Sie sind auf Seite 1von 46

Burner Management System

Safety Functions
On-line Lesson

Welcome to the exida.com on


- line lesson, Burner Management System
(BMS) Safety Functions. In this lesson we will explain typical and example
safety instrumented functions found in a BMS.

Copyright exida.com LLC 2001-2002

e ida.com
excellence in dependable-automation

Prerequisite and Companion Lessons


Introduction to Safety Instrumented
Systems
Introduction to Burner Management
Systems

It is recommended that the exida on


- line lesson, Introduction to Safety
Instrumented Systems, may be helpful as a prerequisiste lesson for those
not familiar with functional safety systems. The exida on
- line lesson
Introduction to Burner Management Systems should be taken by those not
familiar with the BMS hazards and BMS standards.

Copyright exida.com LLC 2001-2002

e ida.com
excellence in dependable-automation

General Lesson Objectives


Review Standards for BMS
Show Safety Functions for typical/example
BMS
Review BMS design process
Present example BMS safety function
verification
3

Copyright 2002, exida.com

Over the duration of this course the participant will:


Review some standards that apply to BMS
Be introduced to typical safety instrumented functions found in a BMS
Review the BMS design process per the Safety Lifecycle
Be shown an example BMS safety verification calculation

Copyright exida.com LLC 2001-2002

e ida.com
excellence in dependable-automation

NFPA Standards
8501 - Single Burner
8502 - Multiple Burner
(Previously 85C)
8503 - Pulverized Fuel
8504 - Fluidized Bed
Boilers
8506 - Ovens & Furnaces

ANSI/NFPA 85C An American National Standard August 16, 1991


ANSI/NFPA 85C An American National Standard August 16, 1991

NFPA
NFPA85C
85C
Prevention
Preventionof
ofFurnace
Furnace
Explosions/Implosions
Explosions/Implosions
in
inMultiple
MultipleBurner
Burner
Boiler-Furnaces
Boiler-Furnaces
1991
Edition
1991Edition

National Fire Protection Association 1 Batterymarch Park, POBox 9101, Quincy, MA 02269-9101
National Fire Protection Association 1 Batterymarch Park, POBox 9101, Quincy, MA 02269-9101

Copyright 2002, exida.com

BMS design requires that the designer understand many standards. The
National Fire Protection Association (NFPA) standard 85 is probably the
most recognized standard worldwide for combustion systems safety. The
current standards are quite prescriptive with very specific design
requirements.

Copyright exida.com LLC 2001-2002

e ida.com
excellence in dependable-automation

ANSI/ISA 84.01 Standard


Recognized by OSHA as industry accepted
good engineering practices.
Approved in 1994
Offers the Safety Lifecycle as a method for
SIS design
Risk reduction targets and compliance
measured by Safety Integrity Levels (SIL)

Copyright 2002, exida.com

The ISA 84.01 standard was not written specifically for BMS. It covers
functional safety of programmable equipment used in the process industries.
Since this standard was endorsed by OSHA in the United States it is
required on many BMS projects as well. This standard describes a lifecycle
approach to risk assessment and management using safety instrument
systems (SIS) as a risk reduction mechanism. A BMS is classified as a SIS.

Copyright exida.com LLC 2001-2002

e ida.com
excellence in dependable-automation

FM 7605 Equipment Certification


BMS Standard written for compliance
with IEC61508.
WEquipment must be IEC61508 certified.
Hardware architecture for specified SIL
Software compliance for specified SIL

WManufacturing facilities examination.


WDemonstrated Quality and Reliability.
6

Copyright 2002, exida.com

FM standard 7605 builds upon an international functional safety standard


IEC61508. The FM standard requires that equipment for BMS applications
be functional safety certified per IEC61508. Other requirements in addition
to those of IEC61508 are listed as well.

Copyright exida.com LLC 2001-2002

e ida.com
excellence in dependable-automation

IEC61508 - Consensus Standard

HSE
PES

ISA
S84
DIN V 19250
DINV VDE0801

EWICS

IEC61508
Copyright 2002, exida.com

IEC 61508 is an international standard for functional safety created by a number of


active groups from around the world.

