Beruflich Dokumente
Kultur Dokumente
http : //www.cigre.org
A3-303
CIGRE 2012
G. ROCCHETTIA.
MPS
USA
PIGINI
Consultant
Italy
SUMMARY
Composite housings are becoming the preferred solutions for most of the EHV and UHV applications
due to their many advantages especially in severe environment.
Specific reference is made in the paper to composite housings with extruded sheds: a technology
which guarantees the maximum flexibility and adaptability to the different applications.
Results of experimental investigations are reported to confirm the good performance of the solution
in laboratory with special attention to severe environment.
The laboratory god experience is confirmed by the experience in test stations and by the return of
service experience. Field feed-back indicates that composite insulators, correctly dimensioned
according to laboratory test results and taking correctly into account the site pollution, present a
satisfactory short and long term performance.
Then the design optimization aspect is analyzed both in AC and DC with particular reference to
pollution. It is shown that pollution determines the design especially in DC, thus needing a specific
detailed accurate design approach.
From the analysis the benefits of the composites over the ceramic solution clearly appear, especially
for applications in the UHVDC range.
KEYWORDS
Composite Insulators- Station Insulators-Pollution-Direct Current-Alternate Voltage-UHV
Applications
emoal@macleanpower.fr
1
INTRODUCTION
Composite housing are becoming the preferred solutions for most of the EHV and UHV applications
due to their many advantages [1], [2], [3]. In the paper, after a brief description of the specific
technology considered (composites with extruded housing), the electrical performance of the solution
is analyzed on the basis of laboratory and field information. Advantages are then described with
respect to the ceramic alternative both for AC and for DC applications, showing how composites can
help to optimize the design.
HV composite housing have been produced since 20 years according to a patented process where HTV
(High temperature vulcanized) Silicone weather sheds are extruded, vulcanized and bonded over an
FRP (Fiberglass Reinforced Polymer) tube with aluminum alloy fittings, fully in agreement with [4].
In particular insulators with extruded HTV housing for apparatus applications are qualified by Utilities
in France, Italy, UK, Spain, USA, Canada, South Africa, Brazil, UAE, and Algeria and used in all the
world by Utilities and manufacturers. More than ten thousand extruded type insulators were already
installed before the year 2000. Today, more than one hundred thousand hollow core insulators with
extruded sheds have been manufactured: the majority for the highest range of system voltage (greater
than 245 kV). In particular hollow core insulators for all types of AC and DC High Voltage
applications for all voltage ratings up to the highest system voltages were produced as specified here
below [3]:
One particular advantage of the extrusion process is its extreme flexibility, much higher than for the
molding processes. In particular the process allows the production of a variety of profiles designed to
meet leakage distances specified by end-users, with spacing, shed shape, overhang and inclination
according to the specific requirements and environmental conditions. Examples of developed shed
profiles are shown in Fig. 2. The insulators may be supplied with simple sheds or alternate sheds to
withstand the most severe environmental conditions.
Single
Double
inefficient, as it is indicated by the fact that the required unified specific creepage distance, USCD, is
much higher than for conventional porcelain station insulators.
On the contrary silicon insulators with a helical profile complying with IEC 60815 indications shows
much better performance than Spirelec insulators. The performance is even better than that of
ceramic insulators with a conventional profile conforming with IEC, due to the HTM (hydrophobic
transfer material) characteristics of silicon insulators, and this in spite of the severe testing procedure
used in [7] to determine the pollution withstand. The advantage of the helical profile versus the
porcelain solution is even greater for large diameter insulators, due to the well known less dependence
of USCD on the insulator diameter for HTM materials [7].
The results confirm that the unsatisfactory performance of old spiral insulators was due to their
inadequate profile and cannot be extrapolated to insulators with helical profile conforming with IEC.
All the helical type silicon insulators manufactured to-day strictly conform IEC 60815 indications.
USCD( mm/kV)
100
10
10
100
S (Kg/m3)
Uwet/Udry
1
0,9
0,8
0,7
porcelain
composite
0,6
0,5
0
100
200
300
D (mm)
400
500
600
Fig. 5 - SI (Switching Impulse) tests, positive polarity voltage. Flashover voltage ratio under wet and
dry conditions versus the insulator external diameter. Comparison between composite and ceramic
housing data.
