Product Description
Issue
01
Date
2011-04-15
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and the
customer. All or part of the products, services and features described in this document may not be within the
purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information,
and recommendations in this document are provided "AS IS" without warranties, guarantees or representations
of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute the warranty of any kind, express or implied.
Website:
http://www.huawei.com
Email:
support@huawei.com
Issue 01 (2011-04-15)
EMUA-02
Product Description
Product Version
The following table lists the product version related to this document.
Name
Product Version
EMUA-02
V200R305
Intended Audience
This document is intended for:
l
System engineers
Organization
1 Changes in EMUA-02 Product Description
This section describes the changes in the EMUA-02 Product Description.
2 Introduction to the EMUA-02
This section describes the Environment Monitoring Unit-02 (EMUA-02). The EMUA-02
monitors the environmental conditions of equipment rooms and cabinets for Huawei base
stations.
3 Introduction to the Sensors Used with the EMUA-02
Issue 01 (2011-04-15)
iii
EMUA-02
Product Description
This section describes the sensors used with the EMUA-02. To ensure that the sensors can be
used with the EMUA-02, you can use the sensors recommended by Huawei or you can purchase
the sensors that meet the relevant technical specifications.
Conventions
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol
Description
Indicates a hazard with a high level of risk, which if not
avoided, will result in death or serious injury.
Indicates a hazard with a medium or low level of risk, which
if not avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation, which if not
avoided, could result in equipment damage, data loss,
performance degradation, or unexpected results.
Indicates a tip that may help you solve a problem or save
time.
Provides additional information to emphasize or supplement
important points of the main text.
General Conventions
The general conventions that may be found in this document are defined as follows.
Convention
Description
Boldface
Italic
Courier New
Command Conventions
The command conventions that may be found in this document are defined as follows.
iv
Convention
Description
Boldface
Issue 01 (2011-04-15)
EMUA-02
Product Description
Convention
Description
Italic
[]
{ x | y | ... }
[ x | y | ... ]
{ x | y | ... }*
[ x | y | ... ]*
GUI Conventions
The GUI conventions that may be found in this document are defined as follows.
Convention
Description
Boldface
>
Keyboard Operations
The keyboard operations that may be found in this document are defined as follows.
Format
Description
Key
Press the key. For example, press Enter and press Tab.
Key 1+Key 2
Key 1, Key 2
Mouse Operations
The mouse operations that may be found in this document are defined as follows.
Issue 01 (2011-04-15)
EMUA-02
Product Description
vi
Action
Description
Click
Double-click
Drag
Press and hold the primary mouse button and move the
pointer to a certain position.
Issue 01 (2011-04-15)
EMUA-02
Product Description
Contents
Contents
About This Document...................................................................................................................iii
1 Changes in EMUA-02 Product Description..........................................................................1-1
2 Introduction to the EMUA-02..................................................................................................2-1
2.1 Functions of the EMUA-02.............................................................................................................................2-2
2.2 EMUA-02 Ports...............................................................................................................................................2-3
2.3 DIP Switches on the EMUA-02....................................................................................................................2-15
2.4 Technical Specifications of the EMUA-02...................................................................................................2-17
Issue 01 (2011-04-15)
vii
EMUA-02
Product Description
Figures
Figures
Figure 2-1 EMUA-02...........................................................................................................................................2-3
Figure 2-2 Ports on the EMUA-02.......................................................................................................................2-3
Figure 2-3 Pins on the RS485 port.......................................................................................................................2-4
Figure 2-4 Port for analog signal detection..........................................................................................................2-5
Figure 2-5 Cable connection for the voltage-type analog sensor.........................................................................2-6
Figure 2-6 Cable connection for the current-type analog sensor......................................................................... 2-7
Figure 2-7 Port to connect the infrared sensor..................................................................................................... 2-7
Figure 2-8 Port to connect the smoke sensor....................................................................................................... 2-8
Figure 2-9 Port to connect the door status sensor................................................................................................ 2-9
Figure 2-10 Six-line port for relay node output control.....................................................................................2-10
Figure 2-11 Cable connection for the relay node output control port................................................................2-11
Figure 2-12 Port for Boolean signal detection...................................................................................................2-12
Figure 2-13 Port to connect the humidity and temperature sensor.....................................................................2-13
