1MRS757846 E
Contents
1. Description..................................................................... 3
2. Default configurations..................................................... 3
3. Protection functions........................................................8
4. Application..................................................................... 9
6. Control......................................................................... 11
7. Measurement............................................................... 12
8. Power quality................................................................12
9. Disturbance recorder....................................................12
26. Tools........................................................................... 61
29. Certificates.................................................................. 65
14. Self-supervision...........................................................13
30. References..................................................................65
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors
that may appear in this document.
Copyright 2015 ABB.
All rights reserved.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks
of their respective holders.
ABB
1. Description
RET620 is a dedicated two-winding power transformer
management relay perfectly aligned for the protection, control,
measurement and supervision of both power and step-up
transformers, including power generator-transformer blocks, in
utility and industrial power distribution systems. RET620 is a
member of ABBs Relion protection and control product family
and its 620 series. The 620 series relays are characterized by
their functional scalability and withdrawable-unit design.
The 620 series has been designed to unleash the full potential
of the IEC 61850 standard for communication and
interoperability of substation automation devices.
The 620 series relays support a range of communication
protocols including IEC 61850 with Edition 2 support, process
bus according to IEC 61850-9-2 LE, IEC 60870-5-103,
Modbus and DNP3. Profibus DPV1 communication protocol is
supported by using the protocol converter SPA-ZC 302.
ABB
1MRS757846 E
Issued: 2015-12-11
Revision: E
2. Default configurations
The 620 series relays are configured with default
configurations, which can be used as examples of the 620
series engineering with different function blocks. The default
configurations are not aimed to be used as real end-user
applications. The end-users always need to create their own
application configuration with the configuration tool. However,
the default configuration can be used as a starting point by
modifying it according to the requirements.
RET620 is available with one default configuration. The default
signal configuration can be altered by means of the graphical
signal matrix or the graphical application functionality of the
Protection and Control IED Manager PCM600. Furthermore,
the application configuration functionality of PCM600 supports
the creation of multi-layer logic functions utilizing various logical
elements including timers and flip-flops. By combining
protection functions with logic function blocks the relay
configuration can be adapted to user specific application
requirements.
1MRS757846 E
RET620
UL1UL2UL3
Uo
Version
2.0 FP1
PROTECTION
2
ALSO AVAILABLE
LOCAL HMI
Master Trip
Lockout relay
94/86
A
U12 0. 0 kV
P 0.00 kW
Q 0.00 kVAr
IL2 0 A
3I (HV)
I2>
46
3I<
37
Io (HV)
3Ith>T
49T
3I>>>
50P/51P
Io>
51N-1
Io>>
51N-2
ESC
Clear
R
L
3I>/Io>BF
51BF/51NBF
CONDITION MONITORING
AND SUPERVISION
U12
3I>
51P-1
3I>>
51P-2
3I2f>
68
dIoLo>
87NL
Io>
67N-1
Io>>
67N-2
3I (HV)
P>/Q>
32R/32O
P<
32U
Io
(HV)
3I>
67-1
3
CBCM
CBCM
FUSEF
60
Io
(LV)
Io
Protocols:
IEC 61580-8-1/-9-2LE
Modbus
IEC 60870-5-103
DNP3
Io
Interfaces:
Ethernet: TX (RJ-45), FX (LC)
Serial:
Serial glass ber (ST),
RS-485, RS-232/485
Redundant protocols:
HSR
PRP
RSTP
OPTS
OPTM
Io
MCS 3I
MCS 3I
MCS 3I, I2
MCS 3I, I2
MCS 3I
MCS 3I
2
CVPSOF
SOFT/21/50
3I>>
67-2
COMMUNICATION
Io (HV)
UL1UL2UL3
Uo
TCS
TCM
dIoHi>
87NH
dIoHi>
87NH
Object
I2>
46
3I<
37
Io
3I>>>
50P/51P
3I>/Io>BF
51BF/51NBF
Io>>
51N-2
3I>
51P-1
ES
2)
3I>>
51P-2
Uo
U12
dIoLo>
87NL
Io
3U<
27
3
Uo>
59G
3
3U>
59
U2>
47O-
f>/f<,
df/dt
81
U1<
47U+
UL1UL2UL3
1)
Current transformer
Voltage transformer
TPOSM
84M
SYNC
25
OTHER FUNCTIONALITY
U/f>
24
UL1UL2UL3
1)
U12b
2
- HV: I, U, Io, Uo
- LV: I, Io
- P, Q, E, pf, f
- Limit value supervision
- Load prole
- Power Quality functions
- RTD/mA measurements
- Symmetrical components
Io>
51N-1
18
MAP12
MAP12
6RTD
2mA
Ind
DC
3)
3I (LV)
MEASUREMENT
3)
CB
1)
Io
(LV)
Ctrl
2)
3
ARC
50L/50NL
3I
(HV)
COLTC
90V
U12b
6
UFLS/R
81LSH
REMARKS
2
Master Trip
Lockout relay
94/86
Optional
function
3 No. of
instances
Io/Uo
Calculated
value
OR Alternative
function to be
dened when
ordering
GUID-BFA69E71-CDBB-4333-A91F-001F2A8A1E6B V2 EN
Figure 1.
ABB
1MRS757846 E
IEC 61850
A
(CTs/VTs)
PHLPTOC1
1 HV
PHLPTOC2
1 LV
PHHPTOC1
1 HV
PHHPTOC2
1 LV
PHIPTOC1
1 HV
PHIPTOC2
1 LV
DPHLPDOC
1 HV
DPHHPDOC
1 HV
EFLPTOC1
1 HV1)
EFLPTOC2
1 LV1)
EFHPTOC1
1 HV1)
EFHPTOC2
1 LV1)
DEFLPDEF
2 HV1)
DEFHPDEF
1 HV1)
NSPTOC1
1 HV
NSPTOC2
1 LV
ROVPTOV
3 HV
PHPTUV
4 HV
PHPTOV
3 HV
PSPTUV
2 HV
NSPTOV
2 HV
Frequency protection
FRPFRQ
3 HV
Overexcitation protection
OEPVPH
2 HV
T2PTTR
1 HV
PHPTUC1
1 HV
PHPTUC2
1 LV
TR2PTDF
LREFPNDF1
1 HV
LREFPNDF2
1 LV
HREFPDIF1
1 HV
HREFPDIF2
1 LV
Protection
Three-phase non-directional overcurrent protection, low stage
ABB
1MRS757846 E
IEC 61850
A
(CTs/VTs)
CCBRBRF1
1 HV
CCBRBRF2
1 LV
CCBRBRF3
1 HV
INRPHAR
1 HV
Master trip
TRPPTRC
Arc protection
ARCSARC
(3)2)
LSHDPFRQ
6 HV
Multipurpose protection
MAPGAPC
18
CVPSOF
1 HV
Underpower protection
DUPPDPR
2 HV
DOPPDPR
3 HV
CBXCBR1
1 HV
CBXCBR2
1 LV
CBXCBR3
1 HV
DCXSWI1
1 HV
DCXSWI2
1 HV
DCXSWI3
1 LV
DCXSWI4
1 LV
ESXSWI1
1 HV
ESXSWI2
1 LV
ESXSWI3
1 HV
DCSXSWI1
1 HV
DCSXSWI2
1 HV
DCSXSWI3
1 LV
DCSXSWI4
1 LV
ESSXSWI1
1 HV
ESSXSWI2
1 LV
ESSXSWI3
1 HV
SECRSYN
1 HV
TPOSYLTC
OLATCC
(1) LV
Control
Circuit-breaker control
Disconnector control
ABB
1MRS757846 E
IEC 61850
A
(CTs/VTs)
SSCBR1
1 HV
SSCBR2
1 LV
SSCBR3
1 HV
TCSSCBR1
1 HV
TCSSCBR2
1 LV
CCSPVC1
1 HV
CCSPVC2
1 LV
CTSRCTF
SEQSPVC
1 HV
MDSOPT
CMMXU1
1 HV
CMMXU2
1 LV
CSMSQI1
1 HV
CSMSQI2
1 LV
RESCMMXU1
1 HV
RESCMMXU2
1 LV
VMMXU
1 HV
VAMMXU2
1 LV
VAMMXU3
1 HV
RESVMMXU
1 HV
VSMSQI
1 HV
PEMMXU
1 HV
LDPRLRC
1 HV
Frequency measurement
FMMXU
1 HV
CMHAI
1 HV
VMHAI
1 HV
Voltage variation
PHQVVR
1 HV
Voltage unbalance
VSQVUB
1 HV
TPGAPC
TPSGAPC
TPMGAPC
PTGAPC
Measurement
Three-phase current measurement
Power quality
Other
ABB
1MRS757846 E
IEC 61850
A
(CTs/VTs)
TOFGAPC
TONGAPC
Set-reset (8 pcs)
SRGAPC
Move (8 pcs)
MVGAPC
MVI4GAPC
SCA4GAPC
SPCGAPC
SPCRGAPC
SPCLGAPC
UDFCNT
12
FKEYGGIO
Disturbance recorder
RDRE
Fault recorder
FLTRFRC
SER
Logging functions
1, 2, ... = Number of included instances. The instances of a protection function represent the number of identical protection function blocks available in
the standard configuration.
