Beruflich Dokumente
Kultur Dokumente
Subscribe
About Us
Magazine Issues
Newsletters
Adv ertise
REGISTER
Shop
LOG IN
Design
Contractor
Safety
Power Quality
T raining
Basics
Products
Tw eet
Recommend 12
Understanding the basic design and operation principles behind VFDs will simplify selection, operation, and
maintenance
Although much has been published on variable-frequency drives (VFDs), people continue
to be confused by them. The intent of this article is to provide a basic overview of these
devices by evaluating key features as well as their impact on a buildings electrical system.
A VFD is used extensively in modern facilities to save energy on mechanical systems,
such as motors, pumps, etc. Selected to match motor curves to ensure speed and loads are
matched, VFDs can help save motor energy by allowing for variable flow of air, water,
etc., based on the demands and needs of a particular site. This is accomplished by
converting the fixed frequency of incoming alternating current (AC) voltage to direct
current (DC) and then reconverting it back to AC voltage by varying the frequency at
which the insulated gate bipolar transistors (IGBTs) are gated on and off.
Shopclues
Basic operation
A VFD operates by converting the input sinusoidal AC voltage to DC voltage and then
back to AC voltage. This conversion occurs by using either silicon-controlled rectifiers
(SCRs) or IGBTs. The DC voltage is switched using IGBTs to create an AC output voltage
(called the inverter). The IGBT can switch on and off to create an AC voltage waveform
that delivers power to the motor. The IGBTs create an AC waveform by using pulse
width-modulated (PWM) switching (click here to see Fig. 1). The frequency at which the
switching occurs, which varies from manufacturer to manufacturer, is called carrier
frequency.
A typical 6-pulse VFD has six diodes as a front-end bridge rectifier that converts AC to
DC. VFDs can also have 12 diodes two sets per phase (2 2 3 = 12 pulse) or 18
diodes three sets per phase (3 2 3 = 18 pulse) and so on (click here to see Table).
One set of diodes is supplied by a Delta-Y transformer to create a phase shift on the AC
side between the two rectifiers to reduce harmonics reflected back to the source.
6-pulse VFD
A 6-pulse VFD develops the output DC voltage by taking each phase of the AC source and
installing one set of diodes to gate on and off (click here to see Fig. 2). A 6-pulse VFD is
most commonly used in the building system. Typical current total harmonic distortion
(THD) back to the source can be as high as 35% at the input terminals of the VFD. Y ou
can install an inline inductor to reduce the reflected harmonics back to the point of
coupling, as defined by IEEE 519. The inductor reduces the current distortion and thus
http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives
Photo Galleries
IDEAL National
Championship
Highlights
IDEAL Electrical hosted its
first-ever national
championship at Disney
Comments
Parallel Transformers
New Topics
1/5
11/24/2016
the voltage distortion at the source. The input line inductors are typically 3% to 5%
impedance. Base the selection of the inductor on harmonic evaluation of the electrical
system at the building, impact of voltage drops across the inductor, and impact of power
factor to the building electrical system.
The impact of harmonics should take into account available fault current (i.e., the
stiffness of the electrical system). See IEEE Standard 519 for more details. However, if
there are significant VFDs and other harmonic-producing devices in a buildings electrical
system, such as electronic ballasts, uninterruptible power supplies, electronic switching
devices, etc., think about using 12- or 18-pulse VFDs to reduce the harmonics reflected
back to the source.
Low-Voltage Transformers
12-pulse VFD
A 12-pulse VFD has phase shift transformers ahead of 6-pulse VFD to cancel the
harmonics reflected back to the source. The phase shift transformers can be tuned to
reduce harmonic distortion to less than 10% at the input terminals of the VFD (click here
to see Fig. 3). The windings of the transformers are offset to cancel the largest harmonics
from the VFD. By reducing the harmonics at the input terminals, the intent is to reduce
voltage distortion at the source because the current THD at each piece of equipment is
reduced. Conduct a harmonic evaluation to validate the findings. Disadvantages in
providing a 12-pulse VFD are the cost (i.e., it can be up to 50% more) and the physical
footprint required. A 6-pulse VFD for a typical 25-hp motor can be installed on the wall
next to the motor. A 12-pulse VFD will be a free-standing switchboard type unit.
18-pulse VFD
EC&M Webinars
NOV 9 , 2 0 1 6
WEBINA R
Technology Enabled
Data Center Life Cycle
Services
NOV 2 , 2 0 1 6
Selection criteria
Before selecting a VFD, evaluate the current THD. A 6-, 12-, 18- or even 24-pulse VFD
should be evaluated to determine the best solution. Harmonics can cause faulty meter
readings, motor bearing failure (due to electrical currents), blown fusing on capacitors,
and/or telephone communication interference. A possible effect of harmonics is
excitement of a system resonance that can significantly raise the voltage and cause
system failures.
The carrier frequency and circuit impedance is a key feature in selection of a VFD to be
aware of in regard to switching speeds and resonance. The manufacturers representation
should ensure that the resonance frequency is skipped during startup of the VFD. The
resonance frequency is a function of the VFD carrier frequency and impedance of the
circuit; therefore, its specific to the site conditions.
