Beruflich Dokumente
Kultur Dokumente
Article views: 50
Introduction
These loading guides [14] have been applied by the utilities, and there have been
no adverse consequences. The winding temperature and hottest spot temperature in
the winding determine the transformer overload conditions. Loss of half the tensile
strength of the cellulose insulation as a result of thermal aging has been decided as
the quantitative end of life criterion. The generally accepted relationship for thermal
aging properties of insulation materials, which is described by Arrhenius Reaction
Rate Law [5,6], is utilized as a basis here. An assumption is made that a single
reaction rate is predominant and is applicable over the full range of temperatures
from those occurring during normal load applications to those used for overload
conditions leading to accelerated loss of transformer life.
where
T = absolute temperature in degrees Kelvin.
625
(1)
626
The commonly accepted values of constants for power and distribution transformers
are
for 65C rise insulation A =
for 55C rise insulation A =
( HST + 273) ]
( 2)
= 2(
98
6
= 100. 05 ( h
= e0. 693 (
98 )
98
6
( 3)
where h = HST in C.
If the transformer is operated at hottest spot temperature of 98C, it will
operate for 20 to 30 years of normal life.
The rate of using life becomes double ( life is halved) for every 6C increase in
the hottest spot temperature.
Basic Thermal Diagram (Fig. 1 )
a =
D b =
D c =
D m c =
=
D T =
D m t =
=
D w =
D m w =
=
D r =
D h =
g =
=
In IEC 354 [1] loading guide, the hottest spot temperature rise (Fig. 2) is given
as follows:
D h = D T + Hg (factor H = 1 .1 to 1.3 given by IEC 354).
( 4)
627
628
1.5
140C
105C
1.8
150C
115C
2.0
160C
115C
Table 2
Ambient temperature
a)
b)
c)
d)
Table 3
Correction for increase of ambient temperature due to enclosure (KIOSKS)
No. of transformers installed 1: Add 10 to 20C to outside ambient temperature.
Note: Some national standards may use other gures that reect local meteorological
conditions ( e.g., arctic or tropical climates) . An ambient temperature range of 20 C to
+ 40 C should therefore be considered before decision.
629
Background to Calculations
A study of heat ows in a transformer can provide some guidance on the problem
of temperature rise, which limits loading capability. Taking the oil as the heat sink,
the temperature rise of oil can be studied as analogous to charging of a capacitor in
an R -C circuit. The heating of core and windings, which are themselves independent thermal sinks, can be modeled as a more complex circuit containing several
interconnected R and C elements.
Four routine calculations which lead to the temperature rise curves of Figure 4,
semiemperical formulas are used.
630
kVA rating
No load loss
Ratio of
(full load loss/
no load loss)
50
100
160
250
400
630
1000
1600
2500
190
320
460
650
930
1300
1700
2600
3800
1100
1750
2350
3250
4600
6500
10500
17000
26500
5.79
5.47
5.11
5.00
4.95
5.00
6.17
6.54
6.97
( 5)
where
h = hot spot temperature, C
a = ambient temperature (assumed to be 20C )
D T ( r a t e d ) = rated top oil temperature rise (for ONAN distribution transformer,
it is assumed to be 55K)
R = ratio of load loss to no-load loss at rated current ( for ONAN transformer
assumed to be 5)
K = load factor = load current/ rated current (p.u)
x = oil exponent (for ONAN transformer assumed to be 0.9)
H = hot spot factor = 1.1 for distribution transformer
g = 20 K
H g = 23K
y = winding exponent = 1.6
o = oil time constant = 3 hours
Hot spot temperatures h can be calculated for any load factor, initial K 1 , and
nal K 2 . The measurement data [22] for R , that is, the ratio of full load loss to no
load loss, is given in Table 4.
The calculation of transient response of temperature rise in the case of cyclic [1013]
loading involves only the oil time constant o . The calculation of steps for hot-spot
temperature at time t 1 hours measured from the beginning of step peak load is
D h (t 1 ) = (D h (at K 2 )
D h (at K 1 ))(1
t 1/ o
) + D h (at K 1 ) ,
( 6)
631
where D h (K 1 ) is calculated from the formula for steady state temperature using
equation (5) for load factor K 1 . D h (K 2 ) is calculated from the formula for steady
state temperature using equation (5) for load factor K 2 .
Example:
A 50 kVA ONAN transformer carries an 80% load for a long time. Calculate the
winding temperature if a 130% load is applied for 4 hours. Ambient temperature
is 20C. The rst step is to calculate the steady state hot spot temperature for
K 1 = 0 .8 per unit load and R = 6, using the formula
h = a + 52((1 + 6K 12 )= (1 + 6))0. 9 + 26(K 1 )1. 6 = 75C
D w o (K 1 ))(1
t 1/ w
),
(7)
The relationship between initial load factor K 1 , overload-load factor K 2 , and time
of overload t is shown in Figure 5. The limiting factor is the hot spot temperature
of 98C (an average value assumed for illustration only). The loss of life is limited
to 0.1%.
632
2(0 + 235)
;
101000
1
2
( 8)
2(0 + 225)
,
43600
1
2
( 9)
J t
for aluminum:
1 = 0 +
J t
where
0 = initial temperature
2
J = short circuit current density, A/ mm
t = duration of short circuit, s (< 2 seconds)
1 max = 250C for copper
The short circuit current depends on percentage impedance between the transformer and fault point. If the fault occurs at the transformer terminal, only the
percentage of impedance of the transformer should be taken into calculation of
fault current.
