Type PPU / GS

Generator Paralleling and Protection Unit


multi-line 2
4921240193L

Compact system in one unit

Generator synchronisation, protection


and control

True 3-phase RMS AC measurements,


all galvanically separated (GS)

Easy-readable, separate display

GSM modem connection


PPU

Application
The PPU generator controller is a microprocessorbased control unit containing all necessary functions for
control of a synchronous/asynchronous generator. The
PPU can synchronise the generator and after
synchronisation carry out all necessary generator
control and protective functions.
The PPU contains all necessary 3-phase measuring
circuits and presents all values and alarms on the LCD
display. Programming is easily done via a menu
structure in the display (password protected) or via the
RS232 PC connection and the multi-line 2 Windows
based service software. The service software offers
additional features such as monitoring of all relevant
information during commissioning, saving/download of
settings and download of software updates.

By combining these all operation schemes of a


generator can be implemented. The modes are
selected via binary inputs or (optional) serial interface.
- Fixed frequency (stand-alone running)
- Fixed power (parallel with mains)
- Droop (controlled frequency drop with increasing
load)
- Load sharing (generators in parallel, island operation)
The PPU performs programmable ramp-up and rampdown of the power in connection with breaker
operations.

The PPU is a compact all-in-one unit designed for


generators running:
- stand-alone
- parallel with other generators
- parallel with the mains

Generator protection
All protection functions have definite time characteristic.
- Overcurrent (2 levels)
(ANSI 51)
- Reverse power
(ANSI 32)

The PPU is well-suited for PLC-controlled systems,


interfacing can be done via binary and analogue I/Os or
via (optional) serial communication.

Reverse power can also be programmed with inverse


time characteristic.

The PPU carries out a cyclical self-test, displaying error


messages in clear text and indicating errors with relay
outputs, should any errors occur.

Display
The display is separate, for mounting directly on the
PPU or the panel front, connected via cable (option J).

DEIF A/S

Power or frequency control


The PPU can control the power or frequency in 4
different
modes
with
selection
of
internal
(programmable) or external +/-10V DC set point.

GSM modem
It is possible to connect a GSM modem to the PPU,
enabling the transmission of SMS alarm messages to
up to 5 receivers as well as the establishment of
telephone line communication using the PC utility
software.

Standard functions
Synchronisation
- Frequency control with programmable slip freq.
- Voltage matching possible
- Breaker ON pulse at exact sync. point with
programmable generator breaker delay time
- Black busbar operation of generator breaker possible

4 programmable relay outputs for alarm/trip.


Measured and calculated values
Generator:
- Voltage (3-phase U + N)
- Current (3-phase I)
- Active power (kW)
- Reactive power (kvar)
- Power factor (cos )
- Frequency (f)
- Energy production (kWh)
Busbar:

- Voltage (3-phase U + N)
- Frequency (f)

Principle diagram

Type PPU / GS
Technical specifications
Accuracy:

Class 1.0, to IEC 688

Operating temp.:

-2570C

Climate:

Class HSE, to DIN 40040

Meas. voltage:

100/110V AC to 690V AC +/-20%


Consumption max. 0.2VA / phase

Meas. current:

-/1 or -/5A AC
Consumption max. 0.3VA / phase

Current overload:

4 x In continuously
20 x In , 10 sec. (max. 75A)
80 x In , 1 sec. (max. 300A)

Meas. frequency:

3070Hz

Aux. supply:

8-32V DC
Max. 8W consumption

Binary inputs:

Optocoupler, bi-directional
Input voltage 9-32V DC
Impedance max. 4.7k

Relay outputs:

250V AC / 24V DC, 8A


(Unit status output: 1A)

Open collector
outputs:

Approvals:

The PPU is approved by the major


classification societies. Contact DEIF
for details

Governors:

multi-line 2 interfaces to all governors,


including GAC, Barber-Colman,
Woodward and Cummins. See interfacing
guide at www.deif.com or request doc.
no. 4189340257 from DEIF

Unit: H x W x D = 120 x 230 x 165 mm

Weight:

PPU
J1, J3
J2

Display: H x W x D: 115 x 220 x 20 mm

Supply 1232V DC, max. 10mA

Analogue inputs:

-100+10V DC
Not galvanically separated
Impedance max. 100k

Mounting:

DIN-rail mount or base mount

Load sharing lines: -50+5V DC


Analogue outputs:

Safety:

0(4)...20mA
Galvanically separated
Active output (internal supply)
Load max. 500
To EN 61010-1, installation category
(overvoltage category) III, 600V,
pollution degree 2

