TITLE
TWO STOREY REINFORCED CONCRETE
BUILDING AT PYIHTAUNG SU STREET,
BAHAN TOWNSHIP, YANGON,
MYANMAR
Prepare for:
Mdecins Sans Frontires (MSF), Myanmar
Page | 0
REPORT TITLE
PROJECT NO
MEC160701
CLIENT
MSF
REVISION NO
DATE
Prepared By:
Approved By:
Page | 1
Contents
Summary........................................................................................................................ 3
Introduction................................................................................................................... 4
Performance Objective .............................................................................................. 5
Seismicity of The Area.................................................................................................. 6
Foundation .................................................................................................................... 7
Material Property.......................................................................................................... 8
Load Path ...................................................................................................................... 8
Redundancy Check .................................................................................................... 8
Column Axial Stress Check ......................................................................................... 8
Connection Check .................................................................................................... 10
Seismic Hazard Assessment ...................................................................................... 10
Recommendations .................................................................................................... 11
Page | 2
Summary
This report presents the findings of the seismic assessment of two storey
reinforced concrete building at No. 38C, Pyihtaungsu Street, Bahan Township,
Yangon, Myanmar.
The purpose of the assessment was to investigate the seismic performance of
the building. The assessment has done in July 2016.
The building has been assessed based on received structural documents and
facts gathered from the site inspection. It was not a benchmark building and
has not designed with seismic resistant design. Therefore, the inherent seismic
resisting capacity of the structural components of the building were checked
and presented in the report.
The report does address mainly to seismic safety structural issue only and does
not address other such as security, fire safety and assess for disabled.
Page | 3
Introduction
Myanmar Earthquake Committee has been engaged by Mdecins Sans
Frontires-Myanmar to provide a seismic assessment of two storey building
situated at 38C, Pyihtaungsu Street, Bahan Township, Yangon.
Following set of structural drawings were received from MSF.
1.
2.
3.
4.
5.
Foundation Plan
Floor Beam Plan
Roof Beam Plan
Section
Foundation Column and
Beam Detail
6. Doors and Windows Detail
7. Stair and Retaining Wall
Detail Schedule of
Reinforcement
Following works have been
carried out at the site.
1. None Destructive Test
2. Visual Inspection
3. Hazard Review
It is two story reinforced
concrete building used for
residential purpose. According
to structural drawings received,
it was built around 2002.
The building type is C1 Concrete
Moment Frame. It is ordinary
moment resisting frame with
brick masonry infilled and has
not designed for seismic
resistant. Although the building
has not designed for seismic, it
has some extent of capacity to resist seismic force with respect of the
strength of the building and seismic demand of the location.
Page | 4
Performance Objective
The assessment is done
according to Tier 1 and Tier 2
analysis of ASCE 41-13 Seismic
Evaluation and Retrofitting of
Existing Buildings
Performance objectives can be
defined according to the
Seismic Hazard Level as follow.
-
Immediate
Occupancy
(IO)
Level
for
Minor
Frequent Seismic event.
Life Safety (LS) Level for
Moderate Rare Seismic
event
(BSE-1E,
20%
exceedance
over
50
years)
Collapse Prevention (CP) Level for Severe Very Rare Seismic event (BSE2E, 5% exceedance over 50 years)
LS
CP
IO
Page | 5
SDS = 2/3 Fa Ss
Fa = 1.6 for Soil Type Sc
SDS = 2/3 x 1.6 x 0.15 = 0.16, <0.33g, Low Seismicity
Foundation
According to geological map of Yangon, the supporting ground of the
building is quite strong. The supporting underground formation is Arzanigon
sandrock which is part of Irrawady formation of Pliocene age.
Therefore, even the foundation
of the building is isolated pad
footing, since the bearing of the
soil is quite strong, the
performance seems to be good.
As a withness, there is no
foundation failure or settlement
seen during the on-site
investigation.
A rough check on its foundation
performance is checked as
follow.
