Daniel C.

Smith, PE
Consulting Engineers

FOR:
Bear Creek Coffee

13237 Melvin Arnold Rd


Raleigh, NC 27613
919-844-6050
Fax 919-846-0643

2002 Southern Blvd.


Rio Rancho, NM 87124
Model# BCC 822

ACCA Manual N and ASHRAE Machine Loads - Simplified Cooling


DESIGN CONDITIONS (COOLING)
Length =
22'
Width =
9'
Height =
8'

Overhang (feet) =
Shading Factor5 =
Window Header (feet) =
Shadow Length (feet) =
Shaded Glass (feet) =

1
2.7
0.9
2.7
1.8

Room design temp. =


Outside dry bulb @ 3p1 =
Outside wet bulb1 =
55% RH grains 1 =
Daily range 1 =
Correction factor2 =
Correction =
Temp. difference (TD) =

DCSPE# 3105

75
Ref. City = Albuquerque NM
94 Time of Day =
Noon
61
Latitude =
35 0'
0
27
0.23
6
13
Sensible
BTU/Hr

Latent
BTU/Hr

SOLAR RADIATION HEAT GAIN THROUGH GLASS


- Overhang

Solar Factor

Shading

Sq. Ft.
23
3
18
20

Sq. Ft.5
6
2
12
11

SHGF3
103
103
103
103

SC4
0.6
0.6
0.6
0.6

Sq. Ft.

U Factor6

TD or Equal7

All

64

1.04

13

865

All (less glazing area)


Floors
Unheated crawl space
Roof/Ceiling
Vented wood trusses

432

0.065

13

365

198

0.053

13

136

198

0.06

44

523

Glazing Exposures
Front (8 x 2.5) + 2(3 x .5)
Rear 2(3 x .5)
Right (2.5 x 2.5) + (3 x 4)
Left (2.5 x 2.5) + (4 x 3.5)

1051
62
371
556

TRANSMISSION GAINS
Glass
Walls

INTERNAL HEAT GAIN


Max. FL Area

Sensible
Latent

Allowances
Sq. Ft /
Occupant
60
60

Incandescent
Flourescent

# Fixtures
0
3

Occupant Load

Lights

Equipment

Heat Gain /
Occupants

Occupant9

3
3

BTUH
315
325

# Bulbs
0
2

Watts / Bulb
0
32

(values transferred from Equipment sheet)

945
975
Constant
3.4
4.1

0
787
2,138

522

Sensible
BTU/Hr

Latent
BTU/Hr

INFILTRATION
Non-Door
Envelope
Envelope Leakage

Volumn
Cu. Ft.
1584

Infiltration10
AC / hr
0.4

Occupancy

Avg stay
Hrs
4

# Doors

Traffic Rate

1.5

TD
13

Grains

Constant
1.1
0.68

Doors
All Doors

Total Loads
Sensible load
Latent load

3
Total
Infiltration
21
21

Total
CFM
11

Total11
CFM / door
10

300
0

SUBTOTAL COOLING - LOAD FOR SPACE

8,099

1,497

SUPPLY DUCT HEAT GAIN


Gain Factor12
Cooling Gain
0.05

Sensible
Subtotal
8099

405

VENTILATION
Ventilation
CFM/person
Requirement Test
Occupant Fresh Air
30
Exhaust Make-up Air

Total Loads
Sensible load
Latent load

Occupants

Total

CFM
90
0

13

Greatest
Ventilation
90
90

no equipment requires make-up air

TD
13

TOTAL COOLING - LOADS ON EQUIPMENT

Grains
0

Constant
1.1
0.68

1287
0

9,791

2,994

Daniel C. Smith, PE
Consulting Engineers

FOR:
Bear Creek Coffee

13237 Melvin Arnold Rd


Raleigh, NC 27613
919-844-6050
Fax 919-846-0643

2002 Southern Blvd.


Rio Rancho, NM 87124
Model# BCC 822

ACCA Manual N and ASHRAE Machine Loads - Simplified Heating

DCSPE# 3105

DESIGN CONDITIONS (HEATING)


Room design temp. =
Outside dry bulb1 =
Temp. difference (TD) =

75
16
59
Load

TRANSMISSION LOSSES
Sq. Ft.

