , 0 are the initial power, torque and speed respectively. From (7.1) we have
P0 P 0 r T0 T
(7.5)
P 0 T T0 r
(7.6)
Pm Pe 0 Tm Te Tm0 Te0 r
(7.7)
Since at steady state electrical and mechanical torques are equal i.e. Tm0 Te0 and with
speed expressed in p.u. i.e. 0 1
Pm Pe Tm Te
(7.8)
Pm
1
Ms
-
r pu
M 2H
Pe
FIG.-7.3 BLOCK DIAGRAM OF GENERATOR
Pe Pl D r
Where,
(7.9)
Pm
1
Ms
-
PL
Pm
1
Ms D
PL
FIG.-7.4 BLOCK DIAGRAM OF GENERATOR WITH LOAD DAMPING
In the absence of speed governor the system response to a load change is determined by
the inertia constant and the damping constant.
TURBINE MODEL
Within the speed range of concern, the turbine mechanical power is essentially a function
of valve or gate position and independent of frequency. The turbine may be steam-turbine or hydroturbine. The transfer function of turbine may be represented by simple transfer function having
single time constant. The steam turbine may be reheat type or non-reheat type.
Turbine
Reheat type
73
74
ISOCHRONOUS GOVERNOR
Isochronous means constant speed. Isochronous Governor adjusts the turbine valve to bring
the frequency to the nominal or scheduled.
Valve/ Gate
Gen
Steam
Or
water
Pm
Pe
Turbine
r
integrator
-K
1
.
KR
1
.
R
Valve/ Gate
Gen
Steam
Or
water
shaft
Turbine
Pm
r
+
Reference
speed
integrator
1
s
R
FIG.-7.8 SIMPLIFIED BLOCK DIAGRAM OF GOVERNOR WITH STEADY STATE FEEDBACK:
1
R
1
1 sTG
(7.10)
NL FL
100
0
f
P
(7.11)
75
76
f f f 0
(7.12)
Frequency
or
Speed (pu)
1.0
The 5% droop or regulation means 5% frequency deviation causes 100% change in valve
position or power output
LOAD SHARING BY THE UNITS
Let us consider two generators having with droop chaaracteristics share a load change in a
power system. The frequency of both can be taken as equal as they belong to same system. Let the
load increases by PL . It shall cause slow down of the generators and the governor has to increase
the output till they reach a new common frequency. It can be seen that change in frequency for
both the generators has to be same as shown in Fig.-7.11.
P1 P1' P1
f
R1
P2 P2' P2
P1 R2
P2 R1
f
R2
(7.13)
(7.14)
(7.15)
UNIT-1
UNIT-2
Power Output
Power Output
If the % of regulation of the units are equal, the change in the outputs will be nearly in
proportion to its rating. Because of the droop characteristics the increase in power output is
accompanied by a steady state speed or frequency deviation ss
CONTROL OF GENERATOR UNIT POWER OUTPUT
The relationship between speed and load can be adjusted by changing an input shown as
load reference set point Fig.-7.12.
Load reference
Set point
When two or more generating units are operating in parallel the speed droop characteristic
(corresponding to a load reference setting) of each generator unit merely establishes the proportion
of the load picked up by the unit when a sudden change in system load occurs. The output of each
unit at any given system frequency can be varied only by changing its load reference, which in
effect moves the speed droop characteristic up and down.
77
78
Power Output
FIG.-7.13 SPEED FROOP CHARACTERISTICS OF DIFFERENT GOVERNOR
Pm 2
1
M eq s D
mn
f r
PL
FIG.-7.14 EQUIVALENT SYSTEM GENERATORS AND LOAD
The composite power or frequency characteristic of a power system thus depends upon the
combined effect of droops of all generator speed governors. It also depends on the frequency
characteristic of all the loads in the system. The steady state frequency deviation following a load
change PL for the equivalent system can be given by
f ss
f ss
PL
(7.16)
1
1
1
D
Rn
R1 R2
PL
1
D
Req
(7.17)
Where
Req
1
1
1
Rn
R1 R2
(7.18)
PL
1
D (MW/Hz)
f ss
Req
(7.19)
of system.