The good laboratory performance of composites is confirmed by experiences in experimental stations
characterized by severe environments [3]. As an example a severe test experience was carried out at
Martigues test station in France. This test station is characterized by very severe marine/industrial
pollutions. The level of pollution at Martigues is equivalent to a very heavy contamination, thus
requiring a USCD of 53,7 mm/kV or higher [8]. In addition Marseilles region offers a high level of
sunlight with typically more than 3000 hours of sunshine per year. Cable terminations with helical
profile has been energized at the Martigues test station for more than 10 years (experience initiated in
1998 and ended 2009) without flashover. No washing was necessary. Several other field experiences
have been made with positive results as that at the Dunkerque test station for 11 years.
Finally a good service performance of the examined composite solution can be reported. Insulators are
installed in many parts of the world including many heavily polluted areas. As an example more than
one hundred SF6 insulated CT are installed in South Africa 275kV Network since 1995 in a severe
pollution environment with good performance.
The performance of insulators are satisfactory also when considering other aspects than pollution.
Insulators are used with satisfactory performance for generator circuit breakers since many years.
These breakers are characterized by a rated current up to 26 kA and short-circuit current up to 210 kA.
Insulators installed in these breakers are highly stressed due to important mechanical loads during
short-circuit operations and high continuous working temperature (105 C) due to the very high
nominal current.
Positive experience is reported on insulators installed on laboratory circuit breakers that are subjected
to severe stresses in terms of arc generated byproducts confirming the arc resistance of the inner
design, protected by a polyester film.
Thousands of insulators are installed in seismic areas after having been qualified by means of severe
seismic testing.
Not to be forgiven the fact that, in contrast to the porcelain solutions, the composite solution is
explosion proof: this is one of the main reasons why the composite solution is becoming the preferred
solutions of many utilities in the world.
14
Lmax (SI)
14
Lmin (SI)
12
LP VL
12
LP VL
10
LP L
10
LP L
LP M
LP H
LP VH
L(m)
L(m)
Similar evaluations are made for the composite solutions and the results are reported in Fig. 7.
In this case SI dominates the design both in the case of SI maximum and minimum, allowing to take a
real benefit of the overvoltage control in all the environmental conditions.
LP M
LP H
LP VH
0
0
500
1000
1500
500
Um (kV)
1000
1500
Um (kV)
Fig. 6 Bushing application; AC. Ceramic housing. Required arcing distance as a function of the
system voltage.
12
Lmax (SI)
10
LP VL
L(m)
L(m)
LP L
LP M
LP H
LP VH
2
0
0
500
1000
1500
9
8
7
6
5
4
3
2
1
0
Lmin (SI)
LP VL
LP L
LP M
LP H
LP VH
1000
1500
Um (kV)
Um (kV)
500
Fig. 7 Bushing application; AC. Composite housing. Required arcing distance as a function of the
system voltage.
100
USCD (mm/kV)
DC
AC
AC ceramic
AC composite HR 4-5
DC ceramic
DC composite HR 4-5
10
0,01
0,1
SDD (mg/cm2)
40
35
30
25
20
15
10
5
0
L(SI)
LP VL
LP L
L(m)
L(m)
An example of application to bushing design is made following the simplified methodology used in
[8] for AC, adopting discrete USCD values for the different pollution levels [11], assuming the same
influence of the diameter on the required USCD as in AC and assuming a CF of 4 for ceramic and 4.4
for composites. Furthermore a design SI voltage value of 2.2 p.u. is assumed. Differently from AC, the
benefits of composites with respect to ceramic in terms of specific creepage distance needs are taken
into account in the calculations.
The results of the calculations are shown in Fig. 9 for the ceramic and composite case.
In the case of porcelain housings (Fig. 9 a), the simplified application approach confirms that,
differently from AC, pollution dominates the design, leading to extremely long bushings. Thus the
adoption of porcelain insulators leads to unpractical and unfeasible solutions, especially in the UHV
range.
