ATV12 - Communication Parameters


DANGER

UNINTENDED EQUIPMENT OPERATION


Read and understand this document, the User Manual and Modbus Manual before installing or operating the Altivar 12 drive.
Any changes made to the parameter settings must be performed by qualified personnel.
Failure to follow these instructions will result in death or serious injury.

WARNING
LOSS OF CONTROL
The designer of any control scheme must
- consider the potential failure modes of control paths and, for certain critical control functions,
- provide a means to achieve a safe state during and after a path failure.
Examples of critical control functions are emergency stop and overtravel stop.
Separate or redundant control paths must be provided for critical control functions.
System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link. (see
note a.)
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Note a.: For additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1
(latest edition), Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems.

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.

EXPLANATORY NOTE
This Excel file is for reference only . Refer to both the Altivar 12 User Manual and the Altivar 12 Modbus Communication Manual for full information.
This Excel file can be used to carry out searches (e.g. parameter address and format) and sort operations.
The columns include the following criteria:
Code: Language-independent, this allows a rapid search in the Altivar 12 User Manual, which includes an index of parameter codes.
Additional information can be found in the Altivar 12 Modbus Communication Manual.
Name: Parameter designation
Logic address: Address for the Modbus messaging are in decimal and hexadecimal (preceded by 16#) format.
To optimize Modbus messaging performance, two addresses are given for the control word (CMD) and the status word (ETA).
The addresses annotated "speed" are for use in rpm; the addresses annotated "frequency" are for use in Hz.
Link: For WORD type parameters, a dynamic link opens the description of a bit register or a listing. Listings are common to several parameters; only
one part is valid for a given parameter. Refer to both the Altivar 12 User Manual and the Altivar 12 Modbus Communication Manual to determine the
valid values. If an invalid value is written to a configuration parameter, the drive will indicate a fault [Invalid config.] (CFI).
Category: Defines the role of the parameter, for example: Command parameter, Status parameter, etc.
Access: Read and write options:
R: Read only
R/W: Read and write
R/WS: Read and write (write only possible when the drive is not in RUN mode).
It is not possible to write these parameters in "5-Operation enabled" or "6-Quick stop active" states.
If the parameter is written in the "4-Switched on" state, transition 10 to "2-Switch on disabled" is activated.
Type:
WORD (bit register): Word where each bit represents a command or a state
WORD (listing): Word where each value represents a possible choice for a configuration or state
INT: Signed integer
UINT: Unsigned integer
DINT: Signed double integer
UDINT: Unsigned double integer
Units: Physical unit and multiplier
Factory setting: Value of the parameter set at the factory.
Range: Possible values
Display: Parameter name displayed on the graphic display terminal, in square brackets [---], and parameter code displayed by the 7-segment digits on
the integrated display terminal, in round brackets (---).
Menu: Indicates the menus or menus where the parameter is located. Menu name displayed on the graphic display terminal, in square brackets [---],
and menu code displayed by the 7-segment digits on the integrated display terminal, in round brackets (---).
Order: Gives the initial storage order of the parameter in the file, from 1 to n. This makes it possible, after sorting operations, to put this file back in its
initial order by sorting the column in ascending order.

www.Schneider-Electric.com

ATV12 - Communication Parameters - BBV51917 04/2009

Page 1 / 15

Parameters
Code

337648898.xls
Name

Logic
address

CMD

Control word

16#2199 = 8601
(speed)
16#2135 = 8501
(frequency)

CMI

Extended control word

16#2138 = 08504

RPR

Reset counters command

16#0C30 = 03120

LFRD Speed setpoint

16#219A = 08602

Link

Category

Access

Type

Units

Factory setting

Range

CMD

Control parameters

R/W

WORD (BitString16)

CMI
RPR

Control parameters

R/W

WORD (BitString16)

Control parameters

R/W

WORD (Enumeration) -

[No](nO)

0 rpm

-32767 rpm ... 32767


rpm

Setpoint parameters

R/W

INT (Signed16)

1 rpm

LFR

Frequency setpoint

16#2136 = 08502

Setpoint parameters

R/W

INT (Signed16)

0.1 Hz

0 Hz

-3276.7 Hz ... 3276.7


Hz

PISP

PID regulator setpoint

16#2137 = 08503

Setpoint parameters

R/W

UINT (Unsigned16)

0.1 %

0%

0 % ... 100 %

Display

Menu

Order

1
2
[Operating t. reset] (rPr)

[FAULT MANAGEMENT] (FLt-)

[HMI Frequency ref.] (LFr)

(rEF-)
(MOn-)
[COMMAND] (CtL-)

(AIU1)

(rEF-)
(MOn-)
[COMMAND] (CtL-)

3
4
5
6

AIV1

PID regulator feedback

16#14A1 = 05281

Setpoint parameters

R/W

INT (Signed16)

0.1 %

0%

0 % ... 100 %

ETA

Status word

16#219B = 8603
(speed)
16#0C81 = 3201
(frequency)

ETA

Status parameters

WORD (BitString16)

HMIS

Status parameters

WORD (Enumeration) -

Status parameters

WORD (BitString16)

10

Status parameters

WORD (BitString16)

11

Status parameters

WORD (BitString16)

12

Status parameters

WORD (Enumeration) -

13
14

CNFS Config. active

16#1F54 = 08020

HMIS
ETI
CCC
CCC
CNFS

RFRD Output velocity

16#219C = 08604

Actual values parameters

INT (Signed16)

1 rpm

0 rpm

-32767 rpm ... 32767


rpm

Drive state

16#0CA8 = 03240

ETI

Extended status word

16#0C86 = 03206

CRC

Active reference channel

16#20F9 = 08441

CCC

Active command channel

16#20FA = 08442

RFR
LCR

Output frequency
Motor current

16#0C82 = 03202
16#0C84 = 03204

Actual values parameters


Actual values parameters

R
R

INT (Signed16)
UINT (Unsigned16)

0.1 Hz
0.1 A

0 Hz
0A

-500 Hz ... 500 Hz


0 A ... 6553.5 A

OPR

Motor power

16#0C8B = 03211

Actual values parameters

INT (Signed16)

1%

0%

FRH

Frequency reference before ramp 16#0C83 = 03203

Reference parameters

INT (Signed16)

0.1 Hz

RPC

PID reference after ramp

16#2ECE = 11982

Reference parameters

UINT (Unsigned16)

RPF

PID regulator feedback reference

16#2ECD = 11981

Reference parameters

RPE

PID regulator discrepancy

16#2ECC = 11980

Reference parameters

ULN
THD
THR
PTH
TAC
TAC2
NPL

Mains voltage
Drive thermal state
Motor thermal state
Total drive operating time
IGBT alarm time
Time at the minimum frequency
Logic input type

16#0C87 = 03207
16#0C89 = 03209
16#259E = 09630
16#0CA1 = 03233
16#0CA3 = 03235
16#0CAA = 03242
16#1003 = 04099

Measurement parameters
Measurement parameters
Measurement parameters
Measurement parameters
Measurement parameters
Measurement parameters
I/O parameters

Logic inputs state

16#1451 = 05201

IL1I

OL1R Logic outputs state


AI1I Analogic input state

16#145C = 05212
16#1466 = 05222

AI1C

Analog input 1 physical value

AI1R

NPL
I/O parameters
IL1I
OL1R I/O parameters

[Output frequency] (rFr)


[Motor current] (LCr)

(MOn-)
(MOn-)

15
16

-32767 % ... 32767 % [Motor power] (OPr)

(MOn-)

17

0 Hz

-3276.7 Hz ... 3276.7


Hz

[Frequency ref.] (FrH)

(rEF-)
(MOn-)

18

0.1 %

0%

0 % ... 6553.5 %

[PID reference] (rPC)

(rEF-)
(MOn-)

19

UINT (Unsigned16)

0.1 %

0%

0 % ... 6553.5 %

[PID feedback] (rPF)

(MOn-)

20

INT (Signed16)

0.1 %

0%

-3276.7 % ... 3276.7


%

[PID error] (rPE)

(MOn-)

21

R
R
R
R
R/WS
R/WS
R/WS

UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
WORD (Enumeration)

1V
1%
1%
0.01 h
1s
1s
-

0V
0%
0%
0h
0s
0s
[1](POS)

0 V ... 65535 V
0 % ... 200 %
0 % ... 200 %
0 h ... 655.35 h
0 s ... 65535 s
0 s ... 65535 s
-

[Mains voltage] (ULn)


[Drv. thermal state] (tHd)
[Motor thermal state] (tHr)
[Power on time] (PtH)

(MOn-)
(MOn-)
(MOn-)
(MAI-)

(nPL)