Figure 2-14 Port to connect the water sensor.....................................................................................................2-14
Figure 2-15 Layout of the EMUA-02.................................................................................................................2-15
Figure 3-1 Water sensor YW517B ......................................................................................................................3-2
Figure 3-2 Smoke sensor JTY-GD-01K ..............................................................................................................3-3
Figure 3-3 Infrared sensor MC-760T...................................................................................................................3-4
Figure 3-4 Door status sensor AGX105F.............................................................................................................3-5
Figure 3-5 Door status sensor HO-03A................................................................................................................3-6
Figure 3-6 Working principle...............................................................................................................................3-6
Figure 3-7 Humidity and temperature sensor WS302A1T4 ................................................................................3-7
Figure 3-8 YW101A003L005 fuel level sensor...................................................................................................3-9
Figure 3-9 Relationship between the humidity and the output current..............................................................3-10
Figure 3-10 Relationship between the temperature and the output current........................................................3-10
Figure 3-11 Relationship between the fuel level and the output current............................................................3-13
Issue 01 (2011-04-15)
ix
EMUA-02
Product Description
Tables
Tables
Table 2-1 Indicators on the EMUA-02.................................................................................................................2-4
Table 2-2 Pins on the RS485 port.........................................................................................................................2-4
Table 2-3 Terminals on the port for analog signal detection................................................................................2-5
Table 2-4 Terminals on the port to which the infrared sensor is connected.........................................................2-8
Table 2-5 Terminals on the port to which the smoke sensor is connected...........................................................2-8
Table 2-6 Terminals on the port to which the door status sensor is connected....................................................2-9
Table 2-7 Terminals on the six-line port for relay node output control.............................................................2-10
Table 2-8 Alarms related to each relay node switch...........................................................................................2-11
Table 2-9 Valid voltage range of voltage-type Boolean signals.........................................................................2-12
Table 2-10 Terminals on the port for Boolean signal detection.........................................................................2-13
Table 2-11 Terminals on the port to which the humidity and temperature sensor is connected........................2-13
Table 2-12 Terminals on the port to which the water sensor is connected.........................................................2-14
Table 2-13 Functions and settings of the DIP switches......................................................................................2-16
Table 2-14 Technical parameters of the EMUA-02...........................................................................................2-18
Table 2-15 Technical specifications of the EMUA-02.......................................................................................2-18
Table 3-1 Technical specifications.......................................................................................................................3-2
Table 3-2 Indicator on the smoke sensor..............................................................................................................3-3
Table 3-3 Technical specifications of the smoke sensor JTY-GD-01K...............................................................3-3
Table 3-4 Technical specifications of the infrared sensor MC-760T...................................................................3-5
Table 3-5 Technical specifications of the door status sensor AGX105F............................................................. 3-7
Table 3-6 Technical specifications of the door status sensor HO-03A................................................................3-7
Table 3-7 Technical specifications of the humidity and temperature sensor WS302A1T4.................................3-8
Table 3-8 Technical specifications of the YW101A003L005 fuel level sensor...................................................3-9
Issue 01 (2011-04-15)
xi
EMUA-02
Product Description
01 (2011-04-15)
This is the first official release.
Issue 01 (2011-04-15)
1-1
EMUA-02
Product Description
Issue 01 (2011-04-15)
2-1
EMUA-02
Product Description
The EMUA-02 provides one +24 V DC current-type port to connect a humidity and
temperature sensor. The output current of the sensor ranges from 4 mA to 20 mA. The
temperature detection range is -20C to +80C (-4F to +176F). The humidity detection
range is 0% RH to 100% RH.
The EMUA-02 provides one +24 V DC voltage-type port to connect a smoke sensor. The
smoke monitoring port controls whether smoke alarms need to be cleared, which is
implemented on the base station maintenance terminal.
The EMUA-02 provides one +12 V DC/24 V DC voltage-type port to connect a water
sensor.
The EMUA-02 provides one +12 V DC/24 V DC voltage-type port to connect an infrared
sensor.
The EMUA-02 provides one dry contact-type port to connect a door status sensor.
The EMUA-02 provides one four-line port for monitoring analog signals of different types.