() = optional
HV = The function block is to be used on the high-voltage side in the application.
LV = The function block is to be used on the low-voltage side in the application.
1)
2)
Function uses calculated value when the high-impedance based restricted earth-fault protection is used
Io is calculated from the measured phase currents
3. Protection functions
RET620 features a three-phase, multi-slope stabilized (biased)
stage transformer differential protection and an instantaneous
stage to provide fast and selective protection for phase-tophase short circuit, winding interturn fault and bushing flashover protection. Besides the second harmonic restraint, an
advanced waveform-based blocking algorithm ensures stability
at transformer energization and the fifth harmonic restraint
function ensures good protection stability at moderate
overexcitation of power transformers. The restricted earth-fault
protection (REF) completes the overall differential protection
providing detection of even single phase-to-earth faults close to
the neutral earthing point of the transformer. Either the
conventional high-impedance scheme or the numerical lowimpedance scheme can be selected for the protection of the
transformer windings. When the low-impedance REF
protection is used, neither stabilizing resistors nor varistors are
needed and, as a further benefit, the transforming ratio of the
neutral earthing CTs can differ from that of the phase current
transformers. Due to its unit protection character and absolute
selectivity, REF does not need to be time-graded with other
8
ABB
1MRS757846 E
3U Uo
RET620
Default conf. + Option A
3I HV
ANSI
IEC
25
SYNC
50L/50NL
ARC
50P/51P
3I>>>
51P/51N
3I/Io
67/67N
3I/Io
84M
TPOSM
87T
3dI>T
90V
COLTC
MAP
MAP
HV
32R/32O
P>/Q>
side
49T
3Ith>T
87NH
dIoHi>
87NL
dIoLo>
LV
87NH
dIoHi>
side
87NL
dIoLo>
U12
Io HV
Io LV
RTD
U12b
3I LV
GUID-A758C254-7907-4965-9389-113BCBD77B75 V2 EN
Figure 2.
ABB
The protection of HV/MV, or an MV/MV transformer with low-impedance earth-fault protection on both sides of the transformer
1MRS757846 E
RET620
Default conf. + Option A
3I HV
ANSI
IEC
25
SYNC
50L/50NL
ARC
50P/51P
3I>>>
51P/51N
3I/Io
84M
TPOSM
87T
3dI>T
90V
COLTC
MAP
MAP
HV
49T
3Ith>T
side
87NH
dIoHi>
87NL
dIoLo>
Io HV
RTD
U12/U12b
3I LV
3U Uo
GUID-510B91B4-88A8-4A57-8789-C38683DC2A92 V2 EN
Figure 3.
Protection of HV/MV transformer with restricted earth-fault protection on the upper side of the transformer
10
1MRS757846 E
Version
System 800xA
5.1 or later
ABB
MicroSCADA Pro/
System 800xA
COM600
Web HMI
Ethernet switch
PCM600
IEC 61850
COM600
Web HMI
Ethernet switch
PCM600
IEC 61850
GUID-4D002AA0-E35D-4D3F-A157-01F1A3044DDB V2 EN
Figure 4.
ABB power system example using Relion relays, Substation Management Unit COM600 and MicroSCADA Pro/System 800xA
6. Control
RET620 integrates functionality for the control of circuit
breakers, disconnectors and earthing switches via the front
panel HMI or by means of remote controls. The relay includes
three circuit breaker control blocks. In addition to the circuit
breaker control, the relay features four disconnector control
blocks intended for the motor-operated control of
disconnectors or circuit breaker truck. Furthermore, the relay
offers three control blocks intended for the motor-operated
control of earthing switch. On top of that, the relay includes
additional four disconnector position indication blocks and
ABB
1MRS757846 E
8. Power quality
In the EN standards, power quality is defined through the
characteristics of the supply voltage. Transients, short-duration
and long-duration voltage variations and unbalance and
waveform distortions are the key characteristics describing
power quality. The distortion monitoring functions are used for
monitoring the current total demand distortion and the voltage
total harmonic distortion.
Power quality monitoring is an essential service that utilities can
provide for their industrial and key customers. A monitoring
system can provide information about system disturbances and
their possible causes. It can also detect problem conditions
throughout the system before they cause customer complaints,
equipment malfunctions and even equipment damage or
failure. Power quality problems are not limited to the utility side
of the system. In fact, the majority of power quality problems
are localized within customer facilities. Thus, power quality
monitoring is not only an effective customer service strategy but
also a way to protect a utility's reputation for quality power and
service.
The protection relay has the following power quality monitoring
functions.
Voltage
Voltage
Current
Voltage
variation
unbalance
harmonics
harmonics
1MRS757846 E
14. Self-supervision
The relays built-in self-supervision system continuously
monitors the state of the relay hardware and the operation of
the relay software. Any fault or malfunction detected is used for
alerting the operator.
A permanent relay fault blocks the protection functions to
prevent incorrect operation.
15. Fuse failure supervision
The fuse failure supervision detects failures between the
voltage measurement circuit and the relay. The failures are
detected either by the negative sequence-based algorithm or
by the delta voltage and delta current algorithm. Upon the
detection of a failure, the fuse failure supervision function
activates an alarm and blocks voltage-dependent protection
functions from unintended operation.
16. Current circuit supervision
Current circuit supervision is used for detecting faults in the
current transformer secondary circuits. On detecting of a fault
the current circuit supervision function activates an alarm LED
and blocks certain protection functions to avoid unintended
operation. The current circuit supervision function calculates
the sum of the phase currents from the protection cores and
compares the sum with the measured single reference current
from a core balance current transformer or from separate cores
in the phase current transformers.
17. Access control
To protect the relay from unauthorized access and to maintain
information integrity, the relay is provided with a four-level, rolebased authentication system with administrator-programmable
individual passwords for the viewer, operator, engineer and
administrator level. The access control applies to the frontpanel user interface, the Web browser-based user interface
and PCM600.
18. Inputs and outputs
The relay is equipped with six phase current inputs, two
residual-current inputs, three phase voltage inputs, one
residual-voltage input, one phase-to-phase voltage for
syncrocheck input and one phase-to-phase voltage for
automatic voltage regulator via online tap change input. In
addition to current and voltage measurements, the relay's basic
configuration includes eight binary inputs and 13 binary
outputs. Additionally, basic configuration offers two RTD inputs
and one mA input. The phase current inputs and the residualcurrent inputs are rated 1/5 A, that is, the inputs allow the
connection of either 1 A or 5 A secondary current transformers.
The three phase voltage inputs and the residual-voltage input
covers the rated voltages 60...210 V. Both phase-to-phase
voltages and phase-to-earth voltages can be connected.
13
1MRS757846 E
Analog channels
Binary channels
5-6
7-8
CT
VT
BI
BO
RTD
mA
AA
AA
16
4 PO + 13 SO
AB
4 PO + 9 SO
AC
16
4 PO + 9 SO
+ 3 HSO
NN
4 PO + 9 SO
14
1MRS757846 E
COM600
Ethernet switch
REF615
REF620
SCADA
RET620
Ethernet switch
REM620
REF615
GUID-334D26B1-C3BD-47B6-BD9D-2301190A5E9D V1 EN
Figure 5.
over the ring. Every node forwards the frames it receives from
one port to another to reach the next node. When the
originating sender node receives the frame it sent, the sender
15
1MRS757846 E
node discards the frame to avoid loops. The HSR ring with 620
series relays supports the connection of up to 30 relays. If more
than 30 relays are connected, it is recommended to split the
COM600
SCADA
Ethernet switch
Redundancy
Box
Redundancy
Box
Redundancy
Box
REF615
REF620
RET620
REM620
REF615
GUID-7996332D-7FC8-49F3-A4FE-FB4ABB730405 V1 EN
Figure 6.
16
ABB
1MRS757846 E
Client A
Client B
Network A
Network B
GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V4 EN
Figure 7.
records are supported. DNP serial and DNP TCP can be used in
parallel. If required, both IEC 61850 and DNP protocols can be
run simultaneously.
