The 4-1-1 on Variable-Frequency Drives


Basic design and operation principles behind variable-frequency drives (VFDs)
Rajan Battish, P.E., LEED AP, RTKL | Electrical Construction and Maintenance
SHARE

Tw eet

Recommend 12

May 24, 2011


COMMENTS 2

Understanding the basic design and operation principles behind VFDs will simplify selection, operation, and
maintenance

Although much has been published on variable-frequency drives (VFDs), people continue
to be confused by them. The intent of this article is to provide a basic overview of these
devices by evaluating key features as well as their impact on a buildings electrical system.
A VFD is used extensively in modern facilities to save energy on mechanical systems,
such as motors, pumps, etc. Selected to match motor curves to ensure speed and loads are
matched, VFDs can help save motor energy by allowing for variable flow of air, water,
etc., based on the demands and needs of a particular site. This is accomplished by
converting the fixed frequency of incoming alternating current (AC) voltage to direct
current (DC) and then reconverting it back to AC voltage by varying the frequency at
which the insulated gate bipolar transistors (IGBTs) are gated on and off.

Shopclues

Six-Step Plan for Bending Raceway


Tip of the Week: Are Your People Lazy?
The Top 10 Highest-Paying Cities for Electrical
Engineers: 2015

Basic operation

Technology Needs a Base

A VFD operates by converting the input sinusoidal AC voltage to DC voltage and then
back to AC voltage. This conversion occurs by using either silicon-controlled rectifiers
(SCRs) or IGBTs. The DC voltage is switched using IGBTs to create an AC output voltage
(called the inverter). The IGBT can switch on and off to create an AC voltage waveform
that delivers power to the motor. The IGBTs create an AC waveform by using pulse
width-modulated (PWM) switching (click here to see Fig. 1). The frequency at which the
switching occurs, which varies from manufacturer to manufacturer, is called carrier
frequency.

Do You Run Your Business?

A typical 6-pulse VFD has six diodes as a front-end bridge rectifier that converts AC to
DC. VFDs can also have 12 diodes two sets per phase (2 2 3 = 12 pulse) or 18
diodes three sets per phase (3 2 3 = 18 pulse) and so on (click here to see Table).
One set of diodes is supplied by a Delta-Y transformer to create a phase shift on the AC
side between the two rectifiers to reduce harmonics reflected back to the source.

World on November 11-12

6-pulse VFD

A 6-pulse VFD develops the output DC voltage by taking each phase of the AC source and
installing one set of diodes to gate on and off (click here to see Fig. 2). A 6-pulse VFD is
most commonly used in the building system. Typical current total harmonic distortion
(THD) back to the source can be as high as 35% at the input terminals of the VFD. Y ou
can install an inline inductor to reduce the reflected harmonics back to the point of
coupling, as defined by IEEE 519. The inductor reduces the current distortion and thus
http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives

Photo Galleries
IDEAL National
Championship
Highlights
IDEAL Electrical hosted its
first-ever national
championship at Disney

Jo in the Discussio n o n EC &M T alk


Hot Topics

Comments

Parallel Transformers

New Topics

la st r eply by eddi eh i l l in Power


Di st r i bu t i on

Old Electrical Books

la st r eply by spa r ky 377 in Gen er a l


El ect r i ca l T a l k Di scu ssi on

1/5

11/24/2016

Basic design and operation principles behind variable-frequency drives (VFDs)

the voltage distortion at the source. The input line inductors are typically 3% to 5%
impedance. Base the selection of the inductor on harmonic evaluation of the electrical
system at the building, impact of voltage drops across the inductor, and impact of power
factor to the building electrical system.
The impact of harmonics should take into account available fault current (i.e., the
stiffness of the electrical system). See IEEE Standard 519 for more details. However, if
there are significant VFDs and other harmonic-producing devices in a buildings electrical
system, such as electronic ballasts, uninterruptible power supplies, electronic switching
devices, etc., think about using 12- or 18-pulse VFDs to reduce the harmonics reflected
back to the source.

44kV Overhead Distribution In-line Switch Issue


1

la st r eply by Ji m Doody in Power


Di st r i bu t i on

Low-Voltage Transformers

la st r eply by eddi eh i l l in Li gh t i n g &


Li gh t i n g Con t r ol s

Proper Wire Size and OCPD

la st r eply by A l v i n con des in Gen er a l


El ect r i ca l T a l k Di scu ssi on

12-pulse VFD

A 12-pulse VFD has phase shift transformers ahead of 6-pulse VFD to cancel the
harmonics reflected back to the source. The phase shift transformers can be tuned to
reduce harmonic distortion to less than 10% at the input terminals of the VFD (click here
to see Fig. 3). The windings of the transformers are offset to cancel the largest harmonics
from the VFD. By reducing the harmonics at the input terminals, the intent is to reduce
voltage distortion at the source because the current THD at each piece of equipment is
reduced. Conduct a harmonic evaluation to validate the findings. Disadvantages in
providing a 12-pulse VFD are the cost (i.e., it can be up to 50% more) and the physical
footprint required. A 6-pulse VFD for a typical 25-hp motor can be installed on the wall
next to the motor. A 12-pulse VFD will be a free-standing switchboard type unit.
18-pulse VFD

