TECHNICAL SPECIFICATION

ABB PTHV S.p.A.


Unita Operativa
ADDA

Multifunctional Air
Insulated Apparatus

123-170 kV

Issued/Emesso

30.08.2002

UA600885

Checked/Controllato
Approved/Approvato
Revision/Revisione

1 26.06.02

20.09.04

17.11.04

31.03.05

TECHNICAL SPECIFICATION

ABB PTHV S.p.A.


Unita Operativa
ADDA

Index
NORMAL SERVICE CONDITIONS ........................................................................................3
WEIGHTS OF EQUIPMENT ...................................................................................................4
SF6 GAS WEIGHT (THREE POLES)...........................................................................................4
STANDARD FINISHING .........................................................................................................4
CURRENT RATINGS ...................................................................................................................6
CIRCUIT BREAKER AND CURRENT TRANSFORMER ......................................................................8
LINE DISCONNECTOR ..............................................................................................................10
EARTHING SWITCH ..................................................................................................................11

UA600885
pag. 2/11

ABB PTHV S.p.A.


Unita Operativa
ADDA

TECHNICAL SPECIFICATION
NOTE:

All values included in this Data Sheet are referred to the standard COMPASS module.
For final technical characteristics please refer to the specific project documentation.

NORMAL SERVICE CONDITIONS


Installation type

Outdoor

Altitude above sea level

1000

Maximum ambient air temperature

40

Minimum ambient air temperature

30*

Relative humidity

100

Wind pressure (wind speed 36 m/s) 740

Pa

740

Solar radiation (IEC 694)

W/m2

Earthquake (IEC1166)

Degree of protection (IEC 60529)

0.5

IP class

Pollution level (IEC 60815)


* -25C with pure SF6 for 750 kV BIL;

1000

44**
III Heavy

**other on request

UA600885
Rev4 dated 31.03.05

pag. 3/11

ABB PTHV S.p.A.


Unita Operativa
ADDA

TECHNICAL SPECIFICATION

WEIGHTS OF EQUIPMENT
COMPASS

kV

123

145

Weight

kg

3200

3700

145170

Support stand

kg

70

control cubicle

kg

120

170

3850

4300

SF6 GAS WEIGHT (THREE POLES)

Weight

kg

123

145

145170

170

18

28

29

32

STANDARD FINISHING
Support structure (hot dip galvanised according to DIN 50976)

45 85*
Grey (RAL7035)

Surface painting
* Average galvanising thickness based on steel support thickness

UA600885
Rev4 dated 31.03.05

pag. 4/11

ABB PTHV S.p.A.


Unita Operativa
ADDA

TECHNICAL SPECIFICATION

RATED INSULATION LEVEL


123

Rated voltage
Rated frequency

145

145170

170

50/60

common value

230

275

275

325

across the isolating distance

265

315

315

325

common value

550

650

650

750

across the isolating distance

630

750

750

750

UA600885
Rev4 dated 31.03.05

pag. 5/11

TECHNICAL SPECIFICATION

ABB PTHV S.p.A.


Unita Operativa
ADDA

CURRENT RATINGS
Rated continuous current

1600*

Rated short-time withstand current

kA

40

Rated peak withstand current

kA

104

Temperature rise of active parts at rated continuous current

< 65

Rated short circuit duration

CURRENT TRANSFORMER
Type

TG

Standard Application

IEC 60044-1

Insulation

SF6

Rated Voltage

kV

123 -170

Number of cores

1 5 **

Rated primary current

50 2000

Rated Overcurrent Factor

1,2

Rated secondary current


Performance

1 or 5

VA

5 60**

Protection Core
Class

5P-10P

Accuracy Limit Factor

10-20-30

Measurement Core
Class

0,2 0,5 -1

* up to 2000 A on request
** This is a general indication. The number of cores available in standard case depends on the primary current
and the performance required.

UA600885
Rev4 dated 31.03.05

pag. 6/11

TECHNICAL SPECIFICATION

ABB PTHV S.p.A.


Unita Operativa
ADDA

SF6 GAS SYSTEM (RELATIVE PRESSURE)


Annual SF6 leakage

<0,5%

CIRCUIT BREAKER and CURRENT TRANSFORMER (Relative


Value)

kV

123

Filling pressure at 20 C

kPa

400

600

Min. service pressure at 20C

kPa

330

540

Rated insul. pressure at 20 C

kPa

330

540

Alarm level 1 at 20 C (Only Alarm)

kPa

350

560

Alarm level 2 at 20 C (Circuit breaker lock or trip)

kPa

330

540

145

145 170

ENCLOSURE
Design pressure

700

Routine test pressure

1100

Bursting pressure

>2900

Bursting disc release pressure

1000

UA600885
Rev4 dated 31.03.05

pag. 7/11

170

ABB PTHV S.p.A.