Foundation under review = F1
According to the structural drawing,
footing size of F1 = 5x5
Estimated load tributary area = 8x16
Estimated total load on floor = 250 psf
Total load on foundation with 25% for
roof and 25% for ground floor = 250 x
(1+0.25+0.25) x 8 x 16 = 48 kip
Estimated pressure on foundation = 48
/5/5 = 1.92 ksf or 0.86 ton/sft
The estimated pressure is significantly less than the bearing capacity of lateric
soil of such area. Therefore, foundation is good enough for such area.
There is no foundation problem and the bearing capacity checking is also
complied with the assumed strength of the underlying ground.
Page | 7
Material Property
According to ASCE, default compressive strength of
structural concrete is 3 ksi. Based on on-site NDT
measurements, the strength of the members can be
seen as follow.
Columns = 3.6 ksi with minimum strength as low as 1.6
ksi
Beams = 6.3 ksi with minimum strength at 4.9 ksi.
Columns
Aveage 25.2 Mpa 3.6 ksi
Maximum 44.0 Mpa 6.4 ksi
Minimum 11.0 Mpa 1.6 ksi
Beams
Aveage 43.7 Mpa 6.3 ksi
Maximum 54.0 Mpa 7.8 ksi
Minimum 34.0 Mpa 4.9 ksi
Load Path
The building has a simple vertical load path as a two story building although
there were shifting of brick walls on first floor. The roofing is made of metal
sheet which is light weight and good for seismic resistant.
Redundancy Check
The number of lines of moment frames in X
direction is 4 and Y direction is 3 which are
greater than 2. Therefore, the building is
complied with redundancy requirement.
Page | 8
Estimated column load at the Ground Floor Level with 25% for roof = 250 x (1+0.25) x 8 x 16 =
40 kip
Estimated stress of typical ground floor column = 40/9/9 = 0.49 ksi
The capacity = 0.49/1.6 = 0.31 for minimum strength 1.6 ksi
The capacity = 0.49/3.6 = 0.14 for average strength 3.6 ksi
Therefore, the average strength columns are enough for the requirement of
0.2 fc. However, the lowest strength columns shall be reviewed further and
strengthen if necessary.
V = C Sa W
For RC 2 story building, C shall be taken as 1.2
Sa = SDS = 0.16
Therefore, Sa = SDS = 0.16
Space
b d
garage
12 16
portico
14 12
main
40 48
deduct 1 -18 6
deduct 2
-6 8
total area
area
192
168
1920
-108
-48
2124
Item
b
d
I
L
K
f'c
E
Beam Column
9
9
18
9
4374
547
12
12
364.5
45.6
1.6 ksi
2280 kip/in3
The calculated drift is much less than the provision. Therefore, drift is complied
with the requirement.
Shear stress of columns can also be calculated as follow.
Shear Stress Vc = 152.9 / 28 = 5.4 kip
Page | 9
unit
sft
sft
sft
sft
sft
sft
Connection Check
According to the drawing received, all
concrete columns are doweled into
the foundation with a minimum of four
bars. Therefore, the building meets the
requirement for connection and anchorage.
Recommendations
In general, although the building
has not designed for seismic
resistance, the risk of seismicity is
less as the mass of the building is
less, the seismicity of the
location is low and the soil
condition of the site is good.
Therefore, it can be concluded
that the building is seismically
not a critical building. In order to
be a seismically safe space,
following few ratifications are
recommended.
1. The columns of the ground floor which shows weak NDT results shall be
strengthened. The deficient columns are C7, C17 and C21. The applied
actual loads will be smaller than the typical stress value. Therefore, the
actual load shall be verified for each column and check for its
capacity individually.
2. The two steel water tanks above the roof has to be anchored securely
to the supporting slab.
3. Wiring works and electrical connections of the water pump beneath
the two steel water tanks have to be replaced with safer system.
Page | 11
Page | 12
Page | 13
Deficient
Columns
Page | 14
Page | 15
Page | 16