Sie sind auf Seite 1von 7

Biflow SB

(CON)
Product
Brochure
t: 01384 275800
f: 01384 275810
e: bs@eltafans.co.uk
visit: eltaselect.com

AXIAL

MIXED FLOW

CENTRIFUGAL

ROOF

BIFURCATED

DESTRATIFICATION

ATEX

SMOKE

CIRCULATING

WINDOW/WALL

HEAT RECOVERY

ACCESSORIES

bi

Biflow SB (CON)

fu

PAGE NO.
1Ph

3Ph

1Ph

3Ph

Accessories & Wiring Data

All

Dimensional Data

All

Performance, SFP & Electrical Data

Sound Data

OVERVIEW
MORE
INFORMATION

The Biflow SB (CON) is a quality range of bifurcated axial fans with


a conical casing, specially developed for handling more hostile
air movement applications. The Biflow SB is designed so that air
throughput totally by-passes the motor, keeping the motor out of the
airstream in a cooler environment.

QUICK FACTS

Bifurcated Conical Axial Flow Fan

4 standard sizes from 250mm to 500mm.


Air volume flow rates up to 3.80 m/s.
Static pressures up to 600 Pa.
Suitable for operating temperatures up to +200C.
Ideal for internal or external mounting.

CASING

IMPELLER

QUALITY MANAGEMENT

The all metal fan casing provides a


long lasting and robust construction.

Adjustable pitch aerofoil impellers are


provided with blades made from high
quality pressure die cast aluminium
(LM6), natural finish.

Units are to be designed and


manufactured with procedures as
defined in BS EN ISO 9001:2008.

The units have been constructed


from sheet steel with both motors
and impeller mounted within the
length of the unit casing. The motor
is located out of the airstream
in a tunnel which traverses the
casing making the unit suitable for
temperatures up to +200C.
All casing parts are heavy gauge mild
steel sheet, roll formed and welded,
then hot dip galvanised to BS EN
ISO 1461:1999 after fabrication.

Impellers are factory set at an angle


to provide maximum performance.

All SB (CON) units are to be tested to


ISO 5801:2007 (airside performance)
and BS 848 Part 2:1985 (sound
performance).

The hubs are manufactured from die


cast aluminium alloy (LM24).
Assembled impellers are to be
dynamically balanced to ISO 14694
Grade G6.3.

TYPICAL APPLICATIONS

MOTORS
Motors are to be foot mounted totally
enclosed metric type to IP55, with
sealed for life bearings, standard
industrial paint finish and Class H
insulation to EN 60034-5.

Kitchen Extract
Spray Booths
Hot Gas Situations
Corrosive Atmospheres
Boiler Houses
Heavy Industrial

Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request.

Tel: 01384 275800

Fax: 01384 275810

Email: bs@eltafans.co.uk Visit: eltaselect.com

Twitter: @eltaselect & @eltafans

Biflow SB (CON)

AC

Performance, SFP & Electrical Data


SINGLE Phase - 220V to 240V / 50Hz
Product
Code

Speed
r/min

SB250-CON4-1

1450

SB315-CON4-1

1370

Airflow
SFP

Airflow m / s @ Static Pressure Pa


0

25

50

75

100

m / s

0.280

0.223

0.150

0.029

W / (L/s)

m / s

0.521

0.483

0.439

0.383

0.257

W / (L/s)

Overall
Efficiency FMEG
%

Motor
Electrical Data
FLC
Amps

SC Output
Amps
kW

1.13

3.73

1.13

0.12

3.73

0.12

dBA @ 3m

Inlet
Outlet
Inlet
Outlet

48
51
-

The overall A-weighted sound pressure level is at a distance of 3m with spherical free-field propagation.
It is expressed in dB re-20Pa and is presented for comparative purposes only.
Outside the scope of ISO12759 and ERP legislation.
Data provided at standard air density of 1.2 kg/m. FLC Amps @ 230V / 1Ph / 50Hz.

Sound Data
SINGLE Phase - 220V to 240V / 50Hz
Product
Code

SB250-CON4-1

SB315-CON4-1

Inlet
Outlet
Inlet
Outlet

Sound Power Level dBW @ Octave Band Hz


63 Hz

125 Hz

250 Hz

500 Hz

1k Hz

2k Hz

4k Hz

8k Hz

77

74

71

64

62

60

57

47

80

77

74

68

66

64

62

Total
dB

Silencer dBA Attenuation


1DENP

2DENP

1DEP

2DEP

80

-7

-11

-10

-14

53

83

-8

-12

-10

-14

Tests and preparation of the sound data have been carried out in accordance with BS 848 Part 2:1985 at 50% peak pressure.
The Sound Power Level Spectra are in dB re-1pW.
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request.