Unita Operativa
ADDA

TECHNICAL SPECIFICATION

CIRCUIT BREAKER AND CURRENT TRANSFORMER


Frequency

50

Hz

Type

60
LTB

Operating mechanism (spring type, three pole operated)

BLK 222

Operating mechanism (spring type, single pole operated)

BLK 82

Maximum number of mechanical operation for drive mechanism

10.000

Rated operating sequence acc. to IEC

O - 0.3 s - CO -1 min CO

Stored switching sequence

O CO

Rated current

1600 *

Rated short-time withstand current

kA

40

Rated making current

kA

Rated short circuit duration

100

104

Maximum number of operations at rated current

3
5.000

CHARACTERISTIC FOR TERMINAL FAULT 100% (test duty 4, 5 based on IEC60056)


Short circuit breaking current

kA

40

First reference voltage

kV

208

Point of time t1

104

Peak value

kV

291

Point of time t2 and t3

312

Starting point td

kV/s

Rate of rise

CHARACTERISTIC FOR SHORT LINE FAULT (90% according to IEC60056)


Frequency

Hz

Short line fault current

kA

36

Wave impedance

450

Peak value

kV

194

Rated peak factor

50

60

1.6

UA600885
Rev4 dated 31.03.05

pag. 8/11

TECHNICAL SPECIFICATION

ABB PTHV S.p.A.


Unita Operativa
ADDA

Time delay tdL

Time tL to peak uL

3.08

2.57

kV/s

7.84

9.04

Rate of rise of transient recovery voltage

< 0.1

23 4

Opening time

ms

Arcing time

ms

Break time

ms

< 50

Closing time

ms

30 5

opening

m/s

4.6 0.5

closing

m/s

4.6 0.5

11.5 21.5

13 21

Contact speed

AUXILIARIES
DC
Rated voltage

110125

220

Rated current

Operating coils
DC
Rated voltage

110125

220

Power Consumption

200

200

Operating current

1,1

Circuit breaker motor


0 - 60 Hz
Rated voltage BLK 222

110125

220

Power Consumption

1500

1500

Operating current

13

Starting current

20

11

Auxiliary contacts

5 NO + 5 NC **

Rated voltage BLK 82

110125

220

Power Consumption

600

600

Operating current

2,5

UA600885
Rev4 dated 31.03.05

pag. 9/11

ABB PTHV S.p.A.


Unita Operativa
ADDA

TECHNICAL SPECIFICATION

Starting current

15

Auxiliary contacts

5 NO + 5 NC **

* up to 2000 A on request
** others by means relays

LINE DISCONNECTOR
Type

SLT

Operating mechanism (three pole operated)

SLT 11
kV

123

145

145170

170

Common value

kV

230

275

275

325

Across the isolating distance

kV

265

315

325

325

Common value

kV

550

650

650

750

Across the isolating distance

kV

630

750

750

750

Rated voltage
Rated power frequency withstand voltage

Rated short time withstand voltage (1 sec)

Rated current

1600*

Rated short time withstand current

kA

40

Rated peak current

kA

108

Rated short circuit duration


Post insulator creapage distance

mm

Motor operating time (disconnector)

3320

3650

3875

4300

<15

AUXILIAIRES
Rated voltage

VDC

110-125/220

Rated current

ADC

Disconnector motor
DC - AC
Rated voltage

110-125

400

Power Consumption

800

1000

Operating current

2,5

UA600885
Rev4 dated 31.03.05

pag. 10/11

ABB PTHV S.p.A.


Unita Operativa
ADDA

TECHNICAL SPECIFICATION

Starting current

Auxiliary contacts

38

4 NO + 4 NC**

* Up to 2000 A on request
** This is a general indication. The final number of available contacts for the customer depends on specific
configuration, please refers to the specific electric diagram in case of order. In any case other contacts will be
available by means relays.

EARTHING SWITCH
Type

STC

Operating mechanism (three pole manual operated)

STC***

Rated voltage

kV

123

145

145170

170

Rated power frequency withstand voltage

kV

230

275

275

325

Rated lightning impulse withstand voltage (1 sec)

kV

550

650

650

750

Rated current

1600 *

Rated short time withstand current

kA

31,5

Rated peak current

kA

80

Rated short circuit duration


Post insulator creapage distance (standard)

mm

3320

3650

3875

4300

AUXILIARIES
Rated voltage

VDC

110125/220

Rated current

ADC

Auxiliary contacts

4 NO + 4 NC **

* Up to 2000 A on request
** This is a general indication. The final number of available contacts for the customer depends on specific
configuration, please refers to the specific electric diagram in case of order. In any case other contacts will be
available by means relays.
*** Motorized drive mechanism type MT available on request.

UA600885
Rev4 dated 31.03.05

pag. 11/11