E C&M White Papers


Five Best Practices to Improve Building
Management Systems (BMS) Cybersecurity
Data breaches and other cyber crime cost companies
billions each year w orldw ide, and the damage to brand
reputation can be incalculable. Since hackers look for
w eakly defended systems to attack, this paper presents
5 cybersecurity best practices to mitigate system
vulnerabilities. Some are commonsense measures like
More
effective passw ord management; others involve securing

VIEW MORE WHITE PAPERS

An 18-pulse VFD provides low harmonic distortion through phased cancellation of


primary harmonics (5th and 7th) and the higher order harmonics that could cause
resonance on capacitive and inductive loads (such as filters, transformer, etc.). Because
cost can be prohibitive for most building applications, only consider this approach for
facilities that have significant harmonics on the electrical system. The THD at the input
terminals can be less than 5%; therefore, lower total voltage harmonic distortion will be
realized at the source (i.e., point of common coupling), depending on the circuit
impedance (click here to see Fig. 4).

EC&M Webinars
NOV 9 , 2 0 1 6
WEBINA R

Technology Enabled
Data Center Life Cycle
Services
NOV 2 , 2 0 1 6

Selection criteria

Before selecting a VFD, evaluate the current THD. A 6-, 12-, 18- or even 24-pulse VFD
should be evaluated to determine the best solution. Harmonics can cause faulty meter
readings, motor bearing failure (due to electrical currents), blown fusing on capacitors,
and/or telephone communication interference. A possible effect of harmonics is
excitement of a system resonance that can significantly raise the voltage and cause
system failures.
The carrier frequency and circuit impedance is a key feature in selection of a VFD to be
aware of in regard to switching speeds and resonance. The manufacturers representation
should ensure that the resonance frequency is skipped during startup of the VFD. The
resonance frequency is a function of the VFD carrier frequency and impedance of the
circuit; therefore, its specific to the site conditions.
The resonance in an electrical system occurs when there are harmonics on the electrical
system and where the inductive/capacitive loads are tuned to specific frequency to
allow for oscillation due to impedance of the circuit. The effects of resonance can be
explained briefly by the basic formula, V = I Z. When current and impedance are
excited to high levels, the voltage increases causing heating on the electrical system.

WEBINA R

There is More to a
Data Center than
White Space; A
Holistic Approach to
Facility Monitoring and Control
VIEW MORE WEBINARS

E C&M TV
IDEAL PowerBlade
Cable Cutters 1
Big enough for any job...

More

BROWSE ALL VIDEOS

In addition to the reflected harmonics back to the source and to the motor, VFD selection
should include voltage rating and system lockout. Keep in mind the nominal voltage of a
VFD with upper and lower limits. Also, evaluate the impact of overvoltage on a VFD.
Some VFDs tend to lock out with overvoltage condition after select restarts. Y ou should
also ensure that single-phase protection includes both time and magnitude components.
How does the motor nominal rating (typically 460V) correlate with nominal voltage of
VFD (typically 480V)? The system utilization voltage should be such that it does not go
beyond the high voltage rating of the motor (causing increased current and prematurely
http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives

2/5

11/24/2016

Basic design and operation principles behind variable-frequency drives (VFDs)

burning the motor). At the same time, it should not be too low where a sag on the system
voltage, combined with building voltage drop, does not shut down the VFD.
When sizing the input breakers for a VFD, think about when the VFD is in bypass mode.
Is the bypass starter specified as across the line or reduced voltage? Although VFDs are
important in reducing the inrush current to generators, consideration should be given
when a VFD is operated in bypass while on generator.
VFDs have losses, just like other electronic devices that transform voltage. Depending on
type (6-, 12- or 18-pulse) and manufacture of VFD, the losses can be 4% to 10%. These
losses should be taken into consideration in sizing electrical systems and requirements for
ventilation.
In addition to matching the VFD to the motor, consider the environment as well. What
are the derating factors for altitude and temperature? This will vary from manufacturer
to manufacturer. In addition, evaluate the VFD for the seismic rating based on
International Building Code and client requirements. A VFD may be designed to survive a
seismic event, operate after a seismic event, or operate during and after a seismic event.

EC&M Learning Center


Understanding the 2014 NEC,
Volume 1 (Articles 90 to 480)
This resource has proven itself in the

VFDs have been known to affect the bearing of the motor and cause premature failures.
The ratio of V/T can create parasitic capacitance between the motor stator and the rotor,
which induces a voltage on the rotor shaft. If this voltage, referred to as common mode
voltage, builds up to a sufficient level, it can discharge to ground through the bearings.
High carrier frequency can also contribute to bearing failure. The higher carrier
frequency can cause increased current discharge pulses, but this also means the VFD will
run more quietly.

field and in the exam room. This latest

Recommendations

to be in the hands...