[INPUTS / OUTPUTS CFG] (I_O-)

22
23
24
25
26
27
28

WORD (BitString16)

29

WORD (BitString16)
INT (Signed16)

-32767 ... 32767

30
31

I/O parameters

R/W
R

16#147A = 05242

I/O parameters

INT (Signed16)

Refer to
program Refer to
Refer to programming
ming
programming manual manual
manual

32

Analog input 1 standardized value 16#1470 = 05232

I/O parameters

INT (Signed16)

33

www.Schneider-Electric.com

ATV12 - Communication Parameters - BBV51917 04/2009

-32767 ... 32767

1/15

Parameters
Code

337648898.xls
Name

Logic
address

Link

Category

Access

Type

Units

Factory setting

Range

Display

Menu

Order

16#1497 = 05271

I/O parameters

R/W

INT (Signed16)

Refer to
program Refer to
Refer to programming
ming
programming manual manual
manual

34

Analog output 1 standardized


value

16#148D = 05261

I/O parameters

R/W

INT (Signed16)

-32767 ... 32767

35

LFT

Altivar fault code

16#1BD1 = 07121

Fault parameters

WORD (Enumeration) -

36

CIC

Incorrect configuration

16#1BDA = 07130

Fault parameters

R/WS

WORD (BitString16)

37

DP0

Fault code on last fault

16#1C20 = 07200

History parameters

WORD (Enumeration) -

[No fault](nOF)

38

EP0

Status word on last fault

16#1C2A = 07210

History parameters

WORD (BitString16)

DP1

Fault code on fault n-1

16#1C21 = 07201

LFT
CIC
LFT
EP0
LFT

History parameters

WORD (Enumeration) -

[No fault](nOF)

ULP1

Supply voltage on fault n-1

16#1C67 = 07271

History parameters

UINT (Unsigned16)

1V

0V

0 V ... 65535 V

41

LCP1

Motor current on fault n-1

16#1C49 = 07241

History parameters

INT (Signed16)

0.1 A

0A

-3276.7 A ... 3276.7 A

42

RFP1

Output frequency on fault n-1

16#1C53 = 07251

History parameters

INT (Signed16)

0.1 Hz

0 Hz

-3276.7 Hz ... 3276.7


Hz

Status word on fault n-1

16#1C2B = 07211

EP0

History parameters

WORD (BitString16)

RTP1

Motor operating time on fault n-1

16#1C5D = 07261

History parameters

UINT (Unsigned16)

1h

0h

0 h ... 65535 h

45

OTP1

Estimated Motor torque value at


fault 1

16#1CA3 = 07331

History parameters

INT (Signed16)

1%

0%

-32767 % ... 32767 %

46

TDP1

Measured drive thermal state at


fault 1

16#1CAD = 07341

History parameters

UINT (Unsigned16)

1%

0%

0 % ... 255 %

47

TJP1

Estimated power component


temperature (Tj) at fault 1

16#1CB7 = 07351

History parameters

UINT (Unsigned16)

1 C

0 C

0 C ... 255 C

48

SFP1

Actual motor switching frequency


at fault 1

16#1CC1 = 07361

History parameters

UINT (Unsigned16)

1 Hz

0 Hz

0 Hz ... 65535 Hz

DP2
ULP2

Fault code on fault n-2


Supply voltage on fault n-2

16#1C22 = 07202
16#1C68 = 07272

LFT
-

History parameters
History parameters

R
R

WORD (Enumeration) UINT (Unsigned16)


1V

[No fault](nOF)
0V

0 V ... 65535 V

LCP2

Motor current on fault n-2

16#1C4A = 07242

History parameters

INT (Signed16)

0.1 A

0A

-3276.7 A ... 3276.7 A

52

RFP2

Output frequency on fault n-2

16#1C54 = 07252

History parameters

INT (Signed16)

0.1 Hz

0 Hz

-3276.7 Hz ... 3276.7


Hz

53

AO1C Analog output 1 physical value

AO1R

EP1

39
[Past fault 1] (dP1)

(MAI-)

40

43
[ETA state word] (EP1)

(MAI-)

44

49
[Past fault 2] (dP2)

(MAI-)

50
51

Status word on fault n-2

16#1C2C = 07212

EP0

History parameters

WORD (BitString16)

RTP2

Motor operating time on fault n-2

16#1C5E = 07262

History parameters

UINT (Unsigned16)

1h

0h

0 h ... 65535 h

55

OTP2

Estimated Motor torque value at


fault 2

16#1CA4 = 07332

History parameters

INT (Signed16)

1%

0%

-32767 % ... 32767 %

56

TDP2

Measured drive thermal state at


fault 2

16#1CAE = 07342

History parameters

UINT (Unsigned16)

1%

0%

0 % ... 255 %

57

TJP2

Estimated power component


temperature (Tj) at fault 2

16#1CB8 = 07352

History parameters

UINT (Unsigned16)

1 C

0 C

0 C ... 255 C

58

SFP2

Actual motor switching frequency


at fault 2

16#1CC2 = 07362

History parameters

UINT (Unsigned16)

1 Hz

0 Hz

0 Hz ... 65535 Hz

59

DP3
ULP3

Fault code on fault n-3


Supply voltage on fault n-3

16#1C23 = 07203
16#1C69 = 07273

LFT
-

History parameters
History parameters

R
R

WORD (Enumeration) UINT (Unsigned16)


1V

[No fault](nOF)
0V

0 V ... 65535 V

LCP3

Motor current on fault n-3

16#1C4B = 07243

History parameters

INT (Signed16)

0A

-3276.7 A ... 3276.7 A

62
63

EP2

RFP3

0.1 A

Output frequency on fault n-3

16#1C55 = 07253

History parameters

INT (Signed16)

0.1 Hz

0 Hz

-3276.7 Hz ... 3276.7


Hz

[ETA state word] (EP2)

[Past fault 3] (dP3)

(MAI-)

54

(MAI-)

60
61

Status word on fault n-3

16#1C2D = 07213

EP0

History parameters

WORD (BitString16)

RTP3

Motor operating time on fault n-3

16#1C5F = 07263

History parameters

UINT (Unsigned16)

1h

0h

0 h ... 65535 h

65

OTP3

Estimated Motor torque value at


fault 3

16#1CA5 = 07333

History parameters

INT (Signed16)

1%

0%

-32767 % ... 32767 %

66

EP3

www.Schneider-Electric.com

ATV12 - Communication Parameters - BBV51917 04/2009

[ETA state word] (EP3)

(MAI-)

64

2/15

Parameters
Code

337648898.xls
Name

Logic
address

Link

Category

Access

Type

Units

Factory setting

Range

Display

Menu

Order

TDP3

Measured drive thermal state at


fault 3

16#1CAF = 07343

History parameters

UINT (Unsigned16)

1%

0%

0 % ... 255 %

67

TJP3

Estimated power component


temperature (Tj) at fault 3

16#1CB9 = 07353

History parameters

UINT (Unsigned16)

1 C

0 C

0 C ... 255 C

68

SFP3

Actual motor switching frequency


at fault 3

16#1CC3 = 07363

History parameters

UINT (Unsigned16)

1 Hz

0 Hz

0 Hz ... 65535 Hz

69

DP4

Fault code on fault n-4

16#1C24 = 07204

LFT

History parameters

WORD (Enumeration) -

[No fault](nOF)

ULP4

Supply voltage on fault n-4

16#1C6A = 07274

History parameters

UINT (Unsigned16)

1V

0V

0 V ... 65535 V

71

LCP4

Motor current on fault n-4

16#1C4C = 07244

History parameters

INT (Signed16)

0.1 A

0A

-3276.7 A ... 3276.7 A

72
73

RFP4

Output frequency on fault n-4

16#1C56 = 07254

History parameters

INT (Signed16)

0.1 Hz

0 Hz

-3276.7 Hz ... 3276.7


Hz

[Past fault 4] (dP4)

(MAI-)

70

Status word on fault n-4

16#1C2E = 07214

EP0

History parameters

WORD (BitString16)

RTP4

Motor operating time on fault n-4

16#1C60 = 07264

History parameters

UINT (Unsigned16)

1h

0h

0 h ... 65535 h

75

OTP4

Estimated Motor torque value at


fault 4

16#1CA6 = 07334

History parameters

INT (Signed16)

1%

0%

-32767 % ... 32767 %

76

TDP4

Measured drive thermal state at


fault 4

16#1CB0 = 07344

History parameters

UINT (Unsigned16)

1%

0%

0 % ... 255 %

77

TJP4

Estimated power component


temperature (Tj) at fault 4

16#1CBA = 07354

History parameters

UINT (Unsigned16)

