2.

FIRE WATER FLOW RATE FOR CONE ROOF TANK PROTECTION

Data
Total storage capacity in one dyke area in M3

No of tanks

Coolng water flow rate


3.1428

cooling water required

Cooing water required for tank falling within R+30 from the centre of the tank und
Total storage capacity in one dyke area in M3

508

No of tanks

3.1428

cooling water required

Total cooing water required

Foam water flow rate


Foam solution application rate

5 lpm/m of liquid surface area

Foam solution required


Foam water required for 3% foam concentration

Total water flow rate for cone roof tank


protection

239.182 M3/ hr.

ANK PROTECTION

Capacity of each tank

Diameter of each tank

17

Cooling water rate

Diameter of each tank

17

Cooling water rate

1442.5452
LPM
86552.712

86.552712 M3/ hr.

ntre of the tank under fire


Capacity of each tank

1442.5452

5000

LPM
Rate of cooling water=3lpm/M3
of tank area

86552.712

86.552712 M3/ hr.


173.105424 M3/ hr.

4541.346 1135.337 LPM/M3


1101.276405

66076.5843

height of each tank

height of each tank

66.0765843 M3/ hr.

2.2

FIRE WATER FLOW RATE FOR CONE ROOF TANK PROTECTION

Data
Total storage capacity in one dyke area in M3

No of tanks

Coolng water flow rate


3.1428

cooling water required

Cooing water required for tank falling within R+30 from the centre of the tank und
Total storage capacity in one dyke area in M3

508

No of tanks

3.1428

cooling water required

Total cooing water required

Foam water flow rate


Foam solution application rate

5 lpm/m of liquid surface area

Foam solution required


Foam water required for 3% foam concentration

Total water flow rate for cone roof tank


protection

545.197 M3/ hr.

ANK PROTECTION

Capacity of each tank

Diameter of each tank

30

Cooling water rate

Diameter of each tank

30

Cooling water rate

2828.52
LPM
169711.2

169.7112 M3/ hr.

ntre of the tank under fire


Capacity of each tank

2828.52

5000

LPM
Rate of cooling water=3lpm/M3
of tank area

169711.2

169.7112 M3/ hr.


339.4224 M3/ hr.

14142.6
3429.5805

3535.65 LPM/M3
205774.83

height of each tank

10

height of each tank

10

205.77483 M3/ hr.

2.2

FIRE WATER FLOW RATE FOR CONE ROOF TANK PROTECTI

Data
Total storage capacity in one dyke area in M3

508

No of tanks

Coolng water flow rate


3.1428

cooling water required

Cooing water required for tank falling within R+30 from the centre of the tank u
Total storage capacity in one dyke area in M3

508

No of tanks

3.1428

cooling water required

Total cooing water required

Foam water flow rate


Foam solution application rate

5 lpm/m of liquid surface area

Foam solution required


Foam water required for 3% foam concentration

Total water flow rate for cone roof tank


protection

216.636

E ROOF TANK PROTECTION

Capacity of each tank

5000

Diameter of each tank

18

Cooling water rate

Diameter of each tank

10

Cooling water rate

1527.4008
LPM
91644.048

91.644048 M3/ hr.

om the centre of the tank under fire


2

Capacity of each tank

848.556

5000

LPM
Rate of cooling water=3lpm/M3
of tank area

50913.36

50.91336 M3/ hr.


142.557408 M3/ hr.

id surface area
5091.336 1272.834 LPM/M3
1234.64898

M3/ hr.

74078.9388

height of each tank

height of each tank

74.0789388 M3/ hr.

18
15

5
1

2.3 FIRE WATER FLOW RATE FOR COOLING POL TANK WAGON LOADING GANTR
a)
Data
Total No. of loading
points
Width
of tank wagon gantry (Cooling two spur)
b)
Cooling water flow rate
Divide total area of gantry into equal segments such that each segment measuring
15 m X 12 m and consider 3 segments operating at a time.
Water rate required
=
=

5508 LPM
330480

330.48 M3/ hr.

AGON LOADING GANTRY


=
=

Conventional or BTPN.
12

3 x 15 m x 12 m x 10.2 lpm/m2.
5508
3
330 mlpm
/hr

2.5

TOTAL DESIGN FIRE WATER FLOW RATE FOR SINGLE FIRE CONTEGENCY
The total fire water flow requirement will be highest of one of the fire water requirement calculated in 2.1 (3
i.e. 659m3/hr plus supplementary water (36 x 4 = 144 m/hr) = 803 m/hr.

when make up water is not avaiable requirement 4hrs

when 50% or more make up water is available for 3hrs

re water requirement calculated in 2.1 (376 m/hr) & 2.2 (458 m/hr), 2.3 (330 m/hr) and 2.4 (659 m/hr) above

2408

M3/hr

1806

M3

458
144

602

FIRE WATER FLOW RATE FOR CONE ROOF TANK PROTECTION


DATA
Storage capcity in one dyke areain M3
Number of tanks
Capacity of each tank
Diameter of each tank
Height of each tank
Radius of the tank