Ensure carrier frequency is less than 6 kHz with adjustable frequency. Ensure the motor
is as close as possible to the VFD to minimize conductor length. If the conductor is longer
than recommended by the manufacturer, consider providing an inductive or RCL filter
(click here to see Fig. 5).

edition w ill provide you w ith a rock-solid


foundation...

Understanding NEC Requirements


for Grounding vs Bonding
One of the most confusing areas of the
trade continues to be grounding and
bonding, w hich is w hy this book needs

Changes to The NEC 2014


Don't let the scale of the code changes
intimidate you, this book w ill get you up
to speed on the most essential...

BROWSE ALL TITLES

Reduced harmonics should be considered for soft loads (such as at the end of an electric
utility feed in a rural area or when powering loads with on-site generators) to reduce the
voltage THD at the point of common coupling (PCC). High voltage distortion can cause
malfunction of electronic devices.
Ensure the VFD output conductors are sized per manufacturer recommendations, and
consider adding output line reactors. The line reactors should be sized to match the
distance requirements of a VFD that is not located near the motor load.
Sizing of the electrical infrastructure should take into account the VFD losses, voltage
tolerance, and footprint requirements. The electrical system should be sized for both when
the motor is operated in VFD mode and when in bypass (across the line) mode.
Big picture

In addition to cost, consider many other factors when selecting a VFD. The carrier
frequency is critical to reduce impact on the motor bearings and motor life. Install the
output and input inductors to reduce harmonic distortion at the motor and at the PCC for
most applications. If the site has high harmonics on the electrical system, a 12-pulse VFD
would typically be used. To minimize resonance of higher order harmonics, an 18-pulse
VFD may be required.
During site startup and acceptance testing, pay special attention to voltage set points
relative to utility source. The resonance frequency should be skipped during startup and
on-site generation equipment should be tested with the VFD in normal operation mode
and in bypass mode. The bottom line is you should always select VFDs based on careful
evaluation of how they will interface with the electrical system of the building in addition
to the pairing with mechanical motor selection.

Sign-up to receive our free newsletters


eTrain - (Bi-Week ly) View Sam ple
Product NewsWire - (Monthly) View
Sam ple
ElectricalZone - (Week ly) View Sam ple
MRO Insider - (Bi-Week ly) View Sam ple
PQ NewsBeat - (Bi-Week ly) View
Sam ple
Illumination Insider - (Bi-Week ly) View
Sam ple
CodeWatch - (Bi-Week ly) View Sam ple
G-Biz - (Varies) View Sam ple
Electrical Testing - (Monthly) View
Sam ple
ECM NECA 2016 Show Coverage (Show Daily)
View Sam ple
E-MAIL*
COUNTRY*

United States

Enter your email above to receive messages about


offerings by Penton, its brands, affiliates and/or thirdparty partners, consistent w ith Pentons Privacy Policy.

Battish is a principal charged with leading RTKLs mission-critical design and


engineering capabilities in Baltimore. He can be reached at rbattish@rtkl.com.

http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives

3/5

11/24/2016

Basic design and operation principles behind variable-frequency drives (VFDs)

Discuss this Article

Recommend 12

Tw eet

SHARE

Connect With Us

on Ju n 1 7 , 2 0 1 3

M ATIQ KHAN (not verif ied)

we are facing problem that our one driv e which used fro 1 800KW motor is going to
damage we need to find the reason for this cause? As this driv e has no Brakecopps .
Please send any technical informations if y ou hav e and help out us.
Thanks
Log In or Regi st er t o post com m en t s

on Sep 1 0 , 2 0 1 3

Imt iaz Mahadi (not verif ied)

how can i design a single phase ac motor with v ariable frequency ?


Log In or Regi st er t o post com m en t s

Please Log In or Register to post comments.

Re late d Article s
The Basics of Variable-Frequency Drives

10

How to Keep Variable-Frequency Drives and Motors Running


Power Factor Correction and Harmonic Resonance: A Volatile Mix
Send Me Another Drive Please
Tips For More Effective VFD Maintenance

Ecmwe b .co m
NEC

Design

Ops & Maintenance

Contractor

Safety

Site Fe ature s

EC &M C o rp o rate

Author Guidelines

Priv acy Policy

RSS

T erm s of Serv ice

Sitem ap

About Us

Site Archiv e

Adv ertise

Subscribe

Contact Us

View Mobile Site

Fo llo w Us

Power Quality

T raining

Basics

Products

Se arch e cmwe b .co m

Sub scrib e to the p rint mag azine

Re late d EC &M Site s


Electrical Wholesaling Electrical Marketing T ransm ission & Distribution World

http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives

4/5

11/24/2016

Basic design and operation principles behind variable-frequency drives (VFDs)

Copy right 2 01 6 Penton

http://ecmweb.com/harmonics/4-1-1-variable-frequency-drives

5/5

Das könnte Ihnen auch gefallen