If the connected sensor is a voltage-type sensor, the voltage ranges from 0 V to 5 V. If the
connected sensor is a current-type sensor, the current ranges from 4 mA to 20 mA. The
input signal type is set using the Dual Inline Package (DIP) switch according to the sensor
type configured on the BTS.
The EMUA-02 provides 32 lines for Boolean signal detection. All 32 lines support settings
of valid level for alarms, and eight of these 32 lines support voltage-type Boolean signal
input.
Issue 01 (2011-04-15)
EMUA-02
Product Description
The EMUA-02 provides an RS232 serial port to facilitate the on-board loading of the software.
Appearance
Figure 2-1 shows the EMUA-02.
Figure 2-1 EMUA-02
Ports
Figure 2-2 shows the ports on the EMUA-02.
Figure 2-2 Ports on the EMUA-02
(3) Indicator
(4) Four-line port for analog signal (5) Port to connect the infrared
detection
sensor
(7) Port to connect the door status (8) Six-line port for relay node
sensor
output control
2-3
EMUA-02
Product Description
State
Description
RUN (green)
Other states
ALM (red)
2-4
Pin
Description
NULL
Issue 01 (2011-04-15)
EMUA-02
Product Description
Pin
Description
NOTE
l This table defines the pins for transmitting signals to or receiving signals from the EMUA-02.
l When a TXD+ pin is connected to an RXD+ pin, and a TXD- is connected to an RXD- pin, the RS485
port works in two-line mode.
l The EMUA-02 runs normally when only one RS485 line is connected. It is recommended that two
RS485 lines be connected in active/standby mode, and that RS485 line 1 function as the primary line.
The RS232 serial port is used only when the EMUA-02 is debugged.
Table 2-3 describes the terminals on the port for analog signal detection.
Table 2-3 Terminals on the port for analog signal detection
Issue 01 (2011-04-15)
Silkscree
n
Description
24Vi
(value
range of i: 1
to 4)
2-5
EMUA-02
Product Description
Silkscree
n
Description
12Vi
(value
range of i: 1
to 4)
ANAi
(value
range of i: 1
to 4)
GNDi
(value
range of i: 1
to 4)
NOTE
You can set the DIP switches SW_AE and SW_AV to enable or disable the port for analog signal detection.
For details, see 2.3 DIP Switches on the EMUA-02.
2-6
Issue 01 (2011-04-15)
EMUA-02
Product Description
NOTE
Table 2-4 describes the terminals on the port to which the infrared sensor is connected.
Issue 01 (2011-04-15)
2-7
EMUA-02
Product Description
Table 2-4 Terminals on the port to which the infrared sensor is connected
Silkscree
n
Description
24VI
12VI
OPTI
GND
NOTE
You can set bit 3 of the DIP switch SW_BKE to enable or disable the port to which the infrared sensor is
connected. For details, see 2.3 DIP Switches on the EMUA-02.
NOTE
Table 2-5 describes the terminals on the port to which the smoke sensor is connected.
Table 2-5 Terminals on the port to which the smoke sensor is connected
2-8
Silkscree
n
Description
24VS
Issue 01 (2011-04-15)
EMUA-02
Product Description
Silkscree
n
Description
Smoke
NOTE
You can set bit 2 of the DIP switch SW_BKE to enable or disable the port to which the smoke sensor is
connected. For details, see 2.3 DIP Switches on the EMUA-02.
Table 2-6 describes the terminals on the port to which the door status sensor is connected.
Table 2-6 Terminals on the port to which the door status sensor is connected
Silkscree
n
Description
12VG
GATE
NOTE
You can set bit 4 of the DIP switch SW_BKE to enable or disable the port to which the door status sensor
is connected. For details, see 2.3 DIP Switches on the EMUA-02.
Issue 01 (2011-04-15)
2-9
EMUA-02
Product Description
Table 2-7 describes the terminals on the six-line port for relay node output control.
Table 2-7 Terminals on the six-line port for relay node output control
Silkscree
n
Description
REi+
(value
range of i: 1
to 6)
REi- (value
range of i: 1
to 6)
Cable Connection
Figure 2-11 shows the cable connection for the relay node output control port.
2-10
Issue 01 (2011-04-15)
EMUA-02
Product Description
Figure 2-11 Cable connection for the relay node output control port
For devices with a voltage of 60 V DC or higher, use a 24 V intermediate relay to convert the
output voltage.
