RECIRCULATING PUMP SELECTION GUIDELINE


RAND Associates, Inc.

June 5, 2011

PROJECT

ANALYST

CALCULATED VALUE,
FORMULA, OR CONSTANT

REQUIRED INPUT

ENERGY AND FLOW REQUIREMENTS


1. Loop Design Conditions
Design Water Temp, F

Ambient
Temp, F

Temperature
Difference, F

C
=A-B

120

75

THERM-OMEGA-TECH, INC.
353 IVYLAND ROAD, WARMINSTER, PA 18974

D)

45

INPUT NOTES:
1. For basic use, enter values only in cells designated for required inputs
2. Do not enter any value in a cell under F if a Standard Dimension tubing not included in a system
3. All indicated Constant values are taken from the Copper Tube Handbook, Copper Development Association, 2006
4. insulation levels are based on requirements in the International Energy Conservation Code for DHW systems
operating in the temperature range of 120 to 200 F.
5. Tabulated values were calculated using 3EPlus v4. The nominal insulation value is R-3.7 per inch. Heat Loss Factors
for different insulation types may be estimated by multiplying the tabulated values by (3.7 / New R Value).

www.CircuitSolver.com
1-877-379-8258

INPUT NOTES:
1. For basic use, enter values only in cells designated for required inputs
2. Do not enter any value in a cell under F if a Standard Dimension tubing not included in a system
3. All indicated Constant values are taken from the Copper Tube Handbook, Copper Development Association, 2006
4. insulation levels are based on requirements in the International Energy Conservation Code for DHW systems
operating in the temperature range of 120 to 200 F.
5. Tabulated values were calculated using 3EPlus v4. The nominal insulation value is R-3.7 per inch. Heat Loss Factors
for different insulation types may be estimated by multiplying the tabulated values by (3.7 / New R Value).

000000

2. Tube in Proposed Recirculation System

6. Fluid Velocity At Minimum Flow Rate. Feet per Minute

Standard
Dimension

Length, Feet

Heat Loss Factor,


BTU/Hr-Ft-F

Heat Loss BTU/Hr-F

Unit Volume,
Gallons/Foot

Flow Rate, GPM

V1

V2

=F*G
1/2"

0.15

945

3/4"

2.9
0.0162

0.17

160.65

0.0269

1"

0.2

0.0454

1-1/4"

0.17

0.0681

1-1/2"

0.18

0.0951

2"

0.16

0.165

2-1/2"

0.17

0.254

3"

0.21

0.363

4"

0.26

0.634

Total Length, ft

I)

945

Total Heat Loss,


BTU/Hr-F

J)

160.65
=D*J

Design Heat Loss,


BTU/Hr

THERM-OMEGA-TECH, INC.
353 IVYLAND ROAD, WARMINSTER, PA 18974

K)

7,229

www.CircuitSolver.com
1-877-379-8258

000000

3. Design Change in HW Loop Temp


Supply Water
Temperature, F

120

Return Water
Temperature, F

dT

=A-M

115

N)

4. Minimum Required Flow , GPM

5. Potential Flow Reduction

Gallons/Hour

Minutes/Hour

Minimum Flow
Rate, GPM

Design Flow Rate,


GPM

Percent Reduction

= K / (N *8.33)

60

=O / P

12

= ((Q - R) / R) * 100

173.6

THERM-OMEGA-TECH, INC.
353 IVYLAND ROAD, WARMINSTER, PA 18974

2.9

-76%

www.CircuitSolver.com
1-877-379-8258

000000

FRICTION LOSS
Table A - Type M Copper Tube - Pressure Loss, Psi Per Linear Foot
Flow Rate, Gallons per Minute
Standard
Dimension

1/2"

0.007

0.024

0.051

0.086

0.130

3/4"

0.001

0.004

0.009

0.015

0.023

0.074

1"

0.000

0.003

0.001

0.004

0.006

0.023

1-1/4"

0.000

0.000

0.001

0.002

0.002

0.009

1-1/2"