620 series supports Profibus DPV1 with support of SPA-ZC
302 Profibus adapter. If Profibus is required the relay must be
ordered with Modbus serial options. Modbus implementation
includes SPA-protocol emulation functionality. This
functionality enables connection to SPA-ZC 302.
When the relay uses the RS-485 bus for the serial
communication, both two- and four wire connections are
supported. Termination and pull-up/down resistors can be
configured with jumpers on the communication card so external
resistors are not needed.
The relay supports the following time synchronization methods
with a time-stamping resolution of 1 ms.
Ethernet-based
SNTP (Simple Network Time Protocol)
With special time synchronization wiring
IRIG-B (Inter-Range Instrumentation Group - Time Code
Format B)
17
1MRS757846 E
Layer 2 mapping
Peer to peer delay calculation
Multicast operation
Required accuracy of grandmaster clock is +/-1 s. The relay
can work as a master clock per BMC algorithm if the external
grandmaster clock is not available for short term.
Ethernet
Serial
100BASE-TX RJ-45
100BASE-FX LC
RS-232/RS-485
Fiber-optic ST
IEC 61850-8-1
IEC 61850-9-2 LE
MODBUS RTU/ASCII
MODBUS TCP/IP
DNP3 (serial)
DNP3 TCP/IP
IEC 60870-5-103
= Supported
18
ABB
1MRS757846 E
Value
Width
Frame
262.2 mm
Case
246 mm
Frame
177 mm, 4U
Case
160 mm
Height
Depth
Weight
201 mm
Complete protection relay
max. 5.5 kg
max. 3.0 kg
Description
Type 1
Type 2
Uaux nominal
50 ms at Un rated
Uaux variation
AC <19.0 W
Fuse type
T4A/250 V
1)
2)
ABB
(max2))
During the power consumption measurement, the relay is powered at rated auxiliary energizing voltage and the energizing quantities are energized without any binary output being active
During the power consumption measurement, the relay is powered at rated auxiliary energizing voltage and the energizing quantities are energized to activate at least half of the binary
outputs
19
1MRS757846 E
Value
Rated frequency
50/60 Hz 5 Hz
Current inputs
Rated current, In
1/5 A1)
20 A
For 1 s
500 A
Voltage inputs
Half-wave value
1250 A
Input impedance
<20 m
Rated voltage
60...210 V AC
Voltage withstand:
1)
Continuous
240 V AC
For 10 s
360 V AC
<0.05 VA
Value
Operating range
Rated voltage
24...250 V DC
Current drain
1.6...1.9 mA
Power consumption
31.0...570.0 mW
Threshold voltage
16...176 V DC
Reaction time
<3 ms
20
ABB
1MRS757846 E
mA inputs
Value
Supported RTD sensors
100 platinum
250 platinum
100 nickel
120 nickel
250 nickel
10 copper
0...2 k
25 per lead
Isolation
Response time
<4 s
Operation accuracy
Resistance
Temperature
2.0% or 1
1C
10 copper: 2C
020 mA
44 0.1%
Operation accuracy
0.5% or 0.01 mA
Value 1)
Rated voltage
250 V AC/DC
5A
15 A
30 A
1 A/0.25 A/0.15 A
100 mA at 24 V AC/DC
1)
X100: SO1
X105: SO1, SO2, when any of the protection relays is equipped with BIO0005.
X110: SO1, SO2 when REF620 or RET620 is equipped with BIO0005
Value 1)
Rated voltage
250 V AC/DC
5A
10 A
15 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC
1 A/0.25 A/0.15 A
10 mA at 5 V AC/DC
1)
ABB
X100:
X105:
X110:
X130:
IRF,SO2
SO3, SO4, when any of the protection relays is equipped with BIO0005
SO3, SO4, when REF620 or RET620 is equipped with BIO0005
SO1, SO2, when RET620 is equipped with RTD0002
21
1MRS757846 E
Table 12. Double-pole power outputs with TCS function X100: PO3 and PO4
Description
Value 1)
Rated voltage
250 V AC/DC
8A
15 A
30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC (two contacts connected in a series)
5 A/3 A/1 A
100 mA at 24 V AC/DC
20...250 V AC/DC
~1.5 mA
20 V AC/DC (15...20 V)
1)
Table 13. Signal/trip output with high make and carry and with TCS function
Description
Value 1)
Rated voltage
250 V AC/DC
5A
15 A
30 A
Breaking capacity when the control-circuit time constant L/R < 40 ms, at
48/110/220 V DC (two contacts connected in series)
1A/0.25A/0.15A
100 mA at 24 V AC/DC
1)
Table 14. Single-pole power output relays X100: PO1 and PO2
Description
Value
Rated voltage
250 V AC/DC
8A
15 A
30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC
5 A/3 A/1 A
100 mA at 24 V AC/DC
22
ABB
1MRS757846 E
Value 1)
Rated voltage
250 V AC/DC
6A
15 A
30 A
Breaking capacity when the control-circuit time constant L/R <40 ms, at
48/110/220 V DC
5 A/3 A/1 A
Operate time
<1 ms
Reset
1)
X105: HSO1, HSO2 HSO3, when any of the protection relays is equipped with BIO0007
Protocol
Cable
Front
TCP/IP protocol
10 MBits/s
Fiber type1)
Wave length
Typical max.
length2)
LC
MM 62.5/125 or 50/125 m
glass fiber core
1300 nm
2 km
<8 dB
ST
MM 62.5/125 or 50/125 m
glass fiber core
820...900 nm
1 km
<11 dB
1)
2)
3)
Value
B004, B0051)
Isolation
500V 1 min
Modulation
Unmodulated
Logic level
5 V TTL
Current consumption
<4 mA
Power consumption
<20 mW
1)
Table 19. Lens sensor and optical fiber for arc protection
Description
Value
-40...+100C
+140C
100 mm
ABB
23
1MRS757846 E
Value
Front side
IP 54
IP 20
Value
-25...+55C (continuous)
-40...+85C (<16h)1)2)
Relative humidity
<93%, non-condensing
Atmospheric pressure
86...106 kPa
Altitude
Up to 2000 m
-40...+85C
1)
2)
24
Degradation in MTBF and HMI performance outside the temperature range of -25...+55 C
For relays with an LC communication interface the maximum operating temperature is +70 C
ABB
1MRS757846 E
IEC 61000-4-18
IEC 60255-26, class III
IEEE C37.90.1-2002
Common mode
2.5 kV
Differential mode
2.5 kV
Reference
IEC 61000-4-18
IEC 60255-26, class III
2.5 kV
IEC 61000-4-2
IEC 60255-26
IEEE C37.90.3-2001
Contact discharge
8 kV
Air discharge
15 kV
IEC 61000-4-6
IEC 60255-26, class III
10 V/m (rms)
f = 80...2700 MHz
IEC 61000-4-3
IEC 60255-26, class III
10 V/m
f = 900 MHz
ENV 50204
IEC 60255-26, class III
All ports
IEC 61000-4-4
IEC 60255-26
IEEE C37.90.1-2002
4 kV
IEC 61000-4-5
IEC 60255-26
Communication
1 kV, line-to-earth
Other ports
4 kV, line-to-earth
2 kV, line-to-line
IEC 61000-4-8
Continuous
1...3 s
300 A/m
1000 A/m
1000 A/m
6.4/16 s
IEC 61000-4-9
IEC 61000-4-10
2s
100 A/m
1 MHz
400 transients/s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
IEC 61000-4-16
IEC 60255-26, class A
Common mode
300 V rms
ABB
25
1MRS757846 E
Differential mode
150 V rms
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
Emission tests
Reference
IEC 61000-4-16
EN 55011, class A
IEC 60255-26
CISPR 11
CISPR 12
Conducted
0.15...0.50 MHz
0.5...30 MHz
Radiated
30...230 MHz
230...1000 MHz
13 GHz
36 GHz
Reference
Dielectric tests
IEC 60255-27
IEC 60255-27
>100 M, 500 V DC
IEC 60255-27
<0.1 , 4 A, 60 s
IEC 60255-27
Description
Reference
Requirement
Class 2
Class 2
Seismic test
IEC 60255-21-3
Class 2
26
ABB
1MRS757846 E