Copyright exida.com LLC 2001-2002

e ida.com
excellence in dependable-automation

IEC 61508 - Objectives


Safety
Management
Accident
Causes

Technical
Requirements

IEC61508
Safety Life
Cycle

Competence
of Persons

Certification

A key objective of of IEC61508 was to address accident causes by creating


a system to manage safety, to assure proper technical requirements and to
assure competent personnel.
A Safety Lifecycle approach is required to assess the magnitude of the
needed risk reduction and design safety instrumented functions that meet
that risk reduction target.

Copyright exida.com LLC 2001-2002

e ida.com

Safety LifecycleAnalysis Phase

excellence in dependable-automation

1. Conceptual
Process Design

Process Information

2. Identify
Potential Hazards

Event History

e ida.com

Layers of Protection
Failure Probabilities

Consequence
Database

3. Layer of
Protection Analysis

Assess Potential
Risk Likelihood

e ida.com

Analyze Potential
Risk Magnitude
Safety
Requirements
Allocation

Hazard
Characteristics

Potential Hazards

Hazard Frequencies

FETCH Tool

excellence in dependable automation

4. Consequence
Analysis

Hazard Consequences

Develop non SIS Layers


SIS
Required?

Target SILs
No
Exit

SRS DOCUMENT Template

Safety Requirements SpecificationFunctional Description of each Safety


Instrumented Function, Target SIL,
Mitigated Hazards, Process parameters,
Logic, Bypass/Maintenance
requirements, Response time, etc

Yes
Tolerable Risk
Guidelines

PROBE Tool

excellence in dependable automation

5. Select Target
SIL
6. Develop Safety
Specification

Copyright 2002, exida.com

In the Analysis phase of the Safety Lifecycle (SLC), the risk of each hazard
is assessed by obtaining an estimate of the likelihood of occurance and
consequence of occurance. For those risks that need to be reduced, safety
requirements are created. Often the needed safety can be achieved without
a safety instrumented system. For those places where a SIS is judged to be
the best solution, a risk reduction target is defined called a Safety Integrity
Level (SIL). A description of the needed safety functions along with all
important information including the SIL is documented in a safety
requirements specification (SRS).

Copyright exida.com LLC 2001-2002

e ida.com

Safety Lifecycle Realization Phase

excellence in dependable-automation

Safety Requirements Specification Functional Description of each Safety


Instrumented Function, Target SIL,
Mitigated Hazards, Process parameters,
Logic, Bypass/Maintenance
requirements, Response time, etc

7. SIS Conceptual
Design
Manufacturers
Failure Data
Failure Data
Database

Manufacturers
Safety Manual

Manufacturers
Installation
Instructions

7a. Select
Technology

Choose sensor, logic solver


and final element technology

7b. Select
Architecture

Redundancy: 1oo1,1oo2,
2oo3, 1oo2D

7c. Determine
Test Philosophy
No

e ida.com

SIL
Achieved?
Yes

excellence in dependable automation

SILver Tool

7d. Reliability,
Safety Evaluation

DD DOCUMENT Template

8. SIS Detailed
Design
9. Installation
& Commission
Planning

SILs Achieved

10. SIS Installation,


Commissioning
and Pre-startup
Acceptance Test

10

Detailed Design Documentation Loop Diagrams, Wiring Diagrams, Logic


Diagrams, Panel Layout, PLC
Programming, Installation
Requirements, Commissioning
Requirements, etc.

Copyright 2002, exida.com

The realization phase begins with conceptual design of the safety


instrumented system based on the Safety Requirements Specification. The
desired technology is chosen for the sensors, logic solver and final elements.
Once the technology is chosen, often redundant devices are selected. There
are different redundant configurations that can be used with names like 1oo1
(which stands for one out of one), 1oo2, 2oo3 and 1oo2D. The architecture
chosen depends on safety and process availability needs.

Copyright exida.com LLC 2001-2002

10

e ida.com
excellence in dependable-automation

Safety Lifecycle Operation Phase

11. Validation
Planning

12. Validation:
Pre-startup
Safety Review

13. Operating and


Maintenance
Planning

14. SIS startup,


operation,
maintenance,
Periodic
Functional Tests

Modify

Decommission

15. Modify,
Decommission?

11

Verify all documentation against


Hazards, design, installation testing,
maintenance procedures,
management of change, emergency
plans, etc.

