Beruflich Dokumente
Kultur Dokumente
by
Mohammed Nasr Zein Abd El-Hamid
A Thesis submitted to the
Faculty of Engineering at Cairo University
in Partial Fulfillment of the
Requirements for the degree of
MASTER OF SCIENCE
in
ELECTRICAL POWER AND MACHINES
by
Mohammed Nasr Zein Abd El-Hamid
Member
Member
CONTENTS
ACKNOWLEDGMENTS .....ii
ABSTRACT ..iii
CONTENTS....v
LIST OF FIGURES .............xii
LIST OF TABLES ......xvi
LIST OF SYMBOLS AND ABBREVIATIONS ......vxii
1
INTRODUCTION........1
1.1 Objectives of the thesis..2
1.2 Contents of this thesis2
OVERVOLTAGES......4
2.1 Introduction.4
2.2 Origin of overvoltages ....4
2.2.1 Lightning Overvoltages ....5
2.2.2 Switching Overvoltage .....................7
2.3 Control of Switching Overvoltage ...7
2.3.1 Draining of Trapped Charge of Line ..8
2.3.2 Series Resistance Switching ...9
2.3.3 Phase Controlled Closure .11
2.3.4 Use of Shunt Reactors ..11
2.3.5 Limiting Value of Minimum Switching Surge..12
2.5
2.6.4 Performance...21
2.6.5 Types of Surge Arresters...22
2.6.5.1 Metal oxide Type...22
2.6.5.2 Gapped Silicon Carbide Type....22
2.6.5.3 Selection .......23
2.6.5.4 Equivalence ..23
2.6.6 Classification of Surge Arresters...23
2.7 Selecting the Line Discharge Class.....................23
2.8 Statistical Characteristics of Overvoltages.27
2.9 Statistical Variations in Lighting Surges.....27
2.10 Statistical Variation in Switching Surges....28
SUBSTATION DESCRIPTION.....30
3.1 A Generator...31
3.2 A Power Transformer....31
3.3 Circuit Breaker......................31
3.4 Transmission Line.32
3.4.1 Under Ground Cable ...32
3.4.2 Over Head Transmission Line conductor .......................32
3.5 Surge Arresters..33
3.5.1 GIS type Surge arrester .....33
3.5.2 Porcelain type surge arrester .....34
3.6 The load simulation.......35
vi
ix
REFERENCES ...........126
APPENDIX (A)...131
Performance of type RVLQD....131
Performance of type RVLQC....132
Performance of type RVLQB133
Performance of type RVLQE....134
Performance of type RVLQA....135
Dimension o type RVLQD, RVLQC, RVLQB, RVLQE, RVLQA..136
Standard ratings.137
Chapter (2)
OVERVOLTAGES
2.1
Introduction
The examination of overvoltages on the power system includes a study
to
the
International
Electrotechnical
Commission
(IEC)
impedance Z, which in this case is half the line surge impedance Zo since the
current will flow in both directions as shown in Figure (2-1). Therefore, the
voltage surge magnitude at the striking point is [1]:
v = ()IZo
(2-1)
The lightning current magnitude is rarely less than 10 kA [6] and thus, for
typical overhead line surge impedance Zo of 300 , the lightning surge voltage
will probably have a magnitude in excess of 1500 kV.
Equation (2-1) assumes that the impedance of the lightning channel itself is
much larger than (1/2) Zo; indeed, it is believed to range from 100 to 3000 .
Equation (2-1) also indicates that the lightning voltage surge will have
approximately the same shape characteristics. In practice, however, the shapes
and magnitudes of lightning surge waves get modified by their reflections at
points of discontinuity as they travel along transmission lines Lightning strokes
represent true danger to life, structures, power systems, and communication
networks. Lightning is always a major source of damage to power systems
where equipment insulation may break down under the resulting overvoltage
and the subsequent high-energy discharge.
Figure (2-3) (a) Four-legged reactor for draining trapped charge and quenching
secondary arc during single-pole reclosing.
(b) Switching arrangement of series resistance in circuit breaker.
MBMain breaker. ABAuxiliary breaker
voltage settles down to the source voltage very quickly. However, when reenergization with trapped charge occurs a maximum of 2 p.u. will be attained.
Thus, with series-resistance switching the overvoltage is never higher than2
p.u. This has been verified by a large number of switching surge studies using
the Transient Network Analyzer and Digital computer. The value of resistance
R in general depends on a large number of factors as follows, [7]:
(a) The value of R is selected to achieve optimum results for the system.
(b) The surge impedance of connected lines when there is a single line or
multiple lines.
The lines switched might not all be of equal length so that complications arise
due to reflections from the shorter lines getting into the longer ones and viceversa.
(c) The insertion time of the resistance controls the overvoltage. From a large
number of studies, the following recommendations are made:
1. The insertion time is 810 ms or 1/ 2 cycle on 60 Hz or 50 Hz basis. After
this time, the resistance is shorted.
2. The value of resistance is slightly higher than the surge impedance of a
single line which is switched. In older designs a value of the order of 1000
Ohms was used, but modern practice is nearly 400 Ohms.
3. The closing span of the circuit-breaker poles must be controlled within 60.
The last item is very important under 3-phase reclosing operations. Poorlymaintained breakers can have a 180 lag between the first and last pole to close
which result in high overvoltages since the last phase has a trapped voltage
induced in it by the other phases which have already been energized. On the
other hand, because of the non-synchronous or nonsimultaneous closure of the
poles with resulting unbalanced conditions, ground-return currents are present
which help to attenuate the surges. However, each case must be studied
carefully on models and the worst case guarded against.
10
11
12
XC
XC X
(2-2)
S
Vr
1
=
Vs cos ol
(2-3)
o = LC where L and C are the inductance and capacitance of the line per
unit length. o has a value of about 6o per 100 km at normal power
frequency[1].
13
'
C
XC
1 X c / X
(2-4)
r
14