Reference
96 h at +55C
16 h at +85C1)
IEC 60068-2-2
96 h at -25C
16 h at -40C
IEC 60068-2-1
IEC 60068-2-30
5 cycles (3 h + 3 h)
at -25C...+55C
IEC60068-2-14
Storage test
96 h at -40C
96 h at +85C
IEC 60068-2-1
IEC 60068-2-2
1)
For relays with an LC communication interface the maximum operating temperature is +70o C
Reference
LV directive
2006/95/EC
Standard
EN 60255-27 (2013)
EN 60255-1 (2009)
Reference
EMC directive
2004/108/EC
Standard
EN 60255-26 (2013)
ABB
27
1MRS757846 E
Protection functions
Table 29. Three-phase non-directional overcurrent protection (PHxPTOC)
Characteristic
Value
Operation accuracy
PHHPTOC
and
PHIPTOC
Typical
Maximum
16 ms
19 ms
23 ms
11 ms
12 ms
14 ms
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
2)
3)
28
Set Operate delay time = 0,02 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, fault current in one phase
with nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Includes the delay of the heavy-duty output contact
ABB
1MRS757846 E
Function
Value (Range)
Step
Start value
PHLPTOC
0.05...5.00 In
0.01
PHHPTOC
0.10...40.00 In
0.01
PHIPTOC
1.00...40.00 In
0.01
PHLPTOC
0.05...15.00
0.01
PHHPTOC
0.05...15.00
0.01
PHLPTOC
40...200000 ms
10
PHHPTOC
40...200000 ms
10
PHIPTOC
40...200000 ms
10
PHLPTOC
PHHPTOC
PHIPTOC
Definite time
Time multiplier
1)
Value
Operation accuracy
Current:
1.5% of the set value or 0.002 In
Voltage:
1.5% of the set value or 0.002 Un
Phase angle: 2
DPHHPDOC
Current:
1.5% of the set value or 0.002 In
(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Voltage:
1.5% of the set value or 0.002 Un
Phase angle: 2
Start time1)2)
IFault = 2.0 set Start value
Minimum
Typical
Maximum
39 ms
43 ms
47 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
2)
3)
ABB
Measurement mode and Pol quantity = default, current before fault = 0.0 In, voltage before fault = 1.0 Un, fn = 50 Hz, fault current in one phase with nominal frequency injected from
random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
29
1MRS757846 E
Function
Value (Range)
Step
Start value
DPHLPDOC
0.05...5.00 In
0.01
DPHHPDOC
0.10...40.00 In
0.01
DPHxPDOC
0.05...15.00
0.01
DPHxPDOC
40...200000 ms
10
DPHLPDOC
DPHHPDOC
Directional mode
DPHxPDOC
1 = Non-directional
2 = Forward
3 = Reverse
Characteristic angle
DPHxPDOC
-179...180
Time multiplier
Operate delay time
Operating curve
1)
type1)
Value
Operation accuracy
EFHPTOC
and
EFIPTOC
Typical
Maximum
16 ms
11 ms
19 ms
12 ms
23 ms
14 ms
23 ms
26 ms
29 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
1)
2)
3)
30
Measurement mode = default (depends on stage), current before fault = 0.0 In, fn = 50 Hz, earth-fault current with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
ABB
1MRS757846 E
Function
Value (Range)
Step
Start value
EFLPTOC
0.010...5.000 In
0.005
EFHPTOC
0.10...40.00 In
0.01
EFIPTOC
1.00...40.00 In
0.01
EFLPTOC
0.05...15.00
0.01
EFHPTOC
0.05...15.00
0.01
EFLPTOC
40...200000 ms
10
EFHPTOC
40...200000 ms
10
EFIPTOC
20...200000 ms
10
EFLPTOC
EFHPTOC
EFIPTOC
Definite time
Time multiplier
1)
ABB
31
1MRS757846 E
Value
Operation accuracy
Current:
1.5% of the set value or 0.002 In
Voltage
1.5% of the set value or 0.002 Un
Phase angle:
2
DEFHPDEF
Current:
1.5% of the set value or 0.002 In
(at currents in the range of 0.110 In)
5.0% of the set value
(at currents in the range of 1040 In)
Voltage:
1.5% of the set value or 0.002 Un
Phase angle:
2
Minimum
Typical
Maximum
42 ms
46 ms
49 ms
58 ms
62 ms
66 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<30 ms
Suppression of harmonics
RMS: No suppression
DFT: -50 dB at f = n fn, where n = 2, 3, 4, 5,
Peak-to-Peak: No suppression
1)
2)
3)
32
Set Operate delay time = 0.06 s, Operate curve type = IEC definite time, Measurement mode = default (depends on stage), current before fault = 0.0 In , fn = 50 Hz, earth-fault current with
nominal frequency injected from random phase angle, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
ABB
1MRS757846 E
Function
Value (Range)
Step
Start value
DEFLPDEF
0.010...5.000 In
0.005
DEFHPDEF
0.10...40.00 In
0.01
Directional mode
DEFxPDEF
1 = Non-directional
2 = Forward
3 = Reverse
Time multiplier
DEFLPDEF
0.05...15.00
0.01
DEFHPDEF
0.05...15.00
0.01
DEFLPDEF
60...200000 ms
10
DEFHPDEF
40...200000 ms
10
DEFLPDEF
DEFHPDEF
DEFxPDEF
1 = Phase angle
2 = IoSin
3 = IoCos
4 = Phase angle 80
5 = Phase angle 88
Operation mode
1)
Value
Operation accuracy
Minimum
Typical
Maximum
23 ms
15 ms
26 ms
18 ms
28 ms
20 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
2)
3)
ABB
Negative sequence current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 2.5 In, Start value multiples in range of 1.5...20
33
1MRS757846 E
Function
Value (Range)
Step
Start value
NSPTOC
0.01...5.00 In
0.01
Time multiplier
NSPTOC
0.05...15.00
0.01
NSPTOC
40...200000 ms
10
NSPTOC
1)
Value
Operation accuracy
Start time1)2)
UFault = 2 set Start value
Minimum
Typical
Maximum
48 ms
51 ms
54 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
2)
Residual voltage before fault = 0.0 Un , fn = 50 Hz, residual voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
Includes the delay of the signal output contact
Function
Value (Range)
Step
Start value
ROVPTOV
0.010...1.000 Un
0.001
ROVPTOV
40...300000 ms
34
ABB
1MRS757846 E
Value
Operation accuracy
Start time1)2)
UFault = 0.9 set Start value
Minimum
Typical
Maximum
62 ms
66 ms
70 ms
Reset time
Typically 40 ms
Reset ratio
Retardation time
<35 ms
Suppression of harmonics
1)
2)
3)
Start value = 1.0 Un, Voltage before fault = 1.1 Un, fn = 50 Hz, undervoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
Includes the delay of the signal output contact
Minimum Start value = 0.50, Start value multiples in range of 0.90...0.20
Function
Value (Range)
Step
Start value
PHPTUV
0.05...1.20 Un
0.01
Time multiplier
PHPTUV
0.05...15.00
0.01
PHPTUV
60...300000 ms
10
PHPTUV
1)
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set Start value
Minimum
Typical
Maximum
23 ms
27 ms
31 ms
Reset time
Typically 40 ms
Reset ratio
Retardation time
<35 ms
Suppression of harmonics
1)
2)
3)
ABB
Start value = 1.0 Un, Voltage before fault = 0.9 Un, fn = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
Includes the delay of the signal output contact
Maximum Start value = 1.20 Un, Start value multiples in range of 1.10...2.00
35
1MRS757846 E
Function
Value (Range)
Step
Start value
PHPTOV
0.05...1.60 Un
0.01
Time multiplier
PHPTOV
0.05...15.00
0.01
PHPTOV
40...300000 ms
10
PHPTOV
1)
Value
Operation accuracy
Start time1)2)
UFault = 0.99 set Start value