1 C

0 C

0 C ... 255 C

78

SFP4

Actual motor switching frequency


at fault 4

16#1CC4 = 07364

History parameters

UINT (Unsigned16)

1 Hz

0 Hz

0 Hz ... 65535 Hz

79

NCV

Drive nominal rating

16#0BC3 = 03011

NCV

Identification parameters

R/WS

WORD (Enumeration) -

[Unknown rating](nO) -

[DrvNomRating] (nCU)

(MAI-)

80

VCAL
INV
VDP
SPN

Drive line voltage


Rated drive current
Drive software version
Specific product number

16#0BC4 = 03012
16#0BC9 = 03017
16#0CE6 = 03302
16#0CE5 = 03301

VCAL Identification parameters

WORD (Enumeration)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)

0.1 A
1
1

[No](nO)
Depends of rating
0
0

0 A ... 6553.5 A
0 ... 65535
0 ... 65535

[Drive mains Volts] (UCAL)

(MAI-)

(SPn)

(MAI-)

81
82
83
84

EP4

[ETA state word] (EP4)

(MAI-)

74

Identification parameters
Identification parameters
Identification parameters

R/WS
R
R
R/W

NC1

Communication scanner, value of


16#31D9 = 12761
write word 1

Communication parameters

R/W

UINT (Unsigned16)

0 ... 65535

[Com Scan Out1 val.] (nC1)

[COM SCAN OUTPUT MAP] (OSA-)

85

NC2

Communication scanner, value of


16#31DA = 12762
write word 2

Communication parameters

R/W

UINT (Unsigned16)

0 ... 65535

[Com Scan Out2 val.] (nC2)

[COM SCAN OUTPUT MAP] (OSA-)

86

NC3

Communication scanner, value of


16#31DB = 12763
write word 3

Communication parameters

R/W

UINT (Unsigned16)

0 ... 65535

[Com Scan Out3 val.] (nC3)

[COM SCAN OUTPUT MAP] (OSA-)

87

NC4

Communication scanner, value of


16#31DC = 12764
write word 4

Communication parameters

R/W

UINT (Unsigned16)

0 ... 65535

[Com Scan Out4 val.] (nC4)

[COM SCAN OUTPUT MAP] (OSA-)

88

NM1

Communication scanner, value of


16#31C5 = 12741
read word 1

Communication parameters

UINT (Unsigned16)

0 ... 65535

[Com Scan In1 val.] (nM1)

[COM. SCANNER INPUT MAP] (ISA-) 89

NM2

Communication scanner, value of


16#31C6 = 12742
read word 2

Communication parameters

UINT (Unsigned16)

0 ... 65535

[Com Scan In2 val.] (nM2)

[COM. SCANNER INPUT MAP] (ISA-) 90

NM3

Communication scanner, value of


16#31C7 = 12743
read word 3

Communication parameters

UINT (Unsigned16)

0 ... 65535

[Com Scan In3 val.] (nM3)

[COM. SCANNER INPUT MAP] (ISA-) 91

NM4

Communication scanner, value of


16#31C8 = 12744
read word 4

Communication parameters

UINT (Unsigned16)

0 ... 65535

[Com Scan In4 val.] (nM4)

[COM. SCANNER INPUT MAP] (ISA-) 92

SCS

Save configuration

16#1F41 = 08001

R/WS

WORD (Enumeration) -

[No](nO)

(SCS)

(COnF-)

93

FCS

Restore configuration

16#1F42 = 08002

Configuration management

R/WS

WORD (Enumeration) -

(nO)

(FCS)

(COnF-)

94

CFG
LSP
HSP
ITH
SFC
CTD
FTD
BFR

Macro configuration
Low speed
High speed
Mot. therm. current
K speed loop filter
Current threshold
Freq. threshold
Standard mot. freq

16#0BEC = 03052
16#0C21 = 03105
16#0C20 = 03104
16#2596 = 09622
16#2391 = 09105
16#2AF9 = 11001
16#2AFB = 11003
16#0BC7 = 03015

SCS
FCS
CFG

Configuration management
Simply start
Settings
Settings
Settings
Settings
Settings
Settings
Motor control

R/WS
R/W
R/W
R/W
R/W
R/W
R/W
R/WS

WORD (Enumeration)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
WORD (Enumeration)

[Start/Stop](StS)
0 Hz
0.1 Hz
0.1 A
0
0.1 A
0.1 Hz
[50Hz IEC](50)

0 Hz ... 400 Hz
0 Hz ... 400 Hz
0 A ... 6553.5 A
0 ... 100
0 A ... 6553.5 A
0 Hz ... 400 Hz
-

[Macro configuration] (CFG)


[Low speed] (LSP)
[High speed] (HSP)
[Mot. therm. current] (ItH)

(FULL-)
(SPL-)
(SPL-)
[MOTOR THERMAL PROT.] (tHt-)

[Current threshold] (Ctd)


[Freq. threshold] (Ftd)
[Standard mot. freq] (bFr)

[INPUTS / OUTPUTS CFG] (I_O-)


[INPUTS / OUTPUTS CFG] (I_O-)
[MOTOR CONTROL] (drC-)

95
96
97
98
99
100
101
102

www.Schneider-Electric.com

BFR

0.1 Hz
0.1 Hz
0.1 A
1
0.1 A
0.1 Hz
-

ATV12 - Communication Parameters - BBV51917 04/2009

3/15

Parameters
Code

337648898.xls
Name

Logic
address

Link

Category

Access

Type

Units

Factory setting

Range

Display

Menu

Order

NPR

Rated motor power

16#258D = 09613

Motor control

R/WS

UINT (Unsigned16)

Refer to
program
Depends of rating
ming
manual

Refer to programming
[Rated motor power] (nPr)
manual

[MOTOR CONTROL] (drC-)

103

UNS
NCR
FRS
NSP
COS
MTM

Rated motor volt.


Rated mot. current
Rated motor freq.
Rated motor speed
Rated motor cos Phi
Motor thermal state memo

16#2581 = 09601
16#2583 = 09603
16#2582 = 09602
16#2584 = 09604
16#2586 = 09606
16#2590 = 09616

Motor control
Motor control
Motor control
Motor control
Motor control
Motor control

R/WS
R/WS
R/WS
R/WS
R/WS
R/WS

UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
WORD (Enumeration)

1V
0.1 A
0.1 Hz
1 rpm
0.01
-

230 V
Depends of rating
0.1 Hz
Depends of rating
Depends of rating
[No](nO)

100 V ... 480 V


0 A ... 6553.5 A
10 Hz ... 400 Hz
0 rpm ... 24000 rpm
0.5 ... 1
-

[Rated motor volt.] (UnS)


[Rated mot. current] (nCr)
[Rated motor freq.] (FrS)
[Rated motor speed] (nSP)
(COS)
(MtM)

[MOTOR CONTROL] (drC-)


[MOTOR CONTROL] (drC-)
[MOTOR CONTROL] (drC-)
[MOTOR CONTROL] (drC-)
[MOTOR CONTROL] (drC-)
[MOTOR THERMAL PROT.] (tHt-)

104
105
106
107
108
109

STUN Autotune selection store

16#2591 = 09617

N_Y
ACT

Motor control

WORD (Enumeration) -

[Not done](tAb)

FLG
STA
TFR

Frequency loop gain


Frequency loop stability
Max frequency

16#2594 = 09620
16#2595 = 09621
16#0C1F = 03103

Motor control
Motor control
Motor control

R/W
R/W
R/WS

UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)

20 %
20 %
0.1 Hz

0 % ... 100 %
0 % ... 100 %
10 Hz ... 400 Hz

[FreqLoopGain] (FLG)
[Fr.Loop.Stab] (StA)
[Max frequency] (tFr)

[MOTOR CONTROL] (drC-)


[MOTOR CONTROL] (drC-)
[MOTOR CONTROL] (drC-)

111
112
113

TUN

Auto tuning

16#2588 = 09608

TUN

Motor control

R/WS

WORD (Enumeration) -

[No](nO)

[Auto tuning] (tUn)

[MOTOR CONTROL] (drC-)

114

CTT

Motor control type

16#2587 = 09607

CTT

Motor control

R/WS

WORD (Enumeration) -

Refer to
programming manual

[Motor control type] (Ctt)

[MOTOR CONTROL] (drC-)

115

UFR
PFL
SLP

IR compensation
Flux profile
Slip compensation

16#2597 = 09623
16#2598 = 09624
16#2599 = 09625

Motor control
Motor control
Motor control

R/W
R/W
R/W

UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)

1%
1%
1%

100 %
20 %
1%

25 % ... 200 %
0 % ... 100 %
0 % ... 150 %

[IR compensation] (UFr)