16. SIS
Decommissioning

Copyright 2002, exida.com

The operation phase of the safety lifecycle begins with a validation of the
design. Answer the questions. Does the system solve the problems
identified during the hazard analysis? Has the design met the target SIL for
each safety instrumented function? Have the maintenance procedures been
created and verified? Is there a management of change procedure in place?
Are operators and maintenance personnel qualified and trained?
If the answers to these questions are acceptable, the process can proceed
with startup and operation.

Copyright exida.com LLC 2001-2002

11

e ida.com
excellence in dependable-automation

Safety Instrumented Function (SIF)

What to measure (sense)


What to do (actuate)
When to do (event logic)
How fast from measure to react (timing)
Loop 1

Logic
Solver
Loop 2
Loop 3

A Safety Instrumented Function (SIF) is defined as the functionality required


to protect against a specific hazard. Often this is also interpreted as the
collection of equipment needed to implement that function. Many systems
are designed using a piece of equipment in more than one SIF.

Copyright exida.com LLC 2001-2002

12

e ida.com
excellence in dependable-automation

Interlocks/Safety Instrumented Functions


Light off Sequences
Trips vs. Permissives
Master Fuel Trip and Purge Sequence
Gas-Fired Systems
Oil-Fired Systems
Pulverized coal-fired systems

13

Copyright 2002, exida.com

Safety Instrumented Functions for a BMS include light off sequences, trips,
permissives, fuel trip sequences and purge sequences.

Copyright exida.com LLC 2001-2002

13

e ida.com
excellence in dependable-automation

Automatic Light-Off Sequence Fuel


Gas (Starting Sequence)
1. Establish an open flow path from the inlets of the
forced draft fans through the stacks.
2. An induced draft fan, if provided, shall be started.
Additional induced or forced draft fans shall be
started, as necessary, to achieve the purge flow
rate
3. Perform operational leak test of fuel header piping
while maintaining purge air flow
4. Dampers and burner registers shall be opened to
the purge position
5. Airflow set to purge rate, and purge shall be
performed
14
Copyright 2002, exida.com

A number of steps are required to performed in a particular order for


automatic light- off per NFPA 85.

Copyright exida.com LLC 2001-2002

14

e ida.com
excellence in dependable-automation

Automatic Light-Off Sequence Fuel


Gas (Starting Sequence)
6. Ensure fuel control and bypass valves are closed,
then set to maintain necessary burner pressure for
light-off.
7. Igniter shutoff valve opened and necessary
pressure established.
8. Air register for burner selected for primary light-off
adjusted to light-off position
9. Source of ignition (sparks) applied to selected
igniter, if no flame in 10 seconds stop and re-purge
10. After stable flame established, dampers adjusted to
normal operating position
15

Copyright 2002, exida.com

These steps involve both sequence and timing.

Copyright exida.com LLC 2001-2002

15

e ida.com
excellence in dependable-automation

Automatic Light-Off Sequence Fuel


Gas (Starting Sequence)
11. Open main fuel shutoff valves
12. Establish main burner flame is stable and
close main gas header vent valve
13. Place additional burners in service

16

Copyright 2002, exida.com

The sequence is automatic as studies have shown that manual light off
procedures have been the source of many industrial boiler accidents.

Copyright exida.com LLC 2001-2002

16

e ida.com
excellence in dependable-automation

Trips and Permissives


Trip Conditions and action taken to move
the heater to a safe state when a hazardous
condition is present (Master Fuel Trip)
Permissive Set of conditions that must be
met prior to an action being taken (Purge
Sequence)

17

Copyright 2002, exida.com

SIF for a BMS include both trips and permissives. In a trip the SIF
recognizes a dangerous condition and shuts down the fuel source. In a
permissive the SIF looks for a dangerous before allowing an action to be
taken (typically done in a sequence).

Copyright exida.com LLC 2001-2002

17

e ida.com
excellence in dependable-automation

Furnace Purge System (All Fuels)


All main, igniter, and individual
burner and igniter safety shutoff
valves are closed?

