Available online at www.sciencedirect.com

ScienceDirect
Procedia Technology 12 (2014) 716 722

The 7th International Conference Interdisciplinarity in Engineering (INTER-ENG 2013)

Simulation of speed steam turbine control system


Mircea Dulaua,*, Dorin Bicab
a,b

Department of Electrical and Computer Engineering, Petru Maior University of Trgu-Mure, 1 N.Iorga st., 540088

Abstract
Steam turbine control systems are being designed with todays technology to operate a turbine in a safe and reliable manner.
There are many considerations to be taken when choosing a controller for steam turbine applications. Many benefits may be
realized by choosing the proper steam turbine control system, whether it is a mechanical, an electrical or a programmable
controller system. This paper presents the basic concepts of the steam turbine control system and develops the fundamentals of
the speed control. Using Matlab/Simulink software facilities, have been simulated the speed variations, of the steam turbine-load
unit, connected with a mechanical-hydraulic system, than the speed deviations of the steam turbine-load unit, to different load
deviations, proportional and proportional-integrative control algorithms.
2013 The Authors. Published by Elsevier B.V.
2013 The Authors. Published by Elsevier Ltd. Open access under CC BY-NC-ND license.
Selection and peer-review under responsibility of Department of Electrical and Computer Engineering, Fac ulty of Engineering,
Selection and peer-review under responsibility of the Petru Maior University of Tirgu Mures.
Petru Maior University of Trgu Mure.
Keywords: steam turbine; mechanical-hydraulic governor; speed control; frequency control;

1. Introduction
Steam turbines are energy conversion machines. They extract energy from the steam and convert it to torque,
which rotates the shaft of the turbine. The amount of energy that t
m is a function of its temperature and pressure, as
outlined in [5, 7, 9, 11].
There are two categories of steam turbine controls as follow: safety (protection) system and process system. The

* Corresponding author. Tel.: +4-075-224-9499.


E-mail address: mircea.dulau@ing.upm.ro

2212-0173 2013 The Authors. Published by Elsevier Ltd. Open access under CC BY-NC-ND license.
Selection and peer-review under responsibility of the Petru Maior University of Tirgu Mures.
doi:10.1016/j.protcy.2013.12.554

717

Mircea Dulau and Dorin Bica / Procedia Technology 12 (2014) 716 722

turbine safety systems are intended to eliminate/minimize the possibility of damage to the machine or the hazard to
operators. It protects the turbine from overspeeding, monitors all critical turbine parameters, and trips the turbine if a
condition exists that could cause equipment damage. The main safety control element on a turbine is the steam
supply valve. This safety valve can be a separate on/off valve or the shut-off function can be incorporated into the
controls of the steam supply valve that is used for speed control.
The process systems control the operation of the steam turbine, so as to follow the load in a stable and efficient
manner. The steam turbine is controlled by the governor, which can be mechanical-hydraulic (developed from
James Watts original flyball governor) and/or electrical. They all include a pilot valve, or controller, which
modulates the turbines inlet valve in order to keep the shaft speed on set point.
An electro-hydraulic control system use electronic circuits, is more flexibility, but the overall requirements are
similar. A digital electro-hydraulic control system, use a digital controller and a lot of functions can be implemented
through software. Even the advanced controls usually operate the high-pressure and low-pressure valves through the
existing electro-hydraulic controls of the turbine.
A typical governor model for steam turbines has two main sections, the governor and steam control valve, whose
output is effective control valve area in response to speed deviation of the machine, and a section modelling the
turbine, whose input is steam flow and output is mechanical power applied to the rotor (Fig. 1) [4,5,7,9,11].
Speed
deviation

Governor control
Steam valve

Steam
flow

Control valve
position

Steam
Turbine

Mechanical
power

Steam pressure at
Control valve
Fig. 1. Typical model for steam turbine control.

In this block diagram, steam flow to the turbine is the product of valve area and throttle pressure. Thus, if throttle
pressure drops due to an increased demand in steam flow, the valve area must further increase to maintain the same
flow as compared with the simplified model.
2. Fundamentals of speed steam turbine control
A steam turbine control system is a closed loop system. The simplest application is one in which a turbine is used
to operate a rotor to constant speed (Fig. 2). The controller senses the shaft speed, compares the actual speed with
the desired set point. If there is a difference between the actual speed and desired speed, the controller sends a signal
to the actuator operating the steam valve, which will adjust the speed until the two are again balanced [1,2,3,5].
Variations in load, caused by shaft loading or variations in pressure supply, affect the balance between the energy
supplied to the turbine from the steam system and the work removed from the turbines shaft. If more energy is
available than is being used, the shaft will speed up. The controller will detect this increase in speed and act to
eliminate it. Its means of doing so is to reduce the energy supplied to the turbine by closing the supply valve.
Valve position
Set point

Controller
(Governor)

Mechanical power
Steam
turbine

Feedback
Fig. 2. Control system block diagram.