TURBINE-GOVERNOR SYSTEM
The complete turbine governing system is now shown in Fig.-7.15
79
80
1
R
Load
(reference)
1
1 sTG
Governor
1 sFHPTRH
Pm +
1 sTCH 1 sTRH
Turbine
Reheat type
1
Ms D
r ( pu)
Rotor inertia
+
Load
PL
FIG.-7.15 COMPLETE BLOCK DIAGRAM OF GENERATOR WITH TURBINE GOVERNING SYSTEM
1 sTR
R
1 s T TR
RP
1
1 sTG
Transient droop
compensation
FIG.-7.16 TRANSIENT DROOP COMPENSATION OF HYDRAULIC GOVERNOR
Area-2
Area-1
+
+
+
Turbine
Turbine
Governor
Governor
+
Load
Ref.1
Load
Ref.2
FIG.-7.17 BLOCK DIAGRAM FOR CONTROL OF TWO INTERCONNECTED POWER SYSTEM FOR
PRIMARY SPEED CONTROL
P12
E1 E 2
sin 1 2
XT
Linearizing about an initial operating point on the power angle curve i.e.
(7.20)
81
82
1 10 , 2 20 ,
We have
P12 T 12
(7.21)
12 1 2
(7.22)
E1 E 2
cos 10 20
XT
(7.23)
A positive P12 represents an increase in power transfer from area-1 to area-2 means
increasing the load of area-1 and decreasing the area-2. Therefore, the feedback for P12 is
negative for area-1 and positive for area-2. The steady state frequency deviation f f 0 is the
same for two areas for a total load change of PL and given by (7.24)
f 1 2
PL
1
1
R1 R2
D1 D2
(7.24)
Consider the steady state values following an increase in area-1 load by PL1 .
For area-1, we have
(7.25)
(7.26)
Pm1
f
R1
(7.27)
Pm 2
f
R2
(7.28)
f
D1 P12 PL1
R1
(7.29)
And f
D2 P12
R2
(7.30)
PL1
1
1
D1
D2
R1
R2
PL1
1 2
PL1
D2
PL1 2
R2
P12
1 2
1
1
D1
D2
R1
R2
(7.31)
(7.32)
An increase in area-1 load by PL1 results in a frequency reduction in both areas and a tie
line flow of P12 . Similarly, for a change in area-2 load by PL 2 , We have
PL 2
1 2
P12 P21
(7.33)
PL 2 1
1 2
(7.34)
(7.35)
Where,
B2 2
1
D2
R2
(7.36)
83
84
ACE1 P12 B1 f
(7.37)
Where,
B1 1
1
D1
R1
(7.38)
ACE represents the required change in area generation and its unit is MW.
+
+
+
+
Turbine
Turbine
Governor
Governor
Load
Ref.1
Load
Ref.2
FIG.-7.18 BLOCK DIAGRAM FOR CONTROL OF TWO INTERCONNECTED POWER SYSTEM WITH
SUPPLEMENTARY CONTROL
(7.39)
ACE 2 A2 P21 B2 f 0
(7.40)
f R
PL1
1 2
(7.41)
The supplementary control which is slower than the primary speed control will now
commence responding.
With B1 1 and B2 2
ACE1 P12 B1f R
ACE1
(7.42)
PL1
1 B2
1 2
(7.43)
ACE1 PL1
(7.44)
ACE 2 P21 B2 f R
(7.45)
ACE 2
PL1
2 B2
1 2
(7.46)
ACE 2 0
(7.47)
Only supplementary control in area-1 will respond to PL1 and change generation so as to
bring ACE to zero. The load change in area-1 is thus unobservable to supplementary control in
area-2.
If B1 and B2 were set to double their respective area frequency response characteristic.
ACE1 P12 B1 f R
1
ACE1 PL1 1
2
PL
21 2
1 2
ACE 2 P12 2 B2 f R
(7.48)
(7.49)
PL1
(7.50)
Thus, both area supplementary control would respond and correct the frequency deviation
twice as fast.
85
86