Phase TOC

Voltage (V)
Load (VA)
Primary Current (A)
Secondary Current (A)
CT ratio
Nominal Current (A)
Pick-up Setting (x pu)
Curve
Time Dial

69kV
69000
10000000
83.67
4.184
100
5
0.837
IEC B
0.4

Main 13.2kV
13200
10000000 Load for each Feeder
437.39
3.645
600
5
0.729
IEC B
To be set according to TRANSCO Settings
0.4
To be set according to TRANSCO Settings

Neutral TOC
% x phase TOC
Pick-up Setting (x pu)
Curve
Time Dial

33%
0.279
IEC B
0.4

Percent Differential
Pick Up
Slope 1
Break 1
Break 2

0.3 pu
33%
2 pu
8 pu

Slope 2

95%

Instantaneous Differential
Pick Up

8 pu

33%
0.243
IEC B
0.4

To be set according to TRANSCO Settings


To be set according to TRANSCO Settings

Phase TOC
Voltage (V)
Load (VA)
Primary Current (A)
Secondary Current (A)
CT ratio
Nominal Current (A)
Pick-up Setting (x pu)
Curve
Time Dial

Main 13.2kV F1 13.2kV F2 13.2kV F3 13.2kV F4 13.2kV


13200
13200
13200
13200
13200
10000000
2500000 2500000 2500000 2500000 Load for each Feeder
437.39
109.35
109.35
109.35
109.35
3.645
1.822
1.822
1.822
1.822
600
300
300
300
300
5
5
5
5
5
0.729
0.364
0.364
0.364
0.364
IEC B
IEC B
IEC B
IEC B
IEC B To be set according to TRANSCO Sett
0.3
0.3
0.3
0.3
0.3
To be set according to TRANSCO Sett

Neutral TOC
% x phase TOC
Pick-up Setting (x pu)
Curve
Time Dial

33%
0.243
IEC B
0.3

Fault Current (A)


Pick-up Setting (x pu)

1500
2.5

% x phase TOC
Pick-up Setting (x pu)

33%
0.833

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

1200
4

1200
4

1200
4

33%
1.333

33%
1.333

33%
1.333

To be set according to TRANSCO Sett


To be set according to TRANSCO Sett

Phase IOC
1200
4

Neutral IOC
33%
1.333

To be set according to the Substation

according to TRANSCO Settings


according to TRANSCO Settings

according to TRANSCO Settings


according to TRANSCO Settings

according to the Substation

Phase TOC
Voltage (V)
Load (VA)
Primary Current (A)
Secondary Current (A)
CT ratio
Nominal Current (A)
Pick-up Setting (x pu)
Curve
Time Dial

Main 13.2kV F1 13.2kV F2 13.2kV F3 13.2kV F4 13.2kV


13200
13200
13200
13200
13200
20000000
5000000 5000000 5000000 5000000 Load for each Feeder
874.77
218.69
218.69
218.69
218.69
4.374
3.645
3.645
3.645
3.645
1000
300
300
300
300
5
5
5
5
5
0.875
0.729
0.729
0.729
0.729
IEC B
IEC B
IEC B
IEC B
IEC B To be set according to TRANSCO Setti
0.3
0.3
0.3
0.3
0.3
To be set according to TRANSCO Setti

Neutral TOC
% x phase TOC
Pick-up Setting (x pu)
Curve
Time Dial

33%
0.292
IEC B
0.3

Fault Current (A)


Pick-up Setting (x pu)

1500
1.5

% x phase TOC
Pick-up Setting (x pu)

33%
0.500

33%
0.243
IEC B
0.3

33%
0.243
IEC B
0.3

33%
0.243
IEC B
0.3

33%
0.243
IEC B
0.3

1200
4

1200
4

1200
4

33%
1.333

33%
1.333

33%
1.333

To be set according to TRANSCO Setti


To be set according to TRANSCO Setti

Phase IOC
1200
4

Neutral IOC
33%
1.333

To be set according to the Substation

according to TRANSCO Settings


according to TRANSCO Settings

according to TRANSCO Settings


according to TRANSCO Settings

according to the Substation

Phase TOC
Voltage (V)
Load (VA)
Primary Current (A)
Secondary Current (A)
CT ratio
Nominal Current (A)
Pick-up Setting (x pu)
Curve
Time Dial

F1 13.2kV
13200
5000000
218.69
1.822
600
5
0.364
IEC B
0.3

% x phase TOC
Pick-up Setting (x pu)
Curve
Time Dial

33%
0.121
IEC B
0.3

Fault Current (A)


Pick-up Setting (x pu)

1200
2

% x phase TOC
Pick-up Setting (x pu)

33%
0.667

F2 13.2kV F3 13.2kV F4 13.2kV F5 13.2kV F6 13.2kV


13200
13200
13200
13200
13200
5000000 5000000 5000000 5000000 5000000 Load for each Feeder
218.69
218.69
218.69
218.69
218.69
1.822
1.822
1.822
1.822
1.822
600
600
600
600
600
5
5
5
5
5
0.364
0.364
0.364
0.364
0.364
IEC B
IEC B
IEC B
IEC B
IEC B To be set according to TRA
0.3
0.3
0.3
0.3
0.3
To be set according to TRA

Neutral TOC
33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

33%
0.121
IEC B
0.3

1200
2

1200
2

1200
2

1200
2

33%
0.667

33%
0.667

33%
0.667

33%
0.667

To be set according to TRA


To be set according to TRA

Phase IOC
1200
2

Neutral IOC
33%
0.667

To be set according to the S

Load for each Feeder

To be set according to TRANSCO Settings


To be set according to TRANSCO Settings

To be set according to TRANSCO Settings


To be set according to TRANSCO Settings

To be set according to the Substation

Das könnte Ihnen auch gefallen