The highest average temperature for copper and aluminum are plotted in Figures 6 and 7.
A mbient Temperature
10
Until the early 1970s, the principal factor in determining the thermal rating, and
thus the loading capability of transformers, was the average temperature rise of
the windings. This temperature rise was determined by measuring the change in
winding resistance when the load was applied to the transformer.
633
Figure 6. Steady state temperature of copper conductor under short circuit condition at dierent current densities.
634
Load
percent
rated
Hot spot
temp.,
C
Top oil
temp.,
C
10
20
100
110
120
130
140
150
98
104
110
116
122
127
75
79
84
87
92
96
0
1
2
4
8
16
0
2
4
8
16
> 20
0
4
8
16
> 20
> 20
% Time at overload
The temperature rise by resistance standard was changed when it was discovered that the hottest spot winding temperature gives a better indication of how
the load aects the life expectancy of a transformer [2329]; however, the hottest
spot temperature cannot be measured directly because of the hazard of inserting
temperature sensors directly into the windings. As a result, numerous methods have
been developed to calculate the hottest spot temperature, but these are very complicated. The winding and oil temperatures of a transformer are measured with a
ber optic temperature measurement system. Although the sensors are not directly
located in the hottest spot of the windings, signicant information can be obtained.
11
Calculation Results
12
Conclusions
635
if the emergency load is only for 10 minutes or so in the case of short circuit and
shifting of load to another transformer due to the outage of the short-circuited one,
the winding time constant must be taken into account. The eect of stray loss due
to harmonics is also important for further study [3031].
References
[1] IEC 354 International Standards, 1991, Loading Guide for Oil Immersed Power
Transformers, International Electrotechnical Commission, Geneva.
[2] IEC 76-5 Amend on, 1994, Maximum Permissible Values of the Average Tempera-
[3] ANSI Guide for Loading Oil Immersed Distribution and Power Transformers, Appendix C.57.92, 1962.
[4] NEMA Guide for Loading Oil Immersed Power Transformers with 65 C Average
W inding Rise, New York, Publication TR-98, 1964.
[5] Sharma, S. N., and Gupta, D. P., 1984, Loading Limits of Power Transformers,
Indian Journal of Power and River Valley Development, p. 179.
[6] Lahoti, B. D., and Flowers, D. E., 1981, Evaluation of Transformer Loading above
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
Nameplate Rating, IEEE Trans. on Power Apparatus and Systems, Vol. 100, No. 4,
pp. 19891997.
Bean, H. L., Chackan, N., Moore, H. R., and Wentz, E. C., 1959, Transformers for
the Electric Power Industry, McGraw Hill Book Co., Inc.
Vogol, F. J., and Narbut, P., 1942, Hot Spot Winding Temperatures in Self-Cooled
Oil Insulated Transformers, AIEE Trans., Vol. 61, p. 133.
Montsinger, V. M., and Clem, J. E., 1946, Temperature Rise for Short Time Overloads, AIEE Trans., Vol. 65, p. 966.
Grady, J. O., 1990, Overloading Power Transformers: A Users View, Power Engineering Journal, pp. 8793.
Goldanu, J., 1995, Investigating the Loadability of Oil Immersed Transformers in
Electricity Distribution, p. 4/ 18, Vol. 1.
Den Outer, F. R., 1991, Cast Resin and Other Dry Type Transformers under Changing Load Compared to the Oil Immersed Transformers, CIRED 11th International
Conference on Electricity Distribution, p. 1.16/ 19, Vol. 1.
Nguyen, T. T., 1995, Constrained Optimization Procedure for Evaluating cyclic
Loading of Power Transformers, Proc. IEE, GTD, U.K., Vol. 142, No. 3, pp. 240
246.
de Kuijper, C. E. M., 1984, Short Time Loading of Oil Immersed Transformers,
Elektrotechniek, 62, No. 9, pp. 757769.
McNutt, W . J., Rouse, T. O., and Kaufmann, G. H., 1985, Mathematical Modeling of
Bubble Evolution in Transformers, IEEE Trans. on Power Apparatus and Systems,
Vol. PAS-104, No. 2, pp. 477487.
Vritanen, E., 1993, Handout of ABB Stromberg Power on Distribution Transformers, Vaasa, Finland.
Aubin, J., Bergeron, R., and Morin, R., 1990, Distribution Transformer Overloading
Capability under Cold Rolled Pick Up Conditions, IEEE Trans. on Power Delivery,
Vol. 5, No. 4, pp. 18831889.
Richardson, B., and Harrison, T. H., 1989, A Range of Distribution Transformer
Multiple Loading Regime, CIRED 10th International Conference on Electricity Distribution, pp. 6265, Vol. 1.
Pierce, L. W ., 1994, Predicting Liquid Filled Transformer Loading Capability, IEEE
Trans. on Industry Application, Vol. 30, No. 1, p. 170.
Jardini, J. A., Tahan, C. M. V., Ahn, S. U, and Ferari, E. L., 1996, Distribution
Transformer Loading Evaluation Based on Load Prole Measurement, IEEE Transmission and Distribution Conference, CH35968, pp. 2024.
636
[21] Wong, C. C., 1994, Substation Power Transformer Loading Analysis and Computer
[22]
[23]
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]