One set of ID and


FD fans running?

Are required burner


registers open?

Yes

Yes

Is air at purge rate?


Yes

Yes

Five-minute
time delay

Yes

Reset master
fuel trip relay(s)

18

Copyright 2002, exida.com

The fuel purge sequence has several permissives included.

Copyright exida.com LLC 2001-2002

18

e ida.com
excellence in dependable-automation

Close individual igniter safety


shutoff valve(s) and
deenergize sparks

1.

Loss of igniter flame

2.

Igniter fuel pressure out of stable range

3.
See Note

Loss of ID fan

6.

Loss of ID fan

Fuel Gas Trip System

5. Cut back main fuel

8.

Combustion airflow low

9.

Excessive furnace pressure

10a.

Burner header fuel pressure high

10b.

Burner header fuel pressure low

11.

Loss of all flame

12.

Partial loss of flame introducing hazard

A
N
D

4. Loss of FD fan
7. Loss of FD fan

13.

All fuel inputs zero

14.

Manual trip switch

15.

Loss of individual burner flame with one or more additional


stable burner flames present

Master
Fuel Trip
Logic

Master
Fuel Trip
Relay(s)
Close main safety shutoff
and individual burner safety
valves

Close individual burner safety shutoff valve(s) and


its individual igniter safety shutoff valve(s) and
deenergize the associated sparks

Note: Based upon two pairs of ID and IF fans; other


arrangements of fans affect actions in blocks 3, 4, 5, 6, and 7

Based on Figure 6-6.3.1.1 NFPA 8502

Typical Cause of
Trip Indication

Close igniter header and


individual igniter safety shutoff
valves and deenergize sparks

19

Copyright 2002, exida.com

There are a number of specific SIF required in NFPA standards. Thirteen


specific hazards have been identified with prescriptive safety instrumented
functions assigned.

Copyright exida.com LLC 2001-2002

19

e ida.com

Fuel Oil Trip System

excellence in dependable-automation

1.
2.

Igniter fuel pressure out of stable range

3.

Igniter atomizing medium out of stable range

4.
See Note

Loss of ID fan

7.

Loss of ID fan

9.

Close individual igniter safety


shutoff valve(s) and
deenergize sparks

Loss of igniter flame

6. Cut back main fuel

A
N
D

5. Loss of FD fan
8. Loss of FD fan

Typical Cause of
Trip Indication

Close igniter header and


individual igniter safety shutoff
valves and deenergize sparks

Combustion airflow low

10.

Excessive furnace pressure

11.

All fuel inputs zero

12.

Low main oil burner pressure

13.

Atomizing medium pressure improper

14.

Manual trip switch

15.

Loss of all flame

16.

Partial loss of flame without introducing hazard

17.

Loss of individual burner flame with one or more additional


stable burner flames present

Master
Fuel Trip
Logic

Close main safety shutoff


valve, circulating valve,
recirculating valve, and
individual burner safety
shutoff valves

Close individual burner safety shutoff valve(s) and


its individual igniter safety shutoff valve(s) and
deenergize the associated sparks

Note: Based upon two pairs of ID and IF fans; other


arrangements of fans affect actions in blocks 4, 5, 6, 7, and 8

Based on Figure 7-6.3.1.1 NFPA 8502

Master
Fuel Trip
Relay(s)

20

Copyright 2002, exida.com

The SIF are different depending on fuel type. Although many hazards are
similar, different fuels may present different hazards.

Copyright exida.com LLC 2001-2002

20

e ida.com
excellence in dependable-automation

Coal Trip System


1.
2.

Igniter fuel pressure out of stable range

3.

Igniter atomizing medium improper

9.
10.

Close individual igniter safety


shutoff valve(s) and
deenergize sparks

Loss of igniter flame

4.

Loss of ID fan

7.

Loss of ID fan

6. Cut back main fuel

A
N
D

5. Loss of FD fan
8. Loss of FD fan

Typical Cause of
Trip Indication

Close igniter header and


individual igniter safety shutoff
valves and deenergize sparks

Combustion airflow low


Excessive furnace pressure

11.