UFault = 0.9 set Start value
Minimum
Typical
Maximum
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time
Typically 40 ms
Reset ratio
Retardation time
<35 ms
Suppression of harmonics
1)
2)
Start value = 1.0 Un, positive-sequence voltage before fault = 1.1 Un, fn = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Function
Value (Range)
Step
Start value
PSPTUV
0.010...1.200 Un
0.001
PSPTUV
40...120000 ms
10
PSPTUV
0.01...1.00 Un
0.01
36
ABB
1MRS757846 E
Value
Operation accuracy
Start time1)2)
UFault = 1.1 set Start value
Minimum
Typical
Maximum
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
2)
Negative-sequence voltage before fault = 0.0 Un, fn = 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
Includes the delay of the signal output contact
Function
Value (Range)
Step
Start value
NSPTOV
0.010...1.000 Un
0.001
NSPTOV
40...120000 ms
Start time
Value
f>/f<
5 mHz
df/dt
f>/f<
<80 ms
df/dt
<120 ms
Reset time
<150 ms
ABB
37
1MRS757846 E
Function
Value (Range)
Step
Operation mode
FRPFRQ
1 = Freq<
2 = Freq>
3 = df/dt
4 = Freq< + df/dt
5 = Freq> + df/dt
6 = Freq< OR df/dt
7 = Freq> OR df/dt
FRPFRQ
0.9000...1.2000 fn
0.0001
FRPFRQ
0.8000...1.1000 fn
0.0001
FRPFRQ
-0.2000...0.2000 fn/s
0.0025
Operate Tm Freq
FRPFRQ
80...200000 ms
10
Operate Tm df/dt
FRPFRQ
120...200000 ms
10
Value
Operation accuracy
Frequency change
Voltage change
Reset time
<60 ms
Reset ratio
Typically 0.96
Retardation time
<45 ms
1)
2)
Function
Value (Range)
Step
Start value
OEPVPH
100...200%
OEPVPH
Time multiplier
OEPVPH
0.1...100.0
0.1
OEPVPH
200...200000 ms
10
Cooling time
OEPVPH
5...10000 s
38
ABB
1MRS757846 E
Table 53. Three-phase thermal overload protection, two time constants (T2PTTR)
Characteristic
Value
Operation accuracy
Table 54. Three-phase thermal overload protection, two time constants (T2PTTR) main settings
Parameter
Function
Value (Range)
Step
Temperature rise
T2PTTR
0.0...200.0C
0.1
Max temperature
T2PTTR
0.0...200.0C
0.1
Operate temperature
T2PTTR
80.0...120.0%
0.1
T2PTTR
6...60000 s
Weighting factor p
T2PTTR
0.00...1.00
0.01
Current reference
T2PTTR
0.05...4.00 In
0.01
Operation
T2PTTR
1 = on
5 = off
Value
Operation accuracy
Start time
Typically <55 ms
Reset time
<40 ms
Reset ratio
Typically 1.04
Retardation time
<35 ms
Function
Value (Range)
Step
PHPTUC
0.00...0.50 In
0.01
Start value
PHPTUC
0.01...1.00 In
0.01
PHPTUC
50...200000 ms
10
ABB
39
1MRS757846 E
Table 57. Stabilized and instantaneous differential protection for two-winding transformers (TR2PTDF)
Characteristic
Value
Operation accuracy
Start time1)2)
Low stage
High stage
Minimum
Typical
Maximum
36 ms
21 ms
41 ms
22 ms
46 ms
24 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Suppression of harmonics
1)
2)
Current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
Includes the delay of the output contact. When differential current = 2 set operate value and f n = 50 Hz.
Table 58. Stabilized differential protection for two-winding transformers (TR2PTDF) main settings
Parameter
Function
Value (Range)
Step
TR2PTDF
500...3000 %Ir
10
TR2PTDF
5...50 %Ir
Slope section 2
TR2PTDF
10...50%
End section 2
TR2PTDF
100...500 %Ir
Restraint mode
TR2PTDF
5 = Waveform
6 = 2.h + waveform
8 = 5.h + waveform
9 = 2.h + 5.h + wav
TR2PTDF
7...20%
TR2PTDF
10...50%
Operation
TR2PTDF
1 = on
5 = off
Winding 1 type
TR2PTDF
1=Y
2 = YN
3=D
4=Z
5 = ZN
Winding 2 type
TR2PTDF
1=y
2 = yn
3=d
4=z
5 = zn
Zro A elimination
TR2PTDF
1 = Not eliminated
2 = Winding 1
3 = Winding 2
4 = Winding 1 and 2
40
ABB
1MRS757846 E
Value
Operation accuracy
Start time1)2)
IFault = 2.0 set Operate value
Minimum
Typical
Maximum
37 ms
41 ms
45 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
Suppression of harmonics
1)
2)
Current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
Table 60. Numerical stabilized low-impedance restricted earth-fault protection (LREFPNDF) main settings
Parameter
Function
Value (Range)
Step
Operate value
LREFPNDF
5...50 %In
LREFPNDF
40...300000 ms
Restraint mode
LREFPNDF
1 = None
2 = Harmonic2
LREFPNDF
10...50%
Operation
LREFPNDF
1 = on
5 = off
Value
Operation accuracy
Start time1)2)
IFault = 2.0 set Operate value
Minimum
Typical
Maximum
16 ms
11 ms
21 ms
13 ms
23 ms
14 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
<35 ms
1)
2)
ABB
Current before fault = 0.0, fn = 50 Hz, results based on statistical distribution of 1000 measurements
Includes the delay of the signal output contact
41
1MRS757846 E
Table 62. High-impedance based restricted earth-fault protection (HREFPDIF) main settings
Parameter
Function
Value (Range)
Step
Operate value
HREFPDIF
1.0...50.0%In
0.1
HREFPDIF
40...300000 ms
Operation
HREFPDIF
1 = on
5 = off
Value
Operation accuracy
Reset time1)
Typically 40 ms
Retardation time
<20 ms
1)
Function
Value (Range)
Step
Current value
CCBRBRF
0.05...2.00 In
0.01
CCBRBRF
0.05...2.00 In
0.01
CB failure mode
CCBRBRF
1 = Current
2 = Breaker status
3 = Both
CCBRBRF
1 = Off
2 = Without check
3 = Current check
Retrip time
CCBRBRF
0...60000 ms
10
CB failure delay
CCBRBRF
0...60000 ms
10
CB fault delay
CCBRBRF
0...60000 ms
10
Value
Operation accuracy
At the frequency f = fn
Current measurement:
1.5% of the set value or 0.002 In
Ratio I2f/I1f measurement:
5.0% of the set value
Reset time
+35 ms / -0 ms
Reset ratio
Typically 0.96
+35 ms / -0 ms
42
ABB
1MRS757846 E
Function
Value (Range)
Step
Start value
INRPHAR
5...100%
INRPHAR
20...60000 ms
Value
Operation accuracy
Operate time
Minimum
Typical
Maximum
9 ms3)
12 ms3)
15 ms3)
4 ms4)
6 ms4)
9 ms4)
9 ms3)
10 ms3)
12 ms3)
ms4)
7 ms4)
4
Reset time
ms4)
Typically 40 ms3)
<55 ms4)
Reset ratio
1)
2)
3)
4)
Typically 0.96
Phase start value = 1.0 In, current before fault = 2.0 set Phase start value, fn = 50 Hz, fault with nominal frequency, results based on statistical distribution of 200 measurements
Includes the delay of the heavy-duty output contact
Normal power output
High-speed output
Function
Value (Range)
Step
ARCSARC
0.50...40.00 In
0.01
ARCSARC
0.05...8.00 In
0.01
Operation mode
ARCSARC
1 = Light+current
2 = Light only
3 = BI controlled
Start time
Value
f<
10 mHz
df/dt
f<
<80 ms
df/dt
<120 ms
Reset time
<150 ms
ABB
43
1MRS757846 E
Function
Value (Range)
Step
LSHDPFRQ
1 = Freq<
6 = Freq< OR df/dt
8 = Freq< AND df/dt
Restore mode
LSHDPFRQ
1 = Disabled
2 = Auto
3 = Manual
LSHDPFRQ
0.800...1.200 fn
0.001
LSHDPFRQ
-0.200...-0.005 fn
0.005
Operate Tm Freq
LSHDPFRQ
80...200000 ms
10
Operate Tm df/dt
LSHDPFRQ
120...200000 ms
10
LSHDPFRQ
0.800...1.200 fn
0.001
LSHDPFRQ
80...200000 ms
10
Value
Operation accuracy
Function
Value (Range)