Rotor
(inertia)

Speed

718

Mircea Dulau and Dorin Bica / Procedia Technology 12 (2014) 716 722

If the net change in the energy balance were negative, the shaft would slow down and the controller would
respond by opening the supply valve.
On a steam turbine, two types of controls are highlights [5,6,7,8,9]:
x droop control or proportional-only control (P), defined as a decrease in speed with an increase in load, produces a
change in valve position proportional to the signal between the speed set point and the actual speed; the main
disadvantage of proportional-only control is that it cannot completely eliminate the error caused by a change in
load.
x isochronous control, defined as no decrease in speed with an increase in load, maintain the speed of shaft rotation
constant regardless of load; in order to eliminate the error and to minimize the overshoot, it is accomplished with
proportional and integrative (PI) controllers, usually in conjunction with derivative (D) controller, resulting the
steam PID type controllers.
Depending on the control required and the number of valves, a steam turbine may employ several control loops,
each of which requires a feedback loop.
3. Simulation of the speed steam turbine control system
Depending on configuration, the steam turbine is equipped with high pressure valves (HPV), re-heater valves
(RHV), and consist of high pressure (HP), medium pressure (MP) and low pressure (LP) sections (Fig. 3) [15].
As a requirement for any turbine - generator unit, the speed/load control function is achieved through the control of
the HPV (adjust the speed/load set point to control admission of steam to the turbine through HPV pos). In addition
to the HPV, a second valve is required. It controls the steam flow rate that is extracted from the HP section of the
turbine and is sent to the MP, LP sections and crossover pipe (CP). The integrity of the turbine depends on the
possibility to limit the speed, involving the reheat valve position (RHV pos). The re-heater stores a large amount of
steam so, the HPVs control is not enough to limit the overspeed. The overspeed control involves fast control of the
HPV and RHV, because the RHV controls about 60% to 80% of the total power (steam flow to MP and LP
sections).
The output of the speed sensor is compared with the speed set point and the error signal is used to control the
HPV and RHV. The power servos are used to amplify the energy levels necessary to move the steam valves.
Boiler

CP
HPV pos

Shaft

HPV

HHP(s)

HMP(s)

HLP(s)

RHV
RHV pos
HRH(s)
Power
servos

Speed
control
Speed/load set point

Fig. 3. The steam turbine configuration with speed controller.

719

Mircea Dulau and Dorin Bica / Procedia Technology 12 (2014) 716 722

Each of the turbine section is described by a transfer function H HP s , H MP s , H LP s , H RH s and depends


on time constants THP , TMP , TLP , TRH . Neglecting the smallest time constants, a simplified transfer function of the
steam turbine configuration (with re-heater) may be written, as follows [3,5,10,13]:

H T s

TRH K HP s  1

(1)

THP s  1 TRH s  1

where: K HP is the power fraction of the HP turbine section.


The load is described by the simplified form:

H L s

1
TL s

(2)

If the control system is a mechanical-hydraulic type, the commonly referred is speed relay in conjunction with
servomotor, described by the transfer functions [5]:

H SR s

1
TSRs  1

(3)

H SM s

1
TSM s

(4)

where: TL , TSR , TSM are time constants.


The block diagram of the turbine-load unit, connected with a mechanical-hydraulic system is presented in Fig. 4.
With Matlab/Simulink facilities, result the speed, as an output variable, depending on the control valves position
(HPV pos and RHV pos), as input variables [14].
The results show the speed variations (Fig. 5a), obtained to different positions of the RHV (where 100% means
fully open), and a profile of the input and command signals (Fig. 5b). The presented responses are computed with:
TSR 0.1 sec., for speed relay, TSM 0.3 sec. for servo, TL 12 sec. for load, THP 0.3 sec., TLP 0.5 sec.,

TRH 7 sec. and K HP 0.3 for steam turbine. These demonstrate that, although the input signal is the same, there
are significant differences in transient responses.
If one parameter of the load varies within a specific range of values or percentage, result the process affected by
uncertainties. In this case, the mechanical-hydraulic control system works properly, according to the simulation
diagrams, presented in Fig. 6, where the nominal value of the load ranges with 25% [14].
SP

Kc

HSR(s)
Speed relay

HSM(s)
Servo

HPV pos
Speed
RHV pos

%
RHV pos
Fig. 4. Simulink block diagram with mechanical-hydraulic control system.

Turbine - load

Speed

720

Mircea Dulau and Dorin Bica / Procedia Technology 12 (2014) 716 722

Fig. 5. Speed variation: (a) to different RHV positions; (b) with input and command signals.

Fig. 6. Speed variation, obtained to variable load.