All fuel inputs zero

12.

Manual trip switch

13.

Loss of all flame

14.

Partial loss of flame introducing hazard

15.

Loss of main burner flame

Master
Fuel Trip
Logic

Master
Fuel Trip
Relay(s)

Other subsystems

Stop coal flow to pulverizers


and burners

Follow tripping strategy


in 8-4.4.2

Note: Based upon two pairs of ID and IF fans; other


arrangements of fans affect actions in blocks 4, 5, 6, 7, and 8

Based on Figure 8-6.3.1.1 NFPA 8502

21

Copyright 2002, exida.com

There are fewer hazards in a coal fired system and that shows in the NFPA
SIF chart for coal.

Copyright exida.com LLC 2001-2002

21

e ida.com
excellence in dependable-automation

SIF Definition Example


Low Fuel Gas Pressure Causes MFT
Hazard: Low fuel gas pressure causes loss of flame and
accumulation of unburned flammable mixture, which
may explode if ignited

Sensors: Fuel gas low pressure switch, total loss of flame


Final
Main fuel header safety shutoff valve(s) are closed,
Elements: individual burner shutoff valve(s) are closed
** SIF can be manually actuated
This information should be documented in a Safety
Requirements Specification per ISA 84.01 and IEC
61508/61511
22

Copyright 2002, exida.com

As an example, one particular hazard is low fuel gas pressure. This hazard
may cause loss of flame and the accumulation of unburned fuel which may
explode if ignited. A SIF designed to protect against this hazard has fuel
gas pressure sensors and a flame sensor. If dangerous conditions are
detected, the final elements will stop fuel flow via shutoff valves.

Copyright exida.com LLC 2001-2002

22

e ida.com
excellence in dependable-automation

Typical SIF in NFPA 8502 Compliant


BMS (Fuel Gas Only)
Loss of igniter closes igniter
valves
Igniter pressure high/low
closes igniter valves
Loss of fans causes master
fuel trip
Low combustion airflow
causes master fuel trip
High furnace pressure
causes master fuel trip
High fuel header pressure
causes master fuel trip

Low fuel header pressure


causes master fuel trip
Total loss of flame causes
master fuel trip
Partial loss of flame causes
burner valve trip
Low steam drum level
causes MFT
High steam drum pressure
causes MFT

23

Copyright 2002, exida.com

A number of typical SIF are included in the NFPA standards as a function of


fuel type. Each SIF has sensors to detect the condition and takes some
action to move the combustion equipment to a safe state. Usually this
involves shutting off the fuel flow and possibly other actions as well.

Copyright exida.com LLC 2001-2002

23

e ida.com
excellence in dependable-automation

Example SIF in NFPA 8502 Compliant


BMS

24

Copyright 2002, exida.com

In one example BMS system designed using the Safety Lifecycle, risks were
assessed and a SIL level was assigned to each SIF. NFPA standards were
followed along with normal hazard identification and risk assessment. SIF
were designed to meet various levels of risk with redundancy used to
achieve NFPA standards, plant availability requirements and risk reduction
requirements.

Copyright exida.com LLC 2001-2002

24

e ida.com
excellence in dependable-automation

SIF Verification

Definition: SIF Verification


The process of demonstrating by
analysis that the design of each
identified safety instrumented function
meets the integrity requirement
specified in the SRS.

When the equipment for each SIF is chosen, an analysis is done to verify
that the design meets the safety and availability requirements. This step is
called SIF verification.

Copyright exida.com LLC 2001-2002

25

e ida.com
excellence in dependable-automation

BMS SIF Design

Failure Modes
Diagnostics
Architectures
Common Cause

Failure modes of the equipment, diagnostic capability of the equipment,


redundancy and any possible common cause failure of the redundant
equipment must be considered.

Copyright exida.com LLC 2001-2002

26

e ida.com
excellence in dependable-automation

Programmable Electronic Systems


have multiple failure modes!
Two critical failure modes for Safety Instrumented
Systems:

For De-Energize to Trip-

1. Outputs de-energized
or open circuit.

SAFE
DANGEROUS

2. Outputs energized or
frozen short circuit.

27

Copyright 2002, exida.com

The equipment used to implement protection systems has multiple failure


modes. The two of most significance are safe and dangerous.
In a normally energized safety system (de
- n
eergize to trip) safe is de
energize, dangerous is energized.