U Factor6

TD

All

64

1.04

59

3927

All (less glazing area)


Floors
Unheated crawl space
Roof/Ceiling
Vented wood trusses

432

0.065

59

1657

198

0.053

59

619

198

0.06

59

701

Volumn
Cu. Ft.
1584

Infiltration10
AC / hr
0.6

Occupancy
3

Avg stay
Hrs
4

Total CFM
26

TD
59

Glass
Walls

INFILTRATION
Non-Door
Envelope
Envelope Leakage

Doors
All Doors

Total Infiltration Load

Total
CFM
16
# Doors

Traffic Rate

1.5
Constant
1.1

SUBTOTAL HEATING - LOAD FOR SPACE

Total11
CFM / door
10

1687
8,591

SUPPLY DUCT HEAT LOSS

Heating Loss

Gain Factor
0.05

12

Sensible
Subtotal
8591

430

VENTILATION
Total Loads
Sensible load

Greatest
Ventilation
90

TD
59

Constant
1.1

5841

Load
HUMIDIFICATION LOAD
Maximum14

Desired
Winter RH

22%
Water
Total CFM

Humidification Load
Water requirement

Consumption15
gal/day/
100 CFM

116
116

2.9

Supply Air
Supplied16
Water
Required
gal/day

Humidifier

Heat Made14
BTUH/
100 CFM
1075

Heat Load
BTUH
1247

TOTAL HEATING - LOADS ON EQUIPMENT

Reference
1 -- ACCA Manual N Commercial 4 ed. - Table 1

1247

3.4

16,109

Conditions
cooling loads ==> summer; heating loads ==> winter

2 -- ACCA Manual N Commercial 4 ed. - Table 6


3 -- ACCA Manual N Commercial 4 ed. - Table 2A

Light construction, 32 deg, worst case direction (SE) @ noon

4 -- ACCA Manual N Commercial 4 ed. - Table 3

1" tinted insulated glass; use (bare, 3/8" 50% tint)

5 -- ACCA Manual N Commercial 4 ed. - Table 4

32 deg, noon, worst case direction (S)

6 (Glazing) -- ACCA Manual N Commercial 4 ed. - Table 5

1" tinted insulated glass; use (1 pane, tinted, summer cooling)

6 (Walls) -- ACCA Manual N Commercial 4 ed. - Table 7B

R-13 2x4 walls w/ 7/16" OSB; use (r13, 1/2" fibrous board, wood material)

6 (Floors) -- Building Plans

2X12 PT FJ w/ R-19 insulation; use (1/R == 1/19)

6 (Roof/Ceiling) -- ACCA Manual N Commercial 4 ed. - Table 7T

wood trusses, R-19 insulation; assume (ventilated truss space)

7 (Walls) -- ACCA Manual N Commercial 4 ed. - Table 8

use (TD value) because orientation unknown

7 (Floors) -- Building Plans

3" air gap below floor; use (TD value)

7 (Roof/Ceiling) -- ACCA Manual N Commercial 4 ed. - Table 9

ETD Group given; use (ETD R-4, noon)

8 -- 2000 International Building Code - Table 1003.2.2.2

Mercantile, areas on other floors

9 -- ACCA Manual N Commercial 4 ed. - Table 10

drive-in but patrons do not eat inside; use (Bank - standing, slow walk, light work)

10 -- ACCA Manual N Commercial 4 ed. - Table 13A

use (low exhaust, average construction, neutral pressure)

11 -- ACCA Manual N Commercial 4 ed. - Table 13B

single door - glass & wood, summer, total entrances based on traffic rate (i.e., none)

12 (Cooling) -- ACCA Manual N Commercial 4 ed. - Table 16


12 (Heating) -- ACCA Manual N Commercial 4 ed. - Table 16

"stubbed" possible, but worst case use (R6 ins. wrap on exposed ducts in vented space)
"stubbed" possible, but worst case use (R6 ins. wrap on exposed ducts in vented space, supply
below 120)

13 -- ACCA Manual N Commercial 4 ed. - Table 14

drive-in; use (30 cfm/person)

14 -- ACCA Manual N Commercial 4 ed. - Table 18

+16 outdoor db, 75 F room db, single pane glass; use (+20 outdoor db)

15 -- ACCA Manual N Commercial 4 ed. - Table 19

75 F room db, +16 outdoor db, 22%; use (Table 19C, +15 outdoor db, 20%)

16 -- Building Plans

assume (no humidifier, supply air used)