[U/F Profile] (PFL)
[Slip compensation] (SLP)

[MOTOR CONTROL] (drC-)


[MOTOR CONTROL] (drC-)
[MOTOR CONTROL] (drC-)

116
117
118

Inertia gain for the derivative term


16#259D = 09629
of the UF laws

Motor control

R/W

UINT (Unsigned16)

1%

40 %

0 % ... 1000 %

119
120

SPGU

1%
1%
0.1 Hz

110

RSM

Stator R measured

16#25A8 = 09640

Motor control

UINT (Unsigned16)

1 mOhm 0 mOhm

0 mOhm ... 65535


mOhm

RSMI
SFT
SFR
CLI
NRD

Measured stator resistance


Switching frequency type
Switching freq.
Current Limitation
Noise reduction

16#25A9 = 09641
16#0C1D = 03101
16#0C1E = 03102
16#23F1 = 09201
16#0C23 = 03107

R
R/WS
R/W
R/W
R/WS

UINT (Unsigned16)
WORD (Enumeration)
UINT (Unsigned16)
UINT (Unsigned16)
WORD (Enumeration)

1
0.1 kHz
0.1 A
-

0
(HF1)
4 kHz
Depends of rating
[No](nO)

0 ... 65535
2 kHz ... 16 kHz
0 A ... 6553.5 A
-

(SFt)
[Switching freq.] (SFr)
[Current Limitation] (CLI)
[Noise reduction] (nrd)

[MOTOR CONTROL] (drC-)


[MOTOR CONTROL] (drC-)
[2nd CURRENT LIMIT.] (CLI-)
[MOTOR CONTROL] (drC-)

121
122
123
124
125

TCC

2/3 wire control

16#2B5D = 11101

Inputs / outputs cfg

R/WS

WORD (Enumeration) -

[2 wire](2C)

[2/3 wire control] (tCC)

[INPUTS / OUTPUTS CFG] (I_O-)

126

TCT

2 wire type

16#2B5E = 11102

N_Y
TCC
TCT

Motor control
Motor control
Motor control
Motor control
Motor control
Inputs / outputs cfg

R/WS

WORD (Enumeration) -

[Transition](trn)

[2 wire type] (tCt)

[INPUTS / OUTPUTS CFG] (I_O-)

127

RRS

Reverse assign.

16#2B61 = 11105

PSL

Inputs / outputs cfg

R/WS

WORD (Enumeration) -

Refer to
programming manual

[Reverse assign.] (rrS)

[APPLICATION FUNCT.] (FUn-)

128

AI1T

AI1 Type

16#1132 = 04402

AIOT

AI1 configuration

R/WS

WORD (Enumeration) -

Refer to
programming manual

[AI1 Type] (AI1t)

[AI1 CONFIGURATION] (AI1-)

129

CRL1

AI1 current scaling parameter of


0%

16#1150 = 04432

AI1 configuration

R/WS

UINT (Unsigned16)

0.1 mA

4 mA

0 mA ... 20 mA

(CrL1)

[AI1 CONFIGURATION] (AI1-)

130

CRH1

AI1 current scaling parameter of


100%

16#115A = 04442

AI1 configuration

R/WS

UINT (Unsigned16)

0.1 mA

20 mA

0 mA ... 20 mA

(CrH1)

[AI1 CONFIGURATION] (AI1-)

131

R1 Assignment

16#1389 = 05001

R1 configuration

R/WS

WORD (Enumeration) -

[No drive flt](FLt)

[R1 Assignment] (r1)

[INPUTS / OUTPUTS CFG] (I_O-)

132

R1S

R1 Active at

16#1069 = 04201

R1 configuration

R/WS

WORD (Enumeration) -

[1](POS)

LO1

LO1 assignment

16#1391 = 05009

LO1 configuration

R/WS

WORD (Enumeration) -

[No](nO)

[LO1 assignment] (LO1)

[LO1 CONFIGURATION] (LO1-)

134

LO1S

LO1 active at

16#1071 = 04209

LO1 configuration

R/WS

WORD (Enumeration) -

[1](POS)

[LO1 active at] (LO1S)

[LO1 CONFIGURATION] (LO1-)

135

AO1

AO1 assignment

16#139D = 05021

AO1 configuration

R/WS

WORD (Enumeration) -

[No](nO)

[AO1 assignment] (AO1)

[AO1 CONFIGURATION] (AO1-)

136

AO1 Type

16#11F9 = 04601

PSL
NPL
PSL
NPL
PSA
AIOT

AO1 configuration

R/WS

WORD (Enumeration) -

[Current](0A)

[AO1 Type] (AO1t)

[AO1 CONFIGURATION] (AO1-)

137

FR1

Ref.1 channel

16#20DD = 08413

PSA

Command

R/WS

WORD (Enumeration) -

Refer to
programming manual

[Ref.1 channel] (Fr1)

[COMMAND] (CtL-)

138

RIN

RV Inhibition

16#0C24 = 03108

N_Y

Command

R/WS

WORD (Enumeration) -

Refer to
programming manual

[RV Inhibition] (rIn)

[COMMAND] (CtL-)

139

R1

AO1T

www.Schneider-Electric.com

SFT
-

ATV12 - Communication Parameters - BBV51917 04/2009

133

4/15

Parameters
Code
PST

337648898.xls
Name

Stop Key priority

CHCF Profile

Logic
address
16#FA02 = 64002
16#20D1 = 08401

CD1

Cmd channel 1

16#20E7 = 08423

RPT
ACC
DEC

Ramp type
Acceleration
Deceleration

16#232C = 09004
16#2329 = 09001
16#232A = 09002

RPS

Ramp switch assignment

16#2332 = 09010

Link

Category

N_Y
CHCF Command
CDX Command
RPT Ramp
Command

Access

Type

Units

Factory setting

Range

Display

Menu

Order

R/WS

WORD (Enumeration) -

[Yes](YES)

[Stop Key priority] (PSt)

[COMMAND] (CtL-)

140

R/WS

WORD (Enumeration) -

[Not separ.](SIM)

[Profile] (CHCF)

[COMMAND] (CtL-)

141

R/WS

WORD (Enumeration) -

[Terminals](tEr)

[Cmd channel 1] (Cd1)

[COMMAND] (CtL-)

142

WORD (Enumeration) UINT (Unsigned16)


0.1 s
UINT (Unsigned16)
0.1 s

[Linear](LIn)
3s
3s

0 s ... 999.9 s
0 s ... 999.9 s

[Ramp type] (rPt)


[Acceleration] (ACC)
[Deceleration] (dEC)

[RAMP] (rPt-)
[RAMP] (rPt-)
[RAMP] (rPt-)

143
144
145

WORD (Enumeration) -

[No](nO)

[Ramp switch ass.] (rPS)

[RAMP] (rPt-)

146
147

Ramp
Ramp

R/W
R/W
R/W

PSL

Ramp

R/WS

AC2

Acceleration 2

16#2334 = 09012

Ramp

R/W

UINT (Unsigned16)

0.1 s

5s

0 s ... 999.9 s

[Acceleration 2] (AC2)

[RAMP] (rPt-)
[PID REGULATOR] (PId-)

DE2

Deceleration 2

16#2335 = 09013

Ramp

R/W

UINT (Unsigned16)

0.1 s

5s

0 s ... 999.9 s

[Deceleration 2] (dE2)

[RAMP] (rPt-)

148

BRA

Dec ramp adapt.

16#232B = 09003

Ramp

R/WS

WORD (Enumeration) -

[Yes](YES)

[Dec ramp adapt.] (brA)

[RAMP] (rPt-)

149

STT

Type of stop

16#2BC1 = 11201

Stop configuration

R/WS

WORD (Enumeration) -

[Ramp stop](rMP)

[Type of stop] (Stt)

[STOP CONFIGURATION] (Stt-)

150

NST

Freewheel stop ass.

16#2BC2 = 11202

Stop configuration

R/WS

WORD (Enumeration) -

[No](nO)

[Freewheel stop ass.] (nSt)

[STOP CONFIGURATION] (Stt-)

151

FST

Fast stop assign.

