EDIFICIO ZONA 06
LARGO
M
11.28
ANCHO
FT
37.01
2,877.00 CFM
4.00 PZA
719.25 CFM
VELOCIDAD RECOMENDARA =
800 FPM
AREA RECOMENDADA =
0.9 FT2
0.995 FT2
CANTIDAD DE LOUVER =
0.90 PZA
SE CONSIDERAN =
1 PZA
M
7.60
ANCHO TOTAL =
12 PULG
0.3048
36 PULG
0.9144
LARGO TOTAL =
36 PULG
0.9144
DISEO FINAL
LOUVER DE 36"X12" =
4 PZA
EN FACHADA
LOUVER DE 36"X12"=
4 PZA
EN FACHADA
ANCHO
AREA
FT
24.94
M
M
M
M2
85.73
ALTURA
FT2
922.88
M
9.50
FT
31.17
VOLMEN
M3
814.44
VOLMEN
FT3
28,766.17
CAMBIOS
ACM
ACH
10
6
CAUDAL DE AIRE
CFM
M3/S
2,877
4,887
ZONA
EDIFICIO ZONA 06
LARGO
M
12.10
ANCHO
FT
39.70
3,106.00 CFM
4.00 PZA
776.50 CFM
VELOCIDAD RECOMENDARA =
800 FPM
AREA RECOMENDADA =
0.97 FT2
0.995 FT2
CANTIDAD DE LOUVER =
0.97 PZA
SE CONSIDERAN =
1 PZA
M
7.65
ANCHO TOTAL =
12 PULG
0.3048
36 PULG
0.9144
LARGO TOTAL =
36 PULG
0.9144
DISEO FINAL
LOUVER DE 36"X12" =
4 PZA
EN FACHADA
LOUVER DE 36"X12"=
4 PZA
EN FACHADA
ANCHO
AREA
FT
25.10
M
M
M
M2
92.57
ALTURA
FT2
996.51
M
9.50
FT
31.17
VOLMEN
M3
879.42
VOLMEN
FT3
31,061.22
CAMBIOS
ACM
ACH
10
6
CAUDAL DE AIRE
CFM
M3/S
3,106
5,277
ZONA
EDIFICIO ZONA 06
LARGO
M
6.12
ANCHO
FT
20.08
1,261.00 CFM
2.00 PZA
630.50 CFM
VELOCIDAD RECOMENDARA =
800 FPM
AREA RECOMENDADA =
0.79 FT2
0.995 FT2
CANTIDAD DE LOUVER =
0.79 PZA
SE CONSIDERAN =
1 PZA
M
6.14
ANCHO TOTAL =
12 PULG
0.3048
36 PULG
0.9144
LARGO TOTAL =
36 PULG
0.9144
DISEO FINAL
LOUVER DE 36"X12" =
4 PZA
EN FACHADA
LOUVER DE 36"X12"=
4 PZA
EN FACHADA
ANCHO
AREA
FT
20.15
M
M
M
M2
37.58
ALTURA
FT2
404.55
M
9.50
FT
31.17
VOLMEN
M3
357.01
VOLMEN
FT3
12,609.82
CAMBIOS
ACM
ACH
10
6
CAUDAL DE AIRE
CFM
M3/S
1,261
2,142
ZONA
CUARTO DE BATERIAS
LARGO
M
6.24
ANCHO
FT
20.47
4,432.00 CFM
1.00 PZA
4,432.00 CFM
VELOCIDAD RECOMENDARA =
800 FPM
AREA RECOMENDADA =
5.54 FT2
5.52 FT2
CANTIDAD DE LOUVER =
1.00 PZA
SE CONSIDERAN =
1 PZA
M
8.47
ANCHO TOTAL =
36 PULG
0.9144
48 PULG
1.2192
LARGO TOTAL =
48 PULG
1.2192
DISEO FINAL
LOUVER DE 36"X48" =
1 PZA
EN FACHADA