The resonance in an electrical system occurs when there are harmonics on the electrical
system and where the inductive/capacitive loads are tuned to specific frequency to
allow for oscillation due to impedance of the circuit. The effects of resonance can be
explained briefly by the basic formula, V = I Z. When current and impedance are
excited to high levels, the voltage increases causing heating on the electrical system.
WEBINA R
There is More to a
Data Center than
White Space; A
Holistic Approach to
Facility Monitoring and Control
VIEW MORE WEBINARS
E C&M TV
IDEAL PowerBlade
Cable Cutters 1
Big enough for any job...
More
In addition to the reflected harmonics back to the source and to the motor, VFD selection
should include voltage rating and system lockout. Keep in mind the nominal voltage of a
VFD with upper and lower limits. Also, evaluate the impact of overvoltage on a VFD.
Some VFDs tend to lock out with overvoltage condition after select restarts. Y ou should
also ensure that single-phase protection includes both time and magnitude components.
How does the motor nominal rating (typically 460V) correlate with nominal voltage of
VFD (typically 480V)? The system utilization voltage should be such that it does not go
beyond the high voltage rating of the motor (causing increased current and prematurely
http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives
2/5
11/24/2016
burning the motor). At the same time, it should not be too low where a sag on the system
voltage, combined with building voltage drop, does not shut down the VFD.
When sizing the input breakers for a VFD, think about when the VFD is in bypass mode.
Is the bypass starter specified as across the line or reduced voltage? Although VFDs are
important in reducing the inrush current to generators, consideration should be given
when a VFD is operated in bypass while on generator.
VFDs have losses, just like other electronic devices that transform voltage. Depending on
type (6-, 12- or 18-pulse) and manufacture of VFD, the losses can be 4% to 10%. These
losses should be taken into consideration in sizing electrical systems and requirements for
ventilation.
In addition to matching the VFD to the motor, consider the environment as well. What
are the derating factors for altitude and temperature? This will vary from manufacturer
to manufacturer. In addition, evaluate the VFD for the seismic rating based on
International Building Code and client requirements. A VFD may be designed to survive a
seismic event, operate after a seismic event, or operate during and after a seismic event.
VFDs have been known to affect the bearing of the motor and cause premature failures.
The ratio of V/T can create parasitic capacitance between the motor stator and the rotor,
which induces a voltage on the rotor shaft. If this voltage, referred to as common mode
voltage, builds up to a sufficient level, it can discharge to ground through the bearings.
High carrier frequency can also contribute to bearing failure. The higher carrier
frequency can cause increased current discharge pulses, but this also means the VFD will
run more quietly.
Recommendations
to be in the hands...
Ensure carrier frequency is less than 6 kHz with adjustable frequency. Ensure the motor
is as close as possible to the VFD to minimize conductor length. If the conductor is longer
than recommended by the manufacturer, consider providing an inductive or RCL filter
(click here to see Fig. 5).
Reduced harmonics should be considered for soft loads (such as at the end of an electric
utility feed in a rural area or when powering loads with on-site generators) to reduce the
voltage THD at the point of common coupling (PCC). High voltage distortion can cause
malfunction of electronic devices.
Ensure the VFD output conductors are sized per manufacturer recommendations, and
consider adding output line reactors. The line reactors should be sized to match the
distance requirements of a VFD that is not located near the motor load.
Sizing of the electrical infrastructure should take into account the VFD losses, voltage
tolerance, and footprint requirements. The electrical system should be sized for both when
the motor is operated in VFD mode and when in bypass (across the line) mode.
Big picture
In addition to cost, consider many other factors when selecting a VFD. The carrier
frequency is critical to reduce impact on the motor bearings and motor life. Install the
output and input inductors to reduce harmonic distortion at the motor and at the PCC for
most applications. If the site has high harmonics on the electrical system, a 12-pulse VFD
would typically be used. To minimize resonance of higher order harmonics, an 18-pulse
VFD may be required.
During site startup and acceptance testing, pay special attention to voltage set points
relative to utility source. The resonance frequency should be skipped during startup and
on-site generation equipment should be tested with the VFD in normal operation mode
and in bypass mode. The bottom line is you should always select VFDs based on careful
evaluation of how they will interface with the electrical system of the building in addition
to the pairing with mechanical motor selection.
United States
http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives
3/5
11/24/2016
Recommend 12
Tw eet
SHARE
Connect With Us
on Ju n 1 7 , 2 0 1 3
we are facing problem that our one driv e which used fro 1 800KW motor is going to
damage we need to find the reason for this cause? As this driv e has no Brakecopps .
Please send any technical informations if y ou hav e and help out us.
Thanks
Log In or Regi st er t o post com m en t s
on Sep 1 0 , 2 0 1 3
Re late d Article s
The Basics of Variable-Frequency Drives
10
Ecmwe b .co m
NEC
Design
Contractor
Safety
Site Fe ature s
EC &M C o rp o rate
Author Guidelines
RSS
Sitem ap
About Us
Site Archiv e
Adv ertise
Subscribe
Contact Us
Fo llo w Us
Power Quality
T raining
Basics
Products
http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives
4/5
11/24/2016
http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives
5/5