50000
4
12500
37.5
12
18.75

Cooling water flow rate


Cooling water rate for the tank under fire--3LPM
Cooling water required

Cooling water rate for the tank falling with in ( R+30) from the center of the

cooling water required

Total cooling water required

Foam Water Flow Rate


Foam solution application rate

foam solution required


Foam water required
For 3% Foam concentrate

5LPM on liquid surface

5524.453125 LPM
5358.71953125 LPM
321523.171875
321.523171875 M3/ hr.

Total water flow rate for cone roof thank protection

Tank cooling
Foam solution application

1018.2672
321.523171875

1339.7904 M3/ hr.

NK PROTECTION
3.1428

4242.78
254566.8

254.5668

M3/ hr.

0) from the center of the tank under fire

ce

12728.34
763700.4
763.7004

M3/ hr.

1018.2672 M3/ hr.

3.3 FIRE WATER FLOW RATE FOR COOLING POL TANK WAGON LOADING GANTRY

water rate required


a) Data
Total No. of loading points
Width of tank wagon gantry
(Cooling two spur)
b) Cooling water flow rate
Divide total area of gantry into equal segments such
that each segment measuring 15 mX 12 m and
consider 3 segments operating at a time.

Length

15

Width

12

sigment

Water Rate required

Conventional or BTPN.
12 m.

5508
LPM
330480

330.48

M3/hr

TOTAL DESIGN FIRE WATER FLOW RATE FOR TWO SIMULTANEOUS FIRE SCENARIO
The total fire water flow requirement will be sum of the two largest fire water requirement calculated in 3.1 (504 m/hr) & 3.2 (13
m/hr), 3.3 (330 m/hr) above i.e. (1341+504) =1845 m3/hr plus supplementary water (36 x 4 = 144 m/hr) = 1989 m/hr.

OR water requirement alone as calculated in 3.4 i.e. 1028 m 3/hr plus supplementary water (36 x 4 = 144 m 3/hr) = 1172 m
Hence water requirement for double contingency locations shall be 1989 m 3/hr

WATER STORAGE REQUIREMENT

Case 1: When make water is not available:


Let us assume three main pumps of capacity 750 m/hr each and two stand-by pump of equal capacity and equal head are pro
Water requirement is 750 x 3 = 2250 m/hr
Design flow rate (Fire water pump discharge) = 2250 m/hr

for four hours storage

9000 M3

FIRE WATER FLOW RATE FOR COOLING POL TANK WAGON LOADING GANTRY
a)
Data
=
Total No. of loading points
Width of tank wagon gantry
=
(Cooling
two
spur)
b)
Cooling water flow rate
Divide total area of gantry into equal segments such that each segment measuring 15 m
X 12 m and consider 3 segments operating at a time
Water rate required
=
3 x 15 m x 12 m x 10.2 lpm/m 2.

Water Requirement for supplementary Hose:


Water for 4 single hydrant streams
Total water requirement
Total water flow rate for gantry protection
(a) Gantry cooling
=
(b) Supplementary hose requirement
=

Conventional or BTPN.
12 m.

a)

Total
----- ) 0 x 0 ( -----

474m/hr.

=
=

4 x 36 = 144 m 3/hr.
144 m3 / hr.
330 m/hr.
144m3/ hr

5508 lpm

330 m3/hr

Conventional or BTPN.
12 m.

5508
=

5508 330.48
lpm

330 m3/hr

330480
M3/hr

1.2
Foam compound calculation for single largest cone roof tank in a dyke.
Tank Data
Total storage capacity in one dyke area =
10,000 m 3. No. of tanks
=
2
3
Capacity of each tank
=
5,000 m .
Diameter of each tank
=
24 m.
Height of each tank
=
12 m.
Foam compound requirement for tank
Foam solution application rate
= 5 lpm/m 2 of liquid surface area of tank. Foam solution required
2
= ( x (12) x 5) lpm = 2262.9 lpm Foam compound required (3%)
= 0.03 x
2262.9 lpm = 67.9 lpm.
Foam compound required for 65 minutes =

65 minutes x 67.9 lpm = 4,414 litres.

2.2
Foam compound calculation for single largest cone roof tank in a dyke.
Tank Data
Total storage capacity in one dyke area =
50,000 m 3. No. of tanks
=
4.
3
Capacity of each tank
=
12,500 m .
Diameter of each tank
=
37.5 m.
Height of each tank
=
12 m.
Foam compound requirement for tank
Foam solution application rate
= 5 lpm/m 2 of liquid surface area of tank. Foam solution required
2
= ( x (18.75) x 5) lpm = 5524.6
Foam compound required (3%)
= 0.03 x 5524.6 lpm = 165.7 lpm.
Foam compound required for 65 minutes = 65 minutes x165.7 lpm = 10,771 litres.
2.3
In case of double fire, foam will be required to pour in both tanks simultaneously.
Foam compound requirement for 65 minutes = (2308 + 10,771) litres = 13,079 litres.