The frequency of the system is dependent on speed, which should remain nearly constant [5,12]. The block
diagram from Fig. 7 includes representation of the speed controllers, turbine and load in a feedback connection [14].
With primary control loop action, a change in system load will result in a steady-state speed deviation, depending on
the controller characteristic. Restoration of system speed to nominal value requires supplementary control loop with
an integral action. Depending on power system type, the supplementary control loop takes effect after the primary
control has stabilized the system speed.
The step responses, for reheat steam turbine, are computed using typical parameters, presented in [5,15]. The
turbine representation is based on the simplified transfer function, described by relationship (1), respectively:
HT s 2.1s  1 > 0.3s  1 7s  1 @ . The load with damper is described by a first order transfer
function, H L s 1 TL s  1 , where: TL

10 sec. is the load time constant. The P and PI controllers are classical,
with tuning parameters: K P 20 , proportional value and TI 15 sec., integrative time [5,15].
Fig. 8 illustrates the speed deviation, obtained with P and PI controllers, to load deviation equal with 0.7 from
load set point, both starting with zero time. Fig. 9a shows the speed deviation, obtained to a profile of load deviation
equal with (0.7; 0.4; 0.9), applied to t0 0 sec., t1 15 sec. and t 2 22 sec. In Fig. 9b the speed deviation is

721

Mircea Dulau and Dorin Bica / Procedia Technology 12 (2014) 716 722

obtained to a profile of load set point equal with (1; 0.5; 0.75), applied to t0 0 sec., t1 15 sec. and t 2 22 sec.
[14]. The results demonstrate that, depending on the controller type, the transient responses are different and the
integrative control action ensures zero speed error in the steady-state.
Supplementary control loop
Speed
dev

Cmd

Cmd

Torque
Torque

PI controller

Load deviation

Turbine
Load
dev

Load set point

Load
ref

Torque
Cmd

Speed
dev

Cmd

Torque

Load

Turbine

P controller

Primary control loop

Fig. 7. Block diagram for speed deviation control.

Fig. 8. Speed deviation control with P and PI controllers.

Speed
dev

Speed
deviation

722

Mircea Dulau and Dorin Bica / Procedia Technology 12 (2014) 716 722

Fig. 9. Speed deviation control, with P and PI controllers, to different: (a) load deviations; (b) load set points.

4. Conclusions
In order to meet the frequency demand, which should remain nearly constant, the speed steam turbine must be
controlled. There is a direct relationship between the turbine speed and the position of the turbine valve.
The dynamic response of the steam turbine is influenced, mainly, by the entrained steam into high pressure
turbine section and the storage action in the re-heater.
When a turbine-load unit is connected and synchronized to the grid, the speed cannot be changed, but the speed
set point can. If the speed set point is raised, the valve will open, increasing the load and if the reference is lowered,
the valve will close and lower the load. In this case, the proportional-only (droop) controller is an excellent means of
load control.
In order to maintain the speed of shaft rotation constant regardless of load (an isolated power system case), a
supplementary control loop is needed, which takes effect after the primary control has stabilized the system speed.
Depending on the size of the load set point, load deviation and on the control type, the response of the stream
turbines may be slower or faster. With the suitable speed controllers, steam turbines can provide very good speed
stability.
References
[1] Azubalis M et al. Identification of model parameters of steam turbine and governor. Oil Shale. Vol. 26; No. 3 Special; Estonian Academy
Publishers; 2009. p. 254268.
[2] Bennauer M et al. Automation and control of electric power generation and distribution system: steam turbine. Encyclopedia of Life Support
Systems. Vol. XVIII; 2012.
[3] Chaibakhsh A et al. Simulation modelling practice and theory. 2008. p. 11451162.
[4] Feltes WJ et al. Boiler effects on steam turbine response. New York Power Technologies Inc; 2002.
[5] Kundur P. Power system stability and control. McGraw-Hill Professional; 1994.
[6] Inoue T et al. A thermal power plant model for dynamic simulation of load frequency control. IEEE Power Systems Conference and
Exposition. Atlanta; 2006; p. 1442 1447.
[7] Lamberson SJ et al. Steam turbine governing system and electronic governor retrofit. Proceedings of the 28th Turbomachinery Symposium.
Texas; 2012; p. 157-164.
[8] Lilje P. Stability analysis of an islanded generator. Power Plant and Power Control. IFAC Publications. Kananaskis; 2006, p. 159-164.
[9] Liptak BG et al. Instrument engineers' handbook. Steam Turbine Controls. 2006; p. 2137-2151.
[10] Moura FAM et al. Steam turbines under abnormal frequency conditions in distributed generation systems. InTech. 2012; p. 381-400.
[11] Murty MS. Modelling of steam turbine and its governing system. Program for CEE on Power System Analysis and Operation. Colombo;
2010.
[12] Vinotha KX. Frequency regulation by free governor mode of operation in power stations. IEEE International Conference on Computational
Intelligence and Computing Research. 2010.
[13] Yang T et al. Parameter identification of steam turbine speed governor system. IEEE Power and Energy Engineering Conference. Shanghai;
2012; p. 1 8.
[14] ***. Matlab and simulink tutorial. The MathWorks; 2010; www.mathworks.com.
[15] ***. Technical documentation. Iernut thermoelectric power plant; 2010.

Das könnte Ihnen auch gefallen