Step
Start value
MAPGAPC
-10000.0...10000.0
0.1
MAPGAPC
0...200000 ms
100
Operation mode
MAPGAPC
1 = Over
2 = Under
Value
Operation accuracy
Suppression of harmonics
Function
Value (Range)
Step
CVPSOF
0...60000 ms
10
44
ABB
1MRS757846 E
Value
Operation accuracy 1)
Start time2)3)
Typically 45 ms
Reset time
Typically 30 ms
Reset ratio
Typically 1.04
Suppression of harmonics
1)
2)
3)
Function
Value (Range)
Step
Start value
DUPPDPR
0.01...2.00 Sn
0.01
DUPPDPR
40...300000 ms
10
Pol reversal
DUPPDPR
0 = False
1 = True
Disable time
DUPPDPR
0...60000 ms
1000
Value
1)
Start time2)3)
Typically 45 ms
Reset time
Typically 30 ms
Reset ratio
Typically 0.94
Suppression of harmonics
1)
2)
3)
ABB
45
1MRS757846 E
Function
Value (Range)
Step
Start value
DOPPDPR
0.01...2.00 Sn
0.01
DOPPDPR
40...300000
10
Directional mode
DOPPDPR
2 = Forward
3 = Reverse
Power angle
DOPPDPR
-90...90
Value (Range)
46
ABB
1MRS757846 E
Control functions
Table 80. Synchronism and energizing check (SECRSYN)
Characteristic
Value
Operation accuracy
Reset time
<50 ms
Reset ratio
Typically 0.96
Function
Value (Range)
Step
SECRSYN
-1 = Off
1 = Both Dead
2 = Live L, Dead B
3 = Dead L, Live B
4 = Dead Bus, L Any
5 = Dead L, Bus Any
6 = One Live, Dead
7 = Not Both Live
Difference voltage
SECRSYN
0.01...0.50 Un
0.01
Difference frequency
SECRSYN
0.001...0.100 fn
0.001
Difference angle
SECRSYN
5...90
Synchrocheck mode
SECRSYN
1 = Off
2 = Synchronous
3 = Asynchronous
SECRSYN
0.1...0.8 Un
0.1
SECRSYN
0.2...1.0 Un
0.1
Close pulse
SECRSYN
200...60000 ms
10
Max energizing V
SECRSYN
0.50...1.15 Un
0.01
Control mode
SECRSYN
1 = Continuous
2 = Command
Phase shift
SECRSYN
-180...180
SECRSYN
0...60000 ms
10
SECRSYN
100...6000000 ms
10
Energizing time
SECRSYN
100...60000 ms
10
Closing time of CB
SECRSYN
40...250 ms
10
Value
Typical 100 ms
ABB
47
1MRS757846 E
Value
Operation accuracy1)
1)
2)
48
ABB
1MRS757846 E
Table 84. Tap changer control with voltage regulator (OLATCC) main settings
Parameter
Function
Value (Range)
Step
OLATCC
2 = Auto master
3 = Auto follower
5 = NRP
7 = MCC
OLATCC
0.000...2.000 Un
0.001
OLATCC
0.0...25.0%
0.1
OLATCC
0.0...25.0%
0.1
Stability factor
OLATCC
0.0...70.0%
0.1
OLATCC
-89...89
OLATCC
1000...300000 ms
100
OLATCC
1000...300000 ms
100
Operation mode
OLATCC
1 = Manual
2 = Auto single
3 = Auto parallel
4 = Input control
5 = Command
OLATCC
1 = Custom disabled
2 = OC
3 = UV
4 = OC, UV
5 = EXT
6 = OC, EXT
7 = UV, EXT
8 = OC, UV, EXT
Delay characteristics
OLATCC
0 = Inverse time
1 = Definite time
OLATCC
1.20...18.00 %Un
0.01
OLATCC
0.10...5.00 In
0.01
OLATCC
0.10...1.20 Un
0.01
Runback raise V
OLATCC
0.80...2.40 In
0.01
OLATCC
0.10...5.00 In
0.01
LDC limit
OLATCC
0.00...2.00 Un
0.01
OLATCC
-36...36
OLATCC
-36...36
OLATCC
500...10000 ms
100
LDC enable
OLATCC
0 = False
1 = True
OLATTC
6...20 s
ABB
49
1MRS757846 E
Value
1.5% or 0.002 In
(at currents in the range of 0.110 In)
5.0%
(at currents in the range of 1040 In)
+10 ms / -0 ms
Value
Operate time 1)
<30 ms
1)
Function
Value (Range)
Step
Start value
CCSPVC
0.05...0.20 In
0.01
CCSPVC
1.00...5.00 In
0.01
Value
<30 ms
time1)
Table 89. Advanced current circuit supervision for transformers (CTSRCTF) main settings
Parameter
Function
Value (Range)
Step
CTSRCTF
0.01...0.50 In
0.01
CTSRCTF
1.00...5.00 In
0.01
CTSRCTF
0.01...1.00 In
0.01
Value
NPS function
50
<33 ms
<18 ms
<30 ms
<24 ms
Lev
Delta function
1)
Includes the delay of the signal output contact, fn = 50 Hz, fault voltage with nominal frequency injected from random phase angle, results based on statistical distribution of 1000
measurements
ABB
1MRS757846 E
Value
0.5%
1)
ABB
51
1MRS757846 E
Measurement functions
Table 92. Three-phase current measurement (CMMXU)
Characteristic
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
52
ABB
1MRS757846 E
Value
Operation accuracy
Suppression of harmonics
Value
Operation accuracy
Suppression of harmonics
Value
At all three currents in range 0.101.20 In
At all three voltages in range 0.501.15 Un
At the frequency fn 1 Hz
1.5% for apparent power S
1.5% for active power P and active energy1)
1.5% for reactive power Q and reactive energy2)
0.015 for power factor
Suppression of harmonics
1)
2)
Value
Operation accuracy
10 mHz
(in measurement range 35...75 Hz)
ABB
53
1MRS757846 E
Value
Operation accuracy
Reset ratio
Function
Value (Range)
Step
PHQVVR
10.0...100.0%
0.1
PHQVVR
10.0...100.0%
0.1
PHQVVR
10.0...100.0%
0.1
PHQVVR
100.0...140.0%
0.1
PHQVVR
100.0...140.0%
0.1
PHQVVR
100.0...140.0%
0.1
PHQVVR
0.0...100.0%
0.1
PHQVVR
100...3600000 ms
100
Value
Operation accuracy
Reset ratio
Typically 0.96
Function
Value (Range)
Step
Operation
VSQVUB
1 = on
5 = off
VSQVUB
1 = Neg Seq
2 = Zero Seq
3 = Neg to Pos Seq
4 = Zero to Pos Seq
5 = Ph vectors Comp
54
ABB
1MRS757846 E
Other functions
Table 105. Pulse timer (PTGAPC)
Characteristic
Value
Value
Value
ABB
55
1MRS757846 E
56
GUID-7A40E6B7-F3B0-46CE-8EF1-AAAC3396347F V1 EN
Figure 8.
Flush mounting
Semi-flush mounting
Rack mounting
Wall mounting
Mounting to a 19" equipment frame
Mounting with a RTXP 24 test switch to a 19" rack
ABB
1MRS757846 E
.6
482
280
246
246
160
177
177
160
160
262
177
,2
246
")
(19
103
153
153
98
48
48
GUID-89F4B43A-BC25-4891-8865-9A7FEDBB84B9 V1 EN
GUID-1DF19886-E345-4B02-926C-4F8757A0AC3E V1 EN
GUID-D83E2F4A-9D9B-4400-A2DC-AFF08F0A2FCA V1 EN
Figure 9.
Figure 10.
Figure 11.
Flush mounting
Semi-flush mounting
Rack mounting
259
186
318
GUID-65A893DF-D304-41C7-9F65-DD33239174E5 V1 EN
Figure 12.
Wall mounting
ABB
57
1MRS757846 E
Description
IED
Standard
IEC
CN
Main application
Functional application
7-8
AA
Optional board
Optional I/Os 8BI+ 4BO
AA
AB
AC
No optional board
NN
GUID-87D41197-0C6A-407B-9ED4-F27D96CDB2D5 V2 EN
58
ABB
1MRS757846 E
NBTNAANNABC1BNN11G
9
10
Communication (Serial/Ethernet)
(1xLC)
(1xRJ45)
AA
AB
AN
BB
BC
BD
BE
BF
BG
BH
BN
CB
CN
NA
NB
NC
ND
NE
IEC61850-9-2LE
NF
NG
NH
No communication module
NN
ABB
59
1MRS757846 E
NBTNAANNABC1BNN11G
#
Description
11
Communication protocols
12
13
14
15
16
17
18
Language
English
Front panel
Large LCD with Single Line Diagram - IEC
Option 1
Arc protection (requires a communication module, cannot be
combined with com. module options BB, BN, CB and CN)
None
Option 2
Automatic voltage regulator
None
Power supply
Power supply 48-250 VDC, 100-240 VAC
Reserved
Product version 2.0 FP1
1G
GUID-8371B9C1-556F-46E4-8171-D6D3FF06ED29 V3 EN
Example code: N B T N A A N N A B C 1 B N N 1 1 G
Your ordering code:
Digit (#)
10 11 12 13 14 15 16 17 18
Code
GUID-4A128E8F-8129-4411-B56A-38A279E6C946 V2 EN
Figure 13.