Alarm Association Function
The alarm association function enables the EMUA-02 to automatically turn on the corresponding
relay node switch when an environment alarm is detected. Table 2-8 lists the alarms related to
each relay node switch.
Table 2-8 Alarms related to each relay node switch
Relay Node Alarm
Switch
Number i
(Value
Range of i: 1
to 6)
Issue 01 (2011-04-15)
Water alarm
Smoke alarm
2-11
EMUA-02
Product Description
NOTE
l The port for Boolean signal detection is of the dry contact type, OC type, voltage type, or current-type
port.
l All ports for Boolean signal detection support input of Boolean signals of the dry contact type and OC
type.
l Ports S12 to S15 and ports S28 to S31 support input of Boolean signals of the voltage type.
Table 2-9 lists the valid voltage range of voltage-type Boolean signals.
Table 2-9 Valid voltage range of voltage-type Boolean signals
Voltage of the
Input Voltage
Signal
Description
x 3 V DC
Low level
x 5 V DC
High level
3 V DC< x <5 V
DC
Unspecified
Table 2-10 describes the terminals on the port for Boolean signal detection.
2-12
Issue 01 (2011-04-15)
EMUA-02
Product Description
Description
NOTE
You can set the DIP switches SW12A, SW12B, SW24A, and SW24B to enable or disable the port for
Boolean signal detection. For details, see 2.3 DIP Switches on the EMUA-02.
NOTE
Table 2-11 describes the terminals on the port to which the humidity and temperature sensor is
connected.
Table 2-11 Terminals on the port to which the humidity and temperature sensor is connected
Issue 01 (2011-04-15)
Silkscreen
Description
24VT
TEMP
2-13
EMUA-02
Product Description
Silkscreen
Description
24VH
HUMI
NOTE
You can set the DIP switch SW_THE to enable or disable the port to which the humidity and temperature
sensor is connected. For details, see 2.3 DIP Switches on the EMUA-02.
NOTE
Table 2-12 describes the terminals on the port to which the water sensor is connected.
Table 2-12 Terminals on the port to which the water sensor is connected
2-14
Silkscreen
Description
24VW
12VW
Water
GND
Issue 01 (2011-04-15)
EMUA-02
Product Description
You can set bit 1 of the DIP switch SW_BKE to enable or disable the port to which the water sensor is
connected. For details, see 2.3 DIP Switches on the EMUA-02.
Layout
Figure 2-15 shows the layout of the EMUA-02.
Figure 2-15 Layout of the EMUA-02
DIP Switch
Table 2-13 describes the functions and settings of the DIP switches on the EMUA-02.
Issue 01 (2011-04-15)
2-15
EMUA-02
Product Description
Function
Description
SW_ADDR
SW_BKE
Reserved
SW_THE
2-16
Issue 01 (2011-04-15)
EMUA-02
Product Description
Silkscreen
Function
Description
SW_AE
SW_AV
SW12A,
SW12B,
SW24A,
SW24B
NOTE
The following describes the priorities between the settings of DIP switches and the settings on the maintenance
terminal.
l When the communications protocol of the EMUA-02 is selected, the setting of the DIP switch
SW_ADDR has a higher priority than the setting on the maintenance terminal.
l You can also set the corresponding detection functions using other DIP switches. However, the settings on
the maintenance terminal have higher priorities than the settings of the DIP switches.
Technical Parameters
Table 2-14 lists the technical parameters of the EMUA-02.
Issue 01 (2011-04-15)
2-17
EMUA-02
Product Description
Object
Description
Voltage
Test range
0 V DC to 100 V DC
Measurement precision
0.5 V
Test range
Measurement precision
2C (35.6F)
Test range
0% RH to 100% RH
Measurement precision
5%
Boolean value
detection
Measurement range
< 10s
Measurement range
Measurement precision
1%
Response duration
< 1s
Temperature
Humidity
Technical Specifications
Table 2-15 describes the technical specifications of the EMUA-02.