ANCHO
AREA
FT
27.79
M
M
M
M2
52.85
ALTURA
FT2
568.93
M
4.75
FT
15.58
VOLMEN
M3
251.04
VOLMEN
FT3
8,863.93
CAMBIOS
ACM
ACH
2
30
CAUDAL DE AIRE
CFM
M3/S
4,432
7,531
ZONA
CUARTO DE BATERIAS
LARGO
M
11.60
ANCHO
FT
38.06
9,987.00 CFM
6.00 PZA
1,664.50 CFM
VELOCIDAD RECOMENDARA =
800 FPM
AREA RECOMENDADA =
2.08 FT2
2.11 FT2
CANTIDAD DE LOUVER =
0.99 PZA
SE CONSIDERAN =
1 PZA
M
5.30
ANCHO TOTAL =
36 PULG
0.9144
24 PULG
0.6096
LARGO TOTAL =
24 PULG
0.6096
DISEO FINAL
LOUVER DE 36"X24" =
6 PZA
EN PUERTA
ANCHO
AREA
FT
17.39
M
M
M
M2
61.48
ALTURA
FT2
661.83
M
4.60
FT
15.09
VOLMEN
M3
282.81
VOLMEN
FT3
9,987.01
CAMBIOS
ACM
ACH
1
60
CAUDAL DE AIRE
CFM
M3/S
9,987
16,969
ZONA
LARGO
M
ANCHO
FT
CUARTO DE BATERIAS
CAUDAL TOTAL REQUERIDO =
No DE LOUVER DISPONIBLES =
CAUDAL POR LOUVER =
165,325.00 CFM
20.00 PZA
8,266.25 CFM
VELOCIDAD RECOMENDARA =
800 FPM
AREA RECOMENDADA =
10.33 FT2
2.11 FT2
CANTIDAD DE LOUVER =
4.90 PZA
SE CONSIDERAN =
1 PZA
ANCHO TOTAL =
36 PULG
0.9144
24 PULG
0.6096
LARGO TOTAL =
24 PULG
0.6096
DISEO FINAL
LOUVER DE 36"X24" =
6 PZA
EN PUERTA
ANCHO
AREA
FT
M
M
M
M2
2,808.47
FT2
30,233.07
ALTURA
M
10.00
FT
32.81
VOLMEN
M3
28,084.70
VOLMEN
FT3
991,947.03
CAMBIOS
ACM
ACH
6
10
CAUDAL DE AIRE
CFM
M3/S
165,325
280,847
ZONA
LARGO
M
ANCHO
FT
CUARTO DE BATERIAS
CAUDAL TOTAL REQUERIDO =
No DE LOUVER DISPONIBLES =
CAUDAL POR LOUVER =
3,136.00 CFM
2.00 PZA
1,568.00 CFM
VELOCIDAD RECOMENDARA =
800 FPM
AREA RECOMENDADA =
1.96 FT2
2.11 FT2
CANTIDAD DE LOUVER =
0.93 PZA
SE CONSIDERAN =
1 PZA
ANCHO TOTAL =
36 PULG
0.9144
21 PULG
0.5334
LARGO TOTAL =
21 PULG
0.5334
DISEO FINAL
LOUVER DE 36"X21" =
2 PZA
EN PUERTA
ANCHO
AREA
FT
M
M
M
M2
71.00
ALTURA
FT2
764.31
M
5.00
FT
16.41
VOLMEN
M3
355.00
VOLMEN
FT3
12,542.33
CAMBIOS
ACM
ACH
4
15
CAUDAL DE AIRE
CFM
M3/S
3,136
5,325
ZONA
LARGO
M
ANCHO
FT
CUARTO DE BATERIAS
CAUDAL TOTAL REQUERIDO =
No DE LOUVER DISPONIBLES =
CAUDAL POR LOUVER =
1,873.00 CFM
2.00 PZA
936.50 CFM