16#2BC4 = 11204

BRA
STT
PSL
PSL

Stop configuration

R/WS

WORD (Enumeration) -

[No](nO)

[Fast stop assign.] (FSt)

[STOP CONFIGURATION] (Stt-)

152

DCF
ADC
SDC1
TDC1

Ramp divider
Auto DC injection
Auto DC inj. level 1
Auto DC inj. time 1

16#2BDE = 11230
16#28A1 = 10401
16#28A3 = 10403
16#28A2 = 10402

Stop configuration
Auto DC injection
Auto DC injection
Auto DC injection

R/W
R/W
R/W
R/W

UINT (Unsigned16)
WORD (Enumeration)
UINT (Unsigned16)
UINT (Unsigned16)

4
[Yes](YES)
0.1 A
0.5 s

1 ... 10
0 A ... 6553.5 A
0.1 s ... 30 s

[Ramp divider] (dCF)


[Auto DC injection] (AdC)
[Auto DC inj. level 1] (SdC1)
[Auto DC inj. time 1] (tdC1)

[STOP CONFIGURATION] (Stt-)


[AUTO DC INJECTION] (AdC-)
[AUTO DC INJECTION] (AdC-)
[AUTO DC INJECTION] (AdC-)

153
154
155
156

JOG

JOG

16#2B66 = 11110

PSL

JOG

R/WS

WORD (Enumeration) -

[No](nO)

[JOG] (JOG)

[APPLICATION FUNCT.] (FUn-)

157

JGF

Jog frequency

16#2B67 = 11111

JOG

R/W

UINT (Unsigned16)

5 Hz

0 Hz ... 10 Hz

PS2

2 preset speeds

16#2C89 = 11401

PSL

Preset speeds

R/WS

WORD (Enumeration) -

Refer to
programming manual

[2 preset speeds] (PS2)

[PRESET SPEEDS] (PSS-)

159

PS4

4 preset speeds

16#2C8A = 11402

PSL

Preset speeds

R/WS

WORD (Enumeration) -

Refer to
programming manual

[4 preset speeds] (PS4)

[PRESET SPEEDS] (PSS-)

160

PS8
SP2
SP3
SP4
SP5
SP6
SP7
SP8
JPF

8 preset speeds
Preset speed 2
Preset speed 3
Preset speed 4
Preset speed 5
Preset speed 6
Preset speed 7
Preset speed 8
Skip frequency

16#2C8B = 11403
16#2C92 = 11410
16#2C93 = 11411
16#2C94 = 11412
16#2C95 = 11413
16#2C96 = 11414
16#2C97 = 11415
16#2C98 = 11416
16#2C25 = 11301

PSL
-

Preset speeds
Preset speeds
Preset speeds
Preset speeds
Preset speeds
Preset speeds
Preset speeds
Preset speeds
Jump frequency

R/WS
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W

WORD (Enumeration)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)

[No](nO)
10 Hz
0.1 Hz
0.1 Hz
25 Hz
30 Hz
35 Hz
40 Hz
0 Hz

[8 preset speeds] (PS8)


[Preset speed 2] (SP2)
[Preset speed 3] (SP3)
[Preset speed 4] (SP4)
[Preset speed 5] (SP5)
[Preset speed 6] (SP6)
[Preset speed 7] (SP7)
[Preset speed 8] (SP8)
[Skip Frequency] (JPF)

[PRESET SPEEDS] (PSS-)


[PRESET SPEEDS] (PSS-)
[PRESET SPEEDS] (PSS-)
[PRESET SPEEDS] (PSS-)
[PRESET SPEEDS] (PSS-)
[PRESET SPEEDS] (PSS-)
[PRESET SPEEDS] (PSS-)
[PRESET SPEEDS] (PSS-)
[APPLICATION FUNCT.] (FUn-)

161
162
163
164
165
166
167
168
169

PIF

PID feedback ass.

16#2E7D = 11901

PSA

PID regulator

R/WS

WORD (Enumeration) -

Refer to
programming manual

[PID feedback ass.] (PIF)

[PID REGULATOR] (PId-)

171

TLS

Low speed time out

16#2DB5 = 11701

PID regulator

R/W

UINT (Unsigned16)

[No](NO)

[No](NO) ... 999.9 s

[Low speed time out] (tLS)

[PID REGULATOR] (PId-)


(SPL-)

170

FBS
PII

PID Feedback scale factor


Act. internal PID ref.

16#2E7F = 11903
16#2E84 = 11908

N_Y

PID regulator
PID regulator

R/W
R/WS

UINT (Unsigned16)
0.1
WORD (Enumeration) -

1
[No](nO)

0.1 ... 100


-

[PID fbk scale factor] (FbS)


[Act. internal PID ref.] (PII)

[PID REGULATOR] (PId-)


[PID REGULATOR] (PId-)

172
173

RPI

Internal PID ref.

16#2E90 = 11920

PID regulator

R/W

UINT (Unsigned16)

0.1 %

0%

0 % ... 100 %

[Internal PID ref.] (rPI)

(rEF-)
[PID REGULATOR] (PId-)

174

RPL
RPH
RPG
RIG
RDG
PRP
PIC

PID minimum value reference


PID max value reference
PID prop. gain
PID integral gain
PID derivative gain
PID ramp
PID correct. reverse

16#2E87 = 11911
16#2E88 = 11912
16#2EA5 = 11941
16#2EA6 = 11942
16#2EA7 = 11943
16#2ED0 = 11984
16#2EA4 = 11940

N_Y

PID regulator
PID regulator
PID regulator
PID regulator
PID regulator
PID regulator
PID regulator

R/W
R/W
R/W
R/W
R/W
R/W
R/WS

UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
WORD (Enumeration)

0.1 %
0.1 %
0.01
0.01
0.01
0.1 s
-

0%
100 %
1
1
0
0s
[No](nO)

0 % ... 100 %
0 % ... 100 %
0.01 ... 100
0.01 ... 100
0 ... 100
0 s ... 99.9 s
-

(rPL)
(rPH)
[PID prop. gain] (rPG)
[PID integral gain] (rIG)
[PID derivative gain] (rdG)
[PID ramp] (PrP)
[PID correct. reverse] (PIC)

[PID REGULATOR] (PId-)


[PID REGULATOR] (PId-)
[PID REGULATOR] (PId-)
[PID REGULATOR] (PId-)
[PID REGULATOR] (PId-)
[PID REGULATOR] (PId-)
[PID REGULATOR] (PId-)

175
176
177
178
179
180
181

PAU

Auto/Manual assign.

16#2EC2 = 11970

PSL

PID regulator

R/WS

WORD (Enumeration) -

Refer to
programming manual

[Auto/Manual assign.] (PAU)

[PID REGULATOR] (PId-)

182

PIM

Manual reference

16#2EB2 = 11954

PSA

PID regulator

R/WS

WORD (Enumeration) -

[No](nO)

[Manual reference] (PIM)

[PID REGULATOR] (PId-)

183

www.Schneider-Electric.com

ADC

1
0.1 A
0.1 s
0.1 Hz

0.1 Hz
0.1 Hz
0.1 Hz
0.1 Hz
0.1 Hz
0.1 Hz
0.1 Hz
0.1 Hz

0.1 s

ATV12 - Communication Parameters - BBV51917 04/2009

0 Hz ... 400 Hz
0 Hz ... 400 Hz
0 Hz ... 400 Hz
0 Hz ... 400 Hz
0 Hz ... 400 Hz
0 Hz ... 400 Hz
0 Hz ... 400 Hz
0 Hz ... 400 Hz

158

5/15

Parameters

337648898.xls
Logic
address

Code

Name

SFS
RSL
UPP
PR2

PID predictive speed


PID wake up thresh.
Wake up threshold
2 preset PID ref.

16#2EB3 = 11955
16#2EB8 = 11960
16#2EBC = 11964
16#2E85 = 11909

Link

PR4

4 preset PID ref.

16#2E86 = 11910

RP2
RP3
RP4
LC2

Preset ref. PID 2


Preset ref. PID 3
Preset ref. PID 4
Current limit 2

16#2E91 = 11921
16#2E92 = 11922
16#2E93 = 11923
16#23F2 = 09202

CL2
RSF

I Limit. 2 value
Fault reset

16#23F3 = 09203
16#1BD4 = 07124

ATR

Automatic restart

16#1BD2 = 07122

TAR

Max. restart time

16#1BD3 = 07123

FLR

Catch on the fly

16#0C26 = 03110

THT

Motor protect. type

16#258C = 09612

PSL
N_Y
DUR
N_Y
THT

TTD

Motor therm. level

16#2AFA = 11002

OLL

Overload fault mgt

16#1B61 = 07009

Category

Access

Type
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
WORD (Enumeration)

PID preset references

R/WS

PID preset references


PID preset references
PID preset references
2nd current limit.

R/W
R/W
R/W
R/WS

2nd current limit.