60
ABB
1MRS757846 E
Order number
1MRS120534-1.5
1MRS120534-3.0
1MRS120534-5.0
Order number
2RCA030573A0001
2RCA030894A0001
2RCA031135A0001
19 rack mounting kit for one relay and one RTXP24 test switch (the test switch and wire harness are not
included in the delivery)
2RCA032818A0001
Mounting bracket for one relay with test switch RTXP in 4U Combiflex (RHGT 19 variant C) (the test switch,
wire harness and Combiflex RGHT 19" variant C are not included in the delivery)
2RCA032826A0001
2RCA036978A00011)
1)
Cannot be used when the IED is mounted with the Combiflex 19" equipment frame (2RCA032826A0001).
26. Tools
The protection relay is delivered as a pre-configured unit
including the example configuration. The default parameter
setting values can be changed from the front-panel user
interface, the Web browser-based user interface (Web HMI) or
the PCM600 tool in combination with the relay-specific
connectivity package.
The Protection and Control IED Manager PCM600 offers
extensive relay configuration functions such as relay signal
configuration, application configuration, graphical display
configuration including single line diagram configuration, and
IEC 61850 communication configuration including horizontal
GOOSE communication.
When the Web browser-based user interface is used, the
protection relay can be accessed either locally or remotely
Version
PCM600
2.1 or later
ABB
61
1MRS757846 E
Web HMI
PCM600
Signal monitoring
Application configuration
Event viewing
Online monitoring
= Supported
62
and Web HMI use TLS encryption with a minimum of 128 bit key
length protecting the data in transit. In this case the used
communication protocols are FTPS and HTTPS. All rear
communication ports and optional protocol services can be
deactivated according to the required system setup.
ABB
1MRS757846 E
n
Positive
Current
Direction
RET620
a
da
P1
P2
dn
S1
S2
Uab
HV
X120
X100
60 210V
2
3
N
60 210V
4
5
6
7
N
60 210V
8
9
N
1/5A
10
11
N
1/5A
12
13
N
1/5A
14
U1
Uaux
-
U2
IRF
U3
N
1/5A
IL1
2)
P2 S2
P1 S1
LV
P2
P1
S2
2
3
4
5
PO1
6
7
IL2
PO2
IL3
8
9
10
Io
SO1
P2 S2
P1 S1
11
12
13
X115
1
60 210V
2
3
N
60 210V
4
5
6
7
N
60 210V
8
9
N
1/5A
10
11
N
1/5A
12
13
N
1/5A
14
SO2
U_SYN
PO3
U_AVR
Uo
N
1/5A
IL1B
2)
TCS1
PO4
IL2B
TCS2
IL3B
14
16
17
15
19
18
20
22
21
23
24
IoB
X105
S1
X110
1
2
3
SO1
16
15
17
BI 2
4
5
6
SO2
BI 3
BI 4
L1
L2
L3
14
BI 1
8
9
SO3
22
21
23
BI 5
SO4
24
BI 6
10
11
12
BI 7
BI 8
13
X130
1
2
3
4
5
6
7
8
19
18
20
X130
mA
mA 1
SO1
10
11
12
RTD 1
SO2
RTD 1 GND
13
14
RTD 2
RTD 2 GND
SO3
16
17
X13
Light sensor input 1
X14
Light sensor input 2
X15
Light sensor input 3
1)
1)
1)
Figure 14.
ABB
63
1MRS757846 E
BIO0005 module
X105/
X110
X105/
X110
1
2
BI 1
3
4
BI 2
5
6
BI 3
14
SO1
16
15
17
SO2
BI 4
7
8
9
19
18
20
SO3
22
21
23
BI 5
SO4
BI 6
10
11
12
24
BI 7
BI 8
13
GUID-5298DCA3-4597-44C2-850A-889384DF423B V2 EN
Figure 15.
BIO0007 module
X105
X105
BI 1
HSO1
15
16
BI 2
HSO2
BI 3
4
5
19
20
BI 4
HSO3
BI 5
23
24
BI 6
BI 7
9
10
BI 8
GUID-D019E095-29EF-41B1-BDF4-D9D427201B88 V2 EN
Figure 16.
RTD003 module
X105/
X110
5
6
mA
7
8
9
10
11
mA
mA 2
RTD 1
RTD 2
12
13
14
15
16
mA 1
RTD 3
Common RTD GND
Common RTD GND
17
18
19
20
21
22
RTD 4
RTD 5
RTD 6
GUID-987D427B-C5F7-4073-8D5F-D0C37BEAF5E5 V2 EN
Figure 17.
64
ABB
29. Certificates
DNV GL has issued an IEC 61850 Edition 2 Certificate Level A1
for Relion 620 series. Certificate number: 74108008-OPE/INC
15-2319.
DNV GL has issued an IEC 61850 Edition 1 Certificate Level A1
for Relion 620 series. Certificate number: 74108008-OPE/INC
15-2323.
1MRS757846 E
30. References
The www.abb.com/substationautomation portal provides
information on the entire range of distribution automation
products and services.
The latest relevant information on the RET620 protection and
control relay is found on the product page. Scroll down the
page to find and download the related documentation.
ABB
65
1MRS757846 E
IEC 61850
IEC 60617
ANSI
PHLPTOC1
3I> (1)
51P-1 (1)
PHLPTOC2
3I> (2)
51P-1 (2)
PHHPTOC1
3I>> (1)
51P-2 (1)
PHHPTOC2
3I>> (2)
51P-2 (2)
PHIPTOC1
3I>>> (1)
50P/51P (1)
PHIPTOC2
3I>>> (2)
50P/51P (2)
DPHLPDOC1
67-1 (1)
DPHHPDOC1
67-2 (1)
EFLPTOC1
Io> (1)
51N-1 (1)
EFLPTOC2
Io> (2)
51N-1 (2)
EFHPTOC1
Io>> (1)
51N-2 (1)
EFHPTOC2
Io>> (2)
51N-2 (2)
DEFLPDEF1
67N-1 (1)
DEFLPDEF2
67N-1 (2)
DEFHPDEF1
67N-2 (1)
NSPTOC1
I2> (1)
46 (1)
NSPTOC2
I2> (2)
46 (2)
ROVPTOV1
Uo> (1)
59G (1)
ROVPTOV2
Uo> (2)
59G (2)
ROVPTOV3
Uo> (3)
59G (3)
PHPTUV1
3U< (1)
27 (1)
PHPTUV2
3U< (2)
27 (2)
PHPTUV3
3U< (3)
27 (3)
PHPTUV4
3U< (4)
27 (4)
PHPTOV1
3U> (1)
59 (1)
PHPTOV2
3U> (2)
59 (2)
PHPTOV3
3U> (3)
59 (3)
PSPTUV1
U1< (1)
47U+ (1)
PSPTUV2
U1< (2)
47U+ (2)
NSPTOV1
U2> (1)
47O- (1)
NSPTOV2
U2> (2)
47O- (2)
FRPFRQ1
f>/f<,df/dt (1)
81 (1)
FRPFRQ2
f>/f<,df/dt (2)
81 (2)
FRPFRQ3
f>/f<,df/dt (3)
81 (3)
Protection
Frequency protection
66
ABB
1MRS757846 E
IEC 61850
IEC 60617
ANSI
Overexcitation protection