Galvanic separation: Between AC voltage, AC current and


other I/Os: 3250V AC, 50Hz, 1 min.
Between analogue outputs: 500V DC,
1 min.
EMC/CE:

To EN 50081-1/2, EN 50082-1/2
SS4631503 (PL4) and IEC 255-3

Material:

All plastic materials are self-extinguishing


according to UL94 (V1)

Plug connections:

AC current: 4 mm2 multi stranded


2
Other:
2.5 mm multi stranded
Display:
9-pole Sub-D female
PC:
9-pole Sub-D male

Protection:

Unit:
IP20
Display: IP52 (IP54 with gasket: Option L)
To IEC 529 and EN 60529

1.55 kg
0.20 kg
0.40 kg

Order specifications
PPU Option
Option
Option

Type PPU / GS
Specification of options
Below the available options for the multi-line 2 PPU / GS gen-set control and protection units with software version 2.30.0 or later
are specified.
For the placement of hardware (slot #), please refer to the Placed in column and specific drawing of the PPU.
OpDescription
tion
A
Loss of mains protection
A1 - Over- and undervoltage (generator and busbar/mains)
- Over- and underfrequency (generator and busbar/mains)
- Vector jump
- Df/dt (ROCOF)
A2 - Over- and undervoltage (generator and busbar/mains)
- Over- and underfrequency (generator and busbar/mains)
- Df/dt (ROCOF)
A3 - Over- and undervoltage (generator and busbar/mains)
- Over- and underfrequency (generator and busbar/mains)
- Vector jump
B
Generator/busbar/mains protection
B1 - Over- and undervoltage (generator and busbar/mains)
- Over- and underfrequency (generator and busbar/mains)
C
Generator add-on protection package
C1 - Over- and undervoltage (generator)
- Over- and underfrequency (generator)
- Overload
- Fast overcurrent (<42 ms)
- High overcurrent (<350%)
- Current unbalance
- Voltage asymmetry
- Reactive power (import (excitation loss)/export (overexcitation))
C2 - Negative sequence voltage high
- Negative sequence current high
- Zero sequence voltage high
- Zero sequence current high
D
Voltage/var/cos control
D1 Selection between:
- Constant voltage control (stand-alone)
- Constant reactive power control (parallel with mains)
- Constant power factor control (parallel with mains)
- Reactive load sharing (island paralleling with other generators)
E
Analogue controller outputs
E1 - +/-20mA for speed governor
- +/-20mA for AVR
F

Placed
in
(ANSI 27/59)
(ANSI 81)
(ANSI 78)
(ANSI 81)
(ANSI 27/59)
(ANSI 81)
(ANSI 81)
(ANSI 27/59)
(ANSI 81)
(ANSI 78)

Software
option
Software
option
Software
option

(ANSI 27/59) Software


(ANSI 81)
option
(ANSI 27/59)
(ANSI 81)
(ANSI 32)
(ANSI 50)
(ANSI 50)
(ANSI 46)
(ANSI 47)
(ANSI 32)
(ANSI 47)
(ANSI 46)
(ANSI 59)
(ANSI 50)

Analogue transducer outputs


F1 - 2 x 0(4)...20mA transducer outputs

EF
Combination outputs
EF2 - +/-20mA for speed governor
- 1 x 0(4)...20mA transducer output
EF3 - 1 x PWM (Pulse Width Modulated) output for CAT speed governor
- 1 x PWM (Pulse Width Modulated) output for droop
- +/-20mA for speed governor or AVR
- 2 x relay outputs for speed governor or AVR
EF4 - +/-20mA for speed governor or AVR
- 2 x relay outputs for speed governor or AVR
(ANSI # as per IEE std. C37.2 1996 (R2001) in parenthesis).

Note

Software
option

Software
option

Software
option

Not with EF2

Slot #4

AVR: Only when option D


is chosen
Not with EF

Slot #6

Not when option EF3 is


chosen

Slot #4

Not with E1, F2, EF3, EF4

Slot #4 +
#6

Not with E1, F1, F2, EF2,


EF4
AVR: Requires D

Slot #4

Not with E1, F2, EF2, EF3


AVR: Requires D

Type PPU / GS
Option
H
H1
H2
H3
H4

Description
Serial communication
- Can-open
- Mod-bus RTU (RS485)
- Profi-bus DP (RS485)
- Caterpillar CCM (RS232)

H5 Can bus engine communication for:


- MTU MDEC
- Detroit Diesel DDEC
- Deutz EMR
- John Deere JDEC
- Volvo Penta D12 AUX
H6 - Cummins ECM (RS485) engine communication
J
J1
J2
J3
J6
K
K1
L
M
M1
*See
note
M2
*See
note
M
M13
M14
M15
N
N1
O
O1