Copyright exida.com LLC 2001-2002

27

e ida.com
excellence in dependable-automation

Diagnostics

Online diagnostics allow:


Quick repair of failed units reduces time operating in degraded
condition.
Conversion of dangerous failures
to safe failures with automatic
shutdown capability.

Diagnostic capability measured by C = Coverage


Factor, the percentage of failures that will be detected.
CS = Coverage Factor for Safe Failures
CD = Coverage Factor for Dangerous Failures
Copyright 2002, exida.com

It is recognized that diagnostics are critical to the proper operation of a


safety equipment. Diagnostics tell the user when the a system component
has failed so that the system does not operate in a degraded mode for a
long period of time. Diagnostics may also be used to directly implement a
trip if that is justified.
The online diagnostic capability of equipment is measured by its Coverage
Factor, the chance of detecting a failure given that one occurs.
Different coverage factors are needed for safe versus dangerous failures.

Copyright exida.com LLC 2001-2002

28

e ida.com
excellence in dependable-automation

ARCHITECTURES
+
Output Circuit

Sensor

Input
Circuit

Logic Solver
Common Circuitry

Actuator

MP

Final Element

1oo1 Architecture.
29

Copyright 2002, exida.com

Different architectures are also used. Sometimes no redundancy is needed.


This architecture is known as 1oo1, one out of one. One set of equipment
is needed to shutdown the process and one set is there.

Copyright exida.com LLC 2001-2002

29

e ida.com
excellence in dependable-automation

Output Circuit
Input
Circuit

Logic Solver
Common Circuitry

MP

Sensor
Output Circuit
Input
Circuit

Logic Solver
Common Circuitry

Actuator

MP

Final Element

1oo2 Architecture
30

Copyright 2002, exida.com

Often the calculations show that one set of equipment is not enough to meet
the risk reduction targets. Another architecture used in such a situation is
the 1oo2. Only one set of equipment is needed to shutdown the process
but two sets are provided. This architecture provides higher safety but has
the disadvantage that either set of equipment can cause a false trip if it fails
safe.
NOTE: See exida on
- line lesson System Reliability Engineering for more
information on architecture evaluation.

Copyright exida.com LLC 2001-2002

30

e ida.com
excellence in dependable-automation

A
Output Circuit 1

Logic Solver

Input Circuit

Common Circuitry

MP

Output Circuit 2

B
Sensor

Output Circuit 1

Logic Solver

Input Circuit

Common Circuitry

MP
C
Input Circuit

Output Circuit 2

Voting Circuit

Output Circuit 1

Logic Solver
Common Circuitry

MP

Output Circuit 2

2oo3 architecture.

Actuator
Final Element

31

Copyright 2002, exida.com

In some cases a 2oo3 architecture is chosen. This arrangement has three


sets of equipment provided with a vote such that one set can fail in either
mode and the architecture remains successful.

Copyright exida.com LLC 2001-2002

31

e ida.com
excellence in dependable-automation

Common Cause
The failure of two or more
units in a redundant system
due to a common stress.

Heat
Humidity
Chemical Corrosion

What Stress?

Shock

Examples?

Vibration
Electrical Surge
Electrostatic Discharge
Radio Interference
Human Errors
32

Copyright 2002, exida.com

Can two or more pieces of equipment fail due to the same stress?
How about the triple redundant system with all three processors mounted in
the same rack. A mechanic calls on the radio and shuts down all three
simultaneously.
The Boeing 747 has four redundant hydralic systems. If this system fails the
plane will crash. Need all four? On July 30, 1971 a PANAM 747 took off
from San Fran on a short runway. It was too low. It failed to clear a pier at
the end of the runway. Various steel shafts ripped the hull and ruptured
three of the four systems. The fourth system worked and the plane landed
safely.
This was a common cause stress!

Copyright exida.com LLC 2001-2002

32

e ida.com
excellence in dependable-automation

Common Cause

A common
cause failure
is a system
failure.