Fault reset

R/W
R/WS

Automatic restart
Automatic restart

0.1 Hz
0.1 %
0.1 %
-

Factory setting

Range

Display

Menu

Order

[No](NO) ... 400 Hz


0 % ... 100 %
0 % ... 100 %
-

(SFS)
[PID wake up thresh.] (rSL)
[PID Wakeup Thres. ] (UPP)
[2 preset PID ref.] (Pr2)

[PID REGULATOR] (PId-)


[PID REGULATOR] (PId-)
[PID REGULATOR] (PId-)
[PID REGULATOR] (PId-)

184
185
186
187

WORD (Enumeration) -

[No](nO)

[4 preset PID ref.] (Pr4)

[PID REGULATOR] (PId-)

188

UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
WORD (Enumeration)

25 %
50 %
75 %
[No](nO)

0 % ... 100 %
0 % ... 100 %
0 % ... 100 %
-

[Preset ref. PID 2] (rP2)


[Preset ref. PID 3] (rP3)
[Preset ref. PID 4] (rP4)
[Current limit 2] (LC2)

[PID REGULATOR] (PId-)


[PID REGULATOR] (PId-)
[PID REGULATOR] (PId-)
[2nd CURRENT LIMIT.] (CLI-)

189
190
191
192

UINT (Unsigned16)
0.1 A
WORD (Enumeration) -

Depends of rating
[No](nO)

0 A ... 6553.5 A
-

[I Limit. 2 value] (CL2)


[Fault reset] (rSF)

[2nd CURRENT LIMIT.] (CLI-)


[FAULT MANAGEMENT] (FLt-)

193
194

R/WS

WORD (Enumeration) -

[No](nO)

[Automatic restart] (Atr)

[AUTOMATIC RESTART] (Atr-)

195

R/WS

WORD (Enumeration) -

[5 minutes](5)

[Max. restart time] (tAr)

[AUTOMATIC RESTART] (Atr-)

196

Catch on the fly

R/WS

WORD (Enumeration) -

[No](nO)

[Catch on the fly] (FLr)

[FAULT MANAGEMENT] (FLt-)

197

Motor thermal prot.

R/WS

WORD (Enumeration) -

[Self cooled](ACL)

[Motor protect. type] (tHt)

[MOTOR THERMAL PROT.] (tHt-)

198

Motor thermal prot.

R/W

UINT (Unsigned16)

100 %

0 % ... 118 %

[Motor therm. level] (ttd)

[INPUTS / OUTPUTS CFG] (I_O-)

199

ECFG Motor thermal prot.

R/WS

WORD (Enumeration) -

[Freewheel](YES)

[Overload fault mgt] (OLL)

[MOTOR THERMAL PROT.] (tHt-)

200

[Output Phase Loss] (OPL)

[FAULT MANAGEMENT] (FLt-)

201

PSL

R/WS
R/WS
R/W
R/WS

Units

[No](NO)
0%
0%
[No](nO)

PSL
PSL

PID regulator
PID regulator
PID regulator
PID preset references

0.1 %
0.1 %
0.1 %
-

1%

OPL

Output Phase Loss

16#258B = 09611

N_Y

Output phase loss

R/WS

WORD (Enumeration) -

[Yes](YES)

ODT

OutPh time detect

16#1BA9 = 07081

Output phase loss

R/W

UINT (Unsigned16)

0.5 s

0.5 s ... 10 s

IPL

Input phase loss

16#1B5A = 07002

ECFG Input phase loss

R/WS

WORD (Enumeration) -

Depends of rating

[Input phase loss] (IPL)

[FAULT MANAGEMENT] (FLt-)

203

USB

UnderV. fault mgt

16#35EB = 13803

R/WS

WORD (Enumeration) -

[Flt&R1open](0)

[UnderV. fault mgt] (USb)

[UNDERVOLTAGE MGT] (USb-)

204

UnderV. prevention
UnderV. restart tm
Max stop time
IGBT test

16#1B5C = 07004
16#35F5 = 13813
16#35F6 = 13814
16#0C28 = 03112

USB
STP

Undervoltage mgt

STP
TSM
STM
STRT

R/WS
R/W
R/W
R/WS

WORD (Enumeration)
UINT (Unsigned16)
UINT (Unsigned16)
WORD (Enumeration)

[No](nO)
1s
1s
[No](nO)

1 s ... 999.9 s
0 s ... 10 s
-

[UnderV. prevention] (StP)

[UNDERVOLTAGE MGT] (USb-)

[Max stop time] (StM)


[IGBT test] (Strt)

[UNDERVOLTAGE MGT] (USb-)


[FAULT MANAGEMENT] (FLt-)

205
206
207
208

INH

Fault inhibit assign.

16#1BD5 = 07125

N_Y
PSL

Undervoltage mgt
Undervoltage mgt
Undervoltage mgt
IGBT tests
Fault inhibition

R/WS

WORD (Enumeration) -

[No](nO)

[Fault inhibit assign.] (InH)

[FAULT MANAGEMENT] (FLt-)

209

SLL

Modbus fault mgt

16#1B62 = 07010

ECFG Com. fault management

R/WS

WORD (Enumeration) -

[Freewheel](YES)

[Modbus fault mgt] (SLL)

[FAULT MANAGEMENT] (FLt-)

210

LFL1

4-20 mA loos behaviour

16#1B69 = 07017

ECFG Com. fault management

R/WS

WORD (Enumeration) -

Refer to
programming manual

(LFL1)

[FAULT MANAGEMENT] (FLt-)

211

NCA1

Communication scanner, address


16#31B1 = 12721
of write word 1

Communication

R/WS

UINT (Unsigned16)

8501

0 ... 65535

[Scan.Out1 address] (nCA1)

[COM. SCANNER OUTPUT] (OCS-)

212

NCA2

Communication scanner, address


16#31B2 = 12722
of write word 2

Communication

R/WS

UINT (Unsigned16)

8602

0 ... 65535

[Scan.Out2 address] (nCA2)

[COM. SCANNER OUTPUT] (OCS-)

213

Communication scanner, address


NCA3
16#31B3 = 12723
of write word 3

Communication

R/WS

UINT (Unsigned16)

0 ... 65535

[Scan.Out3 address] (nCA3)

[COM. SCANNER OUTPUT] (OCS-)

214

Communication scanner, address


16#31B4 = 12724
of write word 4

Communication

R/WS

UINT (Unsigned16)

0 ... 65535

[Scan.Out4 address] (nCA4)

[COM. SCANNER OUTPUT] (OCS-)

215

Communication scanner, address


NMA1
16#319D = 12701
of read word 1

Communication

R/WS

UINT (Unsigned16)

3201

0 ... 65535

[Scan. IN1 address] (nMA1)

[COM. SCANNER INPUT ] (ICS-)

216

Communication scanner, address


16#319E = 12702
of read word 2

Communication

R/WS

UINT (Unsigned16)

8604

0 ... 65535

[Scan. IN2 address] (nMA2)

[COM. SCANNER INPUT ] (ICS-)

217

Communication scanner, address


NMA3
16#319F = 12703
of read word 3

Communication

R/WS

UINT (Unsigned16)

0 ... 65535

[Scan. IN3 address] (nMA3)

[COM. SCANNER INPUT ] (ICS-)

218

Communication scanner, address


16#31A0 = 12704
of read word 4

Communication

R/WS

UINT (Unsigned16)

0 ... 65535

[Scan. IN4 address] (nMA4)

[COM. SCANNER INPUT ] (ICS-)

219

Communication
Communication

R/WS
R/WS

UINT (Unsigned16)
1
WORD (Enumeration) -

[OFF](OFF)
[19.2 Kbps](19 2)

[OFF](OFF) ... 247


-

[Modbus Address] (Add)


[Modbus baud rate] (tbr)

[COMMUNICATION] (COM-)
[COMMUNICATION] (COM-)

220
221

Communication
Communication
Communication

R/WS
R/WS
R/WS

WORD (Enumeration) UINT (Unsigned16)


0.1 s
WORD (Enumeration) -

[8-E-1](8E1)
10 s
[No](nO)

0.1 s ... 30 s
-

[Modbus format] (tFO)


[Modbus time out] (ttO)
[Forced local assign.] (FLO)

[COMMUNICATION] (COM-)
[COMMUNICATION] (COM-)
[COMMAND] (CtL-)

222
223
224

NCA4

NMA2

NMA4
ADD
TBR

Modbus Address
Modbus baud rate

16#1771 = 06001
16#1773 = 06003

TFO
TTO
FLO

Modbus format
Modbus time out
Forced local assign.