Tel: 01384 275800

Fax: 01384 275810

Email: bs@eltafans.co.uk Visit: eltaselect.com

Twitter: @eltaselect & @eltafans

Biflow SB (CON)

AC

Performance, SFP & Electrical Data


THREE Phase - 380V to 415V / 50Hz
Product
Code

Speed
r/min

SB250-CON2-3

2780

SB250-CON4-3

SB315-CON2-3

SB315-CON4-3

SB400-CON2-3

SB500-CON2-3

1370

2780

1370

2800

2840

Airflow m / s @ Static Pressure Pa

Airflow
SFP

25

50

75

100

150

200

250

300

350

400

500

m / s

0.566

0.535

0.502

0.468

0.434

0.360

0.282

0.198

W / (L/s)

m / s

0.270

0.211

0.140

0.040

W / (L/s)

m / s

0.931

0.919

0.906

0.892

0.878

0.846

0.810

0.768

0.716

0.648

0.554

W / (L/s)

m / s

0.521

0.483

0.439

0.383

0.257

W / (L/s)

m / s

2.082

2.065

2.047

2.029

2.010

1.969

1.926

1.878

1.825

1.766

1.698

1.527

W / (L/s)

m / s

3.803

3.780

3.756

3.732

3.707

3.655

3.600

3.541

3.477

3.408

3.332

3.152

W / (L/s)

Motor Electrical Data

Overall
Efficiency FMEG
%

FLC
Amps

0.68

0.48

1.18

0.48

4.42

7.49

dBA @ 3m

SC Output
Amps
kW
3.06

2.40

6.14

2.40

27.4

57.4

Inlet

0.25

Outlet
Inlet

0.12

Outlet
Inlet

0.55

Outlet
Inlet

0.12

Outlet
Inlet

2.2

Outlet
Inlet

4.0

Outlet

The overall A-weighted sound pressure level is at a distance of 3m with spherical free-field propagation. It is expressed in dB re-20Pa and is presented for comparative purposes only.
Outside the scope of ISO12759 and ERP legislation.
Data provided at standard air density of 1.2 kg/m. FLC Amps @ 400V / 3Ph / 50Hz.

Sound Data
THREE Phase - 380V to 415V / 50Hz
Sound Power Level dBW @ Octave Band Hz

Product
Code

SB250-CON2-3

SB250-CON4-3

SB315-CON2-3

SB315-CON4-3

SB400-CON2-3

SB500-CON2-3

Inlet
Outlet
Inlet
Outlet
Inlet
Outlet
Inlet
Outlet
Inlet
Outlet
Inlet
Outlet

63 Hz

125 Hz

250 Hz

500 Hz

1k Hz

2k Hz

4k Hz

8k Hz

83

81

79

78

77

75

73

69

77

74

71

64

62

60

57

47

90

86

82

81

80

77

77

71

80

77

74

68

66

64

62

53

94

87

86

90

84

83

80

73

98

93

90

96

96

95

93

89

Silencer dBA Attenuation

Total dB
88

80

93

83

97

104

1DENP

2DENP

1DEP

2DEP

Inlet

-9

-14

-12

-15

Outlet

Inlet

-8

-12

-10

-14

Outlet

Inlet

-8

-13

-11

-14

Outlet

Inlet

-8

-12

-10

-14

Outlet

Inlet

-9

-14

-12

-15

Outlet

Inlet

-9

-14

-12

-15

Outlet

Tests and preparation of the sound data have been carried out in accordance with BS 848 Part 2:1985 at 50% peak pressure.
The Sound Power Level Spectra are in dB re-1pW.
Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request.

Tel: 01384 275800

Fax: 01384 275810

Email: bs@eltafans.co.uk Visit: eltaselect.com

Twitter: @eltaselect & @eltafans

61
48
64
51
70
80
-

Biflow SB (CON)

AC

Accessories & Wiring Data

For more information on Accessories & Wiring Diagrams, please see individual product downloads,
or visit eltaselect.com/information-centre

SINGLE Phase - 220V to 240V / 50Hz


Product
Code

Impeller Side
Guard

Ancillary Pack

Mounting Feet
(each)

Matching Flanges
(each)

Flexible Connections
(each)

AV Mounts
(set of 4)

Damper

Bell Mouth
Inlet

SB250-CON4-1

078C-0250-C

APK250SBCON/S1G

060B-0250-B

061B-0250-B

063-0250-PU250

062-S1G

019-0250-STD

241B-0250

SB315-CON4-1

078C-0315-C

APK315SBCON/S2B

060B-0315-B

061B-0315

063-0315-PU250

062-S2B

019-0315-STD

241B-0315

Product
Code

Silencer
1D Podded

Silencer
1D Unpodded

Silencer
2D Podded

Silencer
2D Unpodded

Wiring
Diagram
No.