Power Supply
system failure

Power Supply Power Supply


A fails
B fails

33

Common
Cause Power
Supply

Copyright 2002, exida.com

Common cause failures reduce the effectiveness of redundancy and this


must be considered in the design. A common cause failure will often fail the
system.
NOTE: See the exida on
- line lesson System Reliability Engineering for more
information on common cause analysis.

Copyright exida.com LLC 2001-2002

33

e ida.com

SIF Verification Task

excellence in dependable-automation

Safety Requirements
Specification - Safety
Function Requirements
including target SIL

Manufacturers
Failure Data

7d. Reliability and


Safety Evaluation

Failure Data
Database

PFDavg, RRF
MTTFS,
SIL achieved

Given all the information about equipment type, equipment failure rates, equipment
diagnostic capability, common cause susceptibility and operating time intervals a safety
and availability analysis is done to verifiy that the design requirements have been met.
The key variables calculated are:
PFDavg Average Probability of Failure on Demend
RRF Risk Reduction Factor
MTTFS Mean Time To False, Spurious Trip
SIL Safety Integrity Level achieved by the design

Copyright exida.com LLC 2001-2002

34

e ida.com
excellence in dependable-automation

BMS - Safety Function Example


Low steam drum level causes Master Fuel
Trip

9 On detection of low level of water firing should


be stopped
9 Low level of water may result in loss of integrity
of the stream drum vessel and potential physical
explosion of the steam drum
9 A level switch accomplishes detection of an
abnormal condition

35

Copyright 2002, exida.com

As an example, consider the high steam drum level hazard. If this hazard is
detected, a master fuel trip is done.

Copyright exida.com LLC 2001-2002

35

e ida.com
excellence in dependable-automation

Safety Function Architecture


Fuel
Level
Switch

Logic
Solver

To burners

BMS system consists of 6 individual burners


36

Copyright 2002, exida.com

This system has six burners. The equipment for this SIF includes a level
switch wired into a safety PLC. The safety PLC must de- energize seven
outputs that control the main fuel valve and six burner fuel valves. One set
fo equipment is provided in a 1oo1 architecture.

Copyright exida.com LLC 2001-2002

36

e ida.com
excellence in dependable-automation

Fault Tree BMS safety function (I)


Drum level SIS fails

Sensor
system fails

Logic solver
system fails

Actuator
system fails

Level
switch
fails

Logic
solver
fails

37

Copyright 2002, exida.com

A fault tree for this set of equipment starts with an OR gate as failure of the
sensor subsystem or the safety PLC or the valve subsystem will cause a SIF
dangerous failure.

Copyright exida.com LLC 2001-2002

37

e ida.com
excellence in dependable-automation

Fault Tree BMS safety function (II)


1

Master
fuel
valve
fails
Burner
1
valve
fails

Burner
2
valve
fails

38

Burner
3
valve
fails

Burner
4
valve
fails

Burner
5
valve
fails

Burner
6
valve
fails

Copyright 2002, exida.com

The valve subsystem is more complicated. It will fail to stop the fuel if the
main valve fails dangerously and any one of the burner valves fail
dangerously.

Copyright exida.com LLC 2001-2002

38

e ida.com
excellence in dependable-automation

BMS Equipment Data


Dangerous
failure rate
(1/106 hours)

Dangerous
MTTF (years)

Test
Interval
(months)

Dangerous
Pfd

Approx.
Dangerous
Pfdavg

4.6

24.82

12

0.03949

0.02015

12

0.0000353

Main Fuel Shutoff valve

3.7

30.85

12

0.03189

0.01621

Burner Shutoff valve

2.9

39.36

12

0.02508

0.01217

Equipment item
Level Switch
Safety PLC

39

Copyright 2002, exida.com

The dangerous failure rates for the various pieces of equipment are collected
and PFD calculations are done for each device. It is assumed that there are
no diagnostics for the level switch or the valves.
The PFDavg for the safety PLC was provided by the manufacturer.