16#1774 = 06004
16#1775 = 06005
16#20EF = 08431

www.Schneider-Electric.com

TBR
FOR
-

PSL

0.1 s

0.1 s
0.1 s
-

ATV12 - Communication Parameters - BBV51917 04/2009

202

6/15

Parameters
Code

337648898.xls
Name

Logic
address

Link

Category

Access

Type

Units

Factory setting

Range

Display

Menu

Order

PSA

Communication

R/WS

WORD (Enumeration) -

[No](nO)

[Forced local Ref.] (FLOC)

[COMMAND] (CtL-)

225

Measurement parameters
Measurement parameters
Measurement parameters

R
R/W
R

UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)

0.01 h
0.01 h
0.01 h

0h
0h
0h

0 h ... 655.35 h
0 h ... 655.35 h
0 h ... 655.35 h

(rtHI)
[Proc. Operat. Time] (PEt)
(FtH)

(MAI-)
(MAI-)
(MAI-)

226
227
228

16#384B = 14411

Motor load management

R/WS

UINT (Unsigned16)

1s

0s

0 s ... 100 s

[Unld T. Del. Detect] (ULt)

[INPUTS / OUTPUTS CFG] (I_O-)

229

Application underload threshold

16#384F = 14415

Motor load management

R/W

UINT (Unsigned16)

1%

60 %

20 % ... 100 %

[Unld.Thr.0.Speed] (LUL)

[INPUTS / OUTPUTS CFG] (I_O-)

230

TOL
LOC
SH2

Application Overload time delay


Application overload threshold
2 HSP assignment

16#3855 = 14421
16#3859 = 14425
16#3AFD = 15101

R/WS
R/W
R/WS

UINT (Unsigned16)
1s
UINT (Unsigned16)
1%
WORD (Enumeration) -

0s
90 %
[No](nO)

0 s ... 100 s
70 % ... 150 %
-

[Unld Time Detect.] (tOL)


[Ovld Detection Thr.] (LOC)
(SH2)

[INPUTS / OUTPUTS CFG] (I_O-)


[INPUTS / OUTPUTS CFG] (I_O-)
(SPL-)

231
232
233

SH4

4 HSP assignment

16#3AFE = 15102

PSL
PSL

Motor load management


Motor load management
Preset HSP
Preset HSP

R/WS

WORD (Enumeration) -

[No](nO)

(SH4)

(SPL-)

234

Display of High speed value


High speed 2
High speed 3
High speed 4

16#3B05 = 15109
16#3B06 = 15110
16#3B07 = 15111
16#3B08 = 15112

Preset HSP
Preset HSP
Preset HSP
Preset HSP

R
R/W
R/W
R/W

UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)
UINT (Unsigned16)

0 Hz
0.1 Hz
0.1 Hz
0.1 Hz

0 Hz ... 400 Hz
0 Hz ... 400 Hz
0 Hz ... 400 Hz
0 Hz ... 400 Hz

(HSU)
(HSP2)
(HSP3)
(HSP4)

(MAI-)
(SPL-)
(SPL-)
(SPL-)

235
236
237
238

FLOC Forced local Ref.

16#20F0 = 08432

RTHI
PET
FTH

Run elapsed time display


Process elapsed time
Fan time display

16#0CA0 = 03232
16#0CA4 = 03236
16#0CA7 = 03239

ULT

Application underload time delay

LUL

HSU
HSP2
HSP3
HSP4

www.Schneider-Electric.com

0.1 Hz
0.1 Hz
0.1 Hz
0.1 Hz

ATV12 - Communication Parameters - BBV51917 04/2009

7/15

Enumerations

337648898.xls
Code
ACT

ADC

AIOT

BFR
BRA

CDX

CFG

CHCF
CSA

CSL

CTT

www.Schneider-Electric.com

Values

Display

(tAb)

(PEnd)

(PrOG)

(FAIL)

(dOnE)

(nO)

(YES)

(Ct)

(5U)

(10U)

(0A)

(4A)

(n10U)

(GALU)

(50Hz)

(60Hz)

(nO)

(YES)

(dYnA)

(tEr)

(LOC)

(LCC)

10

(Mdb)

(StS)

(PId)

(SPd)

(SIM)

(SEP)

(nO)

(AO1)

129

(AIFr1)

132

(AIPIF)

138

(AIPIM)

163

(AIFLOC)

(nO)

(LIrUn)

(LIFrd)

(LIrrS)

(LIrPS)

(LIJOG)

(LIPS2)

(LIPS4)

10

(LIPS8)

12

(LInSt)

14

(LIFSt)

17

(LIFLO)

18

(LIrSF)

22

(LIPAU)

24

(LIPr2)

25

(LIPr4)

41

(LIInH)

43

(LILC2)

72

(LISH2)

73

(LISH4)

129

(LO1)

145

(r1)

(PErF)

(Std)

Description

ATV12 - Communication Parameters - BBV51917 04/2009

Page 1/15

Enumerations

337648898.xls
Code
DUR

ECFG
FCS

FOR

HMIS

LFT

www.Schneider-Electric.com

Values

Display

(PUMP)

(5)

(10)

(30)

(1H)

(2H)

(3H)

(Ct)

(nO)

(YES)

(nO)

(rEC1)

64

(InI)

71

(InI1)

(8O1)

(8E1)

(8n1)

(8n2)

(tUn)

(dCb)

(rdY)

(nSt)

(rUn)

(ACC)

(dEC)

(CLI)

(FSt)

11

(nLP)

13

(CtL)

14

(Obr)

23

(FLt)

[No fault] (nOF)

[Calibration error] (InF)

[Incorrect config.] (CFF)

[Invalid config.] (CFI)

[Modbus com.] (SLF1)

[Overcurrent] (OCF)

10

[Precharge] (CrF1)

16

[Drive overheat] (OHF)

17

[Motor overload] (OLF)

18

[Overbraking] (ObF)

19

[Mains overvoltage] (OSF)

20

[1 output phase loss] (OPF1)

21

[Input phase loss] (PHF)

22

[Undervoltage] (USF)

23

[Motor short circuit] (SCF1)

24

[Overspeed] (SOF)

25

[Auto-tuning ] (tnF)

26

[Rating error] (InF1)

27

[PWR Calib.] (InF2)

28

[Int.serial link] (InF3)

29

[Int.Mfg area] (InF4)

32

[Ground short circuit] (SCF3)

33

[3out ph loss] (OPF2)

42

[PowerSuite com.] (SLF2)

45

[HMI com.] (SLF3)

51

[Internal- I measure] (InF9)

53

[Internal- th. sensor] (InFb)

54

[IGBT overheat] (tJF)

Description

ATV12 - Communication Parameters - BBV51917 04/2009

Page 2/15

Enumerations

337648898.xls
Code

MPC
N_Y
NCV

NPL
PSA

PSL

www.Schneider-Electric.com

Values

Display

55

[IGBT short circuit] (SCF4)

56

[Motor short circuit] (SCF5)

69

[internal- CPU ] (InFE)

77

(CFI2)

100

[Pr.Underload.Flt] (ULF)

101

[Proc.Overload Flt] (OLC)

106

(LFF1)

253

(XXXX)

(nPr)

(COS)

(nO)

(YES)

(nO)

(U010)

(U018)

(U025)

(U037)

(U055)

(U075)

(U090)

(U110)

(U150)

10

(U185)

11

(U220)

12

(U300)

13

(U370)

14

(U400)

15

(U550)

16

(U750)

(POS)

(nEG)

(nO)

(AI1)

129

(OCr)

130

(OFr)

131

(OrP)

135

(OPS)

136

(OPF)

137

(OPE)

139

(OPr)

140

(tHr)

141

(tHd)

163

(LCC)

164

(Mdb)

183

(AIU1)

(nO)

(FLt)

(rUn)

(FtA)

(FLA)

(CtA)

(SrA)

(tSA)

10

(PEE)

11

(PFA)

21

(ULA)

22

(OLA)

123

(AP1)

129

(LI1)

Description

ATV12 - Communication Parameters - BBV51917 04/2009

Page 3/15

Enumerations

337648898.xls
Code

RPR

RPT

SCS
SFT
STP
STT

TBR

TCC
TCT

THT
TUN

USB
VCAL

www.Schneider-Electric.com

Values

Display

130

(LI2)

131

(LI3)

132

(LI4)

145

(L1L)

146

(L2L)

147

(L3L)

148

(L4L)

(nO)

(rtHI)

(PtH)

(FtH)

(LIn)

(S)

(U)

(nO)

(Str1)

(HF1)

(HF2)

(nO)

(rMP)

(rMP)

(FSt)

13

(nSt)

24

(4800)

28

(9600)

32

(19200)

36

(38400)

(2C)

(3C)

(LEL)

(trn)

(PFO)

(ACL)

(FCL)

(nO)

(YES)

(dOnE)

(0)

(1)

(nO)

(110M)

(110t)

(220M)

(220t)

Description

ATV12 - Communication Parameters - BBV51917 04/2009

Page 4/15

Registers
CMD

CMI

337648898.xls
bit 0:
bit 1:
bit 2:
bit 3:

= 1 : Switch on
= 0 : Disable voltage
= 0 : Quick stop/Emergency stop
= 1 : Enable operation/Run command

bit 4:
bit 5:
bit 6:
bit 7:

Reserved (set to 0).


