FRAME HV 804 S
SPECIFICATIONS & OPTIONS
STANDARDS
DESCRIPTION
The STAMFORD PI range of synchronous ac generators
are brushless with a rotating field. They are separately
excited by the STAMFORD Permanent Magnet Generator
(PMG). This is a shaft mounted, high frequency, pilot
exciter which provides a constant supply of clean power
via the Automatic Voltage Regulator (AVR) to the main
exciter. The main exciter output is fed to the main rotor,
through a full wave bridge rectifier, protected by surge
suppression.
VOLTAGE REGULATORS
The P range generators complete with a PMG are
available with one AVR. The AVR has soft start voltage
build up and built in protection against sustained overexcitation, which will de-excite the generator after a
minimum of 8 seconds.
Underspeed protection (UFRO) is also provided on both
AVRs. The UFRO will reduce the generator output voltage
proportional to the speed of the generator below a presettable level.
The MA330 AVR is 3 phase rms sensed with a voltage
regulation of 0.5% rms (see the note on regulation). The
UFRO circuit has adjustable slope and dwell for controlled
recovery from step loads. An over voltage protection circuit
will shutdown the output device of the AVR, it can also trip
an optional excitation circuit breaker if required. As an
option, short circuit current limiting is available with the
addition of current transformers.
The MA330 AVR needs a generator mounted current
transformer to provide quadrature droop characteristics for
load sharing during parallel operation.
Provision is also made for the connection of the
STAMFORD power factor controller, for embedded
applications, and a remote voltage trimmer.
FRAME HV 804 S
WINDING 83
RATINGS
MAXIMUM ALTITUDE
MAXIMUM AMBIENT TEMPERATURE
INSULATION SYSTEM
PROTECTION
RATED POWER FACTOR
STATOR WINDING
WINDING PITCH
WINDING LEADS
R.F.I. SUPPRESSION
WAVEFORM DISTORTION
MAXIMUM OVERSPEED
BEARING DRIVE END
BEARING NON DRIVE END
EFFICIENCY
FREQUENCY
TELEPHONE INTERFERENCE
COOLING AIR
VOLTAGE STAR (Y)
kVA BASE RATING FOR
REACTANCE VALUES
Xd DIRECT AXIS SYNCHRONOUS
X'd DIRECT AXIS TRANSIENT
X''d DIRECT AXIS SUB-TRANSIENT
Xq QUADRATURE AXIS REACTANCE
X''q QUAD. AXIS SUB-TRANSIENT
XL LEAKAGE REACTANCE
X2 NEGATIVE PHASE SEQUENCE
X0 ZERO PHASE SEQUENCE
REACTANCES ARE SATURATED
T'd TRANSIENT TIME CONSTANT
T''d SUB-TRANSIENT TIME CONSTANT
T'do O.C. FIELD TIME CONSTANT
Ta ARMATURE TIME CONSTANT
SHORT CIRCUIT RATIO
STATOR WINDING RESISTANCE (L-N)
ROTOR WINDING RESISTANCE
EXCITER STATOR FIELD RESISTANCE
EXCITER ROTOR RESISTANCE (L-L)
PMG STATOR RESISTANCE (L-L)
CLASS F
IP23 STANDARD
0.8
DOUBLE LAYER LAP
2/3
6
BS EN 50081/2-1/2 VDE 0875G VDE 0875N For other standards apply to the factory
NO LOAD < 1.5% NON-DISTORTING BALANCED LINEAR LOAD < 3.0%
2250 Rev/Min
ISO 6232 C3
ISO 6324 C3
REFER TO EFFICIENCY CURVES OF THIS SECTION
50Hz
THF< 2%
3
3.0 m /sec
10500
11000
2401
2515
2.494
2.380
0.211
0.202
0.157
0.150
1.771
1.690
0.292
0.279
0.116
0.111
0.226
0.216
0.035
0.033
VALUES ARE PER UNIT AT RATING AND VOLTAGE INDICATED
0.200
0.015
4.150
0.064
1/Xd
0.4900
1.400
17.50
0.076
3.800
RESISTANCE VALUES ARE IN OHMS AT 20 C
15.0
63.0
Continuous development of our products entitles us to change specification details without notice,
therefore they must not be regarded as binding.
FRAME HV 804 S
WDG 83
50 Hz
97.0
1.0
96.5
0.9
96.0
0.8
95.5
95.0
P.F.
2401.0 kVA
94.5
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
2401 kVA
11000 V
97.5
97.0
1.0
96.5
0.9
96.0
0.8
%
95.5
95.0
94.5
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
2515 kVA
1.1
P.F.
10500V
30.0
11000V
25.0
20.0
15.0
10.0
5.0
0.0
0
500
1000
1500
2000
2500
3000
3500
4000
4500
NOTE 1
10000
SYMMETRIC
CURRENT (Amps)
ASYMMETRICAL
VOLTAGE
FACTOR
10500V
11000V
X 0.95
X 1.00
1000
NOTE 2
THE FOLLOWING MULTIPLICATION FACTORS SHOULD BE USED TO CONVERT THE
VALUES CALCULATED IN ACCORDANCE WITH NOTE 1 TO THOSE APPLICABLE
TO THE VARIOUS TYPES OF SHORT CIRCUIT
3 PHASE
2 PHASE L-L
INSTANTANEOUS
X 1.0
X 0.87
X 1.30
MINIMUM
X 1.0
X 1.80
X 3.20
SUSTAINED
X 1.0
X 1.50
X 2.50
10 SEC
5 SEC
2 SEC
100
0.001
0.01
0.1
10
TIME (secs)
1 PHASE L-N
462 Amps
FRAME HV 804 S
WINDING 83
RATINGS
Class - Temp Rise
50Hz
Cont. F - 105/40C
Star (V)
10500
11000
10500
11000
10500
11000
kVA
2401
2515
2568
2690
2663
2790
kW
1921
2012
2054
2152
2130
2232
Efficiency (%)
95.9
96.0
95.8
95.9
95.8
96.0
kW Input
2002
2096
2144
2245
2225
2325
Star (V)
N/A
N/A
N/A
N/A
N/A
N/A
kVA
N/A
N/A
N/A
N/A
N/A
N/A
kW
N/A
N/A
N/A
N/A
N/A
N/A
Efficiency (%)
N/A
N/A
N/A
N/A
N/A
N/A
kW Input
N/A
N/A
N/A
N/A
N/A
N/A
60Hz
TD_HV804S.83.GB_03.09_09_GB