SB250-CON4-1 068-0250-1DEP 068-0250-1DENP 068-0250-2DEP 068-0250-2DENP

152-521

SB315-CON4-1 068-0315-1DEP 068-0315-1DENP 068-0315-2DEP 068-0315-2DENP

152-521

THREE Phase - 380V to 415V / 50Hz


Product
Code

Impeller Side
Guard

Ancillary Pack

Mounting Feet
(each)

Matching Flanges
(each)

Flexible Connections
(each)

AV Mounts
(set of 4)

Damper

Bell Mouth Inlet

SB250-CON2-3

078C-0250-C

APK250SBCON/S1G

060B-0250-B

061B-0250-B

063-0250-PU250

062-S1G

019-0250-STD

241B-0250

SB250-CON4-3

078C-0250-C

APK250SBCON/S1G

060B-0250-B

061B-0250-B

063-0250-PU250

062-S1G

019-0250-STD

241B-0250

SB315-CON2-3

078C-0315-C

APK315SBCON-S2B

060B-0315-B

061B-0315

063-0315-PU250

062-S2B

019-0315-STD

241B-0315

SB315-CON4-3

078C-0315-C

APK315SBCON/S2B

060B-0315-B

061B-0315

063-0315-PU250

062-S2B

019-0315-STD

241B-0315

SB400-CON2-3

078C-0400-C

APK400-SBCON/S2B

060B-0400-B

061B-0400

063-0400-PU250

062-S2B

019-0400-STD

241B-0400-BELL

SB500-CON2-3

078C-0500-C

APK500SBCON/S2G

060B-0500-B

061B-0500

063-0500-PU250

062-S2G

019-0500-STD

241B-0500-BELL

Silencer
2D Podded

Silencer
2D Unpodded

Wiring
Diagram
No.

Product
Code

Silencer
1D Podded

Silencer
1D Unpodded

SB250-CON2-3

068-0250-1DEP

068-0250-1DENP

068-0250-2DEP 068-0250-2DENP

152-600

SB250-CON4-3

068-0250-1DEP

068-0250-1DENP

068-0250-2DEP 068-0250-2DENP

152-600

SB315-CON2-3

068-0315-1DEP

068-0315-1DENP

068-0315-2DEP 068-0315-2DENP

152-600

SB315-CON4-3

068-0315-1DEP

068-0315-1DENP

068-0315-2DEP 068-0315-2DENP

152-600

SB400-CON2-3

068-0400-1DEP

068-0400-1DENP

068-0400-2DEP 068-0400-2DENP

152-600

SB500-CON2-3

068-0500-1DEP

068-0500-1DENP

068-0500-2DEP 068-0500-2DENP

152-601

Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request.

Tel: 01384 275800

Fax: 01384 275810

Email: bs@eltafans.co.uk Visit: eltaselect.com

Twitter: @eltaselect & @eltafans

Biflow SB (CON)

AC

Dimensional Data

AIRFLOW

E-HOLES F
EQUISPACED ON
G PCD

c
OPTIONAL MOUNTING FEET

Product
Code

Weight
kg

1Ph

3Ph

SB250

250

325

460

220

10

299

400

23

23

SB315

315

380

500

250

10

355

460

30

30

SB315-CON2-3

315

380

500

250

10

355

460

31

SB400

400

485

650

305

12

450

570

49

SB500

500

585

710

370

12

12

560

700

86

All dimensions are shown in mm.

Elta Fans Limited has a policy of continuous product development and improvement and therefore reserves the right to supply products which may differ from those illustrated and described in this publication.
Confirmation of dimensions and data will be supplied on request.

Tel: 01384 275800

Fax: 01384 275810

Email: bs@eltafans.co.uk Visit: eltaselect.com

Twitter: @eltaselect & @eltafans

BUILDING SERVICES

APPLIED TECHNOLOGY

EXPORT

Tel: +44 (0) 1384 275800

Tel: +44 (0) 1489 566500

Tel: +44 (0) 1489 566500

Fax: +44 (0) 1384 275810

Fax: +44 (0) 1489 566555

Fax: +44 (0) 1489 566555

e-mail: bs@eltafans.co.uk

e-mail: at@eltafans.co.uk

e-mail: export@eltafans.co.uk

46 Third Avenue
Pensnett Trading Estate
Kingswinford, West Midlands
DY6 7US, United Kingdom

17 Barnes Wallis Road


Segensworth East Industrial Estate
Fareham, Hampshire
PO15 5ST, United Kingdom

17 Barnes Wallis Road


Segnesworth East Industrial Estate
Fareham, Hampshire
PO15 5ST, United Kingdom

www.eltafans.com

BS EN ISO 9001:2008
FM 556465

A member of
HEVAC ASSOCIATION

A member of