Cables
- Display cable with plugs, 3 m. UL94 (V1) approved
- Display cable with plugs, 6 m. UL94 (V1) approved
- PC cable for utility software (RS232). UL94 (V1) approved
- Display cable with plugs, 1 m. UL94 (V1) approved
Designers reference handbook
- Hard copy (as standard enclosed as a CD-ROM)
Display gasket for IP54
Configurable engine control cards
Engine control card with Pt100 sensor inputs
- 4 x 420mA inputs
- 2 x Pt100 inputs
- 1 x tacho input (magnetic pick-up)
- 5 x binary inputs
- 3 x relay outputs
Engine control card with VDO sensor inputs
- 3 x 420mA inputs
- 3 x VDO (resistor) inputs
- 1 x tacho input (magnetic pick-up)
- 9 x binary inputs
- 3 x relay outputs
Configurable I/O extension cards
- 7 x binary inputs
- 4 x relay outputs
- 4 x 0(4)20mA analogue inputs
Ethernet TCP/IP communication
- Integrated WebServer with web pages for plant presentation
Example: See http://ml2.deif.com
Water turbine control
- Water turbine control with integrated water level dependent power control

Placed
in

Note

Slot #2
Slot #2
Slot #2
Slot #8

Not with H2, H3, N1


Not with H1, H3
Not with H1, H2, N1
Only limited engine data
can be displayed. All data
can be read via H2
Only limited engine data
can be displayed. All data
can be read via H2

Slot #8

Slot #8

Only limited engine data


can be displayed. All data
can be read via H2

Slot #7

Engine start/stop logic can


be selected ON or OFF

Slot #7

Engine start/stop logic can


be selected ON or OFF

Slot #8
Slot #8
Slot #8

Not with H4, M14, M15


Not with H4, M13, M15
Not with H4, M13, M14
Requires H2
For asynchronous generators also when combined
with option M1/M2

* NOTE:
If option M1/M2, engine start/stop control, is used in marine applications, separate approved engine protection (overspeed, water
temperature and oil pressure) is needed.

Type PPU / GS
Ethernet
Option N1:

Slot #4, term. 65-72


Governor/AVR outputs

WebServer

Slot #6, term. 90-97


In-/outputs

PPU/GPC:
GPU:

4 x relay as standard
Option G2/D2

Option F1/F2: 2 x 0(4)20mA out,


transducer

Option E1:

2 x +/-20mA out,
governor + AVR

Option EF3:

Option F2:

2 x 0(4)...20mA out,
transducer

Option EF2: 1 x +/-20mA out,


governor
1 x 0(4)20mA out,
transducer
Option EF3: 1 x PWM governor out
1 x +/-20mA out, AVR
2 x relay out
Option EF4: 1 x +/-20mA out, AVR
2 x relay out

Slot #2, term. 29-36


Communication
Option H1:

Can-open

Option H2:

Mod-bus RTU (RS485)

Option H3:

Profi-bus DP (RS485)

PWM droop signal

Slot #8, term. 126-133


Communication / in-/outputs
Option H4:

Engine RS232
Cat. CCM

Option H5:

Engine Can bus

Option H6:

Engine RS485
Cummins ECM

Option M13:

7 x binary inputs

Option M14:

4 x relay outputs

Option M15:

4 x 4...20mA

Slot #7, term. 98-125


Slot #1, term. 1-28
Power supply (std. board)
24V DC supply, 8W
1 x status output relay
5 x relay outputs
2 x pulse outputs (kWh, kvarh)
5 x binary inputs

Engine I/F
Option M1:

4 x 420mA in
2 x Pt100 in
1 x magn. pick-up in
5 x binary in
3 x relay out

Option M2:

3 x 420mA in
3 x VDO in
1 x magn. pick-up in
9 x binary in
3 x relay out

Slot #3, term. 37-64


Load sharing (std.)
13 x binary input
4 x relay output
Power load sharing
Reactive power load sharing (option)
Analogue input for set point:
- Fixed power
- Frequency
- Reactive power
- Power factor
- Voltage

Slot #5, term. 73-89


AC measuring (std.)
3 x generator voltage
3 x generator current
3 x busbar/mains voltage

Due to our continuous development we reserve the right to


supply equipment which may vary from the described.

DEIF A/S, Frisenborgvej 33


DK-7800 Skive, Denmark
Tel.: +45 9614 9614, Fax: +45 9614 9615
E-mail: deif@deif.com, URL: www.deif.com