Table 2-15 Technical specifications of the EMUA-02
2-18
Item
Description
Storage temperature
Working temperature
Storage humidity
5% RH to 95% RH
Working humidity
5% RH to 100% RH
DC power
-48 V
0.2 A
Dimensions (width x
depth x height)
Issue 01 (2011-04-15)
EMUA-02
Product Description
Issue 01 (2011-04-15)
Item
Description
Weight
2-19
EMUA-02
Product Description
Issue 01 (2011-04-15)
3-1
EMUA-02
Product Description
Appearance
Figure 3-1 shows the water sensor YW517B.
Figure 3-1 Water sensor YW517B
NOTE
The cable configured with the water sensor YW517B is 2.7 m (8'-5 5/16") long.
Technical Specifications
Table 3-1 describes the technical specifications of the water sensor YW517B.
Table 3-1 Technical specifications
Parameter Name
Description
12 V DC5%
< 80 uA
10 mA to 15 mA
Current
Working temperature
3-2
Issue 01 (2011-04-15)
EMUA-02
Product Description
Appearance
Figure 3-2 shows the smoke sensor JTY-GD-01K.
Figure 3-2 Smoke sensor JTY-GD-01K
NOTE
The cable configured with the smoke sensor JTY-GD-01K is 10 m (32'-3 11/16") long.
Working Principle
When the smoke sensor detects smoke, the red indicator is on. After the system is powered on
immediately after the system is powered off or reset, the red indicator blinks normally. Table
3-2 describes the red indicator on the smoke sensor.
Table 3-2 Indicator on the smoke sensor
Indicator
Meaning
State
Red indicator
An alarm is generated.
On
No alarm is generated.
Blinking
Technical Specifications
Table 3-3 describes the technical specifications of the smoke sensor JTY-GD-01K.
Table 3-3 Technical specifications of the smoke sensor JTY-GD-01K
Issue 01 (2011-04-15)
Parameter Name
Description
24 V DC5%
Working current
<50 mA
3-3
EMUA-02
Product Description
Parameter Name
Description
Power-on duration
30s
Power-on current
<150 mA
Working temperature
Working humidity
Dry contact
Appearance
Figure 3-3 shows the infrared sensor MC-760T.
Figure 3-3 Infrared sensor MC-760T
NOTE
The cable configured with the infrared sensor MC-760T is 10 m (32'-3 11/16") long.
Working Principle
Based on the pyroelectric effect, the 12 V infrared sensor MC-760T detects moving objects using
microwaves and infrared rays.
You can adjust its sensitivity through the DIP switch. For details, see the user guide for the
sensor. The infrared sensor enters the wait state within three minutes after the sensor is powered
on. During this period of time, it cannot generate alarms. After this period of time, the infrared
sensor enters the detection state. It generates an alarm whenever someone enters the equipment
room.
3-4
Issue 01 (2011-04-15)
EMUA-02
Product Description
Technical Specifications
Table 3-4 lists the technical specifications of the infrared sensor MC-760T.
Table 3-4 Technical specifications of the infrared sensor MC-760T
Parameter Name
Description
12 V DC5%
Working current
30 mA
Detection distance
Dry contact
Working temperature
Appearance
Figure 3-4 shows the door status sensor AGX105F.
Figure 3-4 Door status sensor AGX105F
3-5
EMUA-02
Product Description
NOTE
The cable configured with the door status sensor HO-03A is 10 m (32'-3 11/16") long.
Working Principle
When you press down the button at the top of the door status sensor AGX105F, the reed of the
spring touches pins A and B, as shown in Figure 3-6.
Figure 3-6 Working principle
The door status sensor HO-03A is composed of a reed switch and a ferrous magnetic member.
The reed switch consists of two soft magnetic members that are close to each other. When the
ferrous magnetic member moves close to the reed switch, the soft magnetic members are
magnetized and attracted to each other. When the magnetic field is not present, the reed switch
returns to its original position.
Technical Specifications
Table 3-5 describes the technical specifications of the door status sensor AGX105F.
3-6
Issue 01 (2011-04-15)
EMUA-02
Product Description
Description
Working voltage
250 V AC
Rated Current
10.0 A
Pin length
10.60 mm (0 7/16")
Table 3-6 lists the technical specifications of the door status sensor HO-03A.
Table 3-6 Technical specifications of the door status sensor HO-03A
Parameter Name
Description
Effective distance
25 mm (1")
Contact capacity
Impedance
0.3 ohm
Power
10 W
Dry contact
Appearance
Figure 3-7 shows the humidity and temperature sensor WS302A1T4.
