Smith, PE
Consulting Engineers
FOR:
Bear Creek Coffee
Overhang (feet) =
Shading Factor5 =
Window Header (feet) =
Shadow Length (feet) =
Shaded Glass (feet) =
1
2.7
0.9
2.7
1.8
DCSPE# 3105
75
Ref. City = Albuquerque NM
94 Time of Day =
Noon
61
Latitude =
35 0'
0
27
0.23
6
13
Sensible
BTU/Hr
Latent
BTU/Hr
Solar Factor
Shading
Sq. Ft.
23
3
18
20
Sq. Ft.5
6
2
12
11
SHGF3
103
103
103
103
SC4
0.6
0.6
0.6
0.6
Sq. Ft.
U Factor6
TD or Equal7
All
64
1.04
13
865
432
0.065
13
365
198
0.053
13
136
198
0.06
44
523
Glazing Exposures
Front (8 x 2.5) + 2(3 x .5)
Rear 2(3 x .5)
Right (2.5 x 2.5) + (3 x 4)
Left (2.5 x 2.5) + (4 x 3.5)
1051
62
371
556
TRANSMISSION GAINS
Glass
Walls
Sensible
Latent
Allowances
Sq. Ft /
Occupant
60
60
Incandescent
Flourescent
# Fixtures
0
3
Occupant Load
Lights
Equipment
Heat Gain /
Occupants
Occupant9
3
3
BTUH
315
325
# Bulbs
0
2
Watts / Bulb
0
32
945
975
Constant
3.4
4.1
0
787
2,138
522
Sensible
BTU/Hr
Latent
BTU/Hr
INFILTRATION
Non-Door
Envelope
Envelope Leakage
Volumn
Cu. Ft.
1584
Infiltration10
AC / hr
0.4
Occupancy
Avg stay
Hrs
4
# Doors
Traffic Rate
1.5
TD
13
Grains
Constant
1.1
0.68
Doors
All Doors
Total Loads
Sensible load
Latent load
3
Total
Infiltration
21
21
Total
CFM
11
Total11
CFM / door
10
300
0
8,099
1,497
Sensible
Subtotal
8099
405
VENTILATION
Ventilation
CFM/person
Requirement Test
Occupant Fresh Air
30
Exhaust Make-up Air
Total Loads
Sensible load
Latent load
Occupants
Total
CFM
90
0
13
Greatest
Ventilation
90
90
TD
13
Grains
0
Constant
1.1
0.68
1287
0
9,791
2,994
Daniel C. Smith, PE
Consulting Engineers
FOR:
Bear Creek Coffee
DCSPE# 3105
75
16
59
Load
TRANSMISSION LOSSES
Sq. Ft.
U Factor6
TD
All
64
1.04
59
3927
432
0.065
59
1657
198
0.053
59
619
198
0.06
59
701
Volumn
Cu. Ft.
1584
Infiltration10
AC / hr
0.6
Occupancy
3
Avg stay
Hrs
4
Total CFM
26
TD
59
Glass
Walls
INFILTRATION
Non-Door
Envelope
Envelope Leakage
Doors
All Doors
Total
CFM
16
# Doors
Traffic Rate
1.5
Constant
1.1
Total11
CFM / door
10
1687
8,591
Heating Loss
Gain Factor
0.05
12
Sensible
Subtotal
8591
430
VENTILATION
Total Loads
Sensible load
Greatest
Ventilation
90
TD
59
Constant
1.1
5841
Load
HUMIDIFICATION LOAD
Maximum14
Desired
Winter RH
22%
Water
Total CFM
Humidification Load
Water requirement
Consumption15
gal/day/
100 CFM
116
116
2.9
Supply Air
Supplied16
Water
Required
gal/day
Humidifier
Heat Made14
BTUH/
100 CFM
1075
Heat Load
BTUH
1247
Reference
1 -- ACCA Manual N Commercial 4 ed. - Table 1
1247
3.4
16,109
Conditions
cooling loads ==> summer; heating loads ==> winter
R-13 2x4 walls w/ 7/16" OSB; use (r13, 1/2" fibrous board, wood material)
drive-in but patrons do not eat inside; use (Bank - standing, slow walk, light work)
single door - glass & wood, summer, total entrances based on traffic rate (i.e., none)
"stubbed" possible, but worst case use (R6 ins. wrap on exposed ducts in vented space)
"stubbed" possible, but worst case use (R6 ins. wrap on exposed ducts in vented space, supply
below 120)
+16 outdoor db, 75 F room db, single pane glass; use (+20 outdoor db)
75 F room db, +16 outdoor db, 22%; use (Table 19C, +15 outdoor db, 20%)
16 -- Building Plans