Copyright exida.com LLC 2001-2002

39

e ida.com
excellence in dependable-automation

Fault Tree Results


Drum level SIS fails

Sensor
system fails

0.03949

Logic solver
system fails

---

Level
switch
fails

Logic
solver
fails

Fault Tree calculations


only with probabilities
not with average probabilities

---

Actuator
system fails

0.14138

Burner
1
valve
fails

Burner
2
valve
fails

Burner
3
valve
fails

Burner
4
valve
fails

0.02508

0.02508

0.02508
40

0.02508

0.00451

0.03189

Burner
5
valve
fails

Master
fuel
valve
fails

Burner
6
valve
fails

0.02508
0.02508
Copyright 2002, exida.com

Feeding the probability numbers into the fault tree provides an overall
probability of failure for the SIF.

Copyright exida.com LLC 2001-2002

40

e ida.com
excellence in dependable-automation

Markov Model BMS safety function


DMV

6DBV

Master
fuel
valve
fails

DMV

System
OK

6DBV

System
fail
dangerous

One
burner
valve
fails

DLevel Switch + DLogic Solver


MV : Master fuel valve
BV : Burner valve
41

Copyright 2002, exida.com

The SIF probability of failure could also be calculated with a Markov model.

Copyright exida.com LLC 2001-2002

41

e ida.com
excellence in dependable-automation

PFDavg Calculation (I)


IEC 61508 states:
Pfdavg(Safety Instrumented Function) =
Pfdavg(Sensor) + Pfdavg(Logic Solver) + Pfdavg(Actuator)

BMS SIF:
Pfdavg

= 0.02015 + 0.0000353 + 0.00157


= 0.02172
SIL 1
Pfdavg(Actuator): calculated using Markov Model
42

Copyright 2002, exida.com

When the PFD numbers are obtained, they are compared to the SIL chart
and it is determined that a SIL1 requirement could be met by this design.

Copyright exida.com LLC 2001-2002

42

e ida.com
excellence in dependable-automation

PFDavg Calculation Results


0.07
0.00
Sensor
Logic Solver
Actuator

0.93

43

Copyright 2002, exida.com

Looking at the PFD numbers, it is clear that the sensor is contributing most
of failure probability.

Copyright exida.com LLC 2001-2002

43

e ida.com
excellence in dependable-automation

Conclusion SIF Example


Sensor system is most dominant in Pfdavg of

Safety Instrumented Function


Improving sensor system will be most effective
9 Consider adding voting
9 Additional level indications
9 Capacitance type level switch
9 Differential pressure level transmitter

44

Copyright 2002, exida.com

If SIL1 is not acceptable for this SIF, a better sensor subsystem must
designed. Alternatives include the use of an analog level transmitter or
redundant level switches or even a combination of both.

Copyright exida.com LLC 2001-2002

44

e ida.com
excellence in dependable-automation

General Lesson Objectives


Review Standards for BMS
Show Safety Functions for typical/example
BMS
Review BMS design process
Present example BMS safety function
verification
45

Copyright 2002, exida.com

This lesson has presented a review of some standards tht apply to BMS
design focusing on NFPA 85 and IEC 61508. Typical SIF listed in NFPA
were presented along with an example BMS set of SIF. The Safety Lifecycle
design process was reviewed and a particular SIF verification example was
presented.
Review the lesson again if all the concepts were not clear. When ready,
proceed to the on
- line quiz.

Copyright exida.com LLC 2001-2002

45

e ida.com
excellence in dependable-automation

Questions
Questions: please send any questions to
info@exida.com We will respond as soon as possible.
Additional Resources:
Free articles are available to download from the
exida.com website. These can be reached at
http://www.exida.com/articles.asp
Additional resources including books, tools, and reports
are available from the exida on-line store. A product
listing is available at http://www.exida.com/products2/
46

Copyright 2002, exida.com

If have any questions, they may sent via email to info@exida.com. Please
refer to this particular lessonBurner Management System Safety Functions.
exida.com is a knowledge company focused on system reliability and safety.
We provide training, tools, coaching, and consulting. For general information
about exida, please view our detailed website at www.exida.com.
Thank you for your interest. Please consider other lessons in the on
- line
training series from exida.com.

Copyright exida.com LLC 2001-2002

46

Das könnte Ihnen auch gefallen