VELOCIDAD RECOMENDARA =
800 FPM
AREA RECOMENDADA =
1.17 FT2
1.24 FT2
CANTIDAD DE LOUVER =
0.94 PZA
SE CONSIDERAN =
1 PZA
ANCHO TOTAL =
18 PULG
0.4572
24 PULG
0.6096
LARGO TOTAL =
24 PULG
0.6096
DISEO FINAL
LOUVER DE 18"X24" =
2 PZA
EN PUERTA
ANCHO
AREA
FT
M
M
M
M2
21.20
ALTURA
FT2
228.22
M
5.00
FT
16.41
VOLMEN
M3
106.00
VOLMEN
FT3
3,745.09
CAMBIOS
ACM
ACH
2
30
CAUDAL DE AIRE
CFM
M3/S
1,873
3,180
ZONA
LARGO
M
ANCHO
FT
CUARTO DE BATERIAS
CAUDAL TOTAL REQUERIDO =
No DE LOUVER DISPONIBLES =
CAUDAL POR LOUVER =
1,873.00 CFM
1.00 PZA
1,873.00 CFM
VELOCIDAD RECOMENDARA =
800 FPM
AREA RECOMENDADA =
2.34 FT2
2.35 FT2
CANTIDAD DE LOUVER =
1.00 PZA
SE CONSIDERAN =
1 PZA
ANCHO TOTAL =
18 PULG
0.4572
48 PULG
1.2192
LARGO TOTAL =
48 PULG
1.2192
DISEO FINAL
LOUVER DE 18"X48" =
1 PZA
EN PUERTA
ANCHO
AREA
FT
M
M
M
M2
21.20
ALTURA
FT2
228.22
M
5.00
FT
16.41
VOLMEN
M3
106.00
VOLMEN
FT3
3,745.09
CAMBIOS
ACM
ACH
2
30
CAUDAL DE AIRE
CFM
M3/S
1,873
3,180
ZONA
CUARTO DE BATERIAS
LARGO
M
8.20
ANCHO
FT
3,266.00 CFM
1.00 PZA
3,266.00 CFM
VELOCIDAD RECOMENDARA =
1000 FPM
AREA RECOMENDADA =
3.27 FT2
1.52 FT2
CANTIDAD DE LOUVER =
2.15 PZA
SE CONSIDERAN =
0.3 PZA
M
4.75
354
ANCHO TOTAL =
18 PULG
0.4572
48 PULG
1.2192
LARGO TOTAL =
14.4 PULG
0.36576
DISEO FINAL
LOUVER DE 18"X48" =
1 PZA
EN PUERTA
ANCHO
AREA
FT
M
M
M
M2
38.95
ALTURA
FT2
419.30
M
4.75
FT
15.58
VOLMEN
M3
185.01
VOLMEN
FT3
6,532.69
CAMBIOS
ACM
ACH
2
30
CAUDAL DE AIRE
CFM
M3/S
3,266
5,550
ZONA
CUARTO DE BATERIAS
LARGO
M
8.20
ANCHO
FT
2,178.00 CFM
1.00 PZA
2,178.00 CFM
VELOCIDAD RECOMENDARA =
1000 FPM
AREA RECOMENDADA =
2.18 FT2
1.52 FT2
CANTIDAD DE LOUVER =
1.43 PZA
SE CONSIDERAN =
2 PZA
M
4.75
354
ANCHO TOTAL =
18 PULG
0.4572
48 PULG
1.2192
LARGO TOTAL =
96 PULG
2.4384
DISEO FINAL
LOUVER DE 18"X48" =
1 PZA
EN PUERTA
ANCHO
AREA
FT
M
M
M
M2
38.95
ALTURA
FT2
419.30
M
4.75
FT
15.58
VOLMEN
M3
185.01
VOLMEN
FT3
6,532.69
CAMBIOS
ACM
ACH
3
20
CAUDAL DE AIRE
CFM
M3/S
2,178
3,700