Reserved (set to 0).
Reserved (set to 0).
Fault reset/Fault acknowledgment active on 0 V 1 rising edge

bit 8:
bit 9:
bit 10:
bit 11:

= 0 : RUN asked, 1 : STOP asked

bit 12:
bit 13:
bit 14:
bit 15:
bit 0:
bit 1:

bit 2:
bit 3:

Reserved (set to 0).


Reserved (set to 0).
Reserved (set to 0).
Reserved (set to 0).
Factory setting command (active at 1).
Save configuration to EEPROM non-volatile memory command (active at 1).
This bit automatically changes to 0 after the request is taken into account. The command is only active if the drive is stopped,
and not in "5-Operation enabled" state.
Note: If CMI is a periodic network variable, the PLC program must write it to 0 after the first request is taken into account.
The life of the EEPROM memory is limited to 100,000 write operations.
Note: If the motor or configuration switching function is active, the configuration in the RAM is saved to the EEPROM in the
configuration designated by [Config. Active] (CnFS).
Reserved (= 0).
Reserved (= 0).

bit 4:
bit 5:
bit 6:
bit 7:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 8:
bit 9:

Reserved (= 0).
Definition of the frequency reference (LFr) and output frequency (rFr) unit:
= 0 : 0.1 Hz
= 1 : Standardized value 16 signed bits based on the maximum frequency. The value 32767 corresponds to [Max frequency]
(tFr). The default value of [Max frequency] (tFr) is 60 Hz, and the resolution is then approximately 0.0018 Hz.

Reserved (set to 0).


Reserved (set to 0).
Direction of rotation command
= 0: Forward rotation
= 1: Reverse rotation. Default value, this bit can be assigned to another command.

This function has no effect on the speed reference (LFrd) or the output speed (rFrd).
bit 10: Reserved (= 0).
bit 11: Reserved (= 0).
bit 12:
bit 13:
bit 14:
bit 15:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Parameter consistency check
= 0: 'The check is activated. Each time a parameter is written, the drive checks the relationship between the written
parameter and the configuration in the drive. For example, the [High speed] (HSP) parameter must be less than [Max
frequency] (tFr).
= 1: 'The check is deactivated. The drive is locked in stop mode. In this drive state, the configuration can be written
parameter by parameter and the drive does not modify the values that are written.
The switch from 1 to 0 triggers a calculation of the consistency of the configuration. Some parameters can be modified
automatically by the drive.

www.Schneider-Electric.com

ATV12 - Communication Parameters - BBV51917 04/2009

Page 1 / 15

Registers
ETA

337648898.xls
bit 0:
bit 1:
bit 2:
bit 3:

= 1 : Ready to switch on
= 1 : Switched on, ready
= 1 : Operation enabled, running
= 1 : Fault detection

bit 4:
bit 5:
bit 6:
bit 7:

Voltage enabled (always = 1).


= 0 : Quick stop/Emergency stop
= 1 : Switched on disabled
Reserved (= 0)

bit 8:
bit 9:

Reserved (= 0)
Remote, command or reference via the network
= 0 : Command or reference via the terminals
= 1 : Command or reference via the network
bit 10: Target reached, reference reached
= 0 : The reference is not reached
= 1 : The reference has been reached
When the drive stops, the reference has been reached.
bit 11: Internal limit active, reference outside limits
= 0 : The reference is within the limits
= 1 : The reference is not within the limits
The limits are defined by the "Low speed (LSP)" and "High speed (HSP)" parameters.

ETI

bit 12: Reserved (= 0)


bit 13: Reserved (= 0)
bit 14: Stop key, STOP via stop key
= 0 : STOP key not pressed
= 1 : Stop triggered by the STOP key on the display terminal
bit 15: Direction, direction of rotation
= 0 : Forward rotation at output
= 1 : Reverse rotation at output
bit 0: = 1 : Access to the EEPROM non-volatile memory in progress
bit 1: = 0 : No parameter consistency check
= 1 : Parameter consistency check
bit 2: = 0 : The drive is not in fault state or a fault is detected
= 1 : The drive is in fault state but the fault is no longer present (not reset)
bit 3: Reserved (= 0).
bit 4:
bit 5:
bit 6:

EP0
EP1
EP2
EP3
EP4

bit 7:

= 1 : The drive is in speed mode


= 1 : DC injection
= 0 : Drive in steady state
= 1 : Drive in transient state
= 1 : Motor thermal state threshold reached for the active motor

bit 8:
bit 9:
bit 10:
bit 11:

Reserved (= 0).
= 1 : Acceleration in progress
= 1 : Deceleration in progress
= 1 : Current limit in progress

bit 12: = 1 : Fast stop in progress


bit 13: bit 13 = 0 and bit 14 = 0 : Drive controled by terminal or local keypad
bit 14: bit 13 = 1 and bit 14 = 0 : Drive controled by remote keypad
bit 13 = 0 and bit 14 = 1 : Drive controled by Modbus
bit 13 = 1 and bit 14 = 1 : Reserved
bit 15: = 0 : Forward operation applied before the ramp
= 1 : Reverse operation applied before the ramp
bit 0 : = 1 : Switched on (Same as ETA.1)
bit 1 : = 0 : Quick stop (Same as ETA.5)
bit 2 : = 1 : Switch on disabled (Same as ETA.6)
bit 3 : = 0 : Forced local mode in progress
bit 4 :
bit 5 :
bit 6 :
bit 7 :

= 0 : Motor rotation in forward direction (or stopped) (Same as ETA.15)


= 1 : Run order present (Same as ETI.4)
= 1 : DC injection running (Same as ETI.5)
= 1 : Motor thermal threshold reached (Same as ETI.7)

bit 8 : Reserved (Same as ETI.8)


bit 9 : = 1 : Product in acceleration (Same as ETI.9)
bit 10 : = 1 : Product in deceleration (Same as ETI.10)
bit 11 : = 1 : Current limit is running (Same as ETI.11)

bit 12 : = 1 : Fast stop in progress (Same as ETI.12)


bit 13: bit 13 = 0 and bit 14 = 0 : Drive controled by terminal or local keypad (Same as ETI.13 and ETI.14))
bit 14: bit 13 = 1 and bit 14 = 0 : Drive controled by remote keypad (Same as ETI.13 and ETI.14))
bit 13 = 0 and bit 14 = 1 : Drive controled by Modbus (Same as ETI.13 and ETI.14))
bit 13 = 1 and bit 14 = 1 : Reserved (Same as ETI.13 and ETI.14))
bit 15: = 1: Reverse operation applied before the ramp (Same as ETI.15)

www.Schneider-Electric.com

ATV12 - Communication Parameters - BBV51917 04/2009

Page 2 / 15

Registers
CCC
CRC

IL1I

OL1R

CIC

337648898.xls
bit 0:
bit 1:
bit 2:
bit 3:

= 1: The terminal board is the active channel.


= 1: The local keypad is the active channel.
= 1: The remote keypad is the active channel.
= 1: Modbus is the active channel.

bit 4:
bit 5:
bit 6:
bit 7:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 8:
bit 9:
bit 10:
bit 11:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 12:
bit 13:
bit 14:
bit 15:
bit 0:
bit 1:
bit 2:
bit 3:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
= 1: SoMove software is the active channel.
Value of LI1.
Value of LI2.
Value of LI3.
Value of LI4.

bit 4:
bit 5:
bit 6:
bit 7:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 8:
bit 9:
bit 10:
bit 11:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 12:
bit 13:
bit 14:
bit 15:
bit 0:
bit 1:
bit 2:
bit 3:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Value of R1.
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 4:
bit 5:
bit 6:
bit 7:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 8:
bit 9:
bit 10:
bit 11:

Value of LO1.
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 12:
bit 13:
bit 14:
bit 15:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

The outputs (relays or logic ouputs) can be controlled by the network. The outputs to control should not be assigned to a function of the
drive,
the writing
is without effect.
bit otherwise
0: = 1: Change
of rating.
bit 1: Reserved (= 0).
bit 2: Reserved (= 0).
bit 3: = 1: Saving to the EEPROM non-volatile memory is inconsistent with power on.
bit 4:
bit 5:
bit 6:
bit 7:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 8:
bit 9:
bit 10:
bit 11:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

bit 12:
bit 13:
bit 14:
bit 15:

Reserved (= 0).
Reserved (= 0).
Reserved (= 0).
Reserved (= 0).

If one of these events occurs, the drive will indicate a fault [Invalid config.] (CFI) and then automatically applies a factory setting.