Figure 3-7 Humidity and temperature sensor WS302A1T4
Issue 01 (2011-04-15)
3-7
EMUA-02
Product Description
NOTE
The cable configured with the humidity and temperature sensor WS302A1T4 is 3 m (9'-10 1/8") long.
Working Principle
The humidity and temperature sensor WS302A1T4 uses a Pt100 thermistor as the temperature
sensing component and an S108 macromolecular humidity-sensitive capacitor as the humidity
sensing component. The humidity and temperature sensor WS302A1T4 uses the Surface
Mounting Technology (SMT) and applies to wall installation.
Technical Specifications
Table 3-7 describes the technical specifications of the humidity and temperature sensor
WS302A1T4.
Table 3-7 Technical specifications of the humidity and temperature sensor WS302A1T4
Parameter
Name
Description
Temperature Sensor
Humidity Sensor
Test range
0% RH to 100% RH
Accuracy
2% RH [ambient temperature:
+25C (+77F), ambient humidity:
30% RH to 80% RH]
Power supply
voltage
12 V DC to 24 V DC
Signal output
range
Sampling
resistance
500 ohms
Sensitive
component
Pt100 thermistor
Working
temperature
Storage
temperature
Shell material
Issue 01 (2011-04-15)
EMUA-02
Product Description
Exterior
Figure 3-8 shows a YW101A003L005 fuel level sensor.
Figure 3-8 YW101A003L005 fuel level sensor
NOTE
Principle
The YW101A003L005 fuel level sensor supports liquid level inputs and current outputs. This
ensures high-accuracy detection of the fuel level.
Technical Specifications
Table 3-8 shows the technical specifications of the YW101A003L005 fuel level sensor.
Table 3-8 Technical specifications of the YW101A003L005 fuel level sensor
Issue 01 (2011-04-15)
Item
Specification
Detection range
0 m to 3 m
Overpressure
3 x FS
Static accuracy
0.2% FS
Response time
Operating voltage
12 V DC to 36 V DC
Output signal
4 mA to 20 mA
Insulation resistance
Operating temperature
0C to 85C
Storage temperature
-40C to 85C
Protection class
IP68
3-9
EMUA-02
Product Description
Working voltage: 24 V
The relationship between the humidity and the output current must meet the requirements as
shown in Figure 3-9.
Figure 3-9 Relationship between the humidity and the output current
The relationship between the temperature and the output current must meet the requirements as
shown in Figure 3-10.
Figure 3-10 Relationship between the temperature and the output current
3-10
Issue 01 (2011-04-15)
EMUA-02
Product Description
Current type
The output current is weaker than 200 uA when no water is detected.
The output current is stronger than 1 mA when water is detected.
Voltage type
The output voltage is lower than 3.3 V when no water is detected.
The output voltage is higher than 5 V when water is detected.
Current type
The output current is weaker than 200 uA when the door is closed.
The output current is stronger than 1 mA when the door is open.
Voltage type
The output voltage is lower than 3.3 V when the door is closed.
The output voltage is higher than 5 V when the door is open.
Current type
The output current is weaker than 200 uA when no smoke is detected.
The output current is stronger than 3 mA when smoke is detected.
Voltage type
The output voltage is lower than 3.3 V when no smoke is detected.
The output voltage is higher than 5 V when smoke is detected.
l
Issue 01 (2011-04-15)
3-11
EMUA-02
Product Description
Current type
The output current is weaker than 200 mA when no moving objects are detected.
The output current is stronger than 1 mA when moving objects are detected.
Voltage type
The output voltage is lower than 3.3 V when no moving objects are detected.
The output voltage is higher than 5 V when moving objects are detected.
CAUTION
The fuel level sensor requires high security. Therefore, a customized fuel level sensor is not
recommended. If a customized fuel level sensor must be used, it must meet the requirements for
the operating voltage, output signal type, detection range, operating temperature, insulation
resistance, overpressure, and protection class.
l
Operating voltage: 24 V
Detection range: 0 m to 3 m
Figure 3-11 shows the relationship between the fuel level and the output current.
3-12
Issue 01 (2011-04-15)
EMUA-02
Product Description
Figure 3-11 Relationship between the fuel level and the output current
Issue 01 (2011-04-15)
3-13