Sie sind auf Seite 1von 1

CONSTANT OF 132 KV AND 400 KV OVER HEAD LINES

Single Lines 132


kV
Lark
Teal
Oriole
Redwing
Partridge
Copper
Copper
Twin Lark
Twin Teal
ACRS 300
Twin AAAC
Double Lines
132 kV
Lark
Teal
Oriole
Redwing
Partridge
Copper
Copper
Twin Lark
Twin Teal
ACRS 300
Twin AAAC

Size
mm2
248
377
210
445
157
127
152
2 x 248
2 x 377
300
2 X 551
Size
mm2
248
377
210
445
157
127
152
2 x 248
2 x 377
300
2 X 551
Size

Single Lines 400


kV
Twin AAAC

X1

B1
(x10-6)

Ro

Xo

Xmo

Xoo

/ km
0.147
0.097
0.174
0.082
0.219
0.153
0.121
0.0735
0.0485
0.195
0.034

(/km)
0.428
0.415
0.433
0.4095
0.444
0.454
0.449
0.3065
0.301
0.437
0.315

/ km
2.66
2.75
2.63
2.78
2.57
2.52
2.48
3.70
3.78
2.60
---

/ km
0.378
0.3275
0.406
0.3135
0.4995
0.385
0.353
0.3065
0.2805
0.427
0.30

/ km
1.231
1.218
1.236
1.212
1.246
1.257
1.252
1.109
1.113
1.240
0.976

/ km
-----------------------

/ km
-----------------------

R1

X1

B1
(x10-6)

Ro

Xo

Xmo

Xoo

/ km
0.147
0.097
0.174
0.082
0.219
0.153
0.121
0.0735
0.0485
0.195
0.034

(/km)
0.400
0.387
0.405
0.381
0.417
0.426
0.421
0.278
0.2725
0.409
0.285

/ km
2.87
2.97
2.83
3.01
2.76
2.70
2.75
4.13
4.23
2.8
3.76

/ km
0.378
0.3275
0.406
0.3135
0.4995
0.385
0.353
0.3065
0.2805
0.427
0.221

/ km
1.287
1.274
1.292
1.269
1.303
1.313
1.309
1.165
1.159
1.296
0.734

/ km
0.801
0.801
0.801
0.801
0.800
0.797
0.801
0.801
0.801
0.801
0.801

/ km
2.088
2.075
2.093
2.070
2.103
2.114
2.110
1.966
1.960
2.097
1.535

R1

X1

B1
(x10-6)

Ro

Xo

Xmo

Xoo

/ km

(/km)

/ km

/ km

/ km

/ km

/ km

0.034

0.315

0.300

0.976

Symbol
L
T
O
R
P
C
C
TL
TT
ACRS
TAA

Symbol
L
T
O
R
P
C
C
TL
TT
ACRS
TAA

Symbol

mm2
2 X 551

R1

TAA

Xo/X1 0R
Xoo/X1
2,87
2.93
2.85
2.96
2.81
2.77
2.79
3.62
3.71
2.84
3.10
Xo/X1 0R
Xoo/X1
5.22
5.36
5.16
5.42
5.06
4.96
5.00
7.06
7.20
5.31
5.38
Xo/X1 0R
Xoo/X1
3.10

Thermal rating
MVA
96
120
85
135
73
80
92
192
240
--330

A
420
525
370
590
320
350
400
840
1050
--1440

Thermal rating
MVA
96
120
85
135
73
80
92
192
240
--229

A
420
525
370
590
320
350
400
840
1050
--1440

Thermal rating

For calculation the value of earth resistivity assumed equal 100 .m

2.

Xo = Reactance for one circuit. And Xmo = mutual reactance between two circuits if double

3.

Xoo= Reactance if double line (Xo + Xmo)


Prepared by:

MVA
116
151
104
169
89
106
119
232
300
--395

A
510
660
455
740
390
460
520
1020
1320
--1720

Emergency rating (x1.2)


MVA
116
151
104
169
89
106
119
232
300
--395

A
510
660
455
740
390
460
520
1020
1320
--1700

Emergency rating (x1.2)

MVA

MVA

1000

1440

1190

1700

Note:1.

Emergency rating (x1.2)

Date: 28 Jun 2008

Das könnte Ihnen auch gefallen