Beruflich Dokumente
Kultur Dokumente
PIPING SPECIFICATION
CLASS 125 DUCTILE IRON CEMENT MORTAR LINED
UNDETERMINED CORR. ALLOW.
UNDERGROUND FIRE WATER SERVICE (NFPA-24) UL/FM
200 PSIG @ 33F (0.56C) to 100F (38C) (Note 1, 2)
New
R E V I S I O N
R E C O R D
Revision No: A
Date: 09/25/07
Reviewed By:
O. B. Thomas
Prepared By:
Lucy Li
Checked By:
M. Zaidi
Project Approval:
Client Approval:
200 (51.0)
Temperature - F (C)
COMPONENT &
DESCRIPTION
SIZE RANGE (NPS)
PIPE
4 - 12
Ductile Iron, centrifugally cast,
restrained push-on joint with
cement mortar lining
14 - 24
FITTINGS
4 - 24
RATING /
THICKNESS
Pressure Class
350 psi
Pressure Class
250 psi
COMPONENT
MATERIAL SPECIFICATION
SPECIFICATION (ASTM unless otherwise indicated)
Pipe: ANSI/AWWA C151/A21.51
UL/FM
Lining: ANSI/AWWA C104/A21.4
Pipe: ANSI/AWWA C151/A21.51
UL/FM
Lining: ANSI/AWWA C104/A21.4
SEE
NOTES
1, 2, 4, 5,
6
ANSI/AWWA C153/A21.53
ANSI/AWWA C153/A21.53
ANSI/AWWA C111/A21.10
ANSI/AWWA C111/A21.11
ENCASEMENT
Polyethylene Tube, 8 mill
thickness
ANSI/AWWA C105/A21.5
Page 1 of 3
New
PORT
OR
DISC
VALVE
CODE
ASTM
SPEC
Z340AG-94A A-536
SEE
NOTES
1, 11
COMMENT
UL/ FM approved
Rated to 250 PSI
WWP
Recommended
Manufacturer and
Figure No. AFC
Series 2500 or
approved equal
Page 2 of 3
New
Notes:
1.
2.
All pipe and piping components shall be Factory Mutual/ Underwriter's Laboratory (UL/FM) approved.
Assembly & installation of boltless restrained pipe with field-lok 350 joints, flanges and fittings will be performed per NFPA-24 and
manufacturers recommended instructions.
3. The piping system to be a fully restrained field-lok 350 push-on joint system.
4. All exterior surface of Ductile iron Pipe shall be asphaltic coated one (1) mil average dry thickness (see ANSI/AWWA C110/A21.10 and
Cement-Mortar Lining per ANSI/AWWA C104/A21.4). Fittings to be Fusion Bonded Epoxy Coated interior and exterior per
ANSI/AWWA C116/A21.16 (Note: Based on availability, the fittings may be Cement Mortar lined per ANSI/AWWA C104/A21.4).
5. For soil corrosion protection, all under ground Ductile Iron pipe and fittings and other appurtenances, to be encased in loose
polyethylene wrap or tubes per ANSI/AWWA C105/A21.5. The installation procedure for the polyethylene encasement tube shall be in
accordance with applicable standard and the manufacturer's instructions.
6. All system should be flushed in accordance with the following minimum preferred flow rates:
NPS 4 400gpm,
NPS 6 900gpm,
NPS 8 1600gpm,
NPS 14 and larger 4500gpm.
7. Gaskets for Ductile iron piping and fittings to be furnished by manufacturer and shall be packed separately.
8. Gasket lubricant to be compatible with gasket material and furnished by the pipe manufacturer.
9. Mechanical joint retainer glands to be used on all M.J. connections. Retainer glands to be "Mega-Lug retainer glands" by 'EBBA' Iron or
equal.
10. This Standard is to be used in conjunction with the following standards and codes:
a. ANSI/AWWA C150/A21.50 - Thickness Design of Ductile-Iron Pipe
b. ANSI/AWWA C151/A21.51 - Ductile Iron Pipe, Centrifugally Cast for Water
c. ANSI/AWWA C110/A21.10 - Ductile Iron and Gray-Iron Fittings,3 in. through 48 in. for water
d. ANSI/AWWA C111/A21.11 - Rubber-Gasket joints for Ductile-Iron Pressure pipe and fittings
e. ANSI/AWWA C105/A21.5 - Polyethylene Encasement for Ductile-Iron pipe systems
f.
ANSI/AWWA C104 /A21.4 - Cement-Mortar Lining for Ductile-Iron Pipe and fittings for Water.
g. ANSI/AWWA C116/A21.16 Protective Fusion-Bonded Epoxy Coatings for the Interior and Exterior Surfaces of DuctileIron
and Gray-Iron fittings for Water Supply Service.
h. AWWA C600 - Installation of Ductile-Iron Water Main and their appurtenances
i.
NFPA24 - Standard for the Installation of Private Fire Service Mains and Their Appurtenances
11. Valve Rated to 250 psi WWP, UL/FM, Epoxy Coated, Open Left (use with post indicator), (valve code suffix, option-94A).
12. Any thrust block requirement to be evaluated based on soil conditions or at change in direction.
Page 3 of 3