More reasonable insulator lengths result in the case of composite housing (fig. 9 b). The example
indicates however that also in this case pollution may dominate the design especially for the most
severe contamination conditions.
LP M
LP H
LP VH
200
400
600
800
1000
1200
20
18
16
14
12
10
8
6
4
2
0
L(SI)
LP VL
LP L
LP M
LP H
LP VH
200
400
800
1000
1200
Um (kV)
Um (kV)
600
Fig. 9 Bushing application; DC. Required arcing distance as a function of the system voltage.
Being pollution the dominating design condition, a simplified approach as in Fig. 9 is not
recommended in DC: the simplified approach has been used just to put into evidence the relevance of
pollution in DC and to compare the ceramic and composites solutions. To minimize the uncertainties
when performing insulation design, a detailed accurate approach needs to be followed to quantify all
the aspects that may impact on the insulator dimensions and should include the following activities:
Statistical site severity assessment through an accurate mapping of the area concerned based
on long term data with reference to the DC condition (AC data are not directly applicable ! ).
Assessment of the pollution performance of the insulator selected by means of laboratory tests
(tests on short units may be sufficient, since the results can be linearly extrapolated).
Setting up of an acceptance performance criterion in terms of an acceptable risk of flashover
A more detailed description of the methodology and examples of applications are given in [11] and
[14].
CONCLUSIONS
The composite solution is becoming the prevailing solution for station insulator housings due
to its many advantages, such as its explosion proof characteristics. However another important
advantage is the good performance in severe environment.
A very flexible composite housing solution has been developed, based on extrusion process.
The satisfactory performance of the solution has been confirmed by laboratory tests, long
term experience in severe testing stations and by the wide return of service experience.
The use of the composite solution is essential to optimise the design in severe environment.
For AC applications composites may be essential to develop compact apparatus solutions,
whenever the SI level are contained.
Composites are becoming the preferred solutions for DC applications due to their better
performance in the contamination conditions, allowing to develop UHV applications which
could not be feasible with the ceramic solution.
Due to the criticality of pollution for DC applications, the simplified design approach used for
AC applications, is not recommended for DC insulator design. A detailed statistical design
approach is to be used for design optimization
BIBLIOGRAPHY
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
Cigre WG A3.21 Guidelines for the application of composite insulators to HV apparatus Cigre
Brochure 455-2011
Cardano , A. Pigini , R. Berti , M. de Nigris , E. Moal , G. Rocchetti Application of composite
Housing to High Voltage Bushings Cigre Session 2008 Paper A3 30
E. Moal, M. Fritsch, F. Chevalier, G. Rocchetti, A. Pigini 20 years experience with extruded
HTV housing for EHV application INMR World Congress- Seoul 2011
IEC 61462 2007 Composite hollow insulators - Pressurized and unpressurized insulators for
use in electrical equipment with rated voltage greater than 1 000 V - Definitions, test methods,
acceptance criteria and design recommendations
K. L. Chrzan, J. Kindersberger Pollution behaviour of insulators with spiral shaped sheds
ETG-Fachbericht 99, VDE-Verlag GmbH Berlin Offenbach; S. 97-102
MPF internal report [1992]
P. Cardano, M. de Nigris, A.Pigini, G. Rocchetti Dielectric performance of composite
housing i ISH 2009
IEC TS 60815-1; 2; 3 2008-10 Selection and dimensioning of high-voltage insulators intended
for use in polluted conditions
CIGRE WH 33.07Guidelines for the evaluation of the dielectric strength of external
insulation CIGRE brochure 72 1992
IEC 60137 2004-7 5th edition Insulated bushings for alternating voltages above 1000 V
A. Pigini, R. Cortina Insulation Challenges when Uprating EHV AC Lines or Converting
EHVAC Lines to EHVDC Lines INMR world Congress Seoul 2011
IEC TS 60071-5-2002 Insulation coordination Part 5: Procedure for high voltage direct current
(HVDC) converter stations
IEC TS 62073-2003 Guidance on the measurement of wettability of insulator surfaces
A. Pigini, R. Cortina Evaluation of the performance of polluted insulators under dc: a statistical
approach ISH 2011