OEPVPH1
U/f> (1)
24 (1)
OEPVPH2
U/f> (2)
24 (2)
T2PTTR1
3Ith>T/G/C (1)
49T/G/C (1)
PHPTUC1
3I< (1)
37 (1)
PHPTUC2
3I< (2)
37 (2)
TR2PTDF1
3dI>T (1)
87T (1)
LREFPNDF1
dIoLo> (1)
87NL (1)
LREFPNDF2
dIoLo> (2)
87NL (2)
HREFPDIF1
dIoHi> (1)
87NH (1)
HREFPDIF2
dIoHi> (2)
87NH (2)
CCBRBRF1
3I>/Io>BF (1)
51BF/51NBF (1)
CCBRBRF2
3I>/Io>BF (2)
51BF/51NBF (2)
CCBRBRF3
3I>/Io>BF (3)
51BF/51NBF (3)
INRPHAR1
3I2f> (1)
68 (1)
Master trip
TRPPTRC1
94/86 (1)
TRPPTRC2
94/86 (2)
TRPPTRC3
94/86 (3)
TRPPTRC4
94/86 (4)
ARCSARC1
ARC (1)
50L/50NL (1)
ARCSARC2
ARC (2)
50L/50NL (2)
ARCSARC3
ARC (3)
50L/50NL (3)
LSHDPFRQ1
UFLS/R (1)
81LSH (1)
LSHDPFRQ2
UFLS/R (2)
81LSH (2)
LSHDPFRQ3
UFLS/R (3)
81LSH (3)
LSHDPFRQ4
UFLS/R (4)
81LSH (4)
LSHDPFRQ5
UFLS/R (5)
81LSH (5)
LSHDPFRQ6
UFLS/R (6)
81LSH (6)
Arc protection
ABB
67
1MRS757846 E
IEC 61850
IEC 60617
ANSI
Multipurpose protection
MAPGAPC1
MAP (1)
MAP (1)
MAPGAPC2
MAP (2)
MAP (2)
MAPGAPC3
MAP (3)
MAP (3)
MAPGAPC4
MAP (4)
MAP (4)
MAPGAPC5
MAP (5)
MAP (5)
MAPGAPC6
MAP (6)
MAP (6)
MAPGAPC7
MAP (7)
MAP (7)
MAPGAPC8
MAP (8)
MAP (8)
MAPGAPC9
MAP (9)
MAP (9)
MAPGAPC10
MAP (10)
MAP (10)
MAPGAPC11
MAP (11)
MAP (11)
MAPGAPC12
MAP (12)
MAP (12)
MAPGAPC13
MAP (13)
MAP (13)
MAPGAPC14
MAP (14)
MAP (14)
MAPGAPC15
MAP (15)
MAP (15)
MAPGAPC16
MAP (16)
MAP (16)
MAPGAPC17
MAP (17)
MAP (17)
MAPGAPC18
MAP (18)
MAP (18)
CVPSOF1
CVPSOF (1)
SOFT/21/50 (1)
Underpower protection
DUPPDPR1
P< (1)
32U (1)
DUPPDPR2
P< (2)
32U (2)
DOPPDPR1
P>/Q> (1)
32R/32O (1)
DOPPDPR2
P>/Q> (2)
32R/32O (2)
DOPPDPR3
P>/Q> (3)
32R/32O (3)
CBXCBR1
I <-> O CB (1)
I <-> O CB (1)
CBXCBR2
I <-> O CB (2)
I <-> O CB (2)
CBXCBR3
I <-> O CB (3)
I <-> O CB (3)
DCXSWI1
DCXSWI2
DCXSWI3
DCXSWI4
ESXSWI1
ESXSWI2
ESXSWI3
Control
Circuit-breaker control
Disconnector control
68
ABB
1MRS757846 E
IEC 61850
IEC 60617
ANSI
DCSXSWI1
I <-> O DC (1)
I <-> O DC (1)
DCSXSWI2
I <-> O DC (2)
I <-> O DC (2)
DCSXSWI3
I <-> O DC (3)
I <-> O DC (3)
DCSXSWI4
I <-> O DC (4)
I <-> O DC (4)
ESSXSWI1
I <-> O ES (1)
I <-> O ES (1)
ESSXSWI2
I <-> O ES (2)
I <-> O ES (2)
ESSXSWI3
I <-> O ES (3)
I <-> O ES (3)
SECRSYN1
SYNC (1)
25 (1)
TPOSYLTC1
TPOSM (1)
84M (1)
OLATCC1
COLTC (1)
90V (1)
SSCBR1
CBCM (1)
CBCM (1)
SSCBR2
CBCM (2)
CBCM (2)
SSCBR3
CBCM (3)
CBCM (3)
TCSSCBR1
TCS (1)
TCM (1)
TCSSCBR2
TCS (2)
TCM (2)
CCSPVC1
MCS 3I (1)
MCS 3I (1)
CCSPVC2
MCS 3I (2)
MCS 3I (2)
CTSRCTF1
SEQSPVC1
FUSEF (1)
60 (1)
MDSOPT1
OPTS (1)
OPTM (1)
MDSOPT2
OPTS (2)
OPTM (2)
CMMXU1
3I (1)
3I (1)
CMMXU2
3I (2)
3I (2)
CSMSQI1
CSMSQI2
RESCMMXU1
Io (1)
In (1)
RESCMMXU2
Io (2)
In (2)
VMMXU1
3U (1)
3V (1)
VAMMXU2
U_A (2)
V_A (2)
VAMMXU3
U_A (3)
V_A (3)
RESVMMXU1
Uo (1)
Vn (1)
VSMSQI1
PEMMXU1
P, E (1)
P, E (1)
LDPRLRC1
LOADPROF (1)
LOADPROF (1)
Frequency measurement
FMMXU1
f (1)
f (1)
Measurement
Three-phase current measurement
Power quality
ABB
69
1MRS757846 E
IEC 61850
IEC 60617
ANSI
CMHAI1
PQM3I (1)
PQM3I (1)
VMHAI1
PQM3U (1)
PQM3V (1)
Voltage variation
PHQVVR1
PQMU (1)
PQMV (1)
Voltage unbalance
VSQVUB1
PQUUB (1)
PQVUB (1)
TPGAPC1
TP (1)
TP (1)
TPGAPC2
TP (2)
TP (2)
TPGAPC3
TP (3)
TP (3)
TPGAPC4
TP (4)
TP (4)
TPSGAPC1
TPS (1)
TPS (1)
TPSGAPC2
TPS (2)
TPS (2)
TPMGAPC1
TPM (1)
TPM (1)
TPMGAPC2
TPM (2)
TPM (2)
PTGAPC1
PT (1)
PT (1)
PTGAPC2
PT (2)
PT (2)
TOFGAPC1
TOF (1)
TOF (1)
TOFGAPC2
TOF (2)
TOF (2)
TOFGAPC3
TOF (3)
TOF (3)
TOFGAPC4
TOF (4)
TOF (4)
TONGAPC1
TON (1)
TON (1)
TONGAPC2
TON (2)
TON (2)
TONGAPC3
TON (3)
TON (3)
TONGAPC4
TON (4)
TON (4)
SRGAPC1
SR (1)
SR (1)
SRGAPC2
SR (2)
SR (2)
SRGAPC3
SR (3)
SR (3)
SRGAPC4
SR (4)
SR (4)
MVGAPC1
MV (1)
MV (1)
MVGAPC2
MV (2)
MV (2)
MVGAPC3
MV (3)
MV (3)
MVGAPC4
MV (4)
MV (4)
MVI4GAPC1
MVI4 (1)
MVI4 (1)
MVI4GAPC2
MVI4 (2)
MVI4 (2)
MVI4GAPC3
MVI4 (3)
MVI4 (3)
MVI4GAPC4
MVI4 (4)
MVI4 (4)
Other
Minimum pulse timer (2 pcs)
Set-reset (8 pcs)
Move (8 pcs)
70
ABB
1MRS757846 E
IEC 61850
IEC 60617
ANSI
SCA4GAPC1
SCA4 (1)
SCA4 (1)
SCA4GAPC2
SCA4 (2)
SCA4 (2)
SCA4GAPC3
SCA4 (3)
SCA4 (3)
SCA4GAPC4
SCA4 (4)
SCA4 (4)
SPCGAPC1
SPC (1)
SPC (1)
SPCGAPC2
SPC (2)
SPC (2)
SPCGAPC3
SPC (3)
SPC (3)
SPCRGAPC1
SPCR (1)
SPCR (1)
SPCLGAPC1
SPCL (1)
SPCL (1)
UDFCNT1
UDCNT (1)
UDCNT (1)
UDFCNT2
UDCNT (2)
UDCNT (2)
UDFCNT3
UDCNT (3)
UDCNT (3)
UDFCNT4
UDCNT (4)
UDCNT (4)
UDFCNT5
UDCNT (5)
UDCNT (5)
UDFCNT6
UDCNT (6)
UDCNT (6)
UDFCNT7
UDCNT (7)
UDCNT (7)
UDFCNT8
UDCNT (8)
UDCNT (8)
UDFCNT9
UDCNT (9)
UDCNT (9)
UDFCNT10
UDCNT (10)
UDCNT (10)
UDFCNT11
UDCNT (11)
UDCNT (11)
UDFCNT12
UDCNT (12)
UDCNT (12)
FKEYGGIO1
FKEY (1)
FKEY (1)
Disturbance recorder
RDRE1
DR (1)
DFR (1)
Fault recorder
FLTRFRC1
FAULTREC (1)
FAULTREC (1)
SER1
SER (1)
SER (1)
Product version
History
A/2013-05-07
2.0
First release
B/2013-07-01
2.0
Content updated
C/2014-07-01
2.0
Content updated
D/2014-09-11
2.0
Content updated
E/2015-12-11
2.0 FP1
ABB
71
72
ABB Oy
Medium Voltage Products,
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland
Phone
+358 10 22 11