0.000

0.000

0.000

0.001

0.001

0.004

2"

0.000

0.000

0.000

0.000

0.000

0.001

2-1/2"

0.000

0.000

0.000

0.000

0.000

0.000

3"

0.000

0.000

0.000

0.000

0.000

0.000

4"

0.000

0.000

0.000

0.000

0.000

0.000

Values taken from the Copper Tube Handbook, Copper Development Association, 2006
Psi losses derived using the Hazen-Williams formula
Values in italics indicate velocities in excess of the recommended 5 feet per second
Pressure loss per linear foot for other flow rates may be interpolated from values provided above

Minimum Flow Rate,


GPM

2.9

Design Flow Rate,


GPM

12

THERM-OMEGA-TECH, INC.
353 IVYLAND ROAD, WARMINSTER, PA 18974

www.CircuitSolver.com
1-877-379-8258

10

Psi * 2.31 = Equivalent feet of head per linear foot

000000

7. Tube in Proposed Recirculation System - Friction Loss, Feet


Standard
Dimension

Length, Feet

FL 1

FL 2

psi/Foot at Minimum
Flow

FL 3

Minimum Friction
Loss, Feet

From
Table A @
Minimum GPM

FL 4

psi/Foot at Design Flow

FL 6

Design Friction Loss,


Feet

From
Table A @ Design
GPM

= FL 2 * FL 3

FL 7
= FL 2 * FL 6

Low
High

945

0.03

28.35

0.08

0.007

0.035

1-1/4

0.0023

0.013

1-1/2

0.0012

0.006

0.002

75.6

Delta

2-1/2
3
4
Total Length, Feet

945

Vertical Head, Feet

FL 10

Subtotal

FL 11

Allowance for
Fittings, %

FL 12

Total Head, Feet

FL 13

THERM-OMEGA-TECH, INC.
353 IVYLAND ROAD, WARMINSTER, PA 18974

FL 8)

FL 9)

28.35

30
= FL 8 + FL 10

58.35
120.0%

= FL 11 * FL 12

FL 10) 70.02

75.6

30
= FL 9 + FL 10

105.6
120.0%

= FL 11 * FL 12

www.CircuitSolver.com
1-877-379-8258

Target

FL 11) 126.72

000000

DATE

NO DATA REQUIRED

inputs
n tubing not included in a system
andbook, Copper Development Association, 2006
Energy Conservation Code for DHW systems

insulation value is R-3.7 per inch. Heat Loss Factors


the tabulated values by (3.7 / New R Value).

THERM-OMEGA-TECH, INC.
353 IVYLAND ROAD, WARMINSTER, PA 18974

www.CircuitSolver.com
1-877-379-8258

inputs
000000
n tubing not included in a system
andbook, Copper Development Association, 2006
Energy Conservation Code for DHW systems

insulation value is R-3.7 per inch. Heat Loss Factors


the tabulated values by (3.7 / New R Value).

t Minimum Flow Rate. Feet per Minute


Seconds Per
Minute

Velocity @ GPM Flow,


Ft/Second

V3

V4

60

= V2/(V1*60)

1.79

THERM-OMEGA-TECH, INC.
353 IVYLAND ROAD, WARMINSTER, PA 18974

www.CircuitSolver.com
1-877-379-8258

000000

THERM-OMEGA-TECH, INC.
353 IVYLAND ROAD, WARMINSTER, PA 18974

www.CircuitSolver.com
1-877-379-8258

000000

20

25

Not Recommended
0.084
0.031

0.047

0.014

0.021

0.004

0.005

0.001

0.002

0.001

0.001

0.000

0.000

t of head per linear foot

THERM-OMEGA-TECH, INC.
353 IVYLAND ROAD, WARMINSTER, PA 18974

www.CircuitSolver.com
1-877-379-8258

000000

Table A Interpolation Scratchpad


GPM

PSI/Foot

10

0.009

20

0.031

12

0.022

0.20

0.0044

Interpolated Value

0.013

THERM-OMEGA-TECH, INC.