Sie sind auf Seite 1von 3

11KV BUS

1.4Km 400sq mm 3core 11KV XLPE UG cable

11Kv/433v 3MVA transformer

3MVA Transformer IRON Lo

3MVA Transformer IRON Losse


3mva Transformer Copper loss
load

3mva Transformer Copper loss


load yearly

3mva Transformer Copper losse


to LLF
TOTAL losses =

TOTAL losses

Considering 3

units consumed by

1.4 KM

cable length

3 MVA

Connected peak load


Cable size

Resistance/km

400 sq mm

0.096

cable 3core xlpe


400 sq mm
Load
Factor
LLF

reactance(XL)

peak AMPS

impedance) z
0.072

0.120

11KV Line Losses at Dielectric


Peak load (kwh)
losses in kwh
157.5
36490
13202

0.8
0.672

11KV Cable Losses corrected to LLF= Losses


x LLF

3MVA Transformer IRON Losses

VA Transformer IRON Losses yearly


a Transformer Copper losses @ peak
load

a Transformer Copper losses @ peak


load yearly

33393 Kwh

5000 watts
43800 Kwh
36000 watts
315360 KWH

Transformer Copper losses corrected


to LLF
211922 KWH
L losses =
11KV Cable losses+Transformer Iron losses+ Transformer Cu losses

OTAL losses

289115 Units

Considering 3MVA Peak power and load factor 0.8, pf 0.9 & LLF
units consumed by plant in a year=

Percentage losses= Total


losses/Energy Consumed

15894144 Units
1.81900 %

capacitance
0.7

Total 11kv cable


losses
